SINAMICS drives
SINAMICS DCM DC Converter
Migration Guide
Reference Manual
Edition
06/2015
Answers for industry.
SINAMICS
SINAMICS DC MASTER
Migration Guide
Reference Manual
06/2015
A5E35776390A/RS-AA/001;1
Introduction
SINAMICS DC MASTER
an overview of the highlights
Comparison of the functions
Terminal assignment
SIMOREG DC-MASTER SINAMICS DC MASTER
Commissioning SINAMICS
DC MASTER using the
BOP20 operator panel
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
Siemens AG
Division Process Industries and Drives
Postfach 48 48
90026 NRNBERG
GERMANY
A5E35776390A/RS-AA/001;1
06/2015 Subject to change
Copyright Siemens AG 2015.
All rights reserved
Table of contents
1
Introduction ............................................................................................................................................. 7
SINAMICS DC MASTER an overview of the highlights ....................................................................... 11
Comparison of the functions .................................................................................................................. 13
Terminal assignment SIMOREG DC-MASTER - SINAMICS DC MASTER ............................................ 23
4.1
Digital inputs ...........................................................................................................................23
4.2
Digital outputs .........................................................................................................................24
4.3
Analog inputs ..........................................................................................................................25
4.4
Analog outputs ........................................................................................................................25
4.5
Pulse encoder .........................................................................................................................26
4.6
Interfaces ................................................................................................................................27
Commissioning SINAMICS DC MASTER using the BOP20 operator panel ........................................... 29
5.1
Preconditions ..........................................................................................................................29
5.2
Commissioning steps ..............................................................................................................30
SINAMICS DC MASTER Migration Guide
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
Table of contents
SINAMICS DC MASTER Migration Guide
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
Introduction
As a result of its functionality, range of power ratings and flexibility, for many years now
SIMOREG DC-MASTER has been an extremely successful product series. It has been used
for single and multi-motor applications for production machines, in general machinery
construction and in all industrial sectors.
After the discontinuation of SIMOREG DC-MASTER in February 2014, with our
SINAMICS DC MASTER as successor we are continuing the Siemens success story as
global market leader for DC converters.
Since 2010, with SINAMICS DCM 6RA80 we have a product series completely integrated in
the SINAMICS platform with extended modularity and functionality. For example, Drive
Control Chart (DCC) for graphically configuring and extending the device functionality using
freely available closed-loop control, arithmetic and logic blocks.
Motivation
Frequently, DC drives are being replaced by AC drives; however, many customers have high
regard for the advantages of DC technology
SINAMICS DC MASTER has been developed for this group of customers, and in turn the
proven technology of SIMOREG DC-MASTER integrated in the SINAMICS platform.
This modernization sends a clear signal to our customers: "Also in the future, Siemens will
place a lot of emphasis on DC technology!"
This document is intended to help customers better understand SINAMICS DC MASTER
and especially its new functions, therefore providing valuable support when transitioning to
our new generation of devices.
Figure 1-1
SINAMICS DC MASTER product family
SINAMICS DC MASTER Migration Guide
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
Introduction
Figure 1-2
SIMOREG DC-MASTER product family
Additional documentation on SINAMICS DC MASTER
SINAMICS DC MASTER in the Internet
(https://www.industry.siemens.com/drives/global/de/umrichter/dc-stromrichter/sinamicsdcm)
SINAMICS DC MASTER operating instructions
(http://support.industry.siemens.com/WW/view/en/55622945)
Accessories
SICROWBAR AC overvoltage protection
SICROWBAR DC overvoltage protection
SIMOREG DC-MASTER CCP
Commutating reactors
Radio interference suppression filters
Advanced Operator Panel AOP30
and more
You can obtain more information about all of the accessories in Catalog D23.1:
(https://www.industry.siemens.com/mcms/infocenter/content/de/Seiten/order_form.aspx?nod
eKey=key_9181486&InfoType=catalogs)
SINAMICS DC MASTER Migration Guide
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
Introduction
Additional information in the Internet
FAQ (http://support.industry.siemens.com/WW/view/de/38157755/133000)
Selecting replacement DC converters
(http://support.industry.siemens.com/WW/view/de/26117006)
Service and support
Our specialist support and product management are more than willing to provide you with
information about reference projects and respond to any questions that you might have (
[email protected])
You can find information about our services and regional contact persons in the Internet (www.siemens.de/industry/csi_de/service).
SINAMICS DC MASTER Migration Guide
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
Introduction
SINAMICS DC MASTER Migration Guide
10
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
SINAMICS DC MASTER an overview of the
highlights
SINAMICS DC MASTER devices address all industrial applications involving low-voltage DC
drive technology. The open-design closed-loop control structure offers allows users to
optimally adapt the drive control to their particular requirements.
