Technical Description
FBP FieldBusPlug
V6
Universal Motor Controller
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Please note the following
Target group
This description is intended for use by trained specialists in electrical installation and control and automation engineering, who are familiar with the applicable national standards.
Safety requirements
The responsible staff must ensure that the application or use of the products described satisfy all the
requirements for safety, including all the relevant laws, regulations, guidelines and standards.
Using this Handbook
Symbols
This technical document contains markers to point the reader to important information, potential risks and
precautionary information The following symbols are used:
Symbol to indicate a potentially dangerous situation that can cause damage to the
UMC or connected devices or to the environment
Symbol to indicate important information and conditions.
Symbol that indicates a potentially dangerous situation that can cause personal
injury
Abbreviations
UMC
Universal Motor Controller
DCS
Distributed Control System
PLC
Programmable Logic Controller
GSD
Device description file for PROFIBUS networks
EDS
Device description files for DeviceNet networks
FDT/DTM
Device driver technology for field devices. Specified from the FDT group.
NC / NO
Normall closed / Normally open
FBP
FieldBusPlug is the name for a group of products which allows to connect ABB low
voltage control products to different fieldbusses.
Related Documents
UMC100-FBP
Technical Documentation
Document No.
DTM manual for FBP devices
2CDC 192 012 D02xx
Manual of the custom application editor
2CDC 135 014 D02xx
--
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Content
1 System Overview....................................................................................................................................7
Function Overview...............................................................................................................................7
Compatibility to UMC22......................................................................................................................8
Description of Components.................................................................................................................9
2 Installation............................................................................................................................................15
Assembly and Disassembly of UMC100-FBP and IO Modules........................................................15
Connecting the IO Modules DX111 and DX122................................................................................15
Wiring Inputs and Outputs.................................................................................................................16
Connecting Contactors.....................................................................................................................17
Motor Wiring......................................................................................................................................19
Connecting External Current Transformers (CTs)..............................................................................20
Operation Details for Motors with Small Set Currents......................................................................21
Connecting the UMC100-PAN LCD Panel........................................................................................22
Using the UMC100 in a PROFIBUS DP Network..............................................................................23
Using the UMC100 in a DeviceNet Network.....................................................................................24
Using the UMC100 in a CANopen Network......................................................................................25
Using the UMC100 in a MODBUS RTU Network..............................................................................26
Usage in Draw-Out Systems.............................................................................................................27
3 Commissioning.....................................................................................................................................29
Commissioning Steps........................................................................................................................29
Test Position......................................................................................................................................31
4 Configuring the Motor Protection Functions........................................................................................33
Automatic Reset of Protection Faults................................................................................................33
Long Start, Locked Rotor Protection.................................................................................................37
High Current Protection.....................................................................................................................38
Low Current Protection......................................................................................................................39
Phase Loss Protection.......................................................................................................................40
Phase Imbalance Protection..............................................................................................................40
Phase Sequence Protection..............................................................................................................41
Motor Protection with Thermistor (PTC) acc. to EN 60947-8 (type A sensors).................................41
Earth Fault Protection with CEM11...................................................................................................42
Voltage Dips, Load Shedding............................................................................................................43
5 Configuring the Motor Management Functions...................................................................................47
Starting and Stopping the Motor.......................................................................................................47
Emergency Start................................................................................................................................52
Checkback Monitoring......................................................................................................................53
Using the Digital UMC Inputs............................................................................................................53
FieldBusPlug / Issue: 11.2009
--
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Control Function Transparent............................................................................................................56
Control Function Overload Relay.......................................................................................................58
Control Function Direct Starter (DOL)................................................................................................60
Control Function Reversing Starter (REV).........................................................................................63
Control Function Star-Delta Starter...................................................................................................66
Control Function Pole-Changing Starter...........................................................................................69
Control Function Actuator 1 - 4.........................................................................................................72
6 Configuring the Fieldbus Communication............................................................................................77
Setting the Bus Address....................................................................................................................77
Address Check when using UMC in Motor Control Centres.............................................................77
Defining the Bus Fault Reaction........................................................................................................78
Ignore Block Parameters...................................................................................................................78
7 Using Expansion Modules....................................................................................................................81
8 The LCD Control Panel UMC100-PAN.................................................................................................83
Overview............................................................................................................................................83
Monitoring Status Information...........................................................................................................84
The Menu Tree...................................................................................................................................84
Adjusting Parameters........................................................................................................................90
Starting and Stopping the Motor.......................................................................................................92
9 Error Handling, Maintenance and Service............................................................................................95
Error Handling of the UMC................................................................................................................95
UMC100 Fault Indication...................................................................................................................95
Fault Messages..................................................................................................................................95
Resetting Parameters to Factory Defaults . ......................................................................................99
Resetting the Password.....................................................................................................................99
Reading and Resetting Maintenance Counters.................................................................................99
DX1xx Status Codes........................................................................................................................100
Replacing a UMC100.......................................................................................................................100
Replacing a DX1xx IO Module.........................................................................................................100
Requesting Support.........................................................................................................................100
A1 Parameters and Data Structures on a Fieldbus...............................................................................101
Monitoring Data...............................................................................................................................101
Command Data...............................................................................................................................101
Accessing Data on PROFIBUS........................................................................................................103
Accessing Data on Modbus............................................................................................................103
Accessing Data on DeviceNet.........................................................................................................103
Accessing Data on CANopen..........................................................................................................103
Parameter Organisation...................................................................................................................104
Motor Management Parameters......................................................................................................104
Protection Parameters.....................................................................................................................109
Communication Parameters............................................................................................................112
UMC100-FBP
--
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
IO Module Parameters.....................................................................................................................112
UMC Display Parameters (5)...........................................................................................................113
Function Block Related Parameters................................................................................................114
All Parameters Sorted by Parameter Number.................................................................................115
All Parameters Sorted Alphabetically..............................................................................................117
A2 Examples of Circuit Diagrams..........................................................................................................119
Direct Starter, Category 4................................................................................................................119
Reversing Starter, Category 4..........................................................................................................120
A3 Technical Data..................................................................................................................................121
UMC100...........................................................................................................................................121
Performance Data............................................................................................................................124
UMC100-PAN..................................................................................................................................125
DX111 and DX122...........................................................................................................................125
FieldBusPlug / Issue: 11.2009
--
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
How to get started
There are many options for using the UMC100. Not all functions are required in all cases. Therefore the
documentation is split into separate parts. You only need to read the parts that are relevant for your application.
The following manuals exist.
UMC100-FBP Technical Manual
2CDC 135 013 D02xx1
PBDTM
2CDC 192 012 D02xx1
This is the main technical description and must always be
read carefully before using the UMC.
You are now
reading this
manual
This manual describes the configuration tool (Device
Type Manager) that can be used to configure and monitor the UMC100 and also other ABB control products like
UMC22, softstarters and circuit breakers.
It is based on the standardised FDT/DTM technology.
If you plan to only configure the UMC100 with the device
description files like GSD (for PROFIBUS) or EDS (for
CAN) or via the LCD panel, you do not need to read this
manual.
UMC100-FBP Custom Application Editor
2CDC 135 014 D02xx1
FieldBusPlugs
This manual describes how to create customer-specific
applications for the UMC100.
You only need to read this manual, if the logic built into
the UMC100 does not fulfill your needs.
As the custom application editor is part of the configuration tool (Device Type Manager), it is highly recommended
that you read the PBDTM manual first
Whenever the UMC100 is to be connected to a fieldbus,
read the appropriate FieldBusPlug manual.
Presently the following FieldBusPlugs can be used
together with UMC100:
PDP22
2CDC 192 001 D02xx1
PDQ22
2CDC 192 009 D02xx1
DeviceNet
DNP21
2CDC 193 001 D02xx1
CANopen
COP21
2CDC 194 002 D02xx1
MODBUS RTU
MRP21
2CDC 194 001 D02xx1
PROFIBUS DP
) please replace xx with the latest version (e.g. 02). Consult your local sales representative, if you are unsure regarding the latest version.
UMC100-FBP
--
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
1 System Overview
The Universal Motor Controller (UMC) is an intelligent motor controller for 3-phase AC induction motors
combining the two classical functions of motor protection and motor management in a single device plus
offering diagnostic and fieldbus communication. The device functions can be adjusted in a wide range to
cover the needs of different industries. UMC100 is a further development of the UMC22.
Function Overview
Protection Functions
The UMC provides comprehensive motor protection including phase failure detection, adjustable motor
protection for stalled motors during startup or normal operation, configurable current limits to generate
trips or warnings and many more.
Overload classes 5, 10, 20, 30 and 40
Thermistor motor protection (PTC)
Earth fault detection when used in IT networks
One device type covers the whole current range starting from 0.24 up to 63 A.
For higher currents up to 850 A additional current transformers are available.
Fieldbus Communication
The UMC100 can be integrated into different fieldbus networks such as PROFIBUS DP , DeviceNet,
MODBUS and CANopen via the FieldBusPlug interface. All measured data, status signals and parameters can be accessed via fieldbus.
It is also possible to use the UMC stand-alone (i.e. without FieldBusPlug).
The motor protection and motor management is fully functional in the event of a bus failure.
The fieldbus interface and the UMC can be separated. This offers many benefits in MCC applications
especially for withdrawable systems.
Parameterisation of the protection and control functions can be carried out with the device description
files as defined by the different fieldbuses (e.g. GSD for PROFIBUS). In addition a Device Type Manager
(DTM) offering a very convenient device configuration via a laptop or within a control system is also
available.
Motor Management, Inputs and Outputs
The UMC100-FBP provides six digital inputs, three relay outputs and one 24 V output. Therefore a wide
number of control functions can be covered from the base device.
If further inputs or outputs are needed, the basic device can be expanded with an expansion module.
That provides an additional eight digital inputs, four relay outputs and an analogue output for driving an
analogue meter.
Supported standard configurations are direct starter, reversing starter, star-delta starter, actuator, inching
mode and many more.
The digital inputs can be configured in many ways to adapt the behaviour of the UMC100 to specific
user requirements.
To execute customer specific applications the UMC100 allows free programming of its internal logic.
Function blocks for signal adjustment, boolean logic, timers, counters ... are available (see below).
Different control stations (DCS, DI, Operation Panel ...) with individual, adjustable release opportunities
are available.
FieldBusPlug / Issue: 11.2009
--
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Metering, Monitoring and Diagnosis
Rapid, comprehensive diagnostics and operating status information is available on the UMC100 itself
(LEDs), on the LCD panel (clear text messages), via fieldbus or on a laptop connected directly or via bus
to the UMC.
The fully graphic, multi-language LCD panel allows configuration, control and monitoring of the UMC
and its inputs and outputs.
Available diagnosis includes motor, bus and device status, maintenance counters such as number of
starts and overload releases, remaining cooling time, etc.
Function Block Programming
The UMC100 has a set of predefined applications built in. These applications are built on the basis of
function blocks and can be used directly without the need for a programming tool.
Custom applications can be created in a convenient way. The custom application editor is integrated in
the PBDTM.
You can monitor an application online to support you during development and testing.
Control and protection related and general purpose function blocks are available: boolean logic, timers,
counters, blocks representing the hardware, starter functions, ...
There are basic function blocks like boolean blocks that have no parameters. But there are also very
powerful function blocks such as the multifunction inputs or the starter blocks. Such blocks have parameters accessible via LCD and fieldbus. By setting the block parameters you can adjust the behaviour
of the blocks and the application to your needs.
Please note: It is not necessary to change the function block application if the predefined applications fulfill your requirements.
But if you have specific requirements you can enable the customer application mode
and adapt an existing application to your needs or even create your own one.
This is described in the custom application editor manual (see section 'How to get
started').
Compatibility to UMC22
Hardware
The UMC100 is mechanically compatible with the UMC22. The UMC100 does not need more space and
can be used in all situations the UMC22 was used in.
Please note that terminal 12 was previously a static 24 V output. It is now a switchable 24 V output that
can signal a protection trip for example.
Fieldbus Interface
Both devices follow the PNO profile for motor starters regarding their cyclic command and monitoring
telegram. This means the first two bytes within the cyclic telegrams are the same in both devices. But as
the UMC100 provides many new functions, the command and monitoring telegrams are now longer, so
that additional data can be transferred e.g. the status of the inputs of a connected expansion module.
To configure the new functions also the number and organisation of the parameters have changed.
This means that the UMC100 looks different from a control system integration perspective.
It is not possible to just replace the UMC22 with a UMC100. Changes in the device integration packages
are necessary.
UMC100-FBP
--
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Description of Components
UMC100-FBP
The following diagram shows the terminals, monitoring and operating elements of the UMC100-FBP
Current path
(for measuring
the motor current)
Connecting terminals
for PTC sensors
Connecting terminals
for the relay outputs
Connecting terminals
for communication with
the IO modules
T1
T2
Ca
Cb
5 6 7 8 9
UMC100
READY
Plug connection
for the Control Panel
MOT .O N
Connector
for the FieldBusPlug
LEDs
green READY = operation
yellow MOT.ON = motor on
red
FAULT = overload,
failure
FAUL T
Rela y
5 6 7 8 9
230V AC DO DO DO DO DO
1A
C C 0 1 2
Powe r
0
V
10
Inputs
24V 24VDC
24 DC DI
V Out 0
11 12 13
DI
1
14
DI
2
15
DI
3
16
DI
4
17
Front label,
e.g. for slave address
DI
5
18
Connecting terminals
for the digital outputs
24 V DC, GND
Supply voltage
The UMC100 follows the profile for motor management starters as defined in the PNO profile sheet for
low voltage switchgear devices.
After powering on, the UMC100 performs a self-test of its hardware and checks the configuration for
consistency.
In the event of a failure, a self-test fault is generated and signalled. After a successful self-test the UMC
enters the operational state.
FieldBusPlug / Issue: 11.2009
--
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Building Blocks of UMC100-FBP
The next diagram shows the major function blocks of the UMC100 and the data flow among them.
The upper main block contains the protection-related functions. Signals from different signal sources are
evaluated from the trip unit. Depending on the configuration either a trip or a warning can be created. The
motor protection always has priority regarding control of the relay outputs. In case of a protection trip the
relevant contacts are opened and thereafter the motor is stopped. If the device fails, the watchdog opens
the relay outputs automatically for safety reasons.
