Design and Construction of an Automated Test Bench
for MCB Testing
W.G.M. Amaradasa
H.K.T.R. Karunarathna
Department of Electrical Engineering
University of Moratuwa
Katubedda, Sri Lanka
[email protected]Department of Electrical Engineering
University of Moratuwa
Katubedda, Sri Lanka
[email protected]H.K.J. Amarasinghe
W.M. Wijekoon
Department of Electrical Engineering
University of Moratuwa
Katubedda, Sri Lanka
[email protected]Department of Electrical Engineering
University of Moratuwa
Katubedda, Sri Lanka
[email protected]Abstract Testing of MCBs involves sending a preset
current through the MCB under test for a pre-defined
period of time. The operational state of the MCB should be
recorded for variable currents/times. The project is to
automate this process for household MCBs.
KeywordsMCB, Controllable Current Source, DC motor,
transformer
I.
The primary objective of this project is to test Instantaneous
Tripping Characteristics, Thermal Tripping Characteristics and
Temperature Rise Characteristics of household MCBs with
reliable automated process.
In addition to that, main target is to deliver a product that is
easy in designing and programming, lower cost, more accurate
and reliable and easy to maintain.
REQUIREMENTS
A. Test Conditions
MCB are tested according to IEC 60898-1 and IEC 609472 standards. All Household MCBs are tested according to the
IEC 60898-1 standard and MCBs for industrial application are
tested according to IEC 60947-2 standard. According to the
IEC 60898-1 standard MCB should test under the following
conditions.
MCBs designed for installation in an individual
enclosure are tested in the smallest of such enclosure
specified by the manufacturer.
Unless otherwise specified, the MCBs are wired with
the appropriate cable specified in Table 1 and are fixed
on a dull, black painted plywood board of about 20
mm thickness, the method of fixing complying with
any requirements relating to the means of mounting
recommended by the manufacturer.
If tolerance is not specified, tests are carried out at the
given values in the standard
During the tests MCB should be connected by single
core PVC insulated copper cables
Except Instantaneous tripping tests all other tests are
carried out with single phase current with all poles
connected in series.
The connection are in free air and spaced not less than
the distance between the terminals.
The minimum length of each temporary connection
from terminal to terminal is 1 m for cross sections up
to and including 10 mm2 and 2 m for cross section
larger than 10 mm2
INTRODUCTION
Most of the MCB Test are made with poor testing
equipment which has unstable current sources, due to that
resulting in unreliable test results and a limited capacities in the
tests which can be made.
II.
addition to that MCB should be protected against
undue external heating or cooling.
Mounted individually, vertically an in free air at an
ambient temperature between 20 oC and 25 oC. In
Table 1-Cross-sections of test copper cables
S/ mm2
Values of the rated current In
In6
1.5
6In13
2.5
13In20
20In25
S/ mm2
Values of the rated current In
25In32
10
32In50
16
50In63
25
63In80
35
80In100
50
100In125
According to the IEC 60898-1 standard test of temperature
rise should be done first before doing test of tripping
characteristics.
B. Tests
1) Test of Temperature Rise
a) Temperature Rise Limits
Temperature rise limits of the parts of MCB measured
under the given conditions shall not exceed the values given in
the Table 2.
1.45In
2.55In
B-3In
C-5In
D-10In
B-5In
C-10In
D-20In
Table 2-Temperature Rise Values
Parts
Terminals for external connection
External parts liable to be touched during
manual operation of the MCB, including
operating means of insulating material and
metallic means for coupling insulated
operating means of several poles
External metallic parts of operating means
Other external parts, including that face of the
MCB in direct contact with the mounting
surface
Temperature
Rise (K)
60
40
25
60
b) Test Procedure
A current equal to In at any convenient voltage is passed
simultaneously through all the poles of the MCB for a period
of time sufficient for the temperature-rise to reach the steadystate value. In practice, this condition is reached when the
variation of the temperature-rise does not exceed 1 K/h.
For four-pole circuit-breakers with three protected poles,
the test is first made by passing the specified current through
the three protected poles only. The test is then repeated by
passing the same current through the pole intended for the
connection of the neutral and the adjacent protected pole.
During the test the temperature-rises shall not exceed the
values shown in Table 2.
2) Test of Tripping Characteristics
Tripping characteristics of Type B,C,D MCBs should be
contain according to Table 3.
Test
a
Table 3-Time Current Operating Characteristics
Test
Initial
Limits
Results
Current Condition
1.13In
Cold
t1h
No tripping
Immediately
after Test a
Cold
t1h
Tripping
Tripping
Cold
1 s < t < 60 s
(for In32
A)
1 s < t < 120
s (for In >
32 A)
t 0.1 s
Cold
T 0.1 s
Tripping
No tripping
a) Test of Time Current Characteristics
A current is equal to 1.13 In that is conventional nontripping current is passed though the conventional
time, that is 1 hour though all poles from cold
conditions. The MCB shall not trip. Immediately
current is the steadily increased within 5 s to 1.45 In
that is conventional tripping current then MCB shall
trip within conventional time.
