R05 B4U Analog Standard Detector Base Installation Sheet

The document provides installation instructions for a B4U Analog Standard Detector Base. There are two installation options using either an octagonal electrical box or a 4 inch square electrical box. Wiring connections and specifications for the base are also described.

Uploaded by

Diego
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
376 views4 pages

R05 B4U Analog Standard Detector Base Installation Sheet

The document provides installation instructions for a B4U Analog Standard Detector Base. There are two installation options using either an octagonal electrical box or a 4 inch square electrical box. Wiring connections and specifications for the base are also described.

Uploaded by

Diego
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

B4U Analog Standard Detector Base

Installation Sheet
EN FR

Figure 1: Base installation option 1

EN: Installation Sheet


Description

The B4U Analog Standard Detector Base provides mounting


support and electrical connections for the compatible detectors
listed in "Specifications.

The base does not require a separate address.


The base comes with an adaptor bracket and trim ring for use
with a 4 in. square electrical box.

1.
2.
3.

Installation

Octagonal electrical box


B4U base assembly
Screws

There are two ways to install the B4U base assembly.

Option 1: Use an octagon or single-gang electrical box.

Option 2: Use a 4 in. square electrical box.

To install the B4U using option 2:


1.

Install a 4 in. square electrical box.

2.

Pull the wiring into the box and mount the adapter bracket
that comes with the B4U.

3.

Pull the wires through the hole in the detector base and
attach the detector base to the electrical box, using the
adaptor bracket and the screws provided with the
electrical box. See Figure 2.

4.

Attach the trim ring by aligning the arrows on the trim ring
with those on the base, and pressing down to lock the trim
ring into place.

5.

Make wiring connections as shown in Figure 3.

6.

Apply power and activate the unit to verify that it is


operating.

To install the B4U using option 1:


1.

Install an octagon or single-gang electrical box.

2.

Pull the wiring into the box and through the hole in the
center of the detector base.

3.

Attach the detector base to the electrical box, using the


screws provided with the electrical box.

4.

Make wiring connections as shown in Figure 3.

5.

Apply power and activate the unit to verify that it is


operating.

Note: Attaching the trim ring to the detector can occur before
or after assembling the detector to the base.

2013 UTC Fire & Security. All rights reserved.

1/4

P/N 3101074 REV 05 REB 25JAN13

Figure 2: Base installation option 2

Figure 3: Base wiring (option 2 installation shown)

2
3

6
2

4
5

1.
2.
3.

4 in. square electrical box


Adaptor bracket
B4U base assembly

4
5.
6.

Screws
Trim ring
Aligning arrows

Wiring
Wire in accordance with NFPA 72 or CAN/ULC-S524. Be sure
to observe the polarity of the terminals on the terminal block as
shown in the diagram.
Break the wire run at each terminal. Do not loop signaling
circuit field wires around terminals.
Caution: To avoid accidental damage to the panel, disconnect
all power before wiring the unit.
Note: If shielded cable is used, the following recommendations
apply:

Shielded wire is required only in environments with very


high electrical noise.

Use of shield connections must be continuous and must


be insulated from ground. Electrical tape is recommended
as a minimum to insulate the shield.

For Class B wiring, all shields must be continuous and


insulated from ground, except at the originating panel.

1.
2.
3.
4.
5.

From previous device or controller


Optional trim ring
Optional bracket
Maximum resistance per wire must not exceed 10
To next device

Terminal

Description

Terminal

Description

SLC in + and
SLC out (+)

Not used

SLC in

Remote LED +

Not used

Remote LED
and SLC out

Specifications
Base diameter
Without trim ring
With trim ring
Height from box (including
detector)
Maximum distance
Ceiling
Wall

4.35 in. (110.49 mm)


6.0 in. (152 mm)
2.08 in. (53 mm)

Not less than 4 in. (100 mm) from the


sidewall
Between 4 and 12 in. (100 and
300 mm) from the ceiling

Wire size

12 to 18 AWG wire (0.75 to 2.5 mm)

Compatible detectors

FX-PD, E-PD, FX-PHD, E-PHD,


FX-HD, E-HD, V-PS, V-PHS, V-HRD,
and V-HFD

Compatible electrical boxes

4 4 in. octagonal ring (mud box)


1-7/8 in. (47 mm) deep single-gang
box
4 in. square x 2-1/2 in. (64 mm) deep
box (requires using the included
adaptor bracket and trim ring)

2/4

Operating environment
Temperature
Relative humidity

32 to 120F (0 to 49C)
0 to 93% noncondensing

Storage temperature range

4 to 140F (20 to 60C)

P/N 3101074 REV 05 REB 25JAN13

Regulatory information
Manufacturer

Edwards, A Division of UTC Fire & Security Americas


Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL 34202,
USA

Year of
manufacture

The first two digits of the date code (located on the


product identification label) are the year of
manufacture

North
American
standards

Figure 1 : Option 1 dinstallation de la base

FCC Part 15, Subpart J, Class B; DOC, Class/MDC


Class B. UL 268, UL 521, CAN/ULC-S529-09,
CAN/ULC-S530-M91

Contact information
For contact information, see our Web site:
www.edwardsutcfs.com.

FR : Fiche D'Installation
Description
La base analogique standard B4U pour dtecteur fonctionne
avec les dtecteurs compatibles rpertoris la section
Fiche technique .

