Barrier MTL 5511

The MTLx511 module enables a safe-area load to be controlled by a switch or proximity detector located in a hazardous area. It has one channel and can detect line faults in the field wiring. When selected, open or short circuit conditions are detected and indicated. Phase reversal for the channel is selected by a switch and output is provided by a changeover relay contact. It has inputs that conform to BS EN60947–5–6:2001 standards for proximity detectors and applies 7 to 9V dc to the sensor.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views1 page

Barrier MTL 5511

The MTLx511 module enables a safe-area load to be controlled by a switch or proximity detector located in a hazardous area. It has one channel and can detect line faults in the field wiring. When selected, open or short circuit conditions are detected and indicated. Phase reversal for the channel is selected by a switch and output is provided by a changeover relay contact. It has inputs that conform to BS EN60947–5–6:2001 standards for proximity detectors and applies 7 to 9V dc to the sensor.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

MTL4511

MTL4511 MTL5511
SWITCH/ PROXIMITY
DETECTOR INTERFACE

Hazardous area

Safe area

To earth-leakage
detector *

1-channel, with line fault detection

680

The MTLx511 enables a safe-area load to be controlled by a switch or


proximity detector located in a hazardous-area. When selected, open
or short circuit conditions in the field wiring are detected by the linefault-detect (LFD) facility and also indicated on the top of the module.
Phase reversal for the channel is selected by a switch on the side of the
module and output is provided by changeover relay contacts.

SPECIFICATION

FSM

See also common specification

FUNCTIONAL SAFETY
MANAGEMENT

Number of channels
IEC 61508:2010
One
Location of switches
Zone 0, IIC, T6 hazardous area
Div. 1, Group A hazardous location
Location of proximity detector
Zone 0, IIC, T46 hazardous area if suitably certified
Div. 1, Group A hazardous location
Hazardous-area inputs
Inputs conforming to BS EN6094756:2001 standards for
proximity detectors (NAMUR)
Voltage applied to sensor
7 to 9V dc from 1k 10%
Input/output characteristics
Normal phase
Outputs closed if input > 2.1mA (< 2k in input circuit)
Outputs open if input < 1.2mA (> 10k in input circuit)
Hysteresis: 200A (650) nominal
Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit. A line fault is
indicated by an LED. The channel output relay is de-energised if
an input line fault is detected.
Open-circuit alarm on if Iin < 50A
Open-circuit alarm off if Iin > 250A
Short-circuit alarm on if Rin < 100
Short-circuit alarm off if Rin > 360
Note: Resistors must be fitted when using the LFD facility with a contact input
500 to 1k in series with switch
20k to 25k in parallel with switch

Safe-area output
Single pole relay with changeover contacts

Switch-type sensors
require resistors
if LFD is selected

Hazardous area

MTL5511
10ms maximum

Contact rating
(Safe Area):

10W, 0.5A,
35V dc

250V ac, 2A, cos >0.7,


40V dc, 2A, resistive load

Contact rating
(Zone 2):

10W, 0.5A,
35V dc

35V, 2A, 100VA.

14

20 to 35V dc
Vs+
Vs

Safe area

To earth-leakage
detector *
6
5
4

680
22k

3
2
1

Switch-type sensors
require resistors
if LFD is selected

7
8
9
10
11
12

Output

13
14

Vs
Vs+
20 to 35V dc

* Signal plug HAZ1-3 is required for access to this function


LED indicators
Green: power indication
Yellow: channel status, on when output energised
Red: LFD indication, on when line fault detected
Maximum current consumption
25mA at 24V
Power dissipation within unit
0.6W at 24V
Safety description (each channel)
Uo =10.5V Io =14mA Po =37mW Um = 253V rms or dc

SIL

10ms maximum

13

Output

MTL5511

Note: reactive loads must be adequately suppressed

MTL4511

9
8
7

3
2
1

22k

Relay characteristics
Response time:

12
11
10

6
5
4

IEC 61508:2010

SIL capable
These models have been assessed for use in
IEC 61508 functional safety applications.
See data on MTL web site and refer to the
safety manual.

The given data is only intended as a product description and should not be regarded as a legal warranty of properties
or guarantee. In the interest of further technical developments, we reserve the right to make design changes.

EUROPE (EMEA): +44 (0)1582 723633

THE AMERICAS: +1 800 835 7075

ASIA-PACIFIC: +65 6 645 9888

[email protected]

[email protected]

[email protected]

EPSx511 Rev4 200913

You might also like