Reference Manual
PlantPAx Library of Process Objects:
Discrete 2-, 3-, or 4-state Device (P_D4SD)
Version 2.0
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from
your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
IMPORTANT
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Software, Rockwell Automation, RSLogix, Logix5000, FactoryTalk, PlantPAx, ControlLogix, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Table of Contents
Preface
Library Programming Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Ladder Diagram Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Prescan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Accessing Revision Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Entering Text in FactoryTalk View SE Software . . . . . . . . . . . . . . . . . . 8
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Discrete 2-, 3-, 4-state Device
(P_D4SD)
Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Required Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Controller File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Visualization Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional Template Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Controller Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Discrete 2-, 3-, or 4-state Device Input Structure . . . . . . . . . . . . . . . .
Discrete 2-, 3-, or 4-state Device Output Structure . . . . . . . . . . . . . .
Discrete 2-, 3-, or 4-state Device Local Configuration Tags. . . . . . .
Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Execution. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generic Alarm Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Programming Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Elements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Status/Quality Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance Bypass Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarm Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use Global Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Faceplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarm Configuration Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarms Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Discrete 2-, 3-, 4-state Device Faceplate Help . . . . . . . . . . . . . . . . . . .
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
11
12
13
13
13
14
15
15
20
24
25
25
25
26
26
28
32
35
36
36
37
38
38
41
44
49
51
53
Table of Contents
Notes:
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Preface
The PlantPAx Library of Process Objects is a predefined library of controller
code (Add-On Instructions), display elements (global objects), and faceplate
displays that let you quickly assemble large applications with proven strategies,
rich functionality, and known performance.
The Process Objects can be downloaded from Knowledgebase Answer ID 62682
at http://www.rockwellautomation.custhelp.com.
The PlantPAx Library of Process Objects version 2.0 is compatible with the
following products:
RSLogix 5000 software, version 18 or later
FactoryTalk View Site Edition software, version 6.0 or later
FactoryTalk View Machine Edition software, version 6.0 or later
Library Programming
Considerations
PlantPAx Library Add-On Instructions can be used in ladder diagrams, function
block diagrams, or structured text languages. Select the programming language
based on the type of application you are developing.
The following programming considerations are common for all PlantPAx Library
of Process Objects.
Ladder Diagram Considerations
The controller evaluates ladder diagram instructions based on the rung
condition preceding the instruction (rung-in condition). Based on the
rung-in condition and the instruction, the controller sets the rung
condition following the instruction (rung-out condition), which affects any
subsequent instruction.
If the rung-in condition to an input instruction is true, the controller evaluates
the instruction and sets the rung-out condition based on the results of the
instruction. If the instruction evaluates to true, the rung-out condition is true; if
the instruction evaluates to false, the rung-out condition is false.
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Preface
IMPORTANT
The rung-in condition is reflected in the EnableIn parameter and determines
how the system performs each Process Add-On Instruction. If the EnableIn
signal is true, the system performs the instructions main logic routine.
Conversely, if the EnableIn signal is false, the system performs the instructions
EnableInFalse routine.
The instructions main logic routine sets/clears the EnableOut parameter,
which then determines the rung-out condition. The EnableInFalse routine
cannot set the EnableOut parameter. If the rung-in condition is false, then the
EnableOut parameter and the rung-out condition will also be false.
Prescan
During the transition into Run mode, the controller performs a Prescan before
the first logic scan. Prescan is a special scan of all routines in the controller. The
controller scans all main routines and subroutines during Prescan, but ignores
jumps that could skip the execution of instructions. The controller executes all
FOR loops and subroutine calls. If a subroutine is called more than once, it is
executed each time it is called. The controller uses Prescan instructions to reset
non-retentive data values.
During Prescan, input values are not current and outputs are not written. The
following conditions generate Prescan:
Toggle from Program to Run mode
Automatically enter Run mode from a power-up condition
Prescan does not occur for a program when the following occurs:
Program becomes scheduled while the controller is running
Program is unscheduled when the controller enters Run mode
IMPORTANT
The Prescan performs the Process Add-On Instructions logic routine as all false
and then performs its Prescan routine as true.
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Preface
Accessing Revision Information
Add-On Instructions in the PlantPAx Library of Process Objects can
show revision history in RSLogix 5000 software and the faceplate in
FactoryTalk View software.
Component
Example
The Add-On Instruction in RSLogix 5000 software
has revision information visible when the instruction is
selected in the Controller Organizer.
The faceplate in FactoryTalk View software has revision
information visible when the pointer is paused just inside
the lower left corner of the faceplate when accessed in a
running HMI Client.
The instruction and faceplate are compatible if they have the same Major and
Minor Revision numbers. The Major Revision is the first number, before the
period. The Minor Revision is the second number, after the period and before the
hyphen or space.
Information after the hyphen or space indicates the Service Release. The
instruction and faceplate do not have to have the same Service Release to be
compatible. In the table above, the Add-On Instruction and faceplate shown are
compatible because they have the same Major.Minor (2.0).
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Preface
Entering Text in FactoryTalk View SE Software
When entering data into String Input fields in FactoryTalk View SE software, the
data is not saved to the tag until you press Enter. When the Input field is active, its
border changes based on the state of the input:
When the Input field is active (the cursor is in the field), the Input field
border is a solid line.
EXAMPLE
If you modify the data in the Input field and move to a different field
without pressing Enter, the border remains a solid line. This indicates that
the data has not been saved to the tag.
EXAMPLE
If the data in the Input field has not changed or has been written to the
controller tag, the border is a dashed line.
EXAMPLE
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Preface
Additional Resources
These documents contain additional information concerning related products
from Rockwell Automation.
Resource
Description
PlantPAx Process Automation System Selection Guide,
publication PROCES-SG001
Provides information to assist with equipment
procurement for your PlantPAx system.
PlantPAx Process Automation System Reference Manual,
publication PROCES-RM001
Provides characterized recommendations for
implementing your PlantPAx system.
FactoryTalk View SE Edition User Manual,
publication VIEWSE-UM006
Provides details on how to use this software package for
developing and running human-machine interface
(HMI) applications that can involve multiple users and
servers, distributed over a network.
Logix5000 Controllers Add-On Instructions Programming
Manual, publication 1756-PM010
Provides information for designing, configuring, and
programming Add-On Instructions.
Process Add-On Instructions and Graphics: Standard Alarm
Sub-Block (P_Alarm) Reference Manual,
publication SYSLIB-RM002
Details how to monitor an input condition to raise an
alarm. Information includes acknowledging, resetting,
inhibiting, and disabling an alarm.
Process Add-On Instructions: Standard Modes (P_Mode)
Reference Manual, publication SYSLIB-RM005
Explains how to select the Mode (owner) of an
instruction or control strategy. The Mode instruction is
usually embedded within other instructions to extend
their functionality. It is possible to use a standalone
Mode instruction to enhance a program where modes
are wanted.
You can view or download publications at
http:/www.rockwellautomation.com/literature/. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Preface
Notes:
10
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Discrete 2-, 3-, 4-state Device (P_D4SD)
The P_D4SD (Discrete 2-, 3-, 4-state Device) Add-On Instruction controls
and monitors feedback from a Discrete 2-state, 3-state, or 4-state Device in a
variety of modes, monitoring for fault conditions. These devices include a
multiple-speed motor or a multiple-position valve. The global objects and
faceplate shown below are examples of the graphical interface tools used with the
embedded logic.
Faceplate
Global Objects
Add-On Instruction
Guidelines
Use this instruction in these situations:
You need to operate a discrete device that has two, three, or four unique
states, and the device is not supported by other PlantPAx Library Add-On
Instructions for various motors, valves, and so forth.
You have a device, such as a valve or motor, that is supported by other
Add-On Instructions, but you want the device to use non-standard state
names, such as recycle and deliver for a diverter valve, rather than the
fixed names used in the other Instruction, such as closed and open. The
P_D4SD Instruction has configurable names for each of the device states.
Do not use this instruction in these situations:
You need to operate a device that has more than four states, such as
a six-position rotary selector valve. You may be able to use the P_nPos
(n-Position Device) Add-On Instruction instead.
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
11
Discrete 2-, 3-, 4-state Device (P_D4SD)
You need to operate a single-speed motor, two-speed motor, simple
reversing motor, solenoid valve, motor-operated valve, mix-proof valve or
other device that is better supported by other PlantPAx Library Add-On
Instructions. Instructions such as P_Motor, P_MotorRev, P_Motor2Spd,
P_ValveSO, P_ValveMO and P_ValveMP more closely model the device
under control and may provide better diagnostics for the device.
You need to operate a continuously-variable device. Use the P_AOut
(Analog Output), P_ValveC (Control Valve) or P_VSD (Variable Speed
Drive) Add-On Instruction instead.
You need to operate a two-state device that requires pulsing (single-pulse
or continuous). Use the P_DOut (Discrete Output) Instruction instead.
Functional Description
12
The Discrete 2-, 3-, or 4-state Device Add-On Instruction provides the
following capabilities:
Provides configuration to have two, three, or four selectable states for the
device.
Provides Operator and Program Commands to select one of the two,
three, or four states of the device.
Controls four discrete outputs, with configurable states of each output in
the various device states. Each output can be set, cleared, or left in last state
in a given device state.