The main inputs for motor protection are the current measurement and the thermistor sensor. The current
measurement provides information about the actual motor current in the three phases. An advanced motor model uses the current information and calculates the corresponding motor temperature. At a certain
level it will trigger an overload trip.
The thermistor input measures the PTC resistance. Based on the resistance the cold and hot state of the
motor can be distinguished. Also short-circuit or wire break conditions can be detected.
The lower main block contains the control-related functions. Incoming commands from the panel, the digital inputs or the fieldbus are ranked from the control place selection block according to the user settings
and then forwarded to the active starter function.
The starter function block controls the relay outputs depending on its input signals and the actual state.
Additionally monitoring signals are prepared for the LCD display, the UMC100 signalling LEDs and the
fieldbus monitoring and diagnosis telegrams.
All these blocks run in the so-called logic engine. It is possible to change the application which is running
there but usually the predefined applications will be sufficient. Further information about the creation of
custom applications can be found in the Custom Application Editor manual.
GND
H ard w are
S upervis ion
int. supply
24VDC
P ro te ction
T1
T2
PTC
DI0-DI2
Ext. Earth Fault
DI0
C heck back
S upervis ion
T rip
U n it
T herm al
Motor Model
C urrent
M easurem ent
P hase Loss,
Imbalance
Control Function
Relevant Outputs
O ther Protection
Outputs
F unctions
DI0
DI1
DI2
DI3
DI4
DI5
1Ca
1Cb
DI
IO Bus
FBP
Interface
UMC100-FBP
Relay Out
DO3
M o to r Control
UMC-PAN
DO0
DO1
DO2
Application Trip
Signals
Status Signals,
Measured Values
C om m and s
(D I,
BUS,
P ane l)
DOC
S tart/S top
Logic
S ta rte r
F u n ction
M o n ito rin g
(P an el,
B u s)
Predefined or User-Defined Function Block Model
Overview of the major building blocks of UMC100-FBP and the data flow among them.
- 10 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
DX111-FBP
The DX111-FBP expands the input and output channels of the UMC100.
It provides eight digital inputs for 24 V DC, four relay outputs and a current output to drive an analogue
instrument.
The following diagram shows the terminals and monitoring elements of the DX111-FBP module.
Connecting terminals
for the digital inputs.
Connecting terminals
for communication with
the UMC100
and further IO modules.
1DO0
1DO1
1DOC
2DOC
2DO2
2DO3
1DI2
1DI3
1DI4
2DI7
AO+
AO-
DX111
Connecting terminals
for the relay outputs
Connecting terminals for
the analogue output.
1Ca 1Cb 2Ca 2Cb
Inputs D I 24V DC
LEDs
green READY = operation
yellow DIAG = warning
red
ERROR = module fault
Terminals
for the
24 V DC supply
READY
R ela y D O
230V AC / 1A
Diag
ERROR
1DI0
0V
1DI1
1DIZ
2DIZ
2DI5
Front label,
e.g. for slave address
2DI6
Connecting terminals
for the digital inputs
24V DC
DX122-FBP
The DX122-FBP expands the input and output channels of the UMC-FBP.
It provides eight digital inputs 110 V AC - 230 V AC, four relay outputs and a current output to drive an
analog instrument.
The following figure shows the terminals and monitoring elements of the DX122-FBP module.
Connecting terminals
for the digital inputs.
Connecting terminals
for communication with
the UMC100
and further IO modules.
1DO0
1DO1
1DOC
2DOC
2DO2
2DO3
1DI2
1DI3
1DI4
2DI7
AO+
AO-
DX122
Connecting terminals
for the relay outputs
Connecting terminals for
the analogue output.
1Ca 1Cb 2Ca 2Cb
Inputs D I 230V AC
LEDs
green READY = operation
yellow DIAG = warning
red
ERROR = module fault
Terminals
for the
24 V DC supply
FieldBusPlug / Issue: 11.2009
READY
R ela y D O
230V AC / 1A
Diag
ERROR
1DI0
0V
1DI1
1DIZ
2DIZ
2DI5
Front label,
e.g. for slave address
2DI6
Connecting terminals
for the digital inputs
24V DC
- 11 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Configuration Tool
Asset Vision Basic is the tool to configure the UMC100-FBP via a Laptop. Asset Vision Basic is jointly
used between ABB Instrumentation and ABB Control Products. Therefore it enables a wide range of
ABB products to be configured such as motor controllers, soft starters, flow meters and many more.
It is based on the FDT/DTM standard which also enables the configuration of third-party products that
are connected at the same bus segment.
You can parameterise the UMC100-FBP both online and offline.
In offline mode the configuration can be fully prepared and then later on loaded into the device(s).
If a connection to a device exists, monitoring of all measured values, maintenance counters etc. is
possible.
Toolbar & Menus
Configuration
window
of the
motor protection
functions
Tree view of
all devices on
the bus line
Status Window
UMC100-FBP configuration tool Asset Vision Basic with the motor protection configuration
window (3). In (1) the toolbar of the tool is shown. (2) provides a network view with all the
devices accessible on the PROFIBUS DP line. (4) contains a window to display messages
and buttons to quit or adopt the parameter changes.
The diagram above shows the configuration tool which allows intuitive configuration of all
UMC100 functions.
In this example the window to configure the motor protection parameters is shown.
In similar windows all other parameters can be configured.
Other views enable the monitoring of the diagnosis information, the visualisation of bus monitoring,
command data and much more.
UMC100-FBP
- 12 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
UMC100-PAN LCD Panel
The Control Panel UMC100-PAN is an accessory for the UMC100 and can be used for monitoring, control
and parameterisation of the UMC100. It can be directly plugged on the UMC100 or mounted separately
on the panel door using the mounting kit.
Some of the main features are:
- fully graphic, multi-language user interface
- start and stop of the motor and acknowledgement of faults.
- display of measured values (e.g. motor current in A/% or start-up time) and status of inputs and outputs
- parameterisation
The following diagram shows the UMC100-PAN with the monitoring and operating elements:
LCD
LEDs
green RDY
= Ready
yellow FWD/REV = Motor runing
red
Fault
= Faults
Context-sensitive key
Context-sensitive key
CDC 34015F0009
Down key for navigation
Up key for navigation
Stop motor
FieldBusPlug / Issue: 11.2009
- 13 -
Start motor
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
UMC100-FBP
V6
- 14 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
2 Installation
Assembly and Disassembly of UMC100-FBP and IO Modules
You can attach the UMC100 and the IO modules as follows:
Snap-on mounting onto a 35 mm standard mounting rail, without tools (UMC100 and IO devices)
2CDC252282F0005.eps
2CDC252281F0005.eps
Mounting via screws on a mounting plate (UMC100 only)
Assembly
Disassembly
Connecting the IO Modules DX111 and DX122
The modules DX111 and DX122 enable the number of and type of inputs and outputs provided by the
UMC100 to be increased.
The UMC100 can be expanded with one digital IO module. Thus, 8 additional binary inputs, 4 additional
relay outputs and 1 analogue output for driving an analogue indicator instrument are available.
The IO modules are connected via terminals Ca and Cb (see below) to the UMC100. Because of limited
installation space it might be desirable to mount the IO modules separately from the UMC100. This can
be carried out without any problems as long as the maximum cable length is not exceeded.
The following limits apply when connecting an IO module:
Either the DX111 or DX122 can be connected. It is not possible to connect both of them to the UMC100.
The distance between the UMC100 and the IO module must not be longer than specified in the technical data section.
T1
T2
Ca
Cb
5 6 7 8 9
UMC100
READY
MOT.ON
Wiring is shown
for module
DX111. It is the
same for other
modules.
FAULT
Relay
230VAC DO DO DO DO DO
1A
C C 0 1 2
Power
FieldBusPlug / Issue: 11.2009
0
V
10
Inputs
24V 24VDC
24 DC DI
V Out 0
11 12 13
DI
1
14
DI
2
15
DI
3
16
DI
4
17
DI
5
18
- 15 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Wiring Inputs and Outputs
The diagram below shows the block diagram and wiring for both the DX111 and the DX122 modules.
The digital inputs are galvanically isolated.
The common ground for the inputs 1DI0-4 must be connected to 1DIZ.
The common ground for the inputs 2DI5-7 must be connected to 2DIZ.
If no separate grounds are necessary, 1DIZ and 2DIZ can be connected to each other.
The relay outputs groups 1DO1/1DO2 and 2DO1/2DO2 have separate roots each.
The analogue output (AO+/AO-) is intended to drive an analogue instrument which can be used to display
the motor current. It can be adjusted as a current or voltage output.
Open wire and short-circuit faults are detected.
Supported output levels are:
0/4 - 20 mA
0 - 10 mA
0 - 10 V
The output is scaled in a way that a motor current of 0% results in 0% at the output and a motor current
of 200% results in 100% output level.
Example if the output is set as voltage output:
0% motor current -> Uout=0 V, 200% motor current -> Uout = 10 V.
1DI 0
GND
1DI 1
int. supply
24VDC
1DI 2
Diag
Warn
1DI 3
Error
1DI 4
1CA
2CA
1CB
2CB
RX / TX
1DI Z
Logic /
C
L+
L-
2DI 5
2DI 6
2DI 7
2DI Z
L+
L-
AO+
AO1DO0 1DOC 1DO1
2DO2 2DOC 2DO3
DX111
DX122
UMC100-FBP
L+
+24VDC
230VAC
LGND
N
Wiring diagram of the DX111-FBP and DX122-FBP module.
- 16 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Connecting Contactors
Use spark suppression for larger contactors and also interface relays to maintain the service life of the
UMC100 internal relays. For interfacing contactors with peak current > 0.5 A (Types A50 and larger) use
an interface relay as shown below.
Actual ABB contactors - all currents for 230 V AC (Extract):
Contactor type
Inrush
current
[A]
Holding
current
[A]
Inrush
power
[VA]
Holding VDR for spark
power
suppression
[VA]
(ABB type)
Service life of
UMC100 relays
[Switching cycle]
B6S-30-10-2.8 1)
0.01
0.01
2.4
2.4
500000
A9, A12, A16
0.30
0.03
70
RV5/250
500000 2)
A26, A30, A40
0.52
0.05
120
12
RV5/250
400000
A50, A63, A75
0.78
0.08
120
12
RV5/250
300000 2)
A95, A110 5)
1.52
0.10
180
18
RV5/250
use interface relay
A145, A185 5)
2.39
0.15
550
35
RC5-2
use interface relais
AF210, AF260,
AF300 4)
2.04
0.04
470
10
500000
AF400, AF460,
AF580, AF7504)
3.8
0.05
890
12
500000
1)
2)
3), 5)
The contactor B6S-30-10-2.8 (24 V DC) is recommended as interface contactor due to its internal spark
suppression.
All values only for contactors with spark suppression, see appropriate column.
Use interface contactor if longer service life is required.
3)
Interface contactor is recommended (e.g. B6S-30-10-2.8).
4)
The contactors for higher currents are available with electronic interface only
5)
Also available with electronic interface (AF50 to AF185).
Spark suppression is necessary for all types except the AF types to maintain
a reasonable service life.
L1, L2, L3
24VDC/0V
230VAC
DOC DO0
5
1
On
2
Off-N
3
COM
*)
DO1
DO2
k1
Connection of contactors with
electronic interface (AF types) to
the UMC100-FBP.
*) Slide switch on the left side to
position 'PLC' (up)
3
UMC100
FieldBusPlug / Issue: 11.2009
- 17 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Interfacing contactors with peak current > 0,5 A: Types A50 and larger
L1, L2, L3
AC-15: 120 / 240 V
DC-13: 24 / 125 / 250 V
K2: A45 and larger
K2
K1*
k2
k1
DOC DO0
5
DO1
8
DO2
*) e.g. BS6-30-10-28
In this case the
shownspark supression
isnot needed (built in)
3
UMC100
Connection of contactors with peak currents > 0.5 A (ABB types A50 and larger) to the UMC100-FBP.
For checkback the auxiliary contact of the main contactor has to be used!
UMC100-FBP
- 18 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Motor Wiring
Have a look at the wiring of the motor to set the correct nominal current Ie for perfect motor protection.
Example:
For inner delta wiring the parameter Current Factor can be changed to 1.73 to display the actual currents
on the Control Panel and in the control system. The delta 3 circuitry is normally used for larger motors to
reduce the current transformer size.
Star
Power line: 690 V
IP
UMC
Delta
Power line: 400 V
IP
ISC =
IP
UMC
ISC =
IP
3 wiring
Power line: 400 V
IP
UMC
ISC =
IP * 0.577
U1
V1
W1
U1
V1
W1
U1
V1
W1
W2
U2
V2
W2
U2
V2
W2
U2
V2
Example for motor:
Motor rating plate
Example for motor:
Motor rating plate
Example for motor:
Motor rating plate
400 V / 690 V
4.9 A / 2.8 A
400 V / 690 V
4.9 A / 2.8 A
400 V / 690 V
4.9 A / 2.8 A
IP = 2.8 A / ISC = 2.8 A
IP = 4.9 A / ISC = 4.9 A
IP = 4.9 A / ISC = 2.8 A
Parameter
Set current = 2.80
Parameter
Set current = 4.90
Parameter
Set current = 2.80*
Terminal box
Terminal box
U1
V1
W1
U1
V1
W1
U1
V1
W1
W2
U2
V2
W2
U2
V2
W2
U2
V2
IP = Actual current / phase
ISC = Set current
2CDC 342 020 F0209
Terminal box
* Alternatively it is possible to set the parameter Current factor
to 1.7 and the parameter Set current to 4.9 A.
Related Parameters:
Nominal current Ie1
Nominal current Ie2 (for two speed starters only)
FieldBusPlug / Issue: 11.2009
- 19 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Connecting External Current Transformers (CTs)
If the nominal motor current Ie is above 63 A an external current transformer (CT) must be used.
The external CT transforms the primary current flow in a smaller secondary current according to the transmission ratio. This smaller current is then measured from the UMC100.
With the parameter Current Factor the current transformer transmission ratio can be configured. So the
UMC100 knows the actually flowing primary current which is then used for the internal processing.