In next test, a current equal to 2.55 In is passed through
all poles starting from cold conditions. Then the
opening time shall not be less than 1 s and shall not be
more than 60 s for rated current up to and including 32
A and 120 s for rated currents greater than 32 A
b) Test of Instantaneous Tripping Characteristics
For Type B MCBs, a current equal to 3 In is passed
through all poles starting from cold conditions and
opening time shall not be less than 0.1 s. Then a
current equal to 5 In is passed through all poles from
cold conditions. MCB should trip in a time less than
0.1 s
For Type C MCBs, a current equal to 5 In is passed
through all poles starting from cold conditions and
opening time shall not be less than 0.1 s. Then a
current equal to 10 In is passed through all poles from
cold conditions. MCB should trip in a time less than
0.1 s
For Type D MCBs, a current equal to 10 In is passed
through all poles starting from cold conditions and
opening time shall not be less than 0.1 s. Then a
current equal to 20 In is passed through all poles from
cold conditions. MCB should trip in a time less than
0.1 s
III.
SYSTEM DESIGN
Brief introduction to design and put the designed system.
A. Controllable Current Source
Current through the MCBs needs to be controlled for
testing the instantaneous and thermal tripping characteristics.
For this there are two options available:
1.
Power electronic based controllable current device
2.
Variable autotransformer
transformer
with
the
step-down
Advantages of using power electronic based controllable
current device rather than variable autotransformer with the
step-down transformer are:
1.
Smooth current controlling capability
2.
Easier controlling
Disadvantages are:
which are switched using contactors. Maximum continuous
current of one winding is 48 A and the other winding offers
higher current values above 48 A. The winding for current
values below 48 A has a turns ratio of 5:1. The other secondary
winding has a turns ratio of 169:1. Current carrying capacity of
the cable that is being used in this winding is the limiting factor
that governs the maximum current.
Transformer switching may result in inrush currents in
primary winding. This can affect to the secondary winding as
well for a few cycles. This effect can be controlled by closing
the contactor switch at the peak of the input voltage waveform.
2) Variable Auto Transformer
Input voltage of the variable autotransformer is 230 V. This
is mainly used to control the current of the secondary side by
controlling the secondary winding voltage in the range of 0
230 V by changing the tap position of the autotransformer.
1.
Harmonics being added to the output current
waveform
Maximum continuous current through primary and
secondary windings of the variable autotransformer is 10 A.
2.
Device should be able to withstand a minimum
current of 630 A
3.
Very expensive
3) DC Wormed Gear Motor
Function of the dc wormed gear motor is to control the tap
position of the variable autotransformer.
Due to these reasons variable autotransformer with the
step-down transformer is being used as the controllable current
device.
Supply is connected to the variable autotransformer and the
step-down transformer consecutively. DC wormed gear motor
is connected to the variable autotransformer to control the tap
position. Fig. 1 shows the controllable current device.
The tap position of the variable autotransformer is changed
in a rotary movement. Therefore this is controlled by
controlling the rotation angle of the shaft of the dc motor.
4) PWM Controlled DC Chopper Driver
B. Current Sensing
Current that goes through the MCB should be measured in
order to control it. Methods that are used at present are using:
1.
Resistors
2.
Current transformers
3.
Hall effect sensors
4.
Rogowski coil
Using resistors may cause temperature rise due to heat.
Rogowski coil is the latest technology that is being used for
current sensing. Therefore Hall-Effect sensors and current
transformers are being used for current sensing purpose.
Figure 1: controllable current device
1) Step Down Transfomer
Main function of the step down transformer is to step down
the voltage to a low value in order to step up the current to the
current that is required for testing purposes.
MCBs that are tested are of type C. For a 63 A MCB the
maximum current that should be provided for testing purposes
is 630 A to test instantaneous tripping characteristics and a
continuous current of
63 A to test thermal tripping
characteristics.
Secondary winding current is changed by adjusting the
primary winding current of the step-down transformer with the
use of variable autotransformer.
The step-down transformer can deliver a rated power of 2.3
kVA. Therefore the maximum current through the primary
winding is 10 A. Secondary side consists of two windings
C. Main Control System
1) Microcontroller
Introduction to this and mention the task of this. I will write
about this too
2) Computer Software
I will write about this
D. Units
5. Use either SI (MKS) or CGS as primary units. (SI units
are encouraged.) English units may be used as
secondary units (in parentheses). An exception would
be the use of English units as identifiers in trade, such
as 3.5-inch disk drive.