Monitors four discrete feedback inputs, with configurable states
(including must be on, must be off , and don't care) for each input in the
various device states for monitoring the actual position of the device.
Provides configurable text labels for each of the states.
When feedback inputs are used, detects failure to reach the target state,
after a configurable time, and alarms the failure. Optionally sheds to the
default state (state 0) on a feedback failure.
Monitors Permissive conditions, which allow commanding the device to
each state.
Monitors Interlock conditions, which return the device to its
default state (state 0).
Provides simulation of a normally working device, while holding the
outputs to the real device de-energized, for use in testing or operator
training.
Monitors I/O communication status, providing an alarm on an I/O fault.
Optionally sheds to the default state on an I/O fault condition.
Provides an Available Status when in Program Mode and operating
normally for use by automation logic to determine if the logic can
manipulate the device.
Operates in Hand, Maintenance, Override, Program, and
Operator modes. (See Modes on page 25.)
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Discrete 2-, 3-, 4-state Device (P_D4SD)
Add-On Instructions are reusable code objects that contain encapsulated logic
that can streamline implementing your system. This lets you create your own
instruction set for programming logic as a supplement to the instruction set
provided natively in the ControlLogix firmware. An Add-On Instruction is
defined once in each controller project, and can be instantiated multiple times in
your application code as needed.
Required Files
Controller File
The P_D4SD_2_0-00_AOI.L5X Add-On Instruction must be imported into
the controller project to be able to be used in the controller configuration. The
service release number (boldfaced) may change as service revisions are created.
Visualization Files
The following files from Knowledgebase Answer ID 62682 at
http://www.rockwellautomation.custhelp.com are required in order to use
the P_D4SD Object.
Table 1 - P_D4SD Visualization File Types
Application Type
File Type
FactoryTalk View SE Software
FactoryTalk View ME Software
Description
Graphics - Displays
GFX
(RA-BAS) Common-AnalogEdit
N/A
Faceplate used for analog input data entry.
The FactoryTalk View ME software faceplates
use the native analog input data entry so no
file is required.
(RA-BAS) P_D4SD-Faceplate
(RA-BAS-ME) P_D4SD-Faceplate
The faceplate display used for the object.
(RA-BAS) P_D4SD-Help
(RA-BAS-ME) P_D4SD-Help
The help display used for the object.
(RA-BAS) P_Alarm-Help
(RA-BAS-ME) P_Alarm-Help
P_Alarm Help information that is accessed
from the P_D4SD Help faceplate.
(RA-BAS) P_D4SD-Config
(RA-BAS-ME) P_D4SD-Config
Pop-up used to configure states for a device.
(RA-BAS) P_Mode-Help
(RA-BAS-ME) P_Mode-Help
Mode Help information that is accessed from
the P-D4SD faceplate.
(RA-BAS) P_Mode-Config
(RA-BAS-ME) P_Mode-Config
Pop-up used to set Default mode.
(RA-BAS) Common Faceplate Objects
(RA-BAS-ME) Common Faceplate Objects
Common global objects used on all Process
Object faceplates.
(RA-BAS) Process Faceplate Objects
(RA-BAS-ME) Process Faceplate Objects
Process-specific global objects used on all
Process Object faceplates.
(RA-BAS) Process Alarm Objects
(RA-BAS-ME) Process Alarm Objects
Common global objects used for alarming on
all Process Object faceplates.
(RA-BAS) Process Help Objects
(RA-BAS-ME) Process Help Objects
Common global objects used for all Process
Objects help displays.
(RA-BAS) Process Mode Objects
(RA-BAS-ME) Process Mode Objects
Common global objects used for managing
modes on all Process Object faceplates.
(RA-BAS) P_D4SD Graphics Library
(RA-BAS-ME) P_D4SD Graphics Library
Common global objects in the graphics
library for this instruction.
(RA-BAS) P_D4SD Motor Graphics Library
(RA-BAS) P_D4SD Motor Graphics Library
Common global objects in the motor graphics
library for this instruction.
Graphics - Global
Objects
GGFX
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
13
Discrete 2-, 3-, 4-state Device (P_D4SD)
Table 1 - P_D4SD Visualization File Types
Application Type
File Type
FactoryTalk View SE Software
FactoryTalk View ME Software
Description
Graphics - Images
BMP
All.bmp files in the images folder
All .bmp files in the images folder
These are the common icons used in the
global objects and faceplates for all
Process Objects.
HMI Tags
CSV
N/A
FTVME_PlantPAxOBjx2_0_2011 09 30Tags.CSV
These tags must be imported into the
FactoryTalk View ME project to support
switching tabs on any Process
Object faceplate.
Optional Template Files
You can import the files in Table 1 individually, or you can use the following
template files:
FTVME_6_0_Template_PlantPAxLib_2_0_00(1).apa:
FactoryTalk View ME backup. Contains .gfx, .ggfx, images, and tags for all
Process Objects in a FactoryTalk View Machine Edition project.
FTVSE_6_0_Template_PlantPAxLib_2_0_00(1).apa:
FactoryTalk View SE Station backup. Contains .gfx, .ggfx, and images for
all Process Objects in a FactoryTalk View Site Edition Station project.
Use Knowledgebase Answer ID 39581 at
http://www.rockwellautomation.custhelp.com to load the files in the
restored station project into your HMI server on a FactoryTalk View SE
Distributed application.
RSL5k_18_Template_PlantPAxLib_2_0_00(1).acd:
RSLogix 5000 software template project with all Process Objects
instructions loaded, as well as recommended task structure and
diagnostic objects.
(1) The service release number (boldfaced) may change as service revisions are created.
14
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Discrete 2-, 3-, 4-state Device (P_D4SD)
This section describes the parameter references for this Add-On Instruction.
Controller Code
Discrete 2-, 3-, or 4-state Device Input Structure
Input parameters include the following:
Input data elements (Inp_) are typically used to connect field inputs from
I/O modules or signals from other objects.
Configuration data elements (Cfg_) are used to set configurable
capabilities and features of the instruction.
Command data elements (PCmd_, OCmd_, MCmd_) are used by
program logic, by operators, and by maintenance personnel to request
instruction actions.
Setting data elements (PSet_, OSet_, MSet_) are used by program logic,
by operators, and by maintenance personnel to establish runtime setpoints,
thresholds, and so forth. Set_data elements (without a leading P, O, or M)
establish runtime settings regardless of role or mode.
Table 2 - P_D4SD Input Parameters
Input Parameter
Data Type
Default
Description
EnableIn
BOOL
Ladder Diagram:
Set to the rung-in condition of the condition.
Function Block or Ladder Diagram:
If false, the system performs the EnableInFalse routine. If set, the instruction executes.
Structured Text:
No effect. The instruction executes.
Inp_FdbkA
BOOL
Inp_FdbkB
BOOL
Feedback input signals from device. Use the feedback configuration parameters (for example,
Cfg_FdbkSt0Check and Cfg_FdbkSt0State) to determine how these inputs are used to determine
actual state.
Inp_FdbkC
BOOL
Inp_FdbkD
BOOL
Inp_DeviceFault
BOOL
Input Signal: Device fault from device
Inp_PermOK0
BOOL
1 = Permissives OK, device can be commanded to State 0
Inp_NBPermOK0
BOOL
1 = Non-Bypassable Permissives OK, device can be commanded to State 0
Inp_PermOK1
BOOL
1 = Permissives OK, device can be commanded to State 1
Inp_NBPermOK1
BOOL
1 = Non-Bypassable Permissives OK, device can be commanded to State 1
Inp_PermOK2
BOOL
1 = Permissives OK, device can be commanded to State 2
Inp_NBPermOK2
BOOL
1 = Non-Bypassable Permissives OK, device can be commanded to State 2
Inp_PermOK3
BOOL
1 = Permissives OK, device can be commanded to State 3
Inp_NBPermOK3
BOOL
1 = Non-Bypassable Permissives OK, device can be commanded to State 3
Inp_IntlkOK
BOOL
1 = Interlocks OK
0 = Not OK, go to State 0
Inp_NBIntlkOK
BOOL
1 = Non-bypassable Interlocks OK
0 = Not OK, go to State 0
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
15
Discrete 2-, 3-, 4-state Device (P_D4SD)
Table 2 - P_D4SD Input Parameters
Input Parameter
Data Type
Default
Description
Inp_IOFault
BOOL
Input Communication Status
0 = OK
1 = Fail
Inp_Sim
BOOL
1 = Simulate working device
0 = Control actual device
Inp_Hand
BOOL
1 = Select Hand (hard-wired) mode
Alias for Mode.Inp_Hand
Inp_Ovrd
BOOL
1 = Select Override mode
Alias for Mode.Inp_Ovrd
Inp_OvrdCmd
DINT
Override mode device command:
0 = None
1 = State 0
2 = State 1
3 = St.ate 2
4 = State 3
Inp_Reset
BOOL
1 = Reset all fault conditions and latched alarms
Cfg_St0onShed
BOOL
1 = Go to State 0 on Shed
0 = Hold position on Shed
Cfg_NumStates
DINT
Number of device states (24)
Cfg_OutSt0Write
SINT
2#0000_1111
Cfg_OutSt0State
SINT
2#0000_0001
Cfg_OutSt1Write
SINT
2#0000_1111
Cfg_OutSt1State
SINT
2#0000_0010
Cfg_OutSt2Write
SINT
2#0000_1111
These configuration parameters determine how the outputs are used to command state. The parameter
Cfg_OutSt[x]Write configures which outputs get written for each state. The parameter
Cfg_OutSt[x]State configures what gets written for each state.