All types of protection current transformers of class 5P10 (Standard EN/IEC60044) can be used.
The selection should be made based on the requirements:
Secondary current (= current in the UMC100) range about 4A.
Through-hole area if single strands are used
Max. load: 60 mW (UMC100: 30m, conductor: wire size 2.5 mm, length 2 m each: 30 mW)
Requirements for current transformers acc. to IEC60044-1 table 11 and 14:
Measuring current transformer class 1
Actual / nominal current
Max. inaccuracy
Protection c.t. class 5P10
5%
20 %
100 %
120 %
100 %
1000 %
1.5
These values must be guaranteed by the current transformer supplier. The inaccuracy is added to the
inaccuracy of the UMC100. The pass-through direction of the strands is important if the phase sequence
supervision is enabled. For currents up to 850 A, space saving combinations are recommended.
Max.
max. lenght 2 m each, wire size 2,5 mm2
Type / Korctype
Recommendedcurrent
range [A]
Current
factor
(Default
= 1.0)
Secondary
current
range
[A]
Factor to be
set in the
UMC (e.g.
via LCD
panel)
Hole
area
WxH
[mm2]
Max.
wire
size
[mm2]
Link kit (bar)
type for contactor (Order code
see chapter 6.)
UMC100
alone
0.24-63
100
(default)
11
16
4L185 R/4
60-185
46.2
1.3-4
4620
22x28
2x702)
DT450/A185 ->
AF145, AF185
1)
4L310 R/4
180-310
77.5
2.3-4
7750
22x28
2x702)
1)
5L500 R/4
300-500
125
2.4-4
12500
41x22
3x702)
1)
5L850 R/4
1)
2)
500-850
212.5
2.4-4
21250
41x22
DT450/A300 ->
AF210-AF300
DT500AF460L2)
->AF400, AF460
DT800AF750L2)
-> AF580, AF750
Wire size has to be fixed acc. to IEC/EN 60204
Link kits for star-delta starter (others see catalogue)
If current transformers of other suppliers are used the table above may serve as a
calculation basis for the current factor.
Example: Type 5L500 R/4 means: Primary 500 A, secondary 4 A, current factor 125.
In the UMC to real motor current has to be set e.g. 500A.
Related parameter: Current Factor, Ie1, Ie2
UMC100-FBP
- 20 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Operation Details for Motors with Small Set Currents
When using a UMC100-FBP in an environment with very strong magnetic fields and
a small set current at the same time, the current measurement can deviate a few
percent from the real current. Therefore the displayed motor current is too high and
an overload trip occurs too early.
Very strong magnetic fields can originate from a contactor directly mounted beside
the UMC100, closely passing current links or stray fields caused by large transformers. When observing the effect, the distance between the UMC100 and the contactor shall be increased to about 5 cm or the UMC100 shall be rotated by 90 degrees
or the motor wires shall be looped through the UMC100 two to five times.
When looping the motor wires multiple times, the parameter Current Factor must be
adjusted according the number of loops. I.e. the parameter must be set to two if the
wires are looped through the UMC100 two times. Two to five loops are supported.
The displayed current and the current transmitted over the fieldbus are automatically
corrected by the UMC100.
Please note that the adaptation of the current factor for 3 circuits and multiple
loops through the UMC100 are not possible at the same time.
Via fieldbus also higher values than five e.g. six can be set. The UMC100 ignores
such values and creates a parameter fault. Values above 100 are possible and used
in combination with external current transformers (see previous page).
Related parameters:
Current Factor
FieldBusPlug / Issue: 11.2009
- 21 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Connecting the UMC100-PAN LCD Panel
The UMC100-PAN LCD panel can be used for the following purposes:
Configuration of the UMC100-FBP
Control of the motor and fault reset
Monitoring of all IO signals, motor current and maintenance counters
The operator panel UMC100-PAN is mainly designed for mounting it on the front panel of a motor feeder
or in a switchgear cabinet. A door mounting kit is provided for this purpose. With the mounting kit the
degree of protection is IP54.
The UMC100-PAN can also be plugged directly on the UMC100 itself.
Extension cable to
the UMC100
The UMC100-PAN is incompatible with the UMC22-PAN and cannot be used with the
UMC22-FBP but only with UMC100-FBP.
UMC100-FBP
- 22 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Using the UMC100 in a PROFIBUS DP Network
PROFIBUS DP is at present one of the most common fieldbus for industrial applications worldwide and
is standardised in IEC61158 together with other fieldbus protocols. The PROFIBUS DP standard has defined different network topologies. The most commonly used one is the Party Line topology where one
device is connected after the other.
PROFIBUS DP has evolved over time. The first services offered by PROFIBUS DP are the so-called V0
services. They define block parameterisation, configuration, cyclic data exchange and diagnosis information exchange. DP-V0 only allows the complete parameter set to be written in one block. The bus master
sends the parameter block to the slave during powering up of the slave/device. Some control systems
also allow the sending the parameter block during normal operation.
Later the PROFIBUS DP-V1 specification introduced new acyclic read/write services within the context of the PROFIBUS DP-V1 expansions. These acyclic services are inserted into special telegrams
during ongoing cyclical bus operation and thus ensure compatibility between PROFIBUS DP-V0 and
PROFIBUS DP-V1.
To integrate the UMC100-FBP into a PROFIBUS network either the PDQ22-FBP or the PDP22-FBP
FieldBusPlugs can be used. PDQ22-FBP allows to connect up to four UMC100s via one bus node.
PDP22-FBP integrates one UMC100 only (i.e. one bus address per UMC100).
The diagram below shows the sketch of a PROFIBUS bus line with UMC100s integrated via PDP22 and
PDQ22. A detailed description about the creation of PROFIBUS lines using PDP22 and PDQ22 is available in the FieldBusPlug manuals.
24VDC
PDA11
UMCwith
FieldbusPlug
PDP22
UMCwith
FieldbusPlug
PDP22
UMC
UMC
24VDC
24VDC
CDP15
UMC
UMC
...
CDP15
PDQ22
PROFIBUS Line with PDP22 and PDQ22. Wires in purple are PROFIBUS cables. Wires in black
(CDP15) are standard extension cables to connect PDQ and UMC100.
FieldBusPlug / Issue: 11.2009
- 23 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Integration with the GSD File
Besides the physical connection of a device to a PROFIBUS line, the engineering of the whole PROFIBUS
system in the PROFIBUS master is necessary. Every modern PLC (Programmable Logic Controller) or
DCS (Distributed Control System), that can be used as PROFIBUS master, offer the possibility to configure and parameterise devices connected to the master.
Electronic data sheets are used as a basis. In the PROFIBUS world these electronic data sheets are
called GSD files. Within such a file all properties relevant for operation of the slave are described (e.g.
supported baud rates, max. number of modules etc.).
The GSD file ABB_0A09.GSD (for PDQ22) and ABB_34E0.GSD (for PDP22) are contained in the software
Engineering Package
PBE91-FBP.010x 1SAJ924091R010x.ZIP
The ZIP file can be obtained from ABBs web site (http://www.abb.de -> Control Products and Systems)
or on the FBP System CD (2CDC 190 008 E04xx). Please ask your local sales office for it.
The UMC100 can be parameterised using the GSD file. But due to parameter length
limitations only the most important parameters can be configured with the GSD file
in the event that the PDQ22 is used. For PDP22 this limitation does not exist.
Integration with the Device Type Manager (DTM)
In addition to the option of integrating devices with GSD files more and more modern control systems
support the FDT/DTM concept. FDT (Field Device Tool) technology standardises the communication interface between field devices and systems.
For the UMC100 (and also other FBP devices) a DTM is available which can be ordered separately. Consult the PBDTM manual for more information.
For creating a customer-specific application the DTM must be used! Parameterisation of the control and protection parameters can also be carried out with the GSD
file only.
Using the UMC100 in a DeviceNet Network
DeviceNet is based on the Controller Area Network (CAN) technology and mostly used in the Americas.
To integrate the UMC100 into a DeviceNet network use the DNP21-FBP FieldBusPlug. The figure below
shows the sketch of a DeviceNet line with DNP21-FBP, two UMC100s and available accessories. More
details are available in the technical manual of the DNP21-FBP.
AC500
CPU
with
DeviceNet
Master
UMC with
FieldbusPlug
DNP21
UMC with
FieldbusPlug
DNP21
UMC
UMC
DNR11 Bus
Termination
24VDC
UMC100-FBP
DNF11
24VDC
- 24 -
24VDC
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Integration with the EDS File
Besides the physical connection of a device to a DeviceNet line, the integration and engineering of the
devices in the DeviceNet master is necessary.
An electronic data sheet is provided for the UMC100 for that purpose. In the DeviceNet world these electronic data sheets are called EDS files. Within these files all the properties relevant for operating the slave
are described (e.g. supported baud rates, parameters, ...).
Configuration of the control and protection parameters of the UMC100 can be carried out using the EDS file. For creating a customer-specific application the DTM
with UTF21 communication adapter can be used!
The CANopen fieldbus also uses EDS files. But these are different from the DeviceNet ones. In case of problems make sure you use the correct file!
The EDS file ABB_UMC100.eds is contained in the Software Engineering Package
DNE91-FBP.010x
1SAJ923091R010x.zip
The ZIP file can be obtained from ABBs web site (http://www.abb.de/stotz-kontakt) or on the
FBP Sytem CD (2CDC 190 008 E04xx). Please ask your local sales office for it.
Using the UMC100 in a CANopen Network
CANopen is based on the Controller Area Network (CAN) technology and often used within large machines or vehicles. To integrate UMC100 into a CANopen network use the COP21-FBP FieldBusPlug.
The figure below shows the sketch of a CANopen line with two COP21-FBP, two UMC100s and available
accessories. More details are available in the technical manual of COP21-FBP.
AC500
CPU
with
CANopen
Master
UMC with
FieldbusPlug
COP21
UMC with
FieldbusPlug
COP21
UMC
UMC
DNR11 Bus
Termination
24VDC
DNF11
24VDC
24VDC
CANopen Line with COP21 and UMC100. Please note that the accessories of CANopen and DeviceNet are
the same. Do not be confused by the fact that the DNF and DNR have a 'DN' in their names.
Integration with the EDS File
Besides the physical connection of a device to a CANopen line, the integration and engineering of the devices in the CANopen master is necessary. For that purpose an electronic data sheet is provided by ABB.
In the CANopen world these electronic data sheets are called EDS files. Within these files all the properties relevant for operating the slave are described (e.g. supported baud rates, parameters, ...).
Configuration of the control and protection parameters of the UMC100 can be carried out using the EDS file. For creating a customer-specific application the DTM
with UTF21 communication adapter can be used!
The DeviceNet fieldbus also uses EDS files. But these are different from the CANopen ones. In case of problems make sure you use the correct files!
The EDS file FBP_CO_UMC100.eds are contained in the Software Engineering Package
COE91-FBP.010x
1SAJ923092R010x.zip
The ZIP file can be obtained from ABBs web site (http://www.abb.de/stotz-kontakt) or on the
FBP System CD (2CDC 190 008 E04xx). Please ask your local sales office for it.
FieldBusPlug / Issue: 11.2009
- 25 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Using the UMC100 in a MODBUS RTU Network
The MODICON Modbus RTU protocol is a widely used network protocol based on the RS485 physical layer. It is provided in many PLCs that do not offer any other fieldbus. To integrate the UMC100 into a
Modbus network, use the MRP21-FBP FieldBusPlug.
The diagram below shows the sketch of a Modbus line with two MRP21-FBP, two UMC100s and available accessories. More details are available in the technical manual of MRP21-FBP.
AC500 including
Modbus Master
UMC with
FieldbusPlug
MRP21
UMC with
FieldbusPlug
MRP21
UMC
UMC
DNR11 Bus
Termination
DNF11
24VDC
24VDC
24VDC
Modbus Line with MRP21 and UMC100. Please note that the accessories of CANopen and DeviceNet are
the same. Do not be confused by the fact that the DNF and DNR have a 'DN' in their names.
There are no device description files defined by the Modbus standard.
This makes it more difficult to parameterise Modbus devices via the bus.
Therefore we recommend that you parameterize the UMC100 either using the
UMC100-PAN or using a laptop with the UTF21-FBP communication adapter.
UMC100-FBP
- 26 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Usage in Draw-Out Systems
The withdrawable technique is often used in industries where the highest availability and shortest downtimes are required. In the event of an error in a drawer, the replacement with a spare drawer shall be made
as fast as possible. UMC100 has several unique features supporting its use in drawer systems:
The separation of FieldBusPlug (bus node) and UMC100
from previous
FieldBusPlug
Drawer
UMC
UMC100 and FieldBusPlug
can be mounted separately.
The FieldBusPlug contains the
complete bus node. The UMC100
is connected through the
serial FieldBusPlug
interface.
FieldBusPlug
(e.g. PDP22-FBP)
Serial FBPInterface
PROFIBUS
-Slave
to next
FieldBusPlug
In draw-out installations the UMC100 is usually mounted inside the drawer whereas the FieldBusPlug
is mounted in the cable chamber. This ensures that no trunks are required but a straight bus line can be
implemented. A very stable bus communication even at high baud rates is the result!
In the event of a drawer replacement the FieldBusPlug stays active and sends a diagnosis message to
the control system that the UMC100 is missing. Even more important - the fieldbus address is stored in
the FieldBusPlug. If a new UMC100 is connected the old bus address is automatically used. There is no
need for setting a new address! See parameter Address Check for additional details.
All necessary auxiliaries required for the installation are available. See the diagram below on how to use a
PDP22, MRP21 or COP21 in a drawer system. The example shows PDP22 for PROFIBUS.
Serial Link
into Drawer
Shield
Connection
from previous
FieldBusPlug
CDP12-FBP
FieldBusPlug
(e.g. PDP22-FBP)
Passive Cable
inside Drawer
CDP13-FBP
CDP11-FBP
(Clamp to
fix CDP13)
to next
FieldBusPlug
Cable
Chamber
Universal Motor Controller
(e.g. UMC22-FBP)
FieldBusPlug and accessories in a draw-out installation. The fieldbus node is outside
the drawer so no drops are required.