6.
Avoid combining SI and CGS units, such as current in
amperes and magnetic field in oersteds. This often
leads to confusion because equations do not balance
dimensionally. If you must use mixed units, clearly
state the units for each quantity that you use in an
equation.
7.
8.
Do not mix complete spellings and abbreviations of
units: Wb/m2 or webers per square meter, not
webers/m2. Spell units when they appear in text:
...a few henries, not ...a few H.
Use a zero before decimal points: 0.25, not .25.
Use cm3, not cc. (bullet list)
E. Equations
The equations are an exception to the prescribed
specifications of this template. You will need to determine
whether or not your equation should be typed using either the
Times New Roman or the Symbol font (please no other font).
To create multileveled equations, it may be necessary to treat
the equation as a graphic and insert it into the text after your
paper is styled.
Number equations consecutively. Equation numbers, within
parentheses, are to position flush right, as in (1), using a right
tab stop. To make your equations more compact, you may use
the solidus ( / ), the exp function, or appropriate exponents.
Italicize Roman symbols for quantities and variables, but not
Greek symbols. Use a long dash rather than a hyphen for a
minus sign. Punctuate equations with commas or periods when
they are part of a sentence, as in
ab
Note that the equation is centered using a center tab stop.
Be sure that the symbols in your equation have been defined
before or immediately following the equation. Use (1), not
Eq. (1) or equation (1), except at the beginning of a
sentence: Equation (1) is ...
F. Some Common Mistakes
9. The word data is plural, not singular.
10. The subscript for the permeability of vacuum 0, and
other common scientific constants, is zero with
subscript formatting, not a lowercase letter o.
11. In American English, commas, semi-/colons, periods,
question and exclamation marks are located within
quotation marks only when a complete thought or
name is cited, such as a title or full quotation. When
quotation marks are used, instead of a bold or italic
typeface, to highlight a word or phrase, punctuation
should appear outside of the quotation marks. A
parenthetical phrase or statement at the end of a
sentence is punctuated outside of the closing
parenthesis (like this). (A parenthetical sentence is
punctuated within the parentheses.)
12. A graph within a graph is an inset, not an insert.
The word alternatively is preferred to the word
alternately (unless you really mean something that
alternates).
13. Do not use the word essentially
approximately or effectively.
to mean
14. In your paper title, if the words that uses can
accurately replace the word using, capitalize the u; if
not, keep using lower-cased.
15. Be aware of the different meanings of the homophones
affect
and
effect,
complement
and
compliment, discreet and discrete, principal
and principle.
16. Do not confuse imply and infer.
17. The prefix non is not a word; it should be joined to
the word it modifies, usually without a hyphen.
18. There is no period after the et in the Latin
abbreviation et al.
19. The abbreviation i.e. means that is, and the
abbreviation e.g. means for example.
An excellent style manual for science writers is [7].
IV. USING THE TEMPLATE
After the text edit has been completed, the paper is ready
for the template. Duplicate the template file by using the Save
As command, and use the naming convention prescribed by
your conference for the name of your paper. In this newly
created file, highlight all of the contents and import your
prepared text file. You are now ready to style your paper; use
the scroll down window on the left of the MS Word Formatting
toolbar.
A. Authors and Affiliations
The template is designed so that author affiliations are not
repeated each time for multiple authors of the same affiliation.
Please keep your affiliations as succinct as possible (for
example, do not differentiate among departments of the same
organization). This template was designed for two affiliations.
1) For author/s of only one affiliation (Heading 3): To
change the default, adjust the template as follows.
a) Selection (Heading 4): Highlight all author and
affiliation lines.
b) Change number of columns: Select the Columns icon
from the MS Word Standard toolbar and then select 1
Column from the selection palette.
c) Deletion: Delete the author and affiliation lines for
the second affiliation.
2) For author/s of more than two affiliations: To change
the default, adjust the template as follows.
a) Selection: Highlight all author and affiliation lines.
b) Change number of columns: Select the Columns
icon from the MS Word Standard toolbar and then select 1
Column from the selection palette.
c) Highlight author and affiliation lines of affiliation 1
and copy this selection.
d) Formatting: Insert one hard return immediately after
the last character of the last affiliation line. Then paste down
the copy of affiliation 1. Repeat as necessary for each
additional affiliation.
e) Reassign number of columns: Place your cursor to
the right of the last character of the last affiliation line of an
even numbered affiliation (e.g., if there are five affiliations,
place your cursor at end of fourth affiliation). Drag the cursor
up to highlight all of the above author and affiliation lines. Go
to Column icon and select 2 Columns. If you have an odd
number of affiliations, the final affiliation will be centered on
the page; all previous will be in two columns.
B. Identify the Headings
Headings, or heads, are organizational devices that guide
the reader through your paper. There are two types: component
heads and text heads.