For example, if all outputs must be set to 0 except Out_A which must be set to 1 to command the device
to state 1, then Cfg_OutSt1Write should be 2#0000_1111 and Cfg_OutSt1State should be
2#0000_0001.
By default, all four outputs are written in every state, with a single output set to 1 in each state.
Cfg_OutSt2State
SINT
2#0000_0100
Cfg_OutSt3Write
SINT
2#0000_1111
Cfg_OutSt3State
SINT
2#0000_1000
Cfg_FdbkSt0Check
SINT
2#0000_0000
Cfg_FdbkSt0State
SINT
2#0000_0001
Cfg_FdbkSt1Check
SINT
2#0000_0000
Cfg_FdbkSt1State
SINT
2#0000_0010
Cfg_FdbkSt2Check
SINT
2#0000_0000
Cfg_FdbkSt2State
SINT
2#0000_0100
Cfg_FdbkSt3Check
SINT
2#0000_0000
Cfg_FdbkSt3State
SINT
2#0000_1000
Cfg_HasPerm0Obj
BOOL
1 = Tells HMI a P_Perm is connected to Inp_PermOK0
Cfg_HasPerm1Obj
BOOL
1 = Tells HMI a P_Perm is connected to Inp_PermOK1
Cfg_HasPerm2Obj
BOOL
1 = Tells HMI a P_Perm is connected to Inp_PermOK2
Cfg_HasPerm3Obj
BOOL
1 = Tells HMI a P_Perm is connected to Inp_PermOK3
Cfg_HasIntlkObj
BOOL
1 = Tells HMI a P_Intlk is connected to Inp_IntlkOK
Cfg_PCmdClear
BOOL
When this parameter is 1, program commands are cleared once they are acted upon. When set to 0,
program commands remain set until cleared by the application program logic. This parameter is aliased
to internal tag Mode.Cfg_PCmdClear from P_Mode.
IMPORTANT: Clearing this parameter online may cause unintended program command execution.
16
These configuration parameters determine how the inputs are used to determine state. The parameter
Cfg_FdbkSt[x]Check configures which inputs get checked for each state. The parameter
Cfg_FdbkSt[x]State configures the values of the inputs which determine each state.
For example, if the device returns a 0 to Inp_FdbkA and Inp_FdbkB and a 1 to Inp_FdbkC when the
device is in state 3, then Cfg_FdbkSt3Check should be 2#0000_0111 and Cfg_FdbkSt1Write should
be 2#0000_0100.
By default, all inputs are dont care in every state (no feedback checking).
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Discrete 2-, 3-, 4-state Device (P_D4SD)
Table 2 - P_D4SD Input Parameters
Input Parameter
Data Type
Default
Description
Cfg_ProgDefault
BOOL
This parameter defines the default mode. When this parameter is 1, the mode defaults to Program if no
mode is being requested. When this parameter is 0, the mode defaults to Operator if no mode is being
requested. This parameter is aliased to internal tag Mode.Cfg_ProgDefault of P_Mode.
IMPORTANT: Changing this parameter online may cause unintended mode changes.
Cfg_OCmdResets
BOOL
1 = New Operator state command resets fault
0 = Reset required to clear fault
Cfg_OvrdPermIntlk
BOOL
1 = Override mode ignores Bypassable Permissives/ Interlocks
0 = Override mode uses Bypassable Permissives/Interlocks
Cfg_ShedOnFail
BOOL
1 = Go to shed state and alarm on fail to reach position
0 = Alarm only on fail
Shed state is determined by configuration parameter Cfg_St0onShed.
Cfg_ShedOnDeviceFault
BOOL
1 = Go to State 0 and alarm on device fault
0 = Alarm only on device fault
Shed state is determined by configuration parameter Cfg_St0onShed.
Cfg_ShedOnIOFault
BOOL
1 = Go to State 0 and alarm on I/O fault
0 = Alarm only on I/O fault
Shed state is determined by configuration parameter Cfg_St0onShed.
Cfg_HasFailAlm
BOOL
1 = Fail to reach state alarm exists and will be checked
Alias for Fail.Cfg_Exists
Cfg_HasDeviceFaultAlm
BOOL
1 = Device fault alarm exists and will be checked
Alias for DeviveFault.Cfg_Exists
Cfg_HasIntlkTripAlm
BOOL
1 = Interlock trip alarm exists and will be checked
Alias for IntlkTrip.Cfg_Exists
Cfg_HasIOFaultAlm
BOOL
1 = I/O fault alarm exists and will be checked
Alias for IOFault.Cfg_Exists
Cfg_FailResetReqd
BOOL
Cfg_DeviceFaultResetReqd
BOOL
Cfg_IntlkTripResetReqd
BOOL
Cfg_IOFaultResetReqd
BOOL
This parameter determines whether a reset is required to clear the alarm status. When this parameter
is 1, the alarm is latched On when the alarm occurs. After the alarm condition returns to normal, a reset
is required to clear the alarm status (for example, OCmd_Reset, Inp_Reset, or Fail.OCmd_Reset would
be required to clear the Fail alarm after the alarm is set and the value returns to normal). When this
parameter is 0, no reset is required and the alarm status is cleared when the alarm condition returns to
normal. This parameter is aliased to internal tag .Cfg_ResetReqd of the corresponding P_Alarm object.
IMPORTANT: If the reset clears the alarm, it also acknowledges the alarm.
Cfg_FailAckReqd
BOOL
Cfg_DeviceFaultAckReqd
BOOL
Cfg_IntlkTripAckReqd
BOOL
Cfg_IOFaultAckReqd
BOOL
Cfg_FailSeverity
SINT
Cfg_DeviceFaultSeverity
SINT
Cfg_IntlkTripSeverity
SINT
Cfg_IOFaultSeverity
SINT
These parameters determine the severity of each alarm. This drives the color and symbol that are used
to indicate alarm status on the faceplate and global object. This parameter is aliased to internal tag
.Cfg_Severity of the associated P_Alarm object. The following are valid values:
1 = Information
2 = Warning
3 = Exception
4 = Fault
IMPORTANT: This severity parameter drives only the indication on the global object and faceplate. The
Alarms and Events definition severity drives the color and symbol that is used on the alarm banner and
alarm summary as well as the value returned by FactoryTalk Alarms and Events display commands.
Cfg_OutAPulseT
REAL
0.0
Time to pulse Output A (s) (0=output held continuously)
Cfg_OutBPulseT
REAL
0.0
Time to pulse Output B (s) (0=output held continuously)
Cfg_OutCPulseT
REAL
0.0
Time to pulse Output C (s) (0=output held continuously)
Cfg_OutDPulseT
REAL
0.0
Time to pulse Output D (s) (0=output held continuously)
This parameter determines whether an acknowledgement is required for an alarm. When this
parameter is 1, the acknowledge (ack) bit is cleared when the alarm occurs. An acknowledge command
(for example, PCmd_FailAck or Fail.OCmd_Ack) would be required to acknowledge the alarm. When set
to 0, the Acknowledge bit is set when an alarm occurs indicating an acknowledged alarm and no
acknowledge command is required. This parameter is aliased to internal tag Cfg_AckReqd of the
corresponding P_Alarm object.
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
17
Discrete 2-, 3-, 4-state Device (P_D4SD)
Table 2 - P_D4SD Input Parameters
Input Parameter
Data Type
Default
Description
Cfg_SimFdbkT
DINT
Delay to echo back reaching state when in simulation (s)
Cfg_FailT
DINT
10
Time after new state requested to reach that state before fault (s)
PSet_Owner
DINT
Program owner request ID (non-zero) or release (zero)
PCmd_St0
BOOL
Program command to set device to State 0
PCmd_St1
BOOL
Program command to set device to State 1
PCmd_St2
BOOL
Program command to set device to State 2
PCmd_St3
BOOL
Program command to set device to State 3
PCmd_Acq
BOOL
Program command to Acquire ownership (Oper ator to Program).
This parameter is aliased to internal tag Mode.PCmd_Acq of P_Mode. This parameter is reset
automatically, when Cfg_PCmdClear is 1.
PCmd_Rel
BOOL
Program command to Release ownership (Program to Operator).
This parameter is aliased to internal tag Mode.PCmd_Rel of P_Mode. This parameter is reset
automatically, when Cfg_PCmdClear is 1.
PCmd_Lock
BOOL
Program command to Lock Mode in Program.
This parameter is aliased to internal tag Mode.PCmd_Lock of P_Mode. This parameter is reset
automatically, when Cfg_PCmdClear is 1.
PCmd_Unlock
BOOL
Program command to Unlock Mode.
This parameter is aliased to internal tag Mode.PCmd_Unlock of P_Mode. This parameter is reset
automatically, when Cfg_PCmdClear is 1.