FieldBusPlug / Issue: 11.2009
- 27 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
The following diagram shows the usage of the PDQ22 in a drawer system with the available accessories.
Connection
to drawer
Shield
Connection
to UMC 1- 4
(4 x CDP16-FBP)
from
previous
FieldBusPlug
PDQ22-FBP
to next
FieldBusPlug
(PDX11-FBP)
Cable Chamber
UMC100-FBP
Using PDQ22-FBP in a withdrawable installation allows the connection of up to four UMC100s.
The PROFIBUS node is mounted outside the drawers.
- 28 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
3 Commissioning
This chapter provides an overview of the required commissioning steps. For details about the single steps
please consult the related chapters.
Commissioning Steps
To commission the UMC100-FBP, proceed as follows:
A) Wiring
Wiring and 24 V DC / 0 V connection:
Hard wire with switch apparatus and other components acc. to the application requirements.
Connection of contactors: Use spark suppression, for larger contactors also interface relays to maintain a
good service life of the UMC100 internal relays.
Motor wiring: Check the wiring of the motor to ensure correct setting of Ie for perfect motor protection.
When using UMC100 with motors of nominal currents < 1 A please read section "Operation Details for
Motors with Small Set Currents". If the nominal motor current is above 63 A read section "Connecting
External Current Transformers (CTs)" on how to use the UMC100 with external current transformers.
If an IO expansion module is used connect the UMC100 with the IO module and hard wire the inputs of
the expansion module acc. to the application requirements.
B) Switching on the power supply
Switch on the supply voltage of the UMC100. If connected with a FieldBusPlug also ensure that the
FieldBusPlug is powered. In the fault-free state, the green UMC100 LEDs should light up.
LEDs on the UMC100:
On
Green (ready)
Yellow (motor running) Off
Red (fault/trip)
Off
LEDs on the FieldBusPlug:
In fault free state H1/H3 (left upper and lower LEDs) should light up. If no cyclic bus master is
active H2 (upper right LED) is flashing. See the technical description of the FieldBusPlug in use.
Continue with Step C) if fieldbus communication is required or continue with step D) to start the configuration.
In case of an error use the LED/UMC100-PAN information of the UMC100/FieldBusPlug to find out the
cause of the fault (see section "Fault Handling").
C) Setting the fieldbus node address
Before connecting the UMC100 to a fieldbus network (e.g. PROFIBUS) set the fieldbus address using
UMC100-PAN. That means the slave address is directly adjusted and stored in the UMC100.
To change the bus address, press Menu, select Communication and then Bus Address.
Adjust the address within the limits defined by the fieldbus type (for PROFIBUS e.g. 2 to 125).
D) Start configuring the UMC100 via LCD panel, laptop or control system
The following parameters need to be adjusted
Motor management related parameters e.g. the control function
(see section "Configuring the Motor Management Functions")
Parameters defining how to start and stop the motor from the different control places
(see section "Configuring the Motor Management Functions -> Starting and Stopping the Motor").
Parameters related to the motor and its protection functions
(see section "Configuring the Motor Protection Functions").
Parameters related to the fieldbus communication interface
(see section " Configuring the Fieldbus Communication")
Other settings such as the panel language or the usage of a connected DX1xx module.
FieldBusPlug / Issue: 08.2009
- 29 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Select the Required Configuration Mode for the UMC100-FBP
The UMC100 can be configured in different ways depending on your system setup:
Configuration via LCD panel
The device address has to be configured via LCD panel. And it is possible to adjust the other protection and control parameters of the UMC100 using the panel. The configuration via LCD panel is good for
stand-alone applications (without bus) and when no Laptop for parameterisation is in use.
The configuration via LCD panel can be password-protected to prevent unintentional parameter changes.
Configuration from within the control system
Device description files allow the integration and configuration of a device in the fieldbus master. For
PROFIBUS this file is called a GSD file. In case of CANopen and DeviceNet so-called EDS files are commonly used. The UMC100 can be configured using these configuration files. A considerable benefit of
this method of configuration is that the configuration is stored centrally in the control system and can be
downloaded again in the event of a replacement.
If the UMC100 is connected via PROFIBUS and the control system supports the FDT/DTM technology
it is also possible to configure the UMC100 using the PBDTM (PROFIBUS Device Type Manager) from
within the system. The PBDTM offers a very user-friendly configuration interface which also allows to
adapt the internal UMC100 application logic using the custom application editor.
In online mode the PBDTM additionally provides access to all diagnosis, service and process data.
Configuration via Laptop
The configuration via laptop option is a convenient way to parameterise and monitor the UMC100.
The FDT/DTM based configuration tool provides full access to all data available in the UMC100.
The following functions are available:
Online and offline configuration and parameterisation of the UMC100
Monitoring and diagnosis of the UMC100 during operation
Function block based programming of a user specific application
Utilising of user roles and optional password protection for different tasks (e.g. engineering or operation)
The UTF21 communication adapter provides a point-to-point connection between a single UMC100 and
your laptop. The top half of the following diagram shows this setup.
If several UMC100s are connected via PROFIBUS the UTP22 communication adapter can be used.
This adapter connects your laptop to the PROFIBUS line and allows central configuration and monitoring
of all UMC100s connected to this line. This is recommended for larger PROFIBUS installations.
For configuration via laptop use the ABB tool "Asset Vision Basic". It is jointly used by
ABB Instrumentation and ABB Control Products. It is based on the FDT/DTM standard.
The installation and use of the PBDTM is described in the PBDTM manual. It also provides general information about the FDT/DTM technology.
Please read this manual carefully if you are unfamiliar with the FDM/DTM technology.
UMC100-FBP
- 30 -
FieldBusPlug / Issue: 08.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
UMC
FieldBusPlug
Interface
USB
Interface
UTF21
UMC
Service Laptop
24 V DC
PROFIBUS Master
UMCwith
FieldBusPlug
PDP22
24 V DC
PDA11
UTP22
USB
Interface
Service Laptop
PDA12
UMC
UMC
24 V DC
24 V DC
PROFIBUS Cable
DSUB9 / DSUB9
Connection of the Service Laptop & PROFIBUS adapter
only when required also in
parallel to the PLC/DCS
Connection of a service laptop using UTF21-FBP (point-to-point)
or UTP22-FBP (for a whole PROFIBUS line)
Test Position
It is possible to configure a multifunction input (DI0, DI1 or DI2) to inform the UMC that the feeder is in
test position. If the input signals test position the feeder's main circuit must be isolated from the motor
supply but the control voltage of the UMC must be connected.
During active test position the function of the feeder and its integration into the control system can be
tested. I.e. the motor can be started but the UMC does not trip because of a missing checkback.
Use the parameters Multifunction 0,1,2 to enable this function.
If the feeder is in test position the UMC has disabled the checkback supervision and
other motor current related protection functions. Therefore the test position must be
only active for commissioning purposes.
FieldBusPlug / Issue: 08.2009
- 31 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
UMC100-FBP
V6
- 32 -
FieldBusPlug / Issue: 08.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
4 Configuring the Motor Protection Functions
In this chapter you find information on how to configure the different UMC protection functions.
The following topics are covered:
Function and parameters of the electronic overload protection, the thermal memory and points to
consider if the motor is started cyclically (e.g. S3 motor operation mode)
Locked rotor protection during motor start
Overcurrent and undercurrent protection during normal operation
Imbalance protection
Phase loss protection
Thermistor motor protection
Earth fault protection with auxiliary device CEM11-FBP
Protection functions can be either on or off. If switched on, they can trigger a protection trip or a warning
only (excluding the thermal overload which is always active and triggers a trip). For some functions an optional delay can be specified. Some protection functions are only active after motor start-up while others
are active during motor start.
Below is an overview of the available protection functions. For details see the following sections.
Protection Function
When active
Available Options:
Warning/Trip/Off
Automatic Fault
Reset Possible
Electronic Overload
Always
Trip
Yes
Electronic Overload
Prewarning
Always
Warning
Locked Rotor
During motor start
Trip
High Current
After motor start
Separate warning and trip
levels /Off. Optional delay.
Low Current
After motor start
Separate warning and trip
levels / Off. Optional delay.
Imbalance
Always (Motor current >
60% of Ie and all three
phases available)
Separate warning and trip
levels / Off. Optional delay.
Yes
Phase Loss Protection
Always (Motor current >
60% of Ie)
Trip, Off
PTC Protection
Always
Trip, Warning, Off
Yes (excluding PTC
wire break and short
circuit)
Earth Fault Protection
Configurable
Trip, Warning, Off
Load Shedding / Voltage DIP
Always
See subsection voltage DIP
The motor start-up period ends when the motor current drops to 135% of Ie or if the class
time (i.e. Class 5 -> 1.5 s, Class 10 -> 3 s , class 20 -> 6s, class 30 -> 9s, class 40 -> 12s)
is over. The class time begins with the start command.
The motor-related and protection-related parameters shall be set according to the motor manufacturer's
data sheet. Other parameters of the UMC shall be carefully selected based on the process and the system requirements.
Automatic Reset of Protection Faults
The setting of the "Fault autoreset" parameter determines how the UMC manages protection trips.
Off (the default setting): A protection trip must be acknowledged from the user. This can be done via
LCD panel, fieldbus or the multifunction inputs DI0-DI2 if configured.
On: A protection trip is automatically acknowledged without intervention of a human operator if the trip
condition has gone (e.g. cooling time over).
FieldBusPlug / Issue: 11.2009
- 33 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Electronic Overload Protection
The UMC protects three-phase AC motors in compliance with IEC 60947-4-1. The tripping class can be
set to class 5, 10, 20, 30 or 40. The advanced thermal motor model considers both the copper and iron
parts of the motor thus providing the best protection of the motor.
Before an electronic overload trip actually happens, a pre-warning can be generated. During high overload situations the prewarning might be raised just a few seconds before the actual trip happens.
The presently used thermal capacity (0...100%) of the motor is available to the user and thus a prediction
of the time to trip for the current load situation. If the motor is switched off the time to trip shows 6553
sec (never trips). If the motor is running the predicted trip time is updated regularly. The smaller the value
the earlier the trip happens.
After an overload trip, the remaining cooling down time (=time to restart) is calculated regularly and also
available to the user. The motor can be restarted if the cooling time is 0 sec.
Block Diagram:
Cooling Mode =
Time-based
&
Tcooling
Trip
I/Ie[%]
Thermal
Motor
Model
Trip
Load
Load >
Restart
Level
Cooling Mode =
Load based
Cooling
Time
Running
>
&
Prewarning
Thermal
Overload
Load >
Warning
Level
The thermal information of the motor is cyclically stored (thermal memory) 1).
After a thermal overload trip the motor must cool down before it can be started again. There are two options to define the necessary duration of the cooling time.
Fixed cooling time: The user has to specify a fixed duration e.g. 15 minutes. After a thermal overload
trip a further motor start is inhibited for that time. The time that has to be adjusted depends on: Motor
size, motor with or without ventilation, the environment temperature etc. Considering these points the
appropriate cooling time can be estimated. Some examples of motor cooling time constants (t.c.) (motor
standstill) can help:
Size
1 kW - 1
pole
5 kW -1 pole 5 kW - 2
pole
c.t.
10 min
15 min
20 min
20 kW - 2
20 kW - 3
100 kW - 3
30 min
40 min
70 min
Thermal capacity based cooling: The user specifies to which level (e.g. 60%) the thermal load level must
drop before a motor start is possible again.
If the UMC was switched off while the cooling time was running the UMC restarts the cooling timer with
the remaining cooling time if the power down time was shorter than 20min.
1)
UMC100-FBP
- 34 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Example of trip class selection:
Select the trip class so that the motor is thermally protected, even when the rotor is stalled.
This means that the tripping curve of a cold motor has to be below the coordination point Ia/Ie and tE
whereas Ia is the actual current, Ie is the nominal current of the motor and tE is the maximal heating time as
defined by the motor manufacturer.
Example: Motor with enhanced safety has the data:
Power = 7.5 kW
Relation Ia/Ie = 7.4
Heating time tE = 11 s
The following diagram shows the tripping time for cold motors at 3-pole symmetric load:
100
Class 30
Class 20
Class 10
Class 5
qT: Thermal load
of the motor
tE [s]
T1: Switch-off time
t: Time
11
10
1
1
Ia / In
7,4
10
The trip classes 5 and 10 are allowed because the appropriate times (3 s, 6 s) are below the time tE of the
motor (including the tolerance 10% of the UMC).
FieldBusPlug / Issue: 11.2009
- 35 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Cyclic motor operation modes
Some applications require periodic start/operation/stop cycles. Setting up such applications requires care
when selecting the cooling down times or defining the shortest possible start period.
In the next diagram three successive start cycles are displayed. In each cycle the motor starts at 700% Ie.
This high load lasts for about 7 seconds. Then the current goes back to Ie within 6 seconds and stays at
100% Ie for about 180 seconds. At T1 the motor is switched off and cools down for 200 seconds (cooling
time is set to 200s).
After the cooling time is over the next start takes place at T2. During this cycle the motor also cools down
for 200s but the calculated thermal motor load q is already above 40%. The third start at T4 leads - as
expected - to a thermal overload trip
For cyclic operation modes it is important to keep the cycles long enough to allow the
motor to cool down sufficiently.
For cyclic start patterns it is better to select the cooling mode option "Restart Level"
which allows a restart based on the thermal load level. In the case shown below the third
start would then be allowed at the earliest at T5 for the given qR.
T
120
100
80
60
40
R
20
t[s]
0
0
200
400
600
800
T1
T2
T3
T4
1000
1200
1400
1600
T5
Relevant Parameters for Thermal Overload Protection
Trip Class
Set Current Ie1 and optionally Ie2
Current Factor
Cooling Mode
Cooling Time
Restart Level
Thermal load Pre-Warning level
Fault autoreset
UMC100-FBP
- 36 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Long Start, Locked Rotor Protection
This function detects a long start situation which is caused from a locked rotor for example. The function creates a trip if the motor current continuously exceeds a threshold for a configurable period of time.
Blocking of a motor can occur due to excessive loading of the motor or due to process or mechanical
jam. The early detection and tripping of the motor protects the driven mechanical system by further damage and the motor from thermal stress. This function can only trigger a trip. Both the maximum allowed
current and the delay time until the trip occurs can be adjusted.