SINAMICS DC MASTER offers the following highlights:
UL certification (for all devices up to 575 V)
Marine certification
6 devices can be connected in parallel to increase the power rating and achieve
redundancy (n + m operation)
If a power unit fails, then the remaining functional SINAMICS DC MASTER devices
continue to operate without any interruption.
The power rating can be extended with engineered solutions, up to 60 kA and more in a
cabinet design (12 pulse)
Control Modules for retrofit drive projects and for high current rectifiers in electrochemical
applications up to 100 kA
Rated input voltages from 3 AC 50 V up to 950 V
Single-phase connection (110 V to 575 V AC) for devices up to 125 A
Extended temperature range for transport and storage (-40 C up to +70 C)
The DC motor insulation resistance can be measured without having to disconnect the
motor from the DC converter
SIMOREG CCP to protect against inverter commutation faults
Optimized cooling and service concept (optional, single-phase, quieter, integrated
operating hours counter)
The memory card can be used to save the project, update the firmware and for series
commissioning
Offline and online long-term traces
Field power supply that complies with requirements
Without field (for devices from 60 A rated armature current, with price reduction)
With 1Q field (up to 85 A rated field current)
With 2Q field and active current reduction, including field overvoltage protection (for
devices with 60 A rated armature current and above)
DCC for demanding closed-loop control tasks
Free function blocks the standard (no option S00)
Onboard encoder interfaces
Integrated electronics power supply for 24 V DC (option L05)
SINAMICS DC MASTER Migration Guide
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
11
SINAMICS DC MASTER an overview of the highlights
Integrated in the SINAMICS drive family therefore, the same commissioning tools, same
look & feel, parameterization supported by graphic screen forms, same components used
for expansion
Optional coated modules
Optional nickel-plated busbars
PROFIBUS on board/ PROFINET optional
The Control Units can be variably configured and therefore optimally adapted to
address a wide range of requirements, from a technical and cost perspective
Optional armature circuit supply with low voltage
SINAMICS DC MASTER can be re-equipped for operation with line input voltages from
10 up to 50 V.
Optional Ethernet-IP communication with CBE20
SIMOLINK
replaced by other communication standards:
SINAMICS Link
Parallel interface
CU-Link (controller-controller direct data exchange)
OA link
Position actual value sensing
rms phase current sensing
Password protection and know-how protection
Commissioning engineers are supported by graphic screens
SINAMICS DC MASTER Migration Guide
12
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
Comparison of the functions
The following comparison of the functions provides a factual comparison between
SINAMICS DC MASTER with its predecessor, the SIMOREG DC-MASTER.
The comparison includes all of the usual evaluation criteria.
Reading notes
The symbols in the table columns of the following chapter have the following significance:
+
Advantage
Neutral
Disadvantage
Ambient conditions
SINAMICS DC MASTER
SIMOREG DC-MASTER
IP00, IP20 possible up to 850 A
IP00
Ambient temperature
Storage
-40 C ... +70 C
-25 C ... +70 C
Ambient temperature
Operation
0 C +55 C
0 C +50 C or +60 C
(devices < 125 A)
above 40 C derating
above 40 C derating
up to 5000 m above sea level
up to 5000 m above sea level
Degree of protection
Max. installation altitude
Current derating
from 1000 m above sea level, temperature- from 1000 m above sea level, temperaturedependent current derating max. 70 %
dependent current derating max. 67 %
Voltage derating
Rated frequency
Field power supply
Power semiconductors
were relevant, from 4000 m above sea
level
from 4000 m above sea level
45 - 65 Hz
(extended range on request)
45 - 65 Hz
(extended range on request)
integrated (up to 85 A field current)
for all types 1500 A
integrated (up to 85 A field current)
for 8 specific types 1500 A
thyristor bridges
thyristor bridges
SINAMICS DC MASTER Migration Guide
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
13
Comparison of the functions
SINAMICS DC MASTER
SIMOREG DC-MASTER
Closed-loop control stability
=
(operation with a pulse encoder n = 0.006 %
and digital setpoint and/or rated
speed)
Closed-loop control accuracy
without encoder (EMF control,