PCmd_Reset
BOOL
Program command to reset latched alarms and faults.
PCmd_FailAck
BOOL
Program command to acknowledge Fail alarm.
Alias for Fail,PCmd_Ack
PCmd_FailInhibit
BOOL
Program command to inhibit Fail alarm
This parameter is reset automatically, when Cfg_PCmdClear is 1.
Alias for Fail.PCmd_Inhibit
PCmd_FailUninhibit
BOOL
Program command to uninhibit Fail alarm
Alias for Fail.PCmd_Reset
PCmd_DeviceFaultAck
BOOL
Program command to acknowledge Device Fault alarm
Alias for DeviceFault.PCmd_Ack
PCmd_DeviceFaultInhibit
BOOL
Program command to Inhibit Device Fault alarm
Alias for DeviceFault.PCmd_Inhibit
PCmd_DeviceFaultUninhibit
BOOL
Program command to Uninhibit Device Fault alarm
Alias for DeviceFault.PCmd_Uninhibit
PCmd_IntlkTripAck
BOOL
Program command to acknowledge Interlock Trip alarm
Alias for IntlkTrip.PCmd_Ack
PCmd_IntlkTripInhibit
BOOL
Program command to inhibit Interlock Trip alarm
Alias for IntlkTrip.PCmd_Inhibit
PCmd_IntlkTripUninhibit
BOOL
Program command to uninhibit Interlock Trip alarm
Alias for IntlkTrip.PCmd_Uninhibit
PCmd_IOFaultAck
BOOL
Program command to acknowledge I/O Fault alarm
Alias for IOFault.PCmd_Ack
PCmd_IOFaultInhibit
BOOL
Program command to inhibit I/O Fault alarm
Alias for IOFault.PCmd_Inhibit
PCmd_IOFaultUninhibit
BOOL
Program command to uninhibit I/O Fault alarm
Alias for IOFault.PCmd_Uninhibit
OCmd_St0
BOOL
Operator command to set device to State 0
18
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Discrete 2-, 3-, 4-state Device (P_D4SD)
Table 2 - P_D4SD Input Parameters
Input Parameter
Data Type
Default
Description
OCmd_St1
BOOL
Operator command to set device to State 1
OCmd_St2
BOOL
Operator command to set device to State 2
OCmd_St3
BOOL
Operator command to set device to State 3
OCmd_Bypass
BOOL
Operator command to bypass all bypassable Interlocks and Permissives
OCmd_Check
BOOL
Operator command to check (not bypass) all Interlocks and Permissives
MCmd_Disable
BOOL
Maintenance command to disable device
MCmd_Enable
BOOL
Maintenance command to enable (allow to turn ON) device
OCmd_Reset
BOOL
Operator command to reset all alarms requiring reset and any latched shed conditions
OCmd_ResetAckAll
BOOL
Operator command to reset and acknowledge all alarms and reset any latched shed conditions
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
19
Discrete 2-, 3-, 4-state Device (P_D4SD)
Discrete 2-, 3-, or 4-state Device Output Structure
Output parameters include the following:
Output data elements (Out_) are the primary outputs of the instruction,
typically used by hardware output modules; however, they may be used by
other application logic.
Value data elements (Val_) are numeric outputs of the instruction for
use by the HMI. Values also may be used by other application logic or
software packages.
Status data elements (Sts_) are bit outputs of the instruction for use by the
HMI. Status bits also may be used by other application logic.
Ready data elements (Rdy_) are bit outputs of the instruction used by the
HMI to enable or gray out Command buttons and Setting entry fields.
Table 3 - P_D4SD Output Parameters
Output Parameter
Data Type
Description
EnableOut
BOOL
Enable Output: The EnableOut signal is not manipulated by this instruction. Its output state always reflects
EnableIn input state
Out_A
BOOL
Output A to device
Out_B
BOOL
Output B to device
Out_C
BOOL
Output C to device
Out_D
BOOL
Output D to device
Val_Cmd
SINT
Device Command:
0 = None
1 = State 0
2 = State 1
3 = State 2
4 = State 3
Val_Sts
SINT
Device Confirmed Status:
0 = Powerup/Reset
1 = State 0
2 = State 1
3 = State 2
4 = State 3
9 = Moving
33 = Disabled
Val_Fault
SINT
Device Fault Status:
0 = None
16 = Position Fail
17 = Device Fault
32 = I/O Fault
34 = Configuration Error
20
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Discrete 2-, 3-, 4-state Device (P_D4SD)
Table 3 - P_D4SD Output Parameters
Output Parameter
Data Type
Description
Val_Mode
DINT
Mode enumeration:
0 = No mode
1 = Hand
2 = Maintenance
3 = Override
4 = Program (locked)
5 = Operator (locked)
6 = Program (unlocked, Oper is default)
7 = Operator (unlocked, Prog is default)
8 = Program (unlocked, Prog is default)
9 = Operator (unlocked, Oper is default)
Alias for Mode.Val
Val_Owner
DINT
Current object owner ID (0=not owned)
Val_Notify
SINT
Current alarm level and Acknowledgement (enumeration):
0 = No alarm
1 = Alarm cleared, not acknowledged
2 = Information alarm
3 = Unacknowledged information alarm
4 = Warning alarm
5 = Unacknowledged warning alarm
6 = Exception alarm
7 = Unacknowledged exception alarm
8 = Fault alarm
9 = Unacknowledged fault alarm
Sts_St0
BOOL
1 = Device commanded to and confirmed in State 0
Sts_St1
BOOL
1 = Device commanded to and confirmed in State 1
Sts_St2
BOOL
1 = Device commanded to and confirmed in State 2
Sts_St3
BOOL
1 = Device commanded to and confirmed in State 3
Sts_Moving
BOOL
1 = Device not yet confirmed in commended state
Sts_Available
BOOL
1 = Device available for control by automation (Program)
Sts_Bypass
BOOL
1 = Bypassable interlocks and permissives are bypassed
Sts_BypActive
BOOL
1 = Interlock / permissive bypassing active (Bypassed or Maintenance mode)
Sts_Disabled
BOOL
1 = Device is disabled (output held OFF)
Sts_NotRdy
BOOL
1 = Device is not ready to be operated
Sts_MaintByp
BOOL
1 = Device has a Maintenance Bypass function active
Sts_AlmInh
BOOL
1 = One or more alarms inhibited, disabled or suppressed
Sts_Err
BOOL
1 = Error in configuration: see detail bits for reason
Err_Timer
BOOL
1 = Error in configuration: feeback check timer preset (use 02,147,483 seconds)
Err_Sim
BOOL
1 = Error in configuration: simulation timer preset (use 02,147,483 seconds)
Err_Alarm
BOOL
1 = Error in configuration: alarm minimum on time or severity
Sts_Hand
BOOL
1 = Mode is Hand (supersedes Maintenance, Override, Program, Operator)
Alias for Mode.Sts_Hand
Sts_Maint
BOOL
1 = Mode is Maintenance (supersedes Override, Program, Operator)
Alias for Mode.Sts_Maint
Sts_Ovrd
BOOL
1 = Mode is Override (supersedes Program, Operator)
Alias for Mode.Sts_Ovrd
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
21
Discrete 2-, 3-, 4-state Device (P_D4SD)
Table 3 - P_D4SD Output Parameters
Output Parameter
Data Type
Description
Sts_Prog
BOOL
1 = Mode is Program (auto)
Alias for Mode.Sts_Prog
Sts_Oper
BOOL
1 = Mode is Operator (manual)
Alias for Mode.Sts_Oper
Sts_ProgOperLock
BOOL
1 = Program or Operator has requested Mode Lock
Alias for Mode.Sts_ProgOperLock
Sts_NoMode
BOOL
1 = NoMode (disabled because EnableIn is false)
Alias for Mode.Sts_NoMode
Sts_Fail
BOOL
1 = Device failed to reach commanded state (one-shot)
Alias for Fail.Inp
Alm_Fail
BOOL
1 = Device failed to reach commended state
Alias for Fail.Alm
Ack_Fail
BOOL
1 = Fail to reach commanded state Alarm has been acknowledged
Alias for Fail.Ack
Sts_FailDisabled
BOOL
1 = Fail to reach commanded state Alarm has been disabled (will not be sent)
Alias for Fail.Disabled
Sts_FailInhibited
BOOL
1 = Fail to reach commanded state Alarm has been inhibited by logic
Alias for Fail.Inhibited
Sts_FailSuppressed
BOOL
1 = Fail to reach commanded state Alarm has been suppressed (logged only)
Alias for Fail.Suppressed
Sts_DeviceFault
BOOL
1 = Device fault (from Inp_DeviceFault)
Alias for DefaultFault.Inp
Alm_DeviceFault
BOOL
1 = Device fault alarm
Alias for DeviceFault.Alm
Ack_DeviceFault
BOOL
1 = Device fault alarm has been acknowledged
Alias for DeviceFault.Ack
Sts_DeviceFaultDisabled
BOOL
1 = Device fault alarm has been disabled (will not be sent)
Alias for DeviceFault.Disabled
Sts_DeviceFaultInhibited
BOOL
1 = Device fault alarm has been inhibited by logic
Alias for DeviceFault.Inhibited
Sts_DeviceFaultSuppressed
BOOL
1 = Device fault alarm has been suppressed (logged only)
Alias for DeviceFault.Suppressed
Sts_IntlkTrip
BOOL
1 = Device commanded to State 0 by an Interlock NOT OK (one-shot)
Alias for IntlkTrip.Inp
Alm_IntlkTrip
BOOL
1 =Alarm: Device set to State 0 by an Interlock NOT OK
Alias for IntlkTrip.Alm
Ack_IntlkTrip
BOOL
1 = Interlock Trip Alarm has been acknowledged
Alias for IntlyTrip.Ack
Sts_IntlkTripDisabled
BOOL
1 = Interlock Trip Alarm is disabled (not saved or sent)
Alias for IntlkTrip.Disabled
Sts_IntlkTripInhibited
BOOL
1 = Interlock Trip Alarm has been inhibited by logic
Alias for IntlkTrip.Inhibited
Sts_IntlkTripSuppressed
BOOL
1 = Interlock Trip Alarm has been suppressed (logged only)
Alias for IntlkTrip.Suppressed
22
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Discrete 2-, 3-, 4-state Device (P_D4SD)
Table 3 - P_D4SD Output Parameters
Output Parameter
Data Type
Description
Sts_IOFault
BOOL
I/O communication fault status
0 = OK