Block diagram:
I/Ie[%]
I>Ilocked
Startup Phase
&
Ton
Locked
Rotor
Blocking
Enabled
Example
The diagram on the left below shows the principle operation of the function. The diagram on the right
shows a concrete example. In a blocking situation which results in a given increased inrush current I, the
electronic overload protection would trip the motor at T2 whereas the blocking protection already trips at
T1.
To adjust the blocking current threshold correctly proceed as follows:
Take the highest inrush current value during a normal start. This value is displayed on
the UMC100-PAN.
Add a safety factor depending on how much your start-up load might vary.
Set the blocking delay to a value that is shorter than the trip time resulting from the thermal overload trip at the given current.
LR
threshold
t
LR delay
Startup time
Relevant Parameters:
Locked Rotor Level
Locked Rotor Delay
FieldBusPlug / Issue: 11.2009
- 37 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
High Current Protection
This function is useful to protect the driven mechanical system from jams and excessive overloads
caused by the equipment or the process.
The high-current function signals a warning when the motor current exceeds a set threshold for a configurable period of time, after the motor start-up. The high current function creates a trip when the current
continuously exceeds a separately set threshold for a set period of time, after the motor start-up.
Block Diagram:
I>Ihcwl
&
Thcwd
High Current
Warning
&
Thctd
High Current
Trip
I/Ie[%]
I>Ihctl
After Start-up
Example:
The start-up phase ended at T1. At T2 the current increases above the high current warning level Ihcwl for
a period longer than the high current warning delay time thcwd. Therefore the high current warning signal is
set.
At T3 the current also increases above the high current trip level Ihctl but only for a period shorter than the
specified high current trip delay time thctd. Then at T4 the current rises again above the trip level and stays
there long enough to trigger an overcurrent trip that finally stops the motor.
I/Ie [%]
Ihctl: High current trip
delay time
Ihcwl: High current warning
delay level
Ihctd: High current trip delay
Ihcwd:High current warning
delay
Ie: Nominal current
ISE: Current defining
the end of the start up period
Ihctl
Ihcwl
ISE
Ie
T1
T3
T2
T4
---------------------------------------/===========================================================
hcwd
-------------------------------------------------------------------------------/===================
thctd
thctd
Relevant Parameters:
UMC100-FBP
High Current Trip Level
High Current Warning Level
High Current Trip Delay
High Current Warning Delay
- 38 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Low Current Protection
The low current function is triggered when the motor current falls below a desired level. The function
detects loss of suction for pumps, broken belt for conveyors, loss of airflow for fans, broken tools for machines etc. Such states do not harm the motor but early diagnosis helps to minimise the extent of damage to the mechanical installation and subsequent loss of production
The motors on underload draw mainly the magnetising current and a small load current to overcome frictional losses. Therefore, the other reason to isolate the motors on underload is to reduce the reactive load
on the power system network.
The low current function signals a warning when the motor current falls below the warning level for a
configurable period of time, after motor start-up. The low current function creates a trip when the motor
current falls below the trip level for a configurable period of time, after motor startup.
Block Diagram:
I<Ilcwl
&
Tlcwd
Low Current
Warning
&
Tlctd
Low Current
Trip
I/Ie[%]
I<Ilctl
After Start-up
Example:
The diagram above shows an underload situation of the motor after the startup time is over (T1). At T2 the
motor current falls below the undercurrent warning limit Iucwl. After the undercurrent warning delay time
tucwd an undercurrent warning is set.
Then at T3 the current also falls under the undercurrent trip level Iuctl but only for a period shorter than the
specified undercurrent trip delay time tuctd. Therefore no trip happens. At T4 the current falls again under
the low current level and stays there. Therefore a trip is released and the motor stopped.
Ilctl: Low current trip delay time
I/Ie [%]
Ilcwl: Low current warning delay level
ISE
tlctd:Low current trip delay
Ie
Ilcwl
tlcwd:Low current warning delay
Ie: Nominal current
ISE: Current defining the end of the
start-up period
Ilctl
Low Current
Warning
Low Current
Trip
T1
T4
T3
T2
---------------------------------------/===========================================================
lcwd
-------------------------------------------------------------------------------/===================
tlctd
tlctd
Relevant Parameters
Undercurrent Trip Level
Undercurrent Warning Level
Undercurrent Trip Delay
Undercurrent Warning Delay
FieldBusPlug / Issue: 11.2009
- 39 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Phase Loss Protection
This function protects motors against the extreme situation where a complete phase is lost. An undetected phase loss can cause motor damage because of the sudden rise of current in the two remaining
phases. Thus the thermal overload protection performs an accelerated trip during phase loss.
The phase loss protection function must not be disabled in real applications. The
phase loss protection may only be disabled for demo purposes.
The following table shows the tripping times in case of phase loss for the different trip classes.
Trip class
Tripping time [s]
10
20
30
40
1.5
12
Relevant Parameters:
Phase Loss Protection
Phase Imbalance Protection
Imbalance protection function protects the motor against a small degree of imbalance in the motor
phases.
Function:
The current phase imbalance function signals a warning when the current in a phase differs more than the
configured warning level from the average current in all 3 phases. A fix hysteresis is built in.
The current phase imbalance protection signals a fault when the current in a phase differs more than the
configured trip level from the average current in all 3 phases for a period of time. This time is trip class
dependant and shown in the table above.
Block Diagram:
Imb >
Warning Level
I123
&
Imbalance
Warning
&
Imbalance
Trip
Imbalance
Detection
Imb >
Trip Level
After Start-up
During Start-up
>1
Relevant Parameters:
Phase Imbalance Warning Level
Phase Imbalance Trip Level
UMC100-FBP
- 40 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Phase Sequence Protection
Enable this protection function to prevent connected equipment from a wrong rotation direction e.g when
driving a crusher or conveyor. If this protection function is active the motor wires must have a defined
order which is from left to right. It is possible to change the expected direction if wiring was done in a
different way. Take care that contactors are mounted after the UMC to ensure the phase sequence is not
changed by switching the contactors (e.g. REV starter).
L1
T1
T2
L2
Ca
L3
5 6 7 8 9
Cb
UMC100
READY
MOT.ON
FAULT
5
Relay
230VAC DO DO DO DO DO
C C 0 1 2
1A
Power
0
V
10
Relevant Parameters:
Inputs
24V 24VDC
24 DC DI
V Out 0
11 12 13
DI
1
14
DI
2
15
DI
3
16
DI
4
17
Check phase sequence
DI
5
18
Phase reversal
Motor Protection with Thermistor (PTC) acc. to EN 60947-8 (type A sensors)
PTC thermistors are semiconductor elements with a very high positive temperature coefficient. They are
embedded directly in the phase windings of the stator. In contrast to the thermal overload protection that
responds to the load current, the thermistor protection responds to the change in thermistor resistance
due to temperature change in the motor windings.
The thermistors are selected to have a rated operating temperature that corresponds to the insulation
class, type and construction of the motor. At the rated temperature the thermistor resistance increases
sharply up to the hot temperature resistance value.
The UMC senses this abrupt change in the resistance. When thermistor protection is activated there is
also an internal supervision which detects open or short-circuit faults from the thermistor circuit.
T1
T2
Ca
Cb
2CDC 342 021 F0209
Motor with intergated
PTC sensors
R
u
Relevant Parameters:
PTC
FieldBusPlug / Issue: 11.2009
- 41 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Earth Fault Protection with CEM11
The earth fault protection function protects the motor and the network against ground current flow. During
an earth fault, the motors can reach a dangerous potential above the ground level thus posing a safety
hazard to personnel. The earth faults are mainly caused due to ageing of the insulation, deterioration of
insulation due to sustained or cyclic overloading, moisture or conductive dust. The monitoring of the earth
fault is carried out with the help of the auxiliary device CEM11. The CEM11 device monitors if the sum of
the three phase currents is zero.
Detection of such ground faults can be used to interrupt the motor to prevent further damage, or to alert
the maintenance personnel to perform timely maintenance.
The CEM11 can be connected to one of the multifunction inputs of the UMC. The earth fault signal can be
optionally delayed. It is also possible to suppress the earth fault during the motor start-up phase.
Block Diagram:
CEM11 Signal
Ton
&
Earth Fault
Trip / Warning
Suppress
during
start up
Sample Circuit Diagram:
To use CEM11 with the UMC proceed as follows:
1. Select the CEM11 model that suits your application needs. There are four different models available
with feed-through holes from 35mm to 120mm.
. Connect the CEM11 to one of the multifunction inputs DO0, DI1 or DI2 and 24V DC supply.
3. Configure the corresponding multifuncion input as earth fault input. You can select if the earth fault
supervision shall be suppressed during motor start or not.
4. Optionally a time can be configured to delay the creation of a fault or warning. It is adjustable from 0.1
to 25.5 s.
5. Configure the threshold when an earth fault should be signalled. The threshold can be set directly at
the earth fault monitor (CEM11) itself. See the CEM11 technical manual for further details.
Relevant Parameters:
Multifunction Delay Time
Multifunction Inputs 0,1, or 2
3
UMC100
10 11
13 14
DI0
15
16
17
18
DI1 DI2 DI3 DI4 DI5
0 V 24 V DC
UMC100-FBP
- 42 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Voltage Dips, Load Shedding
Motors switched off during voltage dips or power failure can be restarted on power resumption sequentially to prevent simultaneous switch-on of the motors and thus prevent another mains failure on the
network. The tripping of motors due to undervoltage of short duration can be bypassed. It is also possible
to restart the process on power resumption by sequentially starting the motors (staggered start).
The Voltage DIP function is available for the starter types DOL (Direct Online Starter)
and REV (Reversing Starter).
L1
L2
L3
External
Voltage
Monitor
UMC100
DI0-2
The following diagram shows different cases. In case a) where the voltage dip is shorter than the Auto
Restart Time the UMC output relay does not open. The motor keeps running.
In case b) the voltage dip takes longer than the configured Auto Restart Time which means the UMC
switches off the relay output. The dip is shorter than configured with parameter 'Max. Voltage Dip Duration' so the motor gets started automatically after an optional restart delay time (Parameter 'Dip Autorestart
Enable=On).
In case c) the voltage dip takes longer than the Max. Voltage Dip Duration time. Therefore an error is generated as soon as the dip duration exceeds the allowed dip duration time.
ULmin
Reset
Level
Case a)
Trip
Level
Auto Restart Window
Undervoltage situation
UMC Relay Out
DIP signal at
digital input
FieldBusPlug / Issue: 11.2009
ULmin
Reset
- 43 -
UMC100-FBP
Trip
Level
Universal Motor Controller Auto Restart Window
Undervoltage situation
UMC100-FBP
UMC Relay Out
Technical
Description
V6
DIP signal at
digital input
ULmin
Reset
Level
Case b)
Trip
Level
Restart
Delay
Auto Restart Window
Undervoltage situation
UMC Relay Out
DIP signal at
digital input
Max. DIP Duration
ULmin
Reset
Level
Case c)
Trip
Level
Undervoltage situation
UMC Relay Out
DIP signal at
digital input
Max. DIP Duration
UMC Voltage
DIP Error
UMC100-FBP
- 44 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Double DIPs
Special handling can be activated if two dips occur within one second.
Set parameter 'Enable Voltage Dip' to On + Rapid Cycle Lockout. If within one second two separate
dips occur, immediately after the start of the second dip the contactors are switched off.
They are automatically switched on again after the Restart Delay time if parameter 'AutoRestartAfterDip'
is enabled.
UL
1st DIP
2nd DIP
Reset
Level
Trip
Level
Auto Restart Window
Undervoltage situation
No Delay!
Restart
Delay
UMC Relay Out
DIP signal at
digital input
<1s
Relevant Parameters:
Dip Enable
Dip Duration
Dip Autorestart Window
Dip Duration
Dip Autorestart Enable
FieldBusPlug / Issue: 11.2009
- 45 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
UMC100-FBP
V6
- 46 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
5 Configuring the Motor Management Functions
In this section you find the following information:
Introduction into the supported control stations and operation modes
How to start and stop the motor from the different control stations
Available control functions
Functions related to motor control such as emergency start, checkback monitoring etc.
Starting and Stopping the Motor
Control Stations
From control stations (i.e. source of commands) start/stop commands can be sent to the UMC. Four
control stations are supported:
Digital Inputs: Allow the motor to be controlled from a control panel with push buttons e.g. mounted locally to the motor.
DCS/PLC: Commands are transferred via cyclic communication telegrams from the process controller via fieldbus to the UMC. The UMC uses the PNO motor starter profile which defines the meaning of
each bit in the cyclic telegrams. See section XXX for further details.
LCD-Panel: Allows control via the buttons of the UMC-PAN usually mounted in the switchgear cabinet
door
Service Tool: Allows control commands to be issued via acyclic communication services of the used
fieldbus. The UMC DTM uses this communication channel for example.
For each control station you can configure if a start and/or a stop command is accepted by the UMC.
o
T1
T2
Ca
Cb
5 6 7 8 9
UMC100
READY
MOT .O N
FAUL T
Rela y
5 6 7 8 9
230V AC DO DO DO DO DO
1A
C C 0 1 2
Powe r
0
V
10
Inputs
24V 24VDC
24 DC DI
V Out 0
11 12 13
DI
1
14
DI
2
15
DI
3
16
DI
4
17
DI
5
18
Modes
In practise it is often required to release or block start/stop commands from a control station depending
on various reasons e.g.
If the communication to the bus master is interrupted you want to automatically enable control via digital
inputs which would not be possible if the communication is ok
For service purposes all commands from the bus should be ignored
...
FieldBusPlug / Issue:08.2009
- 47 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Therefore the UMC enables start/stop commands to be individually released or blocked from a control
station depending on modes. Three different modes are available named by their typical usage:
Mode
Default Behaviour
Auto (Remote) In this operation mode the UMC accepts start commands from the DCS/PLC. To
activate this control mode the "Auto Mode Bit" in the cyclic communication telegram must be set to logic one. No start commands from other control sources are
accepted in this mode.
Local 1
In this mode the motor is controlled locally at the motor or the motor control room.