Component heads identify the different components of your
paper and are not topically subordinate to each other. Examples
include ACKNOWLEDGMENTS and REFERENCES, and for
these, the correct style to use is Heading 5. Use figure
caption for your Figure captions, and table head for your
table title. Run-in heads, such as Abstract, will require you to
apply a style (in this case, italic) in addition to the style
provided by the drop down menu to differentiate the head from
the text.
Text heads organize the topics on a relational, hierarchical
basis. For example, the paper title is the primary text head
because all subsequent material relates and elaborates on this
one topic. If there are two or more sub-topics, the next level
head (uppercase Roman numerals) should be used and,
conversely, if there are not at least two sub-topics, then no
subheads should be introduced. Styles named Heading 1,
Heading 2, Heading 3, and Heading 4 are prescribed.
C. Figures and Tables
1) Positioning Figures and Tables: Place figures and
tables at the top and bottom of columns. Avoid placing them in
the middle of columns. Large figures and tables may span
across both columns. Figure captions should be below the
figures; table heads should appear above the tables. Insert
figures and tables after they are cited in the text. Use the
abbreviation Fig. 1, even at the beginning of a sentence.
Figure Labels: Use 8 point Times New Roman for Figure
labels. Use words rather than symbols or abbreviations when
writing Figure axis labels to avoid confusing the reader. As an
example, write the quantity Magnetization, or
Magnetization, M, not just M. If including units in the
label, present them within parentheses. Do not label axes only
with units. In the example, write Magnetization (A/m) or
Magnetization (A ( m(1), not just A/m. Do not label axes
with a ratio of quantities and units. For example, write
Temperature (K), not Temperature/K.
ACKNOWLEDGMENT (Heading 5)
The preferred spelling of the word acknowledgment in
America is without an e after the g. Avoid the stilted
expression one of us (R. B. G.) thanks .... Instead, try R. B.
G. thanks.... Put sponsor acknowledgments in the unnumbered
footnote on the first page.
REFERENCES
Use IEEE referencing style even if your engineering
discipline uses a different referencing style. This is important to
preserve the consistency of papers.
The template will number citations consecutively within
brackets [1]. The sentence punctuation follows the bracket [2].
Refer simply to the reference number, as in [3]do not use
Ref. [3] or reference [3] except at the beginning of a
sentence: Reference [3] was the first ...
Number footnotes separately in superscripts. Place the
actual footnote at the bottom of the column in which it was
cited. Do not put footnotes in the reference list. Use letters for
table footnotes.
Unless there are six authors or more give all authors
names; do not use et al.. Papers that have not been published,
even if they have been submitted for publication, should be
cited as unpublished [4]. Papers that have been accepted for
publication should be cited as in press [5]. Capitalize only
the first word in a paper title, except for proper nouns and
element symbols.
For papers published in translation journals, please give the
English citation first, followed by the original foreign-language
citation [6].
[1]
TABLE I.
Table
Head
copy
TABLE STYLES
Table Column Head
Table column subhead
Subhead
Subhead
More table copya
a.
[2]
[3]
Sample of a Table footnote. (Table footnote)
b.
Fig. 1. Example of a figure caption. (figure caption)
We suggest that you use a text box to insert a graphic
(which is ideally a 300 dpi resolution TIFF or EPS file with
all fonts embedded) because this method is somewhat more
stable than directly inserting a picture.
To have non-visible rules on your frame, use the
MSWord Format pull-down menu, select Text Box >
Colors and Lines to choose No Fill and No Line.
[4]
[5]
[6]
G. Eason, B. Noble, and I.N. Sneddon, On certain integrals of
Lipschitz-Hankel type involving products of Bessel functions, Phil.
Trans. Roy. Soc. London, vol. A247, pp. 529-551, April 1955.
(references)
J. Clerk Maxwell, A Treatise on Electricity and Magnetism, 3rd ed., vol.
2. Oxford: Clarendon, 1892, pp.68-73.
I.S. Jacobs and C.P. Bean, Fine particles, thin films and exchange
anisotropy, in Magnetism, vol. III, G.T. Rado and H. Suhl, Eds. New
York: Academic, 1963, pp. 271-350.
K. Elissa, Title of paper if known, unpublished.
R. Nicole, Title of paper with only first word capitalized, J. Name
Stand. Abbrev., in press.
Y. Yorozu, M. Hirano, K. Oka, and Y. Tagawa, Electron spectroscopy
studies on magneto-optical media and plastic substrate interface, IEEE
Transl. J. Magn. Japan, vol. 2, pp. 740-741, August 1987 [Digests 9th
Annual Conf. Magnetics Japan, p. 301, 1982].
[7]
M. Young, The Technical Writers Handbook. Mill Valley, CA:
University Science, 1989.