1 = Bad
Alias for IOFault.Inp
Alm_IOFault
BOOL
1 = I/O fault alarm
Alias for IOFault.Alm
Ack_IOFault
BOOL
1 = I/O fault alarm has been acknowledged
Alias for IOFault.Ack
Sts_IOFaultDisabled
BOOL
1 = I/O fault alarm is disabled (not saved or sent)
Alias for IOFault.Disabled
Sts_IOFaultInhibited
BOOL
1 = I/O fault alarm has been inhibited by logic
Alias for IOFault.Inhibited
Sts_IOFaultSuppressed
BOOL
1 = I/O fault alarm has been suppressed (logged only)
Alias for IOFault.Suppressed
Rdy_St0
BOOL
1 = Ready to receive OCmd_St0 (enables HMI button)
Rdy_St1
BOOL
1 = Ready to receive OCmd_St1 (enables HMI button)
Rdy_St2
BOOL
1 = Ready to receive OCmd_St2 (enables HMI button)
Rdy_St3
BOOL
1 = Ready to receive OCmd_St3 (enables HMI button)
Rdy_Bypass
BOOL
1 = Ready to receive OCmd_Bypass (enables HMI button)
Rdy_Check
BOOL
1 = Ready to receive OCmd_Check (enables HMI button)
Rdy_Disable
BOOL
1 = Ready to receive MCmd_Disable (enables HMI button)
Rdy_Enable
BOOL
1 = Ready to receive MCmd_Enable (enables HMI button)
Rdy_Reset
BOOL
1 = At least one alarm or latched shed requires reset
Rdy_ResetAckAll
BOOL
1 = At least one alarm or latched shed condition requires reset or acknowledged
P_D4SD
BOOL
Unique parameter name for auto - discovery
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
23
Discrete 2-, 3-, 4-state Device (P_D4SD)
Discrete 2-, 3-, or 4-state Device Local Configuration Tags
Configuration parameters that are arrayed, string, or structure data types cannot
be configured as parameters for Add-On Instructions. Configuration parameters
of these types appear as local tags to the Add-On Instruction. Local tags can be
configured through the HMI faceplates or in RSLogix 5000 software by opening
the Instruction Logic of the Add-On Instruction instance and then opening the
Data Monitor on a local tag. These parameters cannot be modified by using
controller logic or RSLogix 5000 software export/import functionality.
Table 4 - P_D4SD Local Configuration Tags
Tag Name
Data Type
Default
Description
Cfg_Desc
STRING_40
Discrete 2-, 3-, or
4-state Device
Description for display on HMI
Cfg_Label
STRING_20
Discrete Device
Label for graphic symbol displayed on HMI
Cfg_St0Text
STRING_8
Off
Text to display in State 0
Cfg_St1Text
STRING_8
On
Text to display in State 1
Cfg_St2Text
STRING_8
Text to display in State 2
Cfg_St3Text
STRING_8
Text to display in State 3
Cfg_Tag
STRING_20
P_D4SD
Tag name for display on HMI
24
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Discrete 2-, 3-, 4-state Device (P_D4SD)
Operations
This section describes the primary operations for this Add-On Instruction.
Modes
The Discrete 2-, 3-, 4-state Device Add-On Instruction uses the following
standard modes, implemented by using an embedded P_Mode
Add-On Instruction.
Mode
Description
Operator
The operator controls the state of the device by using the HMI faceplate.
Program
Logic outside the P_D4SD instruction controls the device by using Program Commands
(PCmd_St0, PCmd_St1, PCmd_St2, PCmd_St3).
Override
Priority logic outside the P_D4SD instruction controls the device. The default is to set the
device to State 0, but any state can be commanded. Bypassable interlocks and permissives
can optionally by bypassed in Override mode.
Maintenance
Maintenance personnel have control of the device by using the HMI faceplate and it is not
available for normal operation by operators or program logic. Bypassable permissives and
interlocks are bypassed; and checking for device failure to reach target position is
not performed.
Hand
Logic, usually hard-wired, has superseded P_D4SD control of the device. If device state
feedback inputs are used, the P_D4SD instruction tracks the state of the device (to the
extent that unique feedback patterns are used for the states) to facilitate bumpless
transfer back to one of the other modes.
Refer to the Process Add-On Instructions and Graphics: Mode (P_Mode)
Reference Manual, publication SYSLIB-RM005, for more information.
Execution
The following table explains the handling of instruction execution conditions.
Condition
Description
EnableIn False (false rung)
Handled the same as if the device were Disabled by
Command. The device outputs are de-energized and the
device is shown as Disabled on the HMI. The mode is
shown as NO MODE. All alarms are cleared.
Powerup (prescan, first scan)
On Prescan, any Commands received before First Scan are
discarded. The device is de-energized. On first scan, the
device is treated as if it were returning from Hand mode:
the instruction state is set based on the position feedback
received from the device.
Embedded P_Mode and P_Alarm instructions are
handled in accordance with their standard powerup
procedures. Refer to the P_Mode and P-Alarm reference
manuals for details.
Instruction first run
Instruction first run refers to the first time the instruction
executes with a new instance of a data structure. The
controller uses instruction first run to generate
coefficients and other data stores that do not change for a
function block after initial download.
Postscan
No SFC Postscan logic is provided.
Refer to the Logix5000 Controllers Add-On Instructions Programming Manual,
publication 1756-PM010, for more information.
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
25
Discrete 2-, 3-, 4-state Device (P_D4SD)
Alarms
The P_D4SD Instruction uses the following alarms, implemented by using
embedded P_Alarm Add-On Instructions.
Table 5 - P_D4SD Alarm Parameters
Alarm
P_Alarm Name
Description
Interlock Trip
IntlkTrip
Triggered when an Interlock not OK causes the device to transition from another state to State 0.
I/O Fault
IOFault
Triggered by the Inp_IOFault Input, usually used to indicate an I/O communication failure.
The device can be configured to either alarm only or to shed to State 0 on an I/O Fault.
Fail
Fail
Device failed to reach commanded position.
Device Fault
DeviceFault
Device fault from device via an input.
Generic Alarm Parameters
The following parameters of the P_Alarm object can be used for each alarm in
Table 5. These parameters are accessible by the following convention: [P_Alarm
Name].CP_Alarm Parameter] Configuration parameters for the alarms are
aliased to parameters that can be found in the input parameters table. For
example, Fail.Cfg_Exists can be accessed as parameter Cfg_HasFailAlm.
Table 6 - Generic Alarm Input Parameters
P_Alarm Parameter
Description
Inp
Alarm condition input 1 = Alarm
Inp_Reset
1 = Reset alarm requiring a reset
Cfg_AlmMinOnT
Program command to set alarm for minimum on time
PCmd_Reset
Program command to reset a latched alarm
PCmd_Ack
Program command to acknowledge an alarm
PCmd_Inhibit
Program command to inhibit an alarm (force Alm to 0)
PCmd_Uninhibit
Program command to uninhibit an alarm
OCmd_Reset
Operator command to reset a latched alarm
OCmd_Ack
Operator command to acknowledge an alarm
OCmd_Suppress
Operator command to suppress alarm
OCmd_Unsuppress
Operator command to unsuppress an alarm
MCmd_Disable
Maintenance command to disable an alarm (force Alm to 0)
MCmd_Enable
Maintenance command to enable an alarm
Table 7 - Generic Alarm Output Parameters
P_Alarm Parameter
Description
Rdy_Reset
1 = Ready to receive OCmd_Reset (enables the HMI button)
Rdy_Ack
1 = Ready to receive OCmd_Ack (enables the HMI button)
Rdy_Suppress
1 = Ready to receive OCmd_Suppress (enables the HMI button)
Rdy_Unsuppress
1 = Ready to receive OCmd_Unsuppress (enables the HMI button)
26
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Discrete 2-, 3-, 4-state Device (P_D4SD)
Table 7 - Generic Alarm Output Parameters
Rdy_Disable
1 = Ready to receive MCmd_Disable (enables the HMI button)
Rdy_Enable
1 = Ready to receive MCmd_Enable (enables the HMI button)
Val_Notify
Current alarm level and Acknowledgement (enumeration):
0 = No alarm
1 = Alarm cleared, not acknowledged
2 = Information alarm
3 = Unacknowledged information alarm
4 = Warning alarm
5 = Unacknowledged warning alarm
6 = Exception alarm
7 = Unacknowledged exception alarm
8 = Fault alarm
9 = Unacknowledged fault alarm
Alm
Alarm output: 1 = In alarm
Ack
Alarm acknowledged status: 1 = Acknowledged
Inhibited
1 = Alarm inhibited by logic (will not be sent)
Suppressed
1 = Alarm suppressed (not visible on the HMI)
Disabled
1 = Alarm disabled by operator (will not be sent)
Sts_Error
1 = Error in Config: see Err_bits for reason
Err_Timer
1 = Error in Config: Invalid timer preset (use 02,147,483)
Err_Severity
1 = Error in Config: Invalid Severity (use 14)
Refer to the Process Add-On Instructions and Graphics: Alarm (P_Alarm)
Reference Manual, publication SYSLIB-RM002, for more information.