Start commands are accepted from the digital inputs or the LCD control panel. This
mode is active in the following cases:
If the "Auto Mode Bit in the cyclic bus telegram is not set i.e. the PLC/DCS has
enabled local control.
If the LCD panel is used to control the motor locally. As soon as the menu point
"Motor Control" is entered and the UMC signals local control
If the UMC detects a bus fault
Local 2
Is a second local control mode that can be activated via one of the multifunction inputs even if another mode is active. This allows local control to be enforced via digital inputs without involvement of the PLC/DCS (i.e. the "Auto Mode Bit" is ignored).
How to set the mode:
There are three relevant signals that determine which mode is active:
Bus fault: The UMC has detected a bus fault (i.e. the cyclic bus master is missing)
Force Local 2: A multifunction input signals that the local 2 mode shall be activated
Autobit: With bit 5 in byte 0 of the cyclic command telegram, the PLC/DCS signals that the auto mode
shall be activated and control shall happen via bus (according to PNO motor management profile).
The following table shows the activated operation mode depending on these inputs. There is always
one mode selected even if more than one input is active. The bus fault signal has the highest priority
followed by the force local 2 signal. The autobit has lowest priority.
Bus fault (e.g. no sign of life from master)
Force local 2 signal (from DI0-2)
Autobit is set to true on FieldbusBus
Resulting Mode
x: Either 0 or 1
Local 1
Local 1
Local 2
Auto
UMC100-FBP
Mode selection table. Based on the three inputs the active mode is selected.
- 48 -
FieldBusPlug / Issue: 08.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Example:
The following requirements shall be fulfilled:
Switch S1 has the following positions: Remote/Local/Test Position/Off.
(Req. 1) If the switch is in position Local the UMC can only be controlled locally (digital inputs and LCD)
but not started via bus. But it shall be possible to stop the motor also via bus.
(Req. 2) In position Auto the DCS can control the UMC. Locally only a stop command can be issued.
(Req. 3) In position Off the motor cannot be started at all
(Req. 4) Position Test is for commissioning purposes and switches the UMC in simulation mode.
(Req. 5) If there is a bus fault the UMC shall automatically go into local mode and allows starting/stopping via the LCD panel and the digital inputs (as in position Local).
The diagram below shows the simplified circuit diagram:
GND
(24VDC)
L1, L2, L3
Contactor
Supply
(e.g. 230VAC)
K1
24VDC
DO3
DOC DO0
5
12
DO1
DO2
UMCPAN
3
UMC100
Fieldbus
Plug
10 11
13 14
DI0
Local
Remote
15
16
17
18
DI1 DI2 DI3 DI4 DI5
Sim
k1
Off
S1
Fwd Stop
0V 24VDC
From the requirements you can see that the three control places Digital Inputs, Fieldbus and LCD are
used. Furthermore start/stop commands from the different control places shall be blocked or released
depending on the Fieldbus and S1 status. Therefore the different modes can be used.
To read in the S1 commands the three multifunction inputs DI0, DI1 and DI2 are used.
Their configuration is as follows:
Multifunction In 0 = Force Local (NO): This input activates local 2 mode if the user wants to ensure that
the DCS cannot control the motor (Req 1)
Multifunction In 1 = Test Position (NO): This input activates simulation (Req. 4)
Multifunction In 2 = Stop: Stop (NO) is dominant and no start is permitted if the input is active (Req. 3)
For the Remote position no input is needed, because if the UMC is not in local mode, it is automatically in
Auto mode
Finally it is necessary to configure from which control places the motor can be started in the different
FieldBusPlug / Issue:08.2009
- 49 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
operation modes (Auto / Local ).
The following parameters are set according to the requirements (Req 1, Req2, Req 5):
Settings for local mode 1 (For busfault situation)
Loc 1 Start Bus Cyc
Loc 1 Stop Bus Cyc
Loc 1 Start DI
Loc 1 Stop DI
Loc 1 Start LCD
Loc 1 Stop LCD
Loc 1 Start Bus Acyc
Loc 1 Stop Bus Acyc
= YES (Req. 1)
= NO
= YES (Req 5)
= YES (Req 5)
= YES (Req 5)
= YES (Req 5)
= NO
= NO
Settings for Auto/Remote mode (S1 in position Remote)
Auto Start Bus Cyc
Auto Stop Bus Cyc
Auto Start DI
Auto Stop DI
Auto Start LCD
Auto Stop LCD
Auto Start Bus Acyc
Auto Stop Bus Acyc
= YES (Req 2)
= YES (Req 2)
= NO
= YES (Req 2)
= NO
= YES
= YES
= YES
Settings for local mode 2 (Switch S1 in position Local)
Loc 2 Start Bus Cyc
Loc 2 Stop Bus Cyc
Loc 2 Start DI
Loc 2 Stop DI
Loc 2 Start LCD
Loc 2 Stop LCD
Loc 2 Start Bus Acyc
Loc 2 Stop Bus Acyc
= NO
= YES (Req. 1)
= YES (Req. 1)
= YES (Req. 1)
= YES (Req. 1)
= YES (Req. 1)
= NO
= NO
The following diagram shows the simplified UMC internal data flow if S1 is in position Remote as shown
in the circuit diagram before. On the left side there are the four blocks representing the control stations.
Only three of them were required in the example. In the middle the so-called command control selection
block is displayed. On the right the starter function block is displayed. The configuration is as above.
A cross represents a YES, an empty field a NO. The active mode is REMOTE/AUTO as defined by S1.
Therefore the DCS can start the motor. Other start commands (as indicated by DI4) will be blocked.
UMC
Control
Stations
Starter
Function
(e.g. DOL)
...
Digital
Inputs
DI4
DI5
DI0
Start
0
LCD
Panel
Stop
Cyclic Bus
Telegram
1
Acyclic
Bus
Telegram
Bus
Supervision
Fieldbus
UMC100-FBP
0
Force Local 2
Automode
Busfault
Mode
Selection
enable
- 50 -
FieldBusPlug / Issue: 08.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Activating Inching Mode
By default "pulses" are used to issue a start command. This means that a start input has to change its
logic level to issue a start command - i.e. it is edge triggered. After the start command was accepted from
the UMC the input signal can be set back to its initial value (e.g. zero).
For a start signal sent from the digital inputs (DI4/DI5) it is possible to change the behaviour from pulse
mode to inching mode. This means that the motor is only running while the start signal is present. If it is
not present anymore the motor stops automatically.
Relevant Parameters:
For each of the three modes Local Control 1 (Loc1), Local Control 2 (Loc2) and Auto (Auto) the following
parameters are available
- Start bus cyclic
- Stop bus cyclic
- Start LCD
- Stop LCD
- Start bus acyclic
- Stop bus acyclic
- Start DI
- Stop DI
Jog via DI (inching mode)
Invert start DI
Invert stop DI
FieldBusPlug / Issue:08.2009
- 51 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Emergency Start
In some special cases a motor must be started even if the thermal overload protection would prevent the
start (i.e. cooling time is still running). To allow the start in such situations the thermal memory of the UMC
can be reset to cold state. This enables an immediate restart even after a thermal overload trip.
There are two possibilities for an emergency start:
Using the multifunction inputs DI0, DI1 or DI2 an emergency start is carried out as follows:
1. Parameterise DI0, DI1 or DI2 as emergency start input
. Switch the signal on the parameterised input to 1:
- 0 -> 1 transition to reset the UMC100 thermal memory to "cold motor"
- Continuous 1-signal to ignore fault signals on multi-function inputs (if parameterised as fault inputs)
- Switch on motor
To perform an emergency start from the control system / fieldbus, the following steps must be carried out:
1. Set Parameter Emergency = On (default is Off)
. Send command PREPARE EMERGENCY START 0->1 transition via fieldbus to reset the UMC100
thermal memory to cold motor. A continuous 1-signal ignores fault signals originating from the multifunction inputs (if parametrized as fault inputs)
3. Switch on motor
Caution: Starting a hot motor can cause motor damage or destruction of the motor.
Relevant Parameters:
- Emergency Start
- Multifunction 0,1,2
UMC100-FBP
- 52 -
FieldBusPlug / Issue: 08.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Checkback Monitoring
The UMC can be parameterised to monitor that the motor was really started using a checkback signal. By
default the actual motor current is monitored. But it is also possible to use an auxiliary contact mounted
on the main contactor.
If checkback monitoring via motor current is active it is checked that the measured current rose above
20 % within the Checkback Delay Time (tcbd) after switching on the main contactor. Otherwise when the
motor is switched off the function checks that the motor current is zero at the latest after the Checkback
Delay Time.
For checkback via contactors one or more auxiliary contacts must be installed and wired to the UMC's
digital input DI0. The number of monitored signals depends on the selected control functions which are
described in the following sections.
Stop
=================================\--------/=====================
Start
----/=======\-----------------------------------------/=========
Checkback
cbd
cbd
cbd
------/==============================\------------------------/=
Checkback
Fault
------------------------------------------------------------/===
Related Parameters
Checkback Time
Checkback Mode
Using the Digital UMC Inputs
The UMC inputs DI0 ... DI5 are digital inputs according to IEC61131. They can be used to connect status
and control signals to the UMC. UMC's reaction to these signals can be adapted in a wide range to cover
typical user needs (e.g. starting the motor). The status of each digital input is available in the monitoring
telegram sent to the PLC/DCS.
Using the Inputs DI3-DI5
The inputs DI3 to DI5 can be used for local motor control. DI5 is always the stop input whereas DI4 starts
the motor in a forward direction and DI3 in a reverse direction (if supported by the active control function).
If inching mode is enabled the stop can still be used.
Using the Multifunction Inputs DI0-DI2
The digital inputs DI0, DI1 and DI2 are called multifunction inputs because their function can be adapted
flexibly depending to your application requirements. The following diagram shows the way the multifunction inputs work.
The three multifunction inputs operate fully independent - i.e. for each input an own delay time and function can be selected. Functions like 'test position', 'stop motor' etc. internally pass an OR gate so the
UMC does not differentiate from which digital input the signal came.
If an input is configured as fault input the behaviour is different. For each input its own internal error signal
is available and a fault text can be specified which is displayed on the LCD panel in the event of this error.
You can thus find out what input actually triggered the fault. Faults can be auto acknowledged when the
fault has been rectified.
FieldBusPlug / Issue:08.2009
- 53 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
The unchanged signal from the DI is always available for monitoring purposes (Input 1/2/3 status).
*)
Test Postion
On Delay
Ton
DI0
Motor Stop Delayed
External Fault 0
Input 0 Status
Full
DI1
On Delay
Ton
*)
External Fault 1
Input 1 Status
DI2
On Delay
Ton
*)
External Fault 2
Input 2 Status
*) If a digital input is already used for the starter function (e.g. for torque inputs in the actuator modes or
for contactor checkback) they are not available anymore as multifunction inputs.
UMC100-FBP
- 54 -
FieldBusPlug / Issue: 08.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Sample Application for using the Multifunction Inputs
The following diagram shows how to realise a dry-pump protection application. When the motor is starting there is no pressure. It takes some time until the pressure reaches its normal value. In this example we
assume that the pressure has to appear within 4 seconds, otherwise the pump can be destroyed.
T1
T2
Ca
Cb
5 6 7 8 9
UMC100
READY
Pressure switch
MOT.ON
FAULT
Relay
5 6 7 8 9
230VAC DO DO DO DO DO
1A
C C 0 1 2
24 V DC
Power
Inputs
24V 24VDC
24 DC DI
V Out 0
11 12 13
DI
1
14
DI
2
15
DI
3
16
DI
4
17
DI
5
18
2CDC 342 022 F0209
0
V
10
To realize this function the multifunction input can be parameterised in the following way:
Set the delay time to 4s
Set the function to "Fault when motor is running"
Define a meaningful message e.g. "Dry run"
If the pressure switch does not monitor "pressure present" within 4s (or when the pressure signal disappears for more than 4s during operation) the internal fault signal is set and the motor is stopped. The error
message "Dry run" appears as a fault message.
A second example on how to use the multifunction inputs is shown in section "Starting and Stopping the Motor".
FieldBusPlug / Issue:08.2009
- 55 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Control Function Transparent
The UMC100 parametrised with the control function 'Transparent' behaves like an I/O module with an
integrated overload check. The outputs DO0 ... DO3 and the inputs DI0 ... DI5 are directly connected to
the fieldbus and are independent of the overload status.
If a fault output (DO2 or DO3) is activated by configuration the relevant output cannot be controlled from
the fieldbus anymore but is controlled by the UMC itself.
The contactor k1 can be switched on and off for example using a standard maintaining circuit (not
shown).
Alternatively it can be switched on and off from the control system which uses one of the UMC relay outputs to control the motor. This option enables specific control logic to be implemented in the PLC.
The following features are not supported in this control function:
Checkback supervision
UMC controlled starting and stopping (bus, LCD, DI)
Simulation and stop via multifunction inputs
Bus fault reaction
Voltage dip
GND
(24VDC)
24VDC
DO3
DOC DO0
5
12
UMCPAN
L1, L2, L3
Contactor
Supply
(e.g. 230VAC)
DO1
DO2
3
ILim
Fieldbus
Plug
10 11
UMC100
13 14
DI0
15
16
17
18
DI1 DI2 DI3 DI4 DI5
k1
0V 24VDC
Circuit diagram of the UMC in transparent mode.
UMC100-FBP
- 56 -
FieldBusPlug / Issue: 08.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Monitoring Data for Transparent
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Summary
Warning
UMC100
DI5
Summary
Fault
UMC100
DI4
Bit 3
Bit 2
2, 3
Overload warning
UMC100 UMC100
UMC100 UMC100
DI3
DI2
DI1
DI0
Motor Current in % of Ie (0% - 800%)
4, 5
Analogue Word (Thermal Load: 0% - 100%)
6, 7
Analogue Word (Time to trip in seconds)
8, 9
Analogue Word (Time to restart in seconds)
10.11
Analogue Word
0
1
Bit1
Bit 0
12
DX1xx
DI7
DX1xx
DI6
DX1xx
DI5
DX1xx
DI4
DX1xx
DI3
DX1xx
DI2
DX1xx
DI1
DX1xx
DI0
13
14
15
The table above represents the data allocation as realised with the built-in standard applications. It may differ for customer-specific applications!
