Study On New Type of IED With Integrated Functions
Study On New Type of IED With Integrated Functions
Abstract: Intelligent substation is the most important aspect of Smart Grid constructing. There are many problems during
intelligent reconstruction of conventional substation, one of which is to add a variety of secondary equipments. To address this
problem, the paper puts forward two distributed configuration schemes of secondary devices using the IED with integrated
functions of process level and bay level in intelligent substation. Compared with the normal configuration scheme, the
distributed schemes bring a significant reduction of IED. Based on the new schemes, the authors design a new type of
integrated IED, which completely realizes merging-unit, intelligent-terminal, measurement-control and protection functions.
The integrated IED is composed of four dominating parts: Main Processor Model, Data Processing Model, FPGA Integrated
Model and Intelligent Control Model. The IED can receive sampled values from electronic transformers and Ethernet frames
following IEC 61850-9-2 from other merging units. The information model of the integrated IED is established according to
IEC 61850 standard. In conclusion, the integrated IED is especially suit for intelligent reconstruction of lower voltage
substation with the characteristic of reasonable design, superior performance and cost effective.
Keyword: intelligent substation, intelligent
measurement-control and protection
electronic
device,
process
level,
bay
level,
merging
unit,
1 Introduction
Intelligent substation is the most important aspect of Smart
Grid constructing. An essential step toward the development
of an intelligent substation is to introduce digitized primary
equipments and secondary equipments.
Data acquisition and transmission of intelligent
substation is quite different from conventional substation. In
intelligent substation, the automation systems involve three
functional levels [1, 2]: station level, bay level and process
level. The information is exchanged among the IEDs
absolutely trough communication network. The normal
architecture of intelligent substation is shown in Fig.1.
Especially, the process level should be separated into two
parts independently, i.e. SV network and GOOSE network.
After years of theoretical research and product
development, the typical configuration of secondary devices
so called Three-layers and Two-networks has proved that
this kind of configuration is good for the safety and stability
of the substation.
___________________________________
978-1-4244-9621-1/11/$26.00 2011 IEEE
APAP2011 www.apap2011.org
GPS
SV Network
Bus
Digital Electric
Meter
EVT
Fiber
GOOSE
Network
Preamble
60
Start of frame
80
81
A2
Adjacent Bay
Breaker
Incorporated
IED
IED
Header
MAC
IED
Distributed Installation on
Switchgear
Destination Address
Source Address
30
Control Center
Ethertype
PDU
noASDU
sequence
of ASDU
security
L
V
81
82
smpCnt
83
confRev
Length
84
refrTm
85
smpSynch
Reserved
smpRate
87
sequence
of data
Value
Data
Set
ASN.1 Tag
L=Length
datset
86
svID
Ethertype
(0x88 BA)
APPID
(0x40 00)
APDU
IEC 61850-9-2
savPdu
80
Priority Tagged
ASDU
ECT
Value
...
V=Value
3
4
Conclusion
9
10
11
12