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
27
Discrete 2-, 3-, 4-state Device (P_D4SD)
Programming Example
This example uses the P_D4SD Add-On Instruction to control a cooling fan that
has three fixed speeds (low, medium, high) and an off state. This is considered
a 4-state device. In this example, three digital outputs are used to set the speed
setting (when all three are off, the fan is commanded off ) and three digital inputs
providing feedback of the actual fan state (when all three are off, the fan is off ).
In this example, the four cooling fan states are being mapped to the device
as follows:
State 0 = Off
State 1 = Low
State 2 = Medium
State 3 = High
The parameter Cfg_NumStates should be set to 4, indicating this is a four-state
device. The input parameters for states 13 (Inp_FdbkB, Inp_FdbkC,
Inp_FdbkD) are connected to the digital inputs representing the status of the fan.
The output parameters for states 13 (Out_B, Out_C, Out_D) are connected
to the digital outputs that command the fan to the desired state.
28
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Discrete 2-, 3-, 4-state Device (P_D4SD)
Based on the wiring of the I/O, we can now configure the P_D4SD instruction
how we want to process the outputs to get to the desired state. We can do
this via the following table:
x = don't care, 1 = command output On, 0 = command output Off.
Table 8 - P-D4SD Example Outputs
Output A
Output B
Output C
Output D
State 0
State 1
State 2
State 3
We are setting Output A so it can be used for display purposes even though
Output A is not used by the cooling fan device. The parameter
Cfg_OutSt[x]Write determines which outputs get written for each state. The
parameter Cfg_OutSt[x]State determines the state that gets written. These
parameters are single integers where bit 0 represents output A and bit 3 represents
output D.
These parameters are displayed in binary format as indicated by the prefix 2#. By
using Table 8, we can set the settings as follows:
Cfg_OutSt0Write:
2#0000_1111
Cfg_OutSt0State:
2#0000_0001
Cfg_OutSt1Write:
2#0000_1111
Cfg_OutSt1State:
2#0000_0010
Cfg_OutSt2Write:
2#0000_1111
Cfg_OutSt2State:
2#0000_0100
Cfg_OutSt3Write:
2#0000_1111
Cfg_OutSt3State:
2#0000_1000
We can now repeat this same effort to configure how the P_D4SD instruction
determines actual state based on the field inputs via the following table:
x = don't care, 1 = status checked on, 0 = status checked off.
Table 9 - P_D4SD Example Inputs
Input A
Input B
Input C
Input D
State 0
State 1
State 2
State 3
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
29
Discrete 2-, 3-, 4-state Device (P_D4SD)
The parameter Cfg_FdbkSt[x]Check determines which feedback inputs to check
for each state. The parameter Cfg_FdbkSt[x]State determines how the state is
interpreted from the input values.
By using Table 9, we can set the settings as follows:
Cfg_FdbkSt0Check:
2#0000_1110
Cfg_FdbkSt0State:
2#0000_0000
Cfg_FdbkSt1Check:
2#0000_1110
Cfg_FdbkSt1State:
2#0000_0010
Cfg_FdbkSt2Check:
2#0000_1110
Cfg_FdbkSt2State:
2#0000_0100
Cfg_FdbkSt3Check:
2#0000_1110
Cfg_FdbkSt3State:
2#0000_1000
As this is a cooling fan, if there is a device mismatch or fault, we still want the
logic to command to the desired state. Therefore, Cfg_ShedOnFail and
Cfg_ShedOnDeviceFault are both set to 0.
Lastly, the following local configuration tags should be configured to drive the
text on the operations faceplate. In this example, the cooling fan P&ID tag is
M401. In this example, they are set as follows:
30
Cfg_Tag:
M401
Cfg_Label:
Line 4 Rectifier Fan
Cfg_Desc:
Line 4 Rectifier Cooling Fan
Cfg_St0Text:
Stopped
Cfg_St1Text:
Slow
Cfg_St2Text:
Medium
Cfg_St3Text:
Fast
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Discrete 2-, 3-, 4-state Device (P_D4SD)
Local tags can be configured through the HMI faceplates or in RSLogix 5000
software by opening the Instruction Logic of the Add-On Instruction instance
and then selecting the string on the displayed rung.
All the strings in local tags are shown on the first rung of the Add-On
Instruction's Logic routine for your convenience.
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
31
Discrete 2-, 3-, 4-state Device (P_D4SD)
A display element (global object) is created once and can be referenced multiple
times on multiple displays in an application. When changes are made to the
original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, in conjunction with tag structures
in the ControlLogix system, aid consistency and save engineering time.
Display Elements
IMPORTANT
Some display elements have different names in FactoryTalk View ME software
than in FactoryTalk View SE software. This is because display elements that
are shared among objects have to be instantiated separately in FactoryTalk
View ME software to make sure the correct faceplate is accessed from the
display element.
For the P_D4SD Add-On Instruction, the display element names are the same
for the FactoryTalk View SE software and the FactoryTalk View ME software.
Table 10 - P_D4SD Display Elements Description
Display Element Name
GO_P_D4SD_4Way
GO_P_D4SD_Diverter (top display)
GO_P_D4SD_Diverter1 (bottom display)
Display Element
Description
The Three/Four-way Valve parameters define the inlet
and output ports of the valve:
No. 110 - Top port open state
No. 111 - Right port open state
No. 112 - Bottom port open state
No. 113 - Left port open state
0 = Inlet (always shown as open)
1 = Open when Val_Sts = 1 (state 0)
2 = Open when Val_Sts = 2 (state 1)
3 = Open when Val_Sts = 3 (state 2)
4 = Open when Val_Sts = 4 (state 3)
The Two-way Diverter Valve parameters define the state
of the valve:
GO_P_D4SD _3WaySO_Rt (first display)
GO_P_D4SD _3WaySO_Lt (second display)
GO_P_D4SD _3WaySO_Btm (third display)
GO_P_D4SD _3WaySO_Top (fourth display)
32
State 0: Open top-left
State 1: Open top-right
State 2: N/A
State 3: N/A
Parameters define the inlet and output ports of the
Two-way Solenoid-operated Diverter Valve.
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Discrete 2-, 3-, 4-state Device (P_D4SD)
Table 10 - P_D4SD Display Elements Description
Display Element Name
Display Element
Description
GO_P_GO_P_D4SD_3WayMO_Rt (first display)
GO_P_GO_P_D4SD_3WayMO_Rt (second display)
GO_P_GO_P_D4SD_3WayMO_Rt (third display)
GO_P_GO_P_D4SD_3WayMO_Rt (fourth display)
Parameters define the inlet and output ports of the
Two-way Motor-operated Diverter Valve.
GO_P_D4SD_R (top display)
GO_P_D4SD_U (middle display)
GO_P_D4SD_D (bottom display)
Motors operating in different positions.
GO_P_D4SD_Inline_U (first display)
GO_P_D4SD_Inline_D (second display)
GO_P_D4SD_Inline_L (third display)
GO_P_D4SD_Inline_R (fourth display)
Inline motors operating in different positions.
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
33
Discrete 2-, 3-, 4-state Device (P_D4SD)
Table 10 - P_D4SD Display Elements Description
Display Element Name
Display Element
Description
GO_P_D4SD_Agitator_D
Agitator shown as a display element.
GO_P_D4SD_Mixer_U
Mixer shown as a display element.
GO_P_D4SD_Blower_R (first display)
GO_P_D4SD_Blower_U (second display)
GO_P_D4SD_Blower_L (third display)
GO_P_D4SD_Blower_D (fourth display)
Blowers operating in different positions.
GO_P_D4SD_Pump_R
GO_P_D4SD_Pump_U
GO-P_D4SD_Pump_L
Pumps operating in different positions.
GO_P_D4SD_RPump_U
Rotary Gear Pump shown as a display element.
GO_P_D4SD_Fan_D
Fan shown as a display element.
34
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Discrete 2-, 3-, 4-state Device (P_D4SD)
Table 10 - P_D4SD Display Elements Description
Display Element Name
Display Element
Description
GO_P_D4SD_Conveyor_R
Conveyor shown as a display element.