Command Data for Transparent
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit1
Bit 0
Fault
Reset
Prepare
Emergency
Start
UMC100
DO21)
UMC100
DO1
UMC100 UMC100
DO0
24VDC
Out1)
DO1xx
DO3
DX1xx
DO2
DX1xx
DO1
DX1xx
DO0
0
0
1
2
3
1)
4, 5
Analogue Word
6, 7
Analogue Word
Controlled by UMC100 if configured as fault output.
The table above represents the data allocation as realised with the built-in standard applications. It may differ for customer-specific applications!
FieldBusPlug / Issue:08.2009
- 57 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Control Function Overload Relay
The UMC100 parameterised with the control function 'Overload relay' can be used to replace a standard
overload relay.
The outputs DO2 ... DO3 and the inputs DI0 ... DI5 are directly connected to the fieldbus and not used
from the control function.
If a fault output is activated the fault output (DO2 or 24 V DC Out DO3) cannot be controlled from the
fieldbus anymore but is controlled by the UMC itself.
After powering up, contact DO0 immediately closes and contact DO1 opens.
The following features are not supported in this control function:
Checkback supervision
UMC controlled starting and stopping (bus, LCD, DI)
Simulation and stop via multifunction inputs
Bus fault reaction
Voltage dip
L1, L2, L3
Contactor
Supply
(e.g. 230VAC)
GND
(24VDC)
K1
k1
On
Off
24VDC
DO3
DOC DO0
5
12
UMCPAN
DO1
DO2
3
ILim
Fieldbus
Plug
10 11
UMC100
13 14
DI0
15
16
17
18
DI1 DI2 DI3 DI4 DI5
k1
0V 24VDC
Circuit diagram of the UMC overload relay mode.
Fault Behaviour:
Contact DO0 opens
Contact DO1 closes
The fault output DO2/DO3 is activated if configured
The monitoring signal FAULT is sent to the fieldbus
The red LED on the UMC is switched on
The FAULT signal on the control panel flashes.
UMC100-FBP
- 58 -
FieldBusPlug / Issue: 08.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Monitoring Data for Overload Relay
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Summary
Warning
UMC100
DI5
Summary
Fault
UMC100
DI4
Bit 3
Bit 2
2, 3
Overload warning
UMC100 UMC100
UMC100 UMC100
DI3
DI2
DI1
DI0
Motor Current in % of Ie (0% - 800%)
4, 5
Analogue Word (Thermal Load: 0% - 100%)
6, 7
Analogue Word (Time to trip in seconds)
8, 9
Analogue Word (Time to restart in seconds)
10.11
Analogue Word
0
1
Bit1
Bit 0
12
DX1xx
DI7
DX1xx
DI6
DX1xx
DI5
DX1xx
DI4
DX1xx
DI3
DX1xx
DI2
DX1xx
DI1
DX1xx
DI0
13
14
15
The table above represents the data allocation as realised with the built-in standard applications. It may differ for customer-specific applications!
Command Data Overload Relay
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit1
Bit 0
Fault
Reset
Prepare
Emergency
Start
UMC100
DO21)
UMC100
24VDC
Out1)
DO1xx
DO3
DX1xx
DO2
DX1xx
DO1
DX1xx
DO0
0
0
1
2
3
1)
4, 5
Analogue Word
6, 7
Analogue Word
Controlled by UMC100 if configured as fault output.
The table above represents the data allocation as realised with the built-in standard applications. It may differ for customer-specific applications!
FieldBusPlug / Issue:08.2009
- 59 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Control Function Direct Starter (DOL)
Use this function in a feeder that requires a motor to start/stop in one direction of rotation.
Relay output DO0 is used from the control function.
Optionally DI0 can be used for contactor checkback supervision
Optionally DI4/DI5 can be used to start/stop the motor locally
Optionally terminals named 24VDC Out (12) or DO2 can be used as fault output
The following diagram shows the UMC wired for DOL operation. A signal lamp is connected to DO3
which serves as a fault output. The main contactor is connected to DO0. An auxiliary contact of K is used
by contactor checkback monitoring. The motor can be started locally via DI4 and stopped via DI5. The
remaining digital inputs can be freely used.
GND
(24VDC)
L1, L2, L3
Contactor
Supply
(e.g. 230VAC)
K1
24VDC
DO3
DOC
DO0
12
UMCPAN
DO1
DO2
3
ILim
Fieldbus
Plug
10 11
UMC100
13 14
DI0
15
16
17
18
DI1 DI2 DI3 DI4 DI5
k1
k1
Fwd Stop
0V 24VDC
Circuit diagram of the UMC to control a motor in one direction of rotation. The checkback
contact k1 is optional.
UMC100-FBP
- 60 -
FieldBusPlug / Issue: 08.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Timing Diagram for Direct Starter
Run
Commands
(received
telegram)
Overload
Fault
reset
Run
End of
cooling time Run
RUN FORWARD
OFF
FAULT RESET
UMC internal
UMC outputs
Check-back
FAULT
DO0
Motor current /
aux. contact
RUN FORWARD
Monitoring signals
(telegram)
OFF
WARNING
FAULT
DI1
(aux. contact)
Cooling time
Cooling time running
2CDC 342 023 F0209
Diagnosis
(telegram)
Overload
LEDs
Motor on (yellow)
Fault (red)
FieldBusPlug / Issue:08.2009
- 61 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Monitoring Data for Direct Starter
Word
Byte
Bit 7
Bit 6
Bit 5
Summary
Warning
UMC100
DI5
Summary
Fault
UMC100
DI4
Bit 4
Bit 3
Bit 2
2, 3
Local
Overload Run ForControl
warning
ward
UMC100 UMC100
UMC100 UMC100
DI3
DI2
DI1
DI0
Motor Current in % of Ie (0% - 800%)
4, 5
Analogue Word (Thermal Load: 0% - 100%)
6, 7
Analogue Word (Time to trip in seconds)
8, 9
Analogue Word (Time to restart in seconds)
10.11
Analogue Word
0
1
Bit1
Bit 0
Off
12
DX1xx
DI7
DX1xx
DI6
DX1xx
DI5
DX1xx
DI4
DX1xx
DI3
DX1xx
DI2
DX1xx
DI1
DX1xx
DI0
13
14
15
The table above represents the data allocation as realised with the built-in standard applications. It may differ for customer-specific applications!
Command Data for Direct Starter
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit1
Bit 0
Fault
Reset
Auto
Mode
Prepare
Emergency
Start
Run
Forward
Off
UMC100
DO21)
UMC100
DO1
UMC100
24VDC
Out1)
DO1xx
DO3
DX1xx
DO2
DX1xx
DO1
DX1xx
DO0
0
0
1
2
3
1)
4, 5
Analogue Word
6, 7
Analogue Word
Controlled by the UMC100 if configured as fault output
The table above represents the data allocation as realised with the built-in standard applications. It may differ for customer-specific applications!
UMC100-FBP
- 62 -
FieldBusPlug / Issue: 08.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Control Function Reversing Starter (REV)
Use this function in a feeder that requires a motor to start/stop in two direction of rotation (forwards/backwards).
Relay output DO0 is used by the control function to start the motor in a forward direction.
Relay output DO1 is used from the control function to start the motor in a reverse direction.
Optionally DI0 can be used for contactor checkback supervision
Optionally DI3 / DI4 can be used to start the motor and DI5 to stop the motor
Optionally terminals named 24VDC Out (12) or DO2 can be used as a fault output
The following diagram shows the UMC wired for REV operation. A signal lamp is connected to DO3 which
serves as a fault output. The main contactor is connected to DO0 and DO1. Two auxiliary contacts k1
and k2 are used for contactor checkback monitoring. The motor can be started locally via DI3/DI4 and
stopped via DI5. The remaining digital inputs can be freely used.
Contactor
Supply
(e.g. 230VAC)
GND
(24VDC)
690V/400V
K1
K2
24VDC
Out
12
max.
200mA
UMCPAN
DOC
DO0
DO1
DO2
3
UMC100
Fieldbus
Plug
10 11
13 14
DI0
15
16
17
18
DI1 DI2 DI3 DI4 DI5
k1
forwards
k1
k2
k2
reverse
Start Start
Rev For
0V 24VDC
Circuit diagram of the UMC for controlling a motor in two directions of rotation. The checkback contacts k1/k2 are optional.
FieldBusPlug / Issue:08.2009
- 63 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Timing Diagram for Changing Direction
Run
forward
Commands
(received
telegram)
off
Run
reverse
ignored
Run
reverse
RUN FORWARD
RUN REVSERE
OFF
DO0 (forward)
UMC outputs
DO1 (reverse)
Motor current /
aux. contact
Check-ack
RUN FORWARD
RUN REVSERE
Monitoring signals
(telegram)
LOCK-OUT TIME
LEDs
2CDC 342 024 F0209
OFF
Reversing
lock-out time
Motor on (yellow)
Remark:
Opposite direction only possible after OFF and after the reverse lock-out time has elapsed.
Restart in the same direction without consideration of the Reverse lock-out time.
Related parameters
- Reverse Lockout Time
UMC100-FBP
- 64 -
FieldBusPlug / Issue: 08.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Monitoring Data for Reversing Starter
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Summary
Warning
Summary
Fault
Local
Control
UMC100
DI5
UMC100
DI4
Bit 3
Bit 2
2, 3
Reverse
Overload Run
Lockout
warning
Forward
Time
UMC100 UMC100
UMC100 UMC100
DI3
DI2
DI1
DI0
Motor Current in % of Ie (0% - 800%)
4, 5
Analogue Word (Thermal Load: 0% - 100%)
6, 7
Analogue Word (Time to trip in seconds)
8, 9
Analogue Word (Time to restart in seconds)
10.11
Analogue Word
0
1
Bit1
Bit 0
Off
Run
Reverse
12
DX1xx
DI7
DX1xx
DI6
DX1xx
DI5
DX1xx
DI4
DX1xx
DI3
DX1xx
DI2
DX1xx
DI1
DX1xx
DI0
13
14
15
The table above represents the data allocation as realised with the built-in standard applications. It may differ for customer-specific applications!
Command Data for Reversing Starter
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit1
Bit 0
Fault
Reset
Auto
Mode
Prepare
Emergency
Start
Run
Forward
Off
Run Reverse
UMC100
DO21)
UMC100
24VDC
Out1)
DO1xx
DO3
DX1xx
DO2
DX1xx
DO1
DX1xx
DO0
0
0
1
2
3
1)
4, 5
Analogue Word
6, 7
Analogue Word
Controlled by the UMC100 if configured as fault output.
The table above represents the data allocation as realised with the built-in standard applications. It may differ for customer-specific applications!
FieldBusPlug / Issue:08.2009
- 65 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Control Function Star-Delta Starter
Use this function in a feeder that requires to start/stop a motor in one direction of rotation including the
time- or current-controlled transition from star to delta.
Relay output DO0 is used by the control function to control the star contactor
Relay output DO1 is used by the control function to control the delta contactor
Relay output DO2 is used by the control function to control the main contactor. It cannot be used as
fault output. Use the 24VDC output DO3 if a fault output is required.
Optionally DI0 can be used for contactor checkback supervision
Optionally DI4 can be used to start the motor and DI5 to stop it
Optionally terminal named 24VDC Out (12) can be used as a fault output
The voltage dip function is not supported in this control function.
Adjust parameter YD changeover mode
Adjust parameter YD starting time
The following diagram shows the UMC wired for star-delta operation. A signal lamp is connected to DO3
which serves as a fault output. The main contactor is connected to DO0 to DO2. Three auxiliary contacts
are used for contactor checkback monitoring. The motor can be started locally via DI4 and stopped via
DI5. The remaining digital inputs can be freely used.
GND
(24VDC)
L1, L2, L3
Contactor
Supply
(e.g. 230VAC)
K1
K5
K3
24VDC
DO3
DOC DO0
5
12
DO1
DO2
UMCPAN
ILim
Fieldbus
Plug
10 11
UMC100
13 14
DI0
15
16
3
17
K3=star
K5=delta
K1=main
18
DI1 DI2 DI3 DI4 DI5
k3
k1
k5
k1
k3
Fwd Stop
0V 24VDC
k5
Circuit diagram of the UMC for controlling a motor in star-delta mode. The checkback contacts k3/K5
and K1 are optional.
UMC100-FBP
- 66 -
FieldBusPlug / Issue: 08.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Timing Diagram for Star-Delta Starter
RUN
Commands
(received
telegram)
RUN FORWARD
OFF
DO0 (star)
UMC
outputs
OFF
Star-delta starting time
Changeover time 50 ms
DO1 (delta)
DO2 (main)
Checkback
Motor current /
Aux. contact
RUN FORWARD
DI0 (aux. contact)
LED
Motor on (yellow)
FieldBusPlug / Issue:08.2009
2CDC 342 025 F0209
OFF
Monitoring
signals
(telegram)
- 67 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Monitoring Data for Star-Delta Starter
Word
Byte
Bit 7
Bit 6
Bit 5
Summary
Warning
UMC100
DI5
Summary
Fault
UMC100
DI4
Bit 4
Bit 3
Bit 2
2, 3
Local
Overload Run
Control
warning
Forward
UMC100 UMC100
UMC100 UMC100
DI3
DI2
DI1
DI0
Motor Current in % of Ie (0% - 800%)
4, 5
Analogue Word (Thermal Load: 0% - 100%)
6, 7
Analogue Word (Time to trip in seconds)
8, 9
Analogue Word (Time to restart in seconds)
10.11
Analogue Word
0
1
Bit1
Bit 0
Off
12
DX1xx
DI7
DX1xx
DI6
DX1xx
DI5
DX1xx
DI4
DX1xx
DI3
DX1xx
DI2
DX1xx
DI1
DX1xx
DI0
13
14
15
The table above represents the data allocation as realised with the built-in standard applications. It may differ for customer-specific applications!
Command Data for Star-Delta Starter
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit1
Bit 0
Fault
Reset
Auto
Mode
Prepare
Emergency
Start
Run
Forward
Off
UMC100
24VDC
Out1)
DO1xx
DO3
DX1xx
DO2
DX1xx
DO1
DX1xx
DO0
0
0
1
2
3
1)
4, 5
Analogue Word
6, 7
Analogue Word
Controlled by the UMC100 if configured as fault output.