dependent on the motor temperature)
approx. 5 %, field weakening not possible
approx. 5 %, field weakening not possible
SINAMICS DC MASTER
SIMOREG DC-MASTER
Electronics power supply
AC 380 (-25 %) to 480 (+10 %)
Electronics power supply
AC 380 (-25 %) to 480 (+10 %)
15-3000 A
15-3000 A
n = 0.006 %
Power units
Permissible line fluctuations
Power range
Number of devices that can be
connected
in parallel
Compact size
Noise when installed in a cabinet
Overload capability
for devices with high and average
currents; 1200 A devices 268 mm wide
for devices with high and average
currents; 1200 A devices 410 wide
no fan noise up to and including 125 A
devices
no fan noise up to and including 125 A
devices
180%
180%
Discharge resistance from the
very high (> 100 M)
power unit
isolated voltage sensing
(armature and field with respect
to ground)
Armature 575 V = 0.91 M
Armature 830 V = 1.3 M
Armature 1000 V = 1.6 M
Field 460 V = 1.8 M
SINAMICS DC MASTER Migration Guide
14
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
Comparison of the functions
Control Unit (CU/CUD)
Memory card
Power-up time (up to o7.0)
SINAMICS DC MASTER
SIMOREG DC-MASTER
for a firmware update (the drive automatically powers up with the new firmware),
offline trace or series commissioning
no memory card,
internal flash memory
--
40 s
3s
++
onboard
Option
2 x 32 PZDs (IF1 and IF2)
10 PZDs
Data interfaces
PROFIBUS
RS232 or RS485 / USS
Peer-to-peer
Isochronous PROFIBUS
No isochronous PROFIBUS
Slave-to-slave communication
Slave-to-slave communication
onboard
onboard
onboard
onboard
Ethernet / PROFINET
++
via CBE20 + Advanced CUD
no
SIMOLINK
functionally replaced by SINAMICS Link to
CU320-2 and using OA-Link
yes
++
yes
no
yes, via external bus coupler
CANopen on request
(option CBC)
yes, via external bus coupler
yes
++
4 inputs + 4 inputs or outputs
EtherNet/IP
CAN
Device Net
Inputs and outputs
Digital inputs on board
per CUD
Digital outputs on board
++
per CUD
Analog inputs on board
++
7 (+/-10 V)
per CUD
Resolution, analog outputs with
sign
3x with 14 bit
4x with 14 bit
4x with 11 bit
SINAMICS DC MASTER Migration Guide
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
15
Comparison of the functions
Analog outputs on board
SINAMICS DC MASTER
SIMOREG DC-MASTER
per CUD
+ fixed current actual value output
Resolution, analog outputs with
sign
15 bit
11 bit
Onboard encoder interfaces
1 x pulse encoder (15 V) (analog tachometer connected to the basic device)
1x pulse encoder (analog tachometer connected to the
basic device)
1 (PTC / KTY84, PT100 and PT1000)
1 (PTC or KTY84-130)
Electronics power supply
24 V
yes
no
Temperature evaluation
onboard
Others
Accessories and supplementary components
Commutating reactor
single and three-phase
Line-side overvoltage protection to protect the
power semiconductors
Recommendation for overvoltage protection at the output
when supplying high inductances
Protection against the
effects of inverter commutation
faults
Radio interference suppression
filter for
field and armature circuit
SINAMICS DC MASTER
SIMOREG DC-MASTER
as accessory
as accessory
Overvoltage protection
SICROWBAR AC
Overvoltage protection
SICROWBAR AC
SICROWBAR DC overvoltage protection
and special thyristor control
"reliable triggering"
SICROWBAR DC overvoltage protection
and special thyristor control
"reliable triggering"
CCP optional up to 2000 A
rated current up to 690 V
CCP optional up to 2000 A
rated current up to 690 V
Optional
Optional
Integrated semiconductor protection fuses (arm fuse)
existing devices for 900 A
existing devices for 900 A
Optional encoder interfaces
SMC 30
SBP
HTL / TTL encoder
yes
yes
yes
no
SSI encoder
Expanded interfaces
SINAMICS DC MASTER Migration Guide
16
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
Comparison of the functions
SINAMICS DC MASTER
SIMOREG DC-MASTER
Terminal Module TM15
Terminal expansion board EB1
24 digital inputs/digital outputs
3 digital inputs
4 digital inputs/digital outputs
3 analog inputs
Terminal Module TM31
Terminal expansion board EB2
2 analog inputs
2 digital inputs
2 analog outputs
4 relay contacts
4 digital inputs
2 analog outputs
4 digital outputs
or
4 digital inputs/digital outputs
fiber optic cable modules SCI1, SCI2
2 relay contacts
Terminal Module TM150
T100, T300, T400
Up to 9 temperature sensors can be conmax. 2 EB modules possible per CUD
nected (2, 3 or 4-wire connection) including
short-circuit and wire breakage monitoring
PT100
PT1000
KTY84
PTC
Bimetallic NC contact (without monitoring)