Common attributes of the P_D4SD global objects include the following:
Current state of the inputs in text
Status/Quality indicator
Maintenance Bypass indicator
Label
Color changing alarm border that blinks on unacknowledged alarm
Alarm indicator that changes color with the severity of an alarm
Maintenance Bypass
Alarm Indicator
Status/Quality Indicator
Status/Quality Indicators
One of these symbols appears to the left of the graphic symbol or right of the
label when the described condition is true.
Graphic Symbol
Description
Invalid configuration
I/O Fault
Value uncertain
The device is not ready to operate
No symbol displayed
TIP
I/O quality good and configuration valid
When the Invalid Configuration Indicator appears, you can find what
configuration setting is invalid by following the indicators. Click the graphic
symbol to call up the faceplate. The Invalid Configuration indicator appears
next to the appropriate tab at the top of the faceplate to guide you in finding
the configuration error. Once you navigate to the tab, the misconfigured item
will be flagged with this indicator or appear in a magenta box.
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
35
Discrete 2-, 3-, 4-state Device (P_D4SD)
Maintenance Bypass Indicator
This symbol appears to the right of the Label to indicate that a Maintenance
Bypass has been activated.
Graphic Symbol
Description
A Maintenance Bypass is active
No symbol displayed
TIP
No Maintenance Bypass active
When the Maintenance Bypass Indicator appears, you can find what condition
was bypassed by following the indicators. Click the graphic symbol to call up
the faceplate. The Maintenance Bypass Indicator will appear next to the
appropriate tab at the top of the faceplate to guide you in finding the bypass.
Once you navigate to the tab, the bypassed item will be flagged with this
indicator.
Alarm Indicators
One of these symbols appears to the left of the Label to indicate the described
alarm condition. The alarm border and label background blink if
Acknowledgement of an alarm condition is required.
Symbol
Description
Black I in white box
White bell, border, and text
background blinking
Return to Normal (no Alarm condition), but a previous
Alarm has not been acknowledged
Blue border and text background
Yellow rectangle with explanation point (!)
Information Severity Alarm
Yellow border and text background
Orange triangle with explanation point (!)
Warning Severity Alarm
Red border and text background
Orange diamond with explanation point (!)
Exception Severity Alarm
Magenta border and text background
Red circle with two explanation points (!!)
No symbol or border displayed, text is on normal (light
gray) background, not blinking
36
Alarm Inhibit: an alarm is inhibited by the Program,
Disabled by Maintenance, or Suppressed by the Operator
Fault Severity Alarm
No Alarm or Alarm Inhibit condition, and all
Alarms are Acknowledged
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Discrete 2-, 3-, 4-state Device (P_D4SD)
Use Global Objects
The global objects for this instruction can be found in the global object file
(RA-BAS) P_D4SD Graphics Library.ggfx. Complete the following to use a
global object.
1. Copy it from the global object file and paste it in the display file.
2. In the display file, right-click the global object file and choose Global
Object Parameter Values.
The Global Object Parameter Values dialog box appears.
3. Type the tag in the Value column as specified in the Description column.
TIP
You can click the ellipsis () to browse and select a tag.
Values for items marked (optional) may be left blank.
4. Click OK.
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
37
Discrete 2-, 3-, 4-state Device (P_D4SD)
The P_D4SD faceplate consists of five tabbed pages. The Operator tab is
displayed when the faceplate is initially called up. Click the appropriate icon at
the top of the faceplate to access a specific tab.
Faceplate
Maintenance
Operator
Alarm Configuration
Engineering
Alarms
Exit
Help
The faceplate provides the means for operators, maintenance workers, engineers,
and others to interact with the P_D4SD Instruction instance, including viewing
its status and values and manipulating it through its commands and settings.
When a given input is restricted via FactoryTalk View security, the required user
security code letter is shown in the tables that follow.
Operator Tab
Mode Indicator
Reset Acknowledge
All Alarms Button
Requested Modes Indicator
Device State
Indicator
Device Command Buttons
Input Status Indicator
38
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Discrete 2-, 3-, 4-state Device (P_D4SD)
The Operator tab shows the following information:
The current Mode (Program, Operator, Override, Maintenance,
or Hand)
Requested Modes Indicator (This only appears if the Operator or Program
Mode has been superseded by another mode.)
Device states
Permissive states
Communication status (Comm or I/O Fault)
The following table shows the functions included on the Operator tab.
Table 11 - Operator Tab Description
Function
Action
Security
Click to release Operator mode lock.
Manual Device
Operation (Code B)
Click to lock in Operator mode.
Click to reset and acknowledge all alarms.
Acknowledge Alarms
(Code F)
Click to command the device to a state.
None
There are up to four Permissive status indicators/buttons.
Click the button beside each state to view the faceplate for
Permissives associated with that state. The Permissive button
appears when Cfg_HasPerm0Obj, Cfg_HasPerm1Obj,
Cfg_HasPerm2Obj, or Cfg_HasPerm3Obj is set.
Click to open the interlock faceplate for the device. This
button appears if Cfg_HasIntlkObj is set and opens the
faceplate associated with the P_Intlk instruction configured
in the global object instance.
When the P_D4SD instruction does not have associated Permissive (P_Perm)
instructions, the Permissive buttons revert to indicators only.
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
39
Discrete 2-, 3-, 4-state Device (P_D4SD)
The following table shows the alarm status on the Operator tab.
Table 12 - Operator Tab Alarm Status
Graphic Symbol
Alarm Status
In Alarm (Active Alarm)
In Alarm and Acknowledged
Out of Alarm but Not Acknowledged
Alarm Suppressed (by Operator) (Alarm is logged but
not displayed)
Alarm Disabled (by Maintenance)
Alarm Inhibited (by Program Logic)
40
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Discrete 2-, 3-, 4-state Device (P_D4SD)
Maintenance Tab
This tab is divided into two pages.
Page 1 of the Maintenance tab shows the following information:
The current mode (Program, Operator, Override, Maintenance, or Hand)
Requested Modes Indicator - This display highlights all of the modes that
have been requested. The leftmost highlighted mode is the active mode
Shows whether the device is enabled or disabled
Shows Permissive Bypassed/Enabled Indicator
Shows whether Override mode bypasses the bypassable permissives
Maintenance Tab Page 1
Maintenance Mode
Acquire and Release
Command Buttons
Mode Indicator
Requested Modes Indicator
Device Enable and
Disable Command
Buttons
Interlock and Permissive
Bypass and Enable
Command Buttons
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
41
Discrete 2-, 3-, 4-state Device (P_D4SD)
The following table shows the functions on the Maintenance tab page 1.
Function
Action
Security
Configuration Parameters
Click to release device from
Maintenance mode
Equipment
Maintenance
(Code C)
None
Click to place device in
Maintenance mode
Click to enable the device
Click to disable the device
Click to enable checking of all
permissives and interlocks
Click to bypass checking of
bypassable permissives and
interlocks
In Override Mode,
bypass Interlocks
and Permissives
that can be
bypassed
42
Check this box to bypass the
bypassable permissives and
interlocks in Override mode
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Disable Alarms
Bypass
Permissives
and Interlocks
(Code H)
Cfg_OvrdPermIntlk
Discrete 2-, 3-, 4-state Device (P_D4SD)
Maintenance Tab Page 2
Page 2 of the Maintenance tab shows data entry fields for several
configuration parameters.
The following table shows the functions on the Maintenance tab page 2.
Table 13 - Maintenance Tab 2 Description
Function
Action
Security
Configuration Parameters
Time to pulse:
Output A (sec)
Output B (sec)
Output C (sec)
Output D (sec)
Type a value to indicate the time
(seconds) to energize outputs to the
device to be sure they are latched in.
(0 = output held continuously)
Configuration
& Tuning
Maintenance
(Code D)
Time after new
state requested to
reach that state
before Fault (sec)
Type a value to indicate the time
(seconds) to allow the device to reach
state before issuing a fault.
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Cfg_OutAPulseT
Cfg_OutBPulseT
Cfg_OutCPulseT
Cfg_OutDPulseT
Cfg_FailT
43
Discrete 2-, 3-, 4-state Device (P_D4SD)
Engineering Tab
This tab is divided into three pages.
On Page 1 of the Engineering tab, you can configure the description, label, tag,
and state names for the device.
Engineering Tab Page 1
Mode Configuration Button
Configure Device Description,
Label, and Tag Text
The following table lists the functions on the Engineering tab page 1.
Table 14 - Engineering Tab 1 Description
Function
44
Action
Security
Configuration Parameters
Click to navigate to the Mode
Configuration popup.
None
See popup on page 45.
Description
Type the device description to show
on the Faceplate title bar.
Cfg_Desc
Label
Type the label to show on the Graphic
Symbol.
Engineering
Configuration
(Code E)
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Cfg_Label
Discrete 2-, 3-, 4-state Device (P_D4SD)
Table 14 - Engineering Tab 1 Description
Function
Action
Security
Configuration Parameters
Tag
Type the tag name to show on the
Faceplate and Tooltip.
Important: Pausing the mouse over
this field will display a tool tip with
the configured Logix tag/path.