1.
2.
3.

Pour installer le B4U utilisant l'option 2 :


1.

Installez une bote lectrique qui est 4 po. carr.

2.

Tirez le cblage dans la bote et par la parenthse


d'adapteur qui vient avec le B4U.

3.

Attachez la base de dtecteur dans la bote lectrique,


utilisant la parenthse d'adapteur et les vis fournies par la
bote lectrique. Voir la Figure 2.

4.

Alignez les marques sur lanneau de garniture avec celles


de la plaque de la base, pressez lanneau dans la plaque
et faites pivoter lanneau jusqu ce quelle se verrouille en
place.

5.

tablissez les rapports de cblage suivant les indications


du Figure 3.

6.

Activez la base pour vrifier qu'elle fonctionne.

La base n'exige pas une adresse spare.


La base vient avec une parenthse d'adapteur et un anneau
d'quilibre pour l'usage avec les 4 po. bote lectrique carre.

Installation
Il y a deux manires d'installer le montage bas de B4U.

Option 1 : Utilisez une bote lectrique d'octogone ou de


simple-troupe.

Option 2 : Utilisez une bote lectrique qui est 4 po. carr.

Bote lectrique octogonale


La base de B4U
Vis

Figure 2 : Option 2 dinstallation de la base


6

Pour installer le B4U utilisant l'option 1 :


1.

Installez une bote lectrique d'octogone ou de simpletroupe.

2.

Tirez le cblage dans la bote et par le trou au centre de la


base de dtecteur.

3.
4.
5.

Attachez la base de dtecteur dans la bote lectrique,


utilisant les vis fournies par la bote lectrique.

3
4

tablissez les rapports de cblage suivant les indications


du Figure 3.
Activez la base pour vrifier qu'elle fonctionne.

P/N 3101074 REV 05 REB 25JAN13

1.
2.
3.
4.
5.
6.

Flches de alignement
Parenthse facultative
Bote carre de 10 cm (4 po)
La base de B4U
Vis
Anneau facultatif d'quilibre

3/4

Remarque : La fixation de l'anneau d'quilibre au dtecteur


peut se produire avant ou aprs assembler le dtecteur la
base.

Filage
Cblez conformment aux normes NFPA 72 et
CAN/ULC-S524. Assurez-vous de bien observer la polarit des
bornes sur le bornier, tel quindiqu sur le diagramme.
Interrompez le filage chacune des bornes. Ne faites pas de
boucle autour des bornes avec les cbles du champ du circuit
de signalisation.
Avertissement : Pour viter tout dommage accidentel au
panneau, dbranchez toute alimentation lectrique avant de
cbler le dispositif.
Remarque : Recommandations suivre si vous utilisez un
cble arm :

Fiche technique
Diamtre de la base
sans la plaque de base
avec la plaque de la base
Hauteur partir du coffret
(dtecteur inclus)
Distance maximale
montage du plafond
montage mural

Le blindage doit tre continu et isol de la terre. La bande


lectrique est recommande comme minimum pour isoler
le bouclier.

Pour le cblage de la classe B, tous les boucliers doivent


tre continus et isols de la terre, moins qu'au panneau
d'origine.

53 mm (2.08 po.)

Pas moins que 100 mm (4 po.) du


mur lateral
Entre 100 et 300 mm (4 et 12 po.) du
plafond

Dimensions du cble

Cbles de 12 18 AWG (0.75


2.5 mm2)

Dtecteurs compatibles

FX-PD, E-PD, FX-PHD, E-PHD,


FX-HD, E-HD, V-PS, V-PHS, V-HRD
et V-HFD

Coffrets lectriques
compatibles

Anneau octogonal de 10 x 10 cm
(4 x 4 po.) (bote boue)
Coffret de 47 mm de profond

Un fil blind est requis UNIQUEMENT dans les


environnements interfrences lectriques leves.

110.49 mm (4.35 po.)


152 mm (6 po.)

Coffret carre de 10 cm (4 po.) x


64 mm (2.5 po.) de profond (exige
utilisant la parenthse d'adapteur et
l'anneau d'quilibre qui sont inclus)
Cadre oprationnel
Temprature
Plage dhumidit relative
Plage de la temprature
dentreposage

0 4C (32 12F)
0 93 sans condensation
20 60C (4 140F)

Figure 3 : Cblage de la base

Rfrencement des agences

2
3

Fabricant

Edwards, A Division of UTC Fire & Security


Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL 34202,
USA

Lanne de
fabrication

Les deux premiers chiffres du code de date (situ


sur l'tiquette d'identification de produit) sont
l'anne de la fabrication

Normes nordamricaines

FCC Part 15, Subpart J, Class B, DOC Class/MDC


Class B. UL 268, UL 521, CAN/ULC-S529-09,
CAN/ULC-S530-M91

Coordonnes
1.
2.
3.
4.
5.

Du dispositif ou du contrleur prcdent


La rsistance maximum par fil ne doit pas dpasser 10
Au prochain dispositif
Parenthse facultative
Anneau facultatif d'quilibre

Borne Description

Borne

Description

Entre SLC + et sortie SLC +

Non utilis

Entre SLC

DEL distance +

Non utilis

DEL distance et
sortie SLC

4/4

Pour obtenir nos coordonnes, consultez le site Web


www.edwardsutcfs.com.

P/N 3101074 REV 05 REB 25JAN13