Max. 3 TM per CUD possible
Second CUD for performance and
terminal expansion
CUD2 to expand terminals
Optional panel
Advanced Operator Panel AOP30
Operator Panel OP1S
Control panel
yes
yes
Fault diagnostics in plain text
yes
no
Fully graphic capable
yes
no
SINAMICS DC MASTER Migration Guide
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
17
Comparison of the functions
Multilingual
SINAMICS DC MASTER
SIMOREG DC-MASTER
German
no Russian, Chinese with
special software
English
French
Spanish
Italian
Chinese
Russian
Polish
Numerical keypad
yes
yes
SINAMICS DC MASTER
SIMOREG DC-MASTER
SIZER LD web
SIZER (free load cycles)
DT Configurator
SIMOREG Pro
Engineering tools
Engineering support
SINAMICS DCM Pro
SIZER WEB engineering
Engineering software
STARTER commissioning tool
DriveMonitor
Connection
via PROFIBUS, PROFINET
via RS232 / RS485
also routing from a higher-level
control system
Graphic
function diagram screen forms
available
not available
Trace
2 x 8 channels
10 channels
Longer-term trace with memory card
Trace
Arithmetic functions (several y scales)
Function generator
Scripting
Prompted commissioning Wizard
available
not available
yes
yes
yes
only user-defined list
SINAMICS DC MASTER Migration Guide
18
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
Comparison of the functions
Functions
12-pulse series
SINAMICS DC MASTER
SIMOREG DC-MASTER
possible
possible
12-pulse parallel
possible
possible
Topology switchover
series/parallel
yes (option S50)
no
Single-phase connection
(armature circuit)
possible
not possible
Redundant operation
armature circuit
Redundant operation
field circuit
optimized for SINAMICS DC MASTER
possible without interruption
possible without interruption
possible
possible
Data sets
BICO data sets
2 (CDS - command the data set)
4 drive data sets (DDS)
4 function data sets
with 4 encoder data sets each
Automatic optimization runs
Current controller
=
yes
yes
Speed controller including
precontrol (frictional torque and
moment of inertia)
yes
yes
Plotting the field characteristic
yes
yes
EMF controller optimization
Optimization run for
mechanical systems that are
prone to oscillation
yes
yes
yes
no
Free function blocks
52 function blocks for basic
logic interconnections with standard performance available at no additional price
+
DCC (license cost for each PC)
Option S00 (license cost for each device)
for high requirements, graphic editor, simulation mode, as many block instances as
required (only restricted by the arithmetic
and storage capacity)
no graphic editor, no simulation mode, a
maximum of 300 blocks available
SINAMICS DC MASTER Migration Guide
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
19
Comparison of the functions
SINAMICS DC MASTER
SIMOREG DC-MASTER
Expanded by CUD inserted in the righthand
slot
CFC in technology modules T300 and
T400
SINAMICS Link
SIMOLINK
Peer-to-peer
Peer-to-peer
Additional functions
Communication between 2
devices
CU-Link
Control Module
Know-how protection
Same speed controller reference model as for the
SINAMICS S120
available
available
yes
yes
SINAMICS DC MASTER
SIMOREG DC-MASTER
Fan replacement (if a fan is available)
Fan replacement (if a fan is available)
only with higher-level control
only with higher-level control
Services
Maintenance
See also maintenance concept
Remote access
Fault diagnostics
Detailed documentation in
several languages
Range of training courses
Faults and recommendations for resolving
faults are output in plain text (on the
AOP30 or the STARTER commissioning
tool)
Faults and recommendations for resolving
faults are output in plain text (in DriveMonitor)
7-languages including Russian.
Operating instructions and List Manual
including function diagrams
5 languages
Service & commissioning- DR-DCM-SI
Diagnostics & maintenance- DR-DCM-DG
Repair (only for Siemens personnel) - DRDCM-REP
5-day training course
SINAMICS DC MASTER Migration Guide
20
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
Comparison of the functions
Certificates/tests/standards
SINAMICS DC MASTER
SIMOREG DC-MASTER
UL approval
yes
yes
Marine
yes, in the standard version
yes, with EMC envelope/covering
yes
yes
PROFIdrive certified according to PNO
no
PROFIdrive certified according to PNO
no
SINAMICS DC MASTER
SIMOREG DC-MASTER
EAC (GOST)
PROFIBUS
PROFINET
Quality
Ruggedness of the devices
The ruggedness of the devices has been
decisively
improved as a result of continuous improvement,
internal quality standards and the more
stringent
situation regarding standards.