Engineering
Configuration
(Code E)
Cfg_Tag
Text to Display in:
State 0:
State 1:
State 2:
State 3:
Type text to describe the state.
Number of States:
2
3
4
Select the number of states.
Cfg_NumStates
Clear Program
Commands on
Receipt
Set this parameter to the following:
ON to use Edge-triggered Program
Commands (default).
OFF to use Level-triggered
Program Commands.
Cfg_PCmdClear
New operator
command resets
fault
Check this box to reset a fault upon a
new operator command.
Cfg_OCmdResets
Cfg_St0Text
Cfg_St1Text
Cfg_St2Text
Cfg_St3Text
Mode Configuration Popup
This popup lets you set the Cfg_ProgDefault parameter, which sets the default
mode when no mode is being requested. Changing the parameter requires
engineering access (security code E).
IMPORTANT
If no mode is being requested, changing the default mode will change the
mode of the instruction.
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
45
Discrete 2-, 3-, 4-state Device (P_D4SD)
Engineering Tab Page 2
The following table shows the functions on the Engineering tab page 2.
Table 15 - Engineering Tab 2 Description
46
Function
Action
Security
Configuration Parameters
A P_Perm object is
connected to:
Inp_PermOK0
Inp_PermOK1
Inp_PermOK2
Inp_PermOK3
Check a box to have the P_Perm
instruction used with this device for
open Permissives. This changes the
Permissive Indicator to a button that
accesses the Permissive faceplate.
Engineering
Configuration
(Code E)
A P_Intlk object is
connected to
Inp_Intlk
Check this box to have a P_Intlk
object connected to an interlock trip.
Outputs and
Feedback
Click the state to open a popup
window to see what is enabled.
Cfg_HasPerm0Obj
Cfg_HasPerm1Obj
Cfg_HasPerm2Obj
Cfg_HasPerm3Obj
Cfg_HasIntklObj
None
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
See popup on page 47.
Discrete 2-, 3-, 4-state Device (P_D4SD)
State Configuration Popup
This popup directs how the P_D4SD instruction commands the device state via
outputs and determines the actual device state via feedback inputs. The first two
columns for output set parameters, Cfg_OutSt[x]Write, and
Cfg_OutSt[x]Value, determine how outputs are written to command to a state.
The second two columns for feedback set parameters, Cfg_FdbkSt[x]Check, and
Cfg_FdbkSt[x]State, determine how the state is interpreted from the
input values.
Changing the parameters requires engineering access (security code E).
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
47
Discrete 2-, 3-, 4-state Device (P_D4SD)
Engineering Tab Page 3
The following table shows the functions on the Engineering tab page 3.
Table 16 - Engineering Tab 3 Description
Function
Action
Security
Configuration Parameters
Shed Action
Go to State 0
Click the radio button to determine
whether you hold position or go to
state 0 upon a shed condition.
Engineering
Configuration
(Code E)
Cfg_St0onShed
Hold State
48
Shed Triggers:
Click the respective box to enable
whether an I/O Fault, Device Fault,
or Failure to Reach State is
considered a shed condition.
The device always sheds an Interlock
Trip. This item cannot be unchecked.
It is displayed as a reminder that the
Interlock Trip function always
triggers a shed.
Cfg_ShedonDeviceFault
Cfg_ShedonIOFault
Cfg_ShedonFail
Delay to echo back
ON/OFF status in
Simulation (sec)
Type a value (seconds) to indicate
the delay to echo back reaching
state when in simulation.
Cfg_SimFdbkT
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Discrete 2-, 3-, 4-state Device (P_D4SD)
Alarm Configuration Tab
The Alarm Configuration tab contains configuration related to the alarm status
for the device.
Alarm Configuration Tab Page 1
The following table shows the functions on the Alarm Configuration tab page 1.
Table 17 - Alarm Configuration Tab 1 Description
Function
Action
Security
Alarm
Click for a checkmark to indicate the Engineering
alarm exists for this alarm parameter. Configuration
(Code E)
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Configuration Parameters
Cfg_HasFailAlm
Cfg_HasDeviceFaultAlm
Cfg_HasIntlkTripAlm
Cfg_HasIOFaultAlm
49
Discrete 2-, 3-, 4-state Device (P_D4SD)
Table 17 - Alarm Configuration Tab 1 Description
50
Function
Action
Security
Configuration Parameters
Acknowledge
Required
Require acknowledgement of the
alarm.
If using FactoryTalk View Alarm and
Events software, configure its Alarm
Tag with Acknowledge Required. The
controller handles acknowledgement
within this instruction.
Engineering
Configuration
(Code E)
Cfg_FailAckReqd
Cfg_DeviceFaultAckReqd
Cfg_IntlkTripAckReqd
Cfg_IOFaultAckReqd
Reset Required
Require a reset to clear the alarm
status. There is a single alarm reset
that resets all of the alarms for the
device.
If using FactoryTalk View Alarm and
Events software, do not check
Latched. The controller handles the
alarm latching and reset within
this instruction.
Cfg_FailResetReqd
Cfg_DeviceFaultResetReqd
Cfg_IntlkTripResetReqd
Cfg_IOFaultResetReqd
Severity
These parameters determine the
severity of each alarm. The following
are valid values:
1 = Information (blue)
2 = Warning (yellow)
3 = Exception (red)
4 = Fault (magenta)
Important: The Severity is used to
drive the color of the indication of the
global object and faceplate when the
alarm is active.
If using FactoryTalk View Alarm and
Events software, the severity in the
alarm tag must be set to align with
the configuration value. Typical
values are the following:
Severity 1: 1250
Severity 2: 251500
Severity 3: 501750
Severity 4: 7511000
Cfg_FailSeverity
Cfg_DeviceFaultSeverity
Cfg_IntlkTripSeverity
Cfg_IOFaultSeverity
Alarm Minimum ON
Time (seconds)
When an Alarm occurs, the Alarm
output will be held on for at least this
amount of time (sec). If set to 5
seconds or less, the Alarm output will
be held on for at least 5 seconds to
ensure it is seen by polling. Set this
time higher if you want an Alarm to
be held in the Alarm state (and on
the Alarm summary) longer. This will
keep it visible to the Operator, or keep
the Alarm from clearing and being
set again (for an intermittent
condition) until the Operator has had
time to perform any Alarm-related
actions.
Important: If the alarm is
configured with Reset Required
(Cfg_ResetReqd = 1), the operator
can reset the alarm before this time
expires if the input condition has
returned to normal.
Fail.Cfg_AlmMinOnT
DeviceFault.Cfg_AlmMinOnT
IntlkTrip.Cfg_AlmMinOnT
IOFault.Cfg_AlmMinOnT
Code D
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Discrete 2-, 3-, 4-state Device (P_D4SD)
Alarms Tab
The Alarms tab displays each configured alarm for the P_D4SD instruction.
The icon on the tab for the Alarms page changes color based on the current active
alarms. A blinking alarm icon indicates that one or more alarms must be
acknowledged or the device must be reset.
Alarm Acknowledge
Command and Button
Reset and Acknowledge All
Alarms Command Button
If an alarm is active, the panel behind the alarm changes color to match the
severity of the alarm. The color of the bell icon at the top of the faceplate
shows the highest active alarms severity, and the icon blinks if any alarm
is unacknowledged.
Table 18 - Alarm Color Definitions
Color
Definition
Magenta
Fault
Red
Exception
Yellow
Warning
Blue
Information
White (bell icon)
Alarm has cleared but is unacknowledged
Background (light gray)
No alarm
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
51
Discrete 2-, 3-, 4-state Device (P_D4SD)
The following table shows the function on the Alarms tab.
Table 19 - Alarms Tab Description
Function
Action
Security
Click to acknowledge the alarm.
Acknowledge Alarms
(Code F)
Click to reset and acknowledge
all alarms.
Acknowledge Alarms
(Code F)
The panel behind the alarm blinks if the alarm requires acknowledgement.
Click the button with the checkmark to acknowledge the alarm.
The Alarm Acknowledge button is enabled if the corresponding alarm
requires acknowledgement.
The Reset and Acknowledge All Alarms button is enabled if any alarm requires
reset or acknowledgement.
52
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Discrete 2-, 3-, 4-state Device (P_D4SD)
Discrete 2-, 3-, 4-state Device Faceplate Help
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
53
Discrete 2-, 3-, 4-state Device (P_D4SD)
Notes:
54
Rockwell Automation Publication SYSLIB-RM028A-EN-P - August 2012
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products.
At http://www.rockwellautomation.com/support, you can find technical manuals, technical and application notes, sample
code and links to software service packs, and a MySupport feature that you can customize to make the best use of these
tools. You can also visit our Knowledgebase at http://www.rockwellautomation.com/knowledgebase for FAQs, technical
information, support chat and forums, software updates, and to sign up for product notification updates.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer
TechConnectSM support programs. For more information, contact your local distributor or Rockwell Automation
representative, or visit http://www.rockwellautomation.com/support/.
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this
manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada
1.440.646.3434
Outside United States or Canada
Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell
Automation representative.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the
manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States
Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
distributor to complete the return process.
Outside United States
Please contact your local Rockwell Automation representative for the return procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this