Eed3001 Lab2 Single Phase Transformer Loading EM3000
Eed3001 Lab2 Single Phase Transformer Loading EM3000
Faculty of Engineering
Electrical and Electronics Engineering
Dokuz Eyl
ul Universitesi,
M
uhendislik Fak
ultesi,
Elektrik-Elektronik M
uhendisli
gi, TR35160 Kaynaklar, Buca/Izmir.
T 0090/232/ 301-7155
Objective(s):
The object of this experiment is to show how the input power, efficiency, output voltage, and regulation of a single phase transformer vary with resistive, inductive, and
capacitive loading conditions.
Equipment will be available at the laboratory:
Three-phase Power Supply Module
EM-3310-1B
Three-pole Current Limit Protection Switch Module EM-3310-2A
Resistive Load Module
EM-3310-4R
Inductive Load Module
EM-3310-4L
Capacitive Load Module
EM-3310-4C
Digital ACA Meter
EM-3310-3C
Digital ACV Meter
EM-3310-3D
Digital Power Analysis Meter
EM-3310-3H
Fuse Set
EM-3310-5B
Single-phase Transformer
EM-3340-1A
Connecting Leads Set
EM-3390-3A
Safety Bridging Plugs Set
EM-3390-4A
Equipment will be ensured by the students:
None
Procedure:
1. Install the required modules in the experimental frame. Construct the circuit in accordance with the circuit diagram in Figure (1) and the connection diagram in Figure
(2). The single-phase transformer is connected to a purely resistive load.
2. Sequentially turn on the 3-P current limit protection switch and three-phase power
supply modules
3. Record the rms voltage, current, real power, and power factor values from digital
ACA, ACV, and power analysis meters for each of switch positions of the resistive load
module in Table (1).
1
Figure 2: Circuit diagram of the experimental setup with resistive load bank.
3
SW
V1 [V]
All OFF
S1=ON
S1 to S2=ON
S1 to S3=ON
S1 to S4=ON
S1 to S5=ON
S1 to S6=ON
Measured values
I1 [A] P1 [W] V2 [V] I2 [A]
cos
Calculated Values
P2 [W] VR [%] [%]
SW
V1 [V]
All OFF
S1=ON
S1 to S2=ON
S1 to S3=ON
S1 to S4=ON
S1 to S5=ON
S1 to S6=ON
Measured values
I1 [A] P1 [W] V2 [V] I2 [A]
cos
Calculated Values
Q2 [V.A.R.] VR [%] [%]
SW
V1 [V]
All OFF
S1=ON
S1 to S2=ON
S1 to S3=ON
S1 to S4=ON
S1 to S5=ON
S1 to S6=ON
Measured values
I1 [A] P1 [W] V2 [V] I2 [A]
Calculated Values
Q2 [V.A.R.] VR [%] [%]
cos
P1
V1 I1
V22
= V2 I2
R
V22
= V2 I2
X
V1 V20
100
V20
P2
100
P1
[1]
(1)
[W]
(2)
[V.A.R.]
(3)
[%]
(4)
[%]
(5)
Where V20 is the value of the secondary voltage referred to the primary side by the turns
ratio of the transformer under test.
End of the document.