SINAMICS DC MASTER Migration Guide
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
21
Comparison of the functions
SINAMICS DC MASTER Migration Guide
22
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
Terminal assignment SIMOREG DC-MASTER SINAMICS DC MASTER
4.1
Digital inputs
Table 4- 1
Digital inputs
Terminal number
SIMOREG DC-MASTER
Terminal number
SINAMICS DC MASTER
Comment
X171.34
X177.9, X177.10
24 V DC short-circuit proof
X171.35
X177.23, X177.24
Digital ground
X171.36
X177.11
Binary select input 1
X171.37
X177.12
Binary select input 2
X171.38
X177.13
Binary select input 3
X171.39
X177.14
Binary select input 4
X163.40
X177.15
Binary select input/output 1
X163.41
X177.16
Binary select input/output 2
X163.42
X177.17
Binary select input/output 3
X163.43
X177.18
Binary select input/output 4
X163.44
X177.9
24 V DC short-circuit proof
If CUD2 is inserted
Replaced by Terminal Module TM31
X161.210
X540.1
24 V DC short-circuit proof
X161.211
X520.1
Binary select input
X161.212
X520.2
Binary select input
X161.213
X520.3
Binary select input
X161.214
X520.4
Binary select input
X161.215
Ground for binary inputs
X161.216
X520.5
Ground for binary inputs
X161.217
X520.6
Ground
SINAMICS DC MASTER Migration Guide
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
23
Terminal assignment SIMOREG DC-MASTER - SINAMICS DC MASTER
4.2 Digital outputs
4.2
Digital outputs
Table 4- 2
Digital outputs
Terminal number
SIMOREG DC-MASTER
Terminal number
SINAMICS DC MASTER
Comment
X171.46
X177.19
Binary select output 1
X171.47
X177.23
Ground, digital
X171.48
X177.20
Binary select output 2
X171.54
X177.23
Ground, digital
X163.50
X177.21
Binary select output 3
X163.51
X177.24
Ground, digital
X163.52
X177.22
Binary select output 4
X163.53
X177.24
Ground, digital
If CUD2 is inserted
SINAMICS DC MASTER Migration Guide
24
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
Terminal assignment SIMOREG DC-MASTER - SINAMICS DC MASTER
4.3 Analog inputs
4.3
Analog inputs
Table 4- 3
Analog inputs
Terminal number
SIMOREG DC-MASTER
Terminal number
SINAMICS DC MASTER
Comment
X174.1
X177.33, X177.34
Ground, analog
X174.2
X177.31
P10
X174.3
X177.32
N10
X174.4
X177.25
Main setpoint +
X174.5
X177.26
Main setpoint -
X174.6
X177.27
Analog select input 1 +
X174.7
X177.28
Analog select input 1 -
X174.22
X177.53
Motor temperature +
X174.23
X177.55
Motor temperature-
X174.24
X177.33
Ground, analog
X164.8
X177.29
Analog select input 2
X164.9
X177.30
Ground, analog
X164.10
X177.1
Analog select input 3
X164.11
X177.2
Ground, analog
X164.204
X522.7
Motor temperature 2 + (on TM31)
X164.205
X522.8
Motor temperature 2 - (on TM31)
Terminal number
SINAMICS DC MASTER
Comment
If CUD2 is inserted
4.4
Analog outputs
Table 4- 4
Analog outputs
Terminal number
SIMOREG DC-MASTER
X175.12
Current actual value
X175.13
Ground, analog
X175.14
X177.49
Analog output 1
X175.15
X177.50
Ground, analog
X175.16
X177.51
Analog output 2
X175.17
X177.52
Ground, analog
X164.18
X522.1
Analog output 3 (on TM31)
X164.19
X522.2
Ground, analog
X164.20
X522.4
Analog output 4 (on TM31)
X164.21
X522.5
Ground, analog
If CUD2 is inserted
SINAMICS DC MASTER Migration Guide
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
25
Terminal assignment SIMOREG DC-MASTER - SINAMICS DC MASTER
4.5 Pulse encoder
4.5
Pulse encoder
Table 4- 5
Pulse encoder
Terminal number
SIMOREG DC-MASTER
Terminal number
SINAMICS DC MASTER
Comment
X173.26
X177.41
P15 for supply in the
pulse encoder
X173.27
X177.42
Ground
X173.28
X177.43
Track 1 +
X173.29
X177.44
Track 1 -
X173.30
X177.45
Track 2 +
X173.31
X177.46
Track 2 -
X173.32
X177.47
Zero mark +
X173.33
X177.48
Zero mark -
SINAMICS DC MASTER Migration Guide
26
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
Terminal assignment SIMOREG DC-MASTER - SINAMICS DC MASTER
4.6 Interfaces
4.6
Interfaces
Table 4- 6
Interfaces
Terminal number
SIMOREG DC-MASTER
Terminal number
SINAMICS DC MASTER
Comment
X165
X165
Parallel interface
