4 Option Components
Option LED Display
The option has four bicolor, red/green LEDs to relay information about power, communication status, and errors. The
operational states of the LEDs after completion of the power-up diagnostic process are described in Table 5. Wait at least
2 seconds for the power-up diagnostic process to complete before verifying the states of the LEDs.
Table 4 Option LED States
Display
Color
Status
LED
RUN
(Power)
Operating Status
ON
Power supply ON
OFF
Power supply OFF
ON
Option error
Drive connection
error
Normal operation
Communication
connected
Green
ERR
(Option Error)
Red
Flashing
OFF
COMM
(Communication
Status)
ON
Green
OFF
No data exchange
ON
BF
(PROFIBUS-DP
Error)
Red
Flashing
OFF
Waiting for
communication
procedure setting
Communication
setting error
Normal operation
Remarks
Power is supplied to the option, and the option hardware self-diagnostics check
is complete.
The drive has no power supply.
Option and drive are not connected properly and/or no power is supplied to
the option.
An internal, self-diagnostic error occurred in the option.
Self-diagnostic error occurred in the option.
Connection error between option and drive. This includes node address setting
errors to parameter F6-30 on the drive side.
Drive and option are properly connected.
Normal send/receive between the option and the PROFIBUS-DP master.
There is a problem establishing communication between the option and the
PROFIBUS-DP master.
Communication-related parameters are in the process of being set or initialized
by the PROFIBUS-DP master.
Communication parameter error from PROFIBUS-DP master.
LED shuts off when the PROFIBUS-DP master is finished setting
communication-related parameters.
Table 5 LED Operation After Power-up Diagnostic
LED
Communication
Status
RUN ERR COMM BF
No power
Possible Cause
Solution
Drive has no power.
Check all wiring to the drive, then turn on the power.
Option is not properly connected to the
drive or is not receiving enough power.
Shut off the drive and make sure the option is
connected properly. Turn the power back on.
Checking
connection with
the drive
Waiting for data
from the master
Option selfdiagnostics error
The option is damaged.
Problem connecting
to the drive
Problem initializing the drive and the
option.
Incorrect node address.
Waiting for data
from the master
device
Incorrect data or
option time out
waiting for data
Sending or
receiving data
Option is reading the node address or
parameter configuration.
Waiting for initial input data from
master device.
Cycle power to the drive. If the LED status does not
change, replace the option.
Cycle power to the drive. If the LED status does
not change, replace the option.
Check the node address setting in the drive (F6-10)
Check master network settings.
Make sure the master device is operating normally.
Waiting for data from the master device. Check terminal resistance settings on the data line.
Check for problems with the data line and
(Set_Parm_Message or
Chk_Cfg_Message)
connector.
Check if the data line is connected properly to
communication connector CN5.
The communication settings in the
master are set incorrectly.
Check the communication settings in the master.
{: On / : Flashing / : Off