X166
X166
Parallel interface
RS232/G-SST1
X300.1
Housing ground
X300.2
X179.4
Receive line RXD1
X300.7
X179.3
Transmit line TXD1
X300.5
X179.2
Ground
X300.3
X178.3
Transmit and receive line
RxD/TxD-P
X300.8
X178.4
Transmit and receive line
RxD/TxD-N
X300.9
X178.5
Ground
RS485/G-SST1
RS485/G-SST2 -if parameter 790 = 2
X172.58
Not replicated
Transmit and receive line
RxD/TxD-P
X172.59
Not replicated
Transmit and receive line
RxD/TxD-N
X172.60
Not replicated
Ground
RS485/G-SST2 -if parameter 790 = 5
X172.56
X177.37
Transmit line TX+
X172.57
X177.38
Transmit line TX-
X172.58
X177.39
Receive line RX+
X172.59
X177.40
Receive line RX-
X172.60
X177.35, X177.36
Ground
X162.61
Not replicated
Transmit line TX+
X162.62
Not replicated
Transmit line TX-
X162.63
Not replicated
Receive line RX+
X162.64
Not replicated
Receive line RX-
X162.65
Not replicated
Ground
X162.63
Not replicated
RS485/GSST3
RS485/G-SST3
SINAMICS DC MASTER Migration Guide
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
27
Terminal assignment SIMOREG DC-MASTER - SINAMICS DC MASTER
4.6 Interfaces
SINAMICS DC MASTER Migration Guide
28
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
Commissioning SINAMICS DC MASTER using the
BOP20 operator panel
5.1
Preconditions
Fundamentals of SINAMICS
If you do not already know the fundamentals of SINAMICS (parameters, drive objects, BICO
technology etc.), then before starting commissioning, in the SINAMICS DCM operating
instructions in Chapter Operation read the "Fundamentals" section.
BOP20 basic operator panel
If you still do not know the BOP20 operator panel, before commissioning, in the SINAMICS
DCM operating instructions, in Chapter "Operation", read the section "Parameterizing using
the BOP20".
Parameter notation
A complete parameter comprises
drive object + parameter number + index the following notation
(oo)pxxxxx[ii]
for indexed parameters
(oo)pxxxxx
for non-indexed parameters
To improve readability, in this chapter, the drive object is omitted for all parameters
belonging to the drive object "Closed-loop drive control" (= drive object 2).
For example, p50076[1] means parameter (2)p50076[1] (= drive object 2, parameter 50076,
index 1).
SINAMICS DC MASTER Migration Guide
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
29
Commissioning SINAMICS DC MASTER using the BOP20 operator panel
5.2 Commissioning steps
5.2
Commissioning steps
Note
Parameter with [D] depend on a data set. Commissioning must be carried out for each data
set.
1Access authorization
In order to be able to set access authorization, at the BOP20 basic operator panel, drive
object 1 (DO1) must be activated; see the operating instructions of SINAMICS DCM,
Chapter 9, Section Display and operation using the BOP20 basic operator panel.
Access level
(1)p0003 = 1
Standard
(1)p0003 = 2
Advanced
(1)p0003 = 3
Expert
2Adapting the rated device currents
Note
For the base drives produced in North America (Type 6RA80xx-2xxxx), the US rating must
be adjusted at p50067.
The rated armature DC current for the unit must be adjusted by setting p50076[0] (in %) or
p50067 if:
Maximum armature current < 0.5 rated armature DC current for the unit
The rated field DC current for the unit must be adapted by setting p50076[1] (in %) if:
Maximum field current < 0.5 rated field DC current for the unit
3Adapting the actual device supply voltage
p50078[0]
Rated DC converter input voltage, armature (in Volt)
p50078[1]
Rated DC converter input voltage, field (in Volt)
SINAMICS DC MASTER Migration Guide
30
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
Commissioning SINAMICS DC MASTER using the BOP20 operator panel
5.2 Commissioning steps
4Entering the motor data
The motor data according to the motor rating plate must be entered into the following
parameters (see also the operating instructions of SINAMICS DCM, Chapter "Thermal
overload protection of the DC motor" and "Speed-dependent current limiting"):
Fig.
p50100[D]
Rated armature current (in amperes)
p50101[D]
Rated armature voltage (in volts)
p50102[D]
Rated excitation current (in amperes)
p50104[D]
Speed n1 (in rpm)
p50105[D]
Armature current I1 (in amperes)
p50106[D]
Speed n2 (in rpm)
p50107[D]
Armature current I2 (in amperes)
p50108[D]
Maximum operating speed n3 (in rpm)
p50109[D]
1 = Speed-dependent current limitation active
p50114[D]
Motor thermal time constant (in seconds)
5Speed actual value sensing data
5.1Operation with analog tachometer
p50083[D] = 1 The actual speed value comes from the "Main actual value" (r52013) channel
(terminals XT.103, XT.104).
p50741[D]
Tachometer voltage at maximum speed ( 270.00 to +270.00 V)
Remark:
The value set here defines 100% speed for the closed-loop speed control.
p2000
Speed in rpm for tachometer voltage set on p50741[0]
Comment 1:
Parameter p2000 is used to convert from a "physical speed" (rpm) into a
"relative speed" (%) and vice versa.
This conversion is required for:
Speed setpoint input via the operator panel in the STARTER
commissioning tool
Speed setpoint input via the operating screen form of the AOP30
advanced operator panel
Calculating the display values r020, r021, r060 and r063
Remark 2:
Parameter p2000 and parameters r020, r021, r060 and r063 are not data-set
dependent. This is the reason that the physical speed can only be displayed
correctly for one data set (DDS).
SINAMICS DC MASTER Migration Guide
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
31
Commissioning SINAMICS DC MASTER using the BOP20 operator panel
5.2 Commissioning steps
5.2Operation with pulse encoder
p50083[D] = 2 The speed actual value is received from a pulse encoder (r0061) connected
at terminal block X177
p0400[0]
Encoder type selection
p2000
Speed in rpm at 100% speed
Remark:
The value set here defines 100% speed for the closed-loop speed control.
5.3Operation without tachometer (EMF control)
p50083[D] = 3 The actual speed value comes from the "Actual EMF value" channel
(r52287),
but is evaluated with p50115.
p50115[D]
EMF at 100% speed
(1.00 to 140.00 % of the rated device supply voltage (p50078[0])
Remark:
The value set here defines 100% speed for the closed-loop speed control.
p2000
Speed in rpm for EMF set on p50115[0]
Comment 1:
Parameter p2000 is used to convert from a "physical speed" (rpm) into a
"relative speed" (%) and vice versa.
This conversion is required for:
Speed setpoint input via the operator panel in the STARTER
commissioning tool
Speed setpoint input via the operating screen form of the AOP30
advanced operator panel
Calculating the display values r020, r021, r060 and r063
Remark 2:
Parameter p2000 and parameters r020, r021, r060 and r063 are not data-set
dependent. This is the reason that the physical speed can only be displayed
correctly for one data set (DDS).
5.4Freely wired actual value
p50083[D] = 4 The actual-value input is defined with p50609[C]
p50609[C]
Number of the parameter that is switched to the actual speed controller
value
SINAMICS DC MASTER Migration Guide
32
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
Commissioning SINAMICS DC MASTER using the BOP20 operator panel
5.2 Commissioning steps
p2000
Speed in rpm at which the parameter selected on p50609[0] accepts the
value 100%
Comment 1:
Parameter p2000 is used to convert from a "physical speed" (rpm) into a
"relative speed" (%) and vice versa.
This conversion is required for:
Speed setpoint input via the operator panel in the STARTER
commissioning tool
Speed setpoint input via the operating screen form of the AOP30
advanced operator panel
Calculating the display values r020, r021, r060 and r063
Remark 2:
Parameter p2000 and parameters r020, r021, r060 and r063 are not data-set
dependent. For that reason, the physical speed can only be displayed correctly for one data set (CDS).
5.5Operation with pulse encoder and SMC30
p50083[D] = 5 The actual speed value comes from an incremental encoder connected to
an SMC30 (r3770).
p0400[1]
Encoder type selection
p2000
Speed in rpm at 100% speed
Remark:
The value set here defines 100% speed for the closed-loop speed control.
6Field data
6.1Controlling the field
p50082 = 0
Internal field is not used
(e.g. for permanent-magnet motors)
p50082 = 1
The field is also switched with the line contactor
(the field pulses are energized de-energized simultaneously with the
line contactor)
p50082 = 2
The selected standstill field set using p50257 is automatically activated after
a time that can be parameterize using p50258 after operating state o7 or
higher is reached
p50082 = 3
Field current permanently switched on
6.2Field weakening
p50081 = 0
No speed or EMF-dependent field weakening
p50081 = 1
Field weakening operation using the internal EMF control, so that in the
field-weakening range, this means speeds above the rated motor speed
(= "Transition speed"), the motor EMF is kept constant at the setpoint
EMFset (r52289) = p50101 p50100 * p50110.
SINAMICS DC MASTER Migration Guide
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
33
Commissioning SINAMICS DC MASTER using the BOP20 operator panel
5.2 Commissioning steps
7Setting the basic technological functions
7.1Current limits
p50171[D]
System current limit in torque direction I (as % of p50100)
p50172[D]
System current limit in torque direction II (as % of p50100)
7.2Torque limits
p50180[D]
Torque limit 1 in torque direction I
(as % of rated motor torque)
p50181[D]
Torque limit 1 in torque direction II
(as % of rated motor torque)
7.3Ramp-function generator
p50303[D]
Ramp-up time 1 (in seconds)
p50304[D]
Ramp-down time 1 (in seconds)
p50305[D]
Initial rounding 1 (in seconds)
p50306[D]
Final rounding 1 (in seconds)
8Completing fast commissioning
Set p3900 = 3.
This triggers the calculation of the motor data (Ra, La, Lf) as well as the calculation of the
controller parameters resulting from the data that was entered in the previous steps.
p3900 is then set back to 0 and fast commissioning completed; this means that p0010 is
reset to 0.
9Executing the optimization runs
Perform the optimization runs one after the other:
p50051 = 24
Optimization of closed-loop field-current control
p50051 = 25
Optimization of closed-loop armature current control
p50051 = 26
Optimization of speed control
p50051 = 27
Optimizing the EMF control (including plotting the field characteristic)
p50051 = 28
Plotting the friction characteristic
p50051 = 29
Optimization of closed-loop speed control for drives with a mechanical system capable of oscillation
For more detailed information, refer to the SINAMICS DCM operating instructions, Chapter
"Drive optimization".
If an optimization run is not carried out, the motor control uses the motor characteristic
values calculated from the rating plate data rather than the measured values.
SINAMICS DC MASTER Migration Guide
34
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
Commissioning SINAMICS DC MASTER using the BOP20 operator panel
5.2 Commissioning steps
DANGER
During optimization runs, the drive initiates motor movements that can reach the maximum
motor speed. The EMERGENCY OFF functions must be fully operational during
commissioning. To protect man and machines, the relevant safety regulations must be
observed.
10Checking and possibly finely calibrating the maximum speed
Once the optimization runs have been executed, the maximum speed needs to be checked
and, if necessary, the setting for it corrected.
If the maximum speed has now shifted by more than around 10%, the control response of
the closed-loop speed control circuit will need to be checked; it may be necessary to repeat
the optimization run for the speed controller or carry out re-optimization manually.
The optimization runs for field weakening and for friction and moment of inertia
compensation must be repeated if there is any change to the maximum speed.
11Checking the drive settings
The optimization runs do not produce the best results for every application, so in all cases it
is necessary to check the controller settings using the appropriate tools (oscilloscope,
STARTER trace, and so on). Some cases may require manual re-optimization.
12Manually (post) optimizing (if required)
If the result of the optimization runs is not satisfactory, then manual post or new optimization
can be performed.
The procedure is described in the operating instructions, in Chapter "Manual optimization".
13Saving the setting values in a non-volatile fashion
Previously, all changes in the set values were made in the RAM (Random Access Memory).
If the device is switched off in this state, all settings made previously are lost. To
permanently store the settings in the ROM (non-volatile memory), a RAM to ROM must be
triggered by setting p0977 to 1 (p0977 is allocated to the DO 1). While data is being saved,
the BOP20 flashes (and the RDY-LED on the CUD also flashes); this takes approx. 45 s.
After the save operation the settings are backed up in the ROM.
The drive can now be switched off (POWER OFF) without losing the settings that have been
made. Also refer to the "Operation" chapter, "CompactFlash Card functions" section.
SINAMICS DC MASTER Migration Guide
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
35
Commissioning SINAMICS DC MASTER using the BOP20 operator panel
5.2 Commissioning steps
14Documenting the setting values
The following facilities are available so that the settings made can be recorded outside the
unit:
External CompactFlash Card was inserted during the RAM to ROM (p0977=1). The
parameters were therefore also transferred to the external CompactFlash Card.
Write the parameters to a CompactFlash Card (p0804).
Document the parameters in a STARTER project (load to PG). Also refer to the
"Operation" chapter, "CompactFlash Card functions" section and "Commissioning with
the STARTER commissioning tool" chapter.
SINAMICS DC MASTER Migration Guide
36
Reference Manual, 06/2015, A5E35776390A/RS-AA/001;1
Siemens AG
Division Process Industries & Drives
Postfach 48 48
90026 NRNBERG
GERMANY
Subject to change without prior notice
6A5E35776390A/RS-AA/001;1
Siemens AG 2015