The table above represents the data allocation as realised with the built-in standard applications. It may differ for customer-specific applications!
UMC100-FBP
- 68 -
FieldBusPlug / Issue: 08.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Control Function Pole-Changing Starter
Use this function in a feeder that requires a two-pole or dahlander motor to start-stop in one direction of
rotation.
Relay output DO0 is used by the control function to start the motor at speed one
Relay output DO1 is used by the control function to start the motor at speed two
Optionally DI0 can be used for contactor checkback supervision
Optionally DI4/D3 can be used to start the motor at speed one/two and DI5 to stop it
Optionally terminals named 24VDC Out (12) or DO2 (9) can be used as a fault output
The voltage dip function is not supported in this control function
Set Ie2 according to the motor nameplate
The following diagram shows the UMC wired for two-pole operation. A signal lamp is connected to DO3
which serves as a fault output. The main contactor is connected to DO0 and DO1. Two auxiliary contacts
are used for contactor checkback monitoring. The motor can be started locally via DI4 (speed one) or DI3
(speed two) and stopped via DI5. The remaining digital inputs can be freely used.
Two-Pole Motor
L1, L2, L3
GND
(24VDC)
Contactor
Supply
(e.g. 230VAC)
K91
K81
24VDC
DO3
DOC DO0
5
12
UMCPAN
DO1
DO2
K81=spped one
K91=speed two
3
ILim
Fieldbus
Plug
10 11
UMC100
13 14
DI0
15
16
17
18
DI1 DI2 DI3 DI4 DI5
k81
k81
k91
Speed2 Speed1 Stop
U1
V1
w1
k91
U2
V2
w2
0V 24VDC
Circuit diagram of the UMC for controlling a two-pole motor. The checkback contacts k81/k91 are
optional.
FieldBusPlug / Issue:08.2009
- 69 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Dahlander Motor
L1, L2, L3
GND
(24VDC)
Contactor
Supply
(e.g. 230VAC)
K81=speed one
K91=speed two
K91a
K91b
K81
24VDC
DO3
DOC DO0
12
UMCPAN
DO1
DO2
3
ILim
Fieldbus
Plug
UMC100
13 14
10 11
DI0
15
16
17
18
DI1 DI2 DI3 DI4 DI5
k81
k91a
k91b
k81
k91
Speed2 Speed1 Stop
U1
V1
w1
U2
V2
w2
0V 24VDC
Circuit diagram of the UMC for controlling dahlander motors. The checkback contacts k81/k91 are
optional.
Timing Diagram for Pole-Changing Starter
Run K1
Command
received
telegram)
UMC
outputs
Check-back
Run K2
RUN FORWARD
RUN FAST FORWARD
DO0 (contactor K1)
DO1 (contactor
K2a, K2b)
Motor current /
aux. contact
RUN FORWARD
RUN FAST FORWARD
OFF
UMC100-FBP
UMC internal
min.
changeover time
LEDs
Motor on (yellow)
approx.
50 ms
- 70 -
2CDC 342 026 F0209
Monitoring signals
(telegram)
FieldBusPlug / Issue: 08.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Monitoring Data for Pole-Changing Starter
Word
Byte
0
0
1
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit1
Bit 0
Summary
Warning
UMC100
DI5
Summary
Fault
UMC100
DI4
Local
Control
UMC100
DI3
Overload
warning
UMC100
DI1
Run
Forward
UMC100
DI0
Off
Run
Fast
Forward
UMC100
DI2
2, 3
Motor Current in % of Ie (0% - 800%)
4, 5
Analogue Word (Thermal Load: 0% - 100%)
6, 7
Analogue Word (Time to trip in seconds)
8, 9
Analogue Word (Time to restart in seconds)
10.11
Analogue Word
12
DX1xx
DI7
DX1xx
DI6
DX1xx
DI5
DX1xx
DI4
DX1xx
DI3
DX1xx
DI2
DX1xx
DI1
DX1xx
DI0
13
14
15
The table above represents the data allocation as realised with the built-in standard applications. It may differ for customer-specific applications!
Command Data for Pole-Changing Starter
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit1
Bit 0
Fault
Reset
Auto
Mode
Prepare
Emergency
Start
Run
Forward
Off
UMC100
DO21)
UMC100
24VDC
Out1)
Run
Fast
Forward
DO1xx
DO3
DX1xx
DO2
DX1xx
DO1
DX1xx
DO0
0
0
1
2
3
1)
4, 5
Analogue Word
6, 7
Analogue Word
Controlled by UMC100 if configured as fault output.
The table above represents the data allocation as realised with the built-in standard applications. It may differ for customer-specific applications!
FieldBusPlug / Issue:08.2009
- 71 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Control Function Actuator 1 - 4
Use this function in a feeder that requires the operation of an actuator that opens/closes e.g. a valve.
Please note that the actuator operation mode is not able to keep a valve at a certain setpoint.
The voltage dip function is not supported and checkback via DIO is not supported in
these control functions.
Set the following parameters as listed here:
- Inv DI start input = No
- Inv DI stop input = No
- Inching DI start input (Jog) = Yes
- Multifunction 0/1 = Off
- Checkback: Current or Simulation (test purposes only)
- Adjust Time Limit Actuator
GND
(24VDC)
L1, L2, L3
Contactor
Supply
(e.g. 230VAC)
K1
K2
24VDC
DO3
DOC DO0
5
12
UMCPAN
DO1
DO2
3
ILim
Fieldbus
Plug
UMC100
10 11
13 14
DI0
Limit
Open
15
16
17
18
DI1 DI2 DI3 DI4 DI5
Limit
Closed
Close
K1=Open
K2=Close
k1
Open
k2
Torque
Open/
Closed
0V 24VDC
Control function = Actuator 2 (Basic circuit)
The control functions Actuator 1, 2, 3 and 4 provide different use of and reaction to the limit switches
Closed and Open as well as the torque switches. The switches must be connected in a predefined
manner to DI0, DI1 and DI3.
Optionally terminals named 24VDC Out (12) or DO2 can be used as a fault output
UMC100-FBP
- 72 -
FieldBusPlug / Issue: 08.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Overview:
Control function
Open <-> Closed
Torque open
Limit open
Limit closed
Torque closed
Actuator 1
Stop
Stop
Actuator 2
Stop
Prepare
Prepare
Stop
Actuator 3
Stop
Prepare
Stop
Actuator 4
Stop
Prepare
Stop
Acutator 1
Open and Closed position via limit switches
Usage with limit switches
DI0: Motor off, start only in Closed direction
DI1: Motor off, start only in Open direction
24V
12
DI0
13
Limit switches
DI1
14
Torque
DI3
16
DI3: Fault: motor stops
Remark:
Open
2CDC 342 020 F0205
Open,
Closed
Closed
Torque signals are not necessary but can
be used for surveillance.
After switching off the motor continues
to run for some milliseconds due to its
rotating mass. Adjustment of the Closed
and Open limit switches is necessary to
achieve the correct end positions.
DI0: Motor off, start only in Close direction
Usage without torque switches
DI1: Motor off, start only in Open direction
DI0
13
Limit switches
DI1
14
Open
FieldBusPlug / Issue:08.2009
DI3
16
Remark:
Connection if torque contacts are not available
2CDC 342 021 F0205
24V
12
Closed
- 73 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Actuator 2
Open and Closed position via torque and limit switches
DI0: Preparation for Open limit motor off
DI0
13
Limit switches
DI1
14
Open
Closed
DI1: Preparation for Closed limit motor off
Torque
DI3
16
DI3:
- Motor off, start only in opposite direction
- Fault if not prepared*
Open,
Closed
2CDC 342 020 F0206
24V
12
*) Start is only possible in the opposite direction after resetting the fault. The torque signal has to disappear within 0.5
s otherwise a fault is generated again.
Remark:
The limit switches Open or Closed prepare
the stop. Torque Open or Closed stops the
motor. Starting is only possible in the opposite direction.
The single torque signals in the telegram
- torque Open or torque Closed - are
calculated based on the direction of movement before the stop.
If after powering up a torque signal is detected and neither an Open nor a Closed
limit is present it is presumed that the
torque occurred during closing. The start
is possible only after fault acknowledgement and only in the opposite direction.
Actuator 3
Open position via limit switch only, Closed position via
torque and limit switches
DI0: Motor off, start only in Closed direction
DI1: Preparation for Closed limit off
24V
12
Limit switches
DI0
DI1
13
14
Torque
DI3
16
DI3:
Motor off if prepared for Closed limit motor
off, start only in Open direction
Open,
Closed
UMC100-FBP
2CDC 342 021 F0206
Open
Fault if not prepared*
Closed
- 74 -
Remark:
The limit switch Open prepares the stop.
Torque Open stops the motor. Starting is
only possible in the opposite direction
The single torque signals in the telegram
- torque open or torque closed - are calculated based on the direction of movement
before the stop.
FieldBusPlug / Issue: 08.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Actuator 4
Open position via torque and limit switches, Closed position via limit switch only
DI0: Preparation for Open limit motor off
DI0
13
Limit switches
DI1
14
Open
Closed
DI1: Motor off, start only in Open direction
Torque
DI3
16
DI3:
Motor off if prepared for Open off, start only
in Closed direction
Open,
Closed
Fault if not prepared or if during closing
2CDC 342 022 F0206
24V
12
Remark:
The limit switch Closed prepares the stop.
Torque closed stops the motor. Starting is
only possible in the opposite direction
The single torque signals in the telegram
- torque Open or torque Closed - are calculated based on the direction of movement
before the stop.
Definitions and monitoring signals particular to the control functions Actuator 1,2,3 and 4
Input signals: Open and Closed inputs are active signals, torque input is a closed loop signal.
The two torque signals are connected in series. The discrete torque signal is created based on the previous direction of movement.
Remark:
If DI2 is not needed as fault input it can be connected to the link between the torque contacts to find out
which torque signal is active.
Run-time Open <-> Closed: The Run-time limit (= Star-delta starting time) must be changed and should
be set according to actuator data. Setting the Run-time limit = 1 s disables the supervision.
Starting from Open or Closed: The limit switch has to open within the start monitoring time of 3 s.
Exceeding the time results in the fault signal Open limit switch 1 -> 0 not occurring within 3 s after the
Closed command. The start monitoring time can be extended.
A faulty torque signal in the intermediate position sets the internal fault signal. The motor is stopped and
can be started again
- after fault reset via fieldbus or other - AND - only in the opposite direction (previous direction is blocked).
After starting the torque signal must disappear within 0.5 s. Otherwise the internal fault signal is set
again. A fault reset and start in the opposite direction can be repeated as often as desired.
If after powering up a torque signal (0-signal) is present and neither an Open nor a Closed signal is
present it is presumed that the torque occurred during closing. The motor can be started:
- after fault reset via fieldbus or other - AND - only in the Open direction
FieldBusPlug / Issue:08.2009
- 75 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Monitoring Data for Actuator 1 - 4
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Summary
Warning
Summary
Fault
Local
Control
UMC100
DI5
UMC100
DI4
Bit 3
Bit 2
2, 3
Reverse
Overload Opening
Lockout
warning
Time
UMC100 UMC100
UMC100 UMC100
DI3
DI2
DI1
DI0
Motor Current in % of Ie (0% - 800%)
4, 5
Analogue Word (Thermal Load: 0% - 100%)
6, 7
Analogue Word (Time to trip in seconds)
8, 9
Analogue Word (Time to restart in seconds)
10.11
Analogue Word
0
1
Bit 0
Off
Closing
DX1xx
DI0
DX1xx
DI1
DX1xx
DI2
DX1xx
DI3
DX1xx
DI4
DX1xx
DI5
DX1xx
DI6
DX1xx
DI7
Runtime
Exceeded
Out of
Position
Torque
Open
Torque
Closed
End Pos
Open
End Pos
Closed
14
15
12
6
13
Bit1
The table above represents the data allocation as realised with the built-in standard applications. It may differ for customer-specific applications!
Command Data for Actuator 1 - 4
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit1
Bit 0
Fault
Reset
Auto
Mode
Prepare
Emergency
Start
Opening
Off
Closing
UMC100
DO21)
UMC100
24VDC
Out1)
DO1xx
DO3
DX1xx
DO2
DX1xx
DO1
DX1xx
DO0
0
0
1
2
3
1)
4, 5
Analogue Word
6, 7
Analogue Word
Controlled by UMC100 if configured as fault output.
The table above represents the data allocation as realised with the built-in standard applications. It may differ for customer-specific applications!
UMC100-FBP
- 76 -
FieldBusPlug / Issue: 08.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
6 Configuring the Fieldbus Communication
The UMC can be integrated into different fieldbus networks with the help of a FieldBusPlug.
FieldBbusPlugs exist presently for PROFIBUS (PDP22 / PDQ22), DeviceNet(DNP21), Modbus (MRP21)
and CANopen (COP21).
Since the fieldbuses and the various fieldbus master configuration tools are very different no common
integration procedure can be described here. In general the following generic steps are usually necessary:
1. Make the UMC known to the tool e.g. by importing the device description file (GSD, EDS)
. Create a network and insert nodes like the UMC as required
3. Set the UMC parameters according to your needs (if parameterisation from within the system is required)
4. Make the I/O signals available in your programming tool (e.g. a IEC61131 based tool)
To use the UMC in a fieldbus network the following parameters should be considered.
Setting the Bus Address
The bus address can be adjusted with the help of the UMC LCD panel. The UMC allows an address to be
set between 000 and 255. But there are different limitations depending on the fieldbus in use. Setting the
address to 255 means that the UMC will take over the address from a connected FieldBusPlug.
PROFIBUS: Use addresses from 2 ...125 only.
DeviceNet: 2-64
Modbus: With the bus address you also select the baud rate used by the MRP21 FieldBusPlug.
Check the MRP21 manual about the available options.
CANopen: 1-127
Ensure that the chosen bus address is not used twice. If an address is used twice the
whole bus line might go out of operation.
Related Parameter: Bus Address
Address Check when using UMC in Motor Control Centres
If the UMC is used in MCCs the address check can be enabled. This ensures that the bus address in the
FieldBusPlug and the UMC must match before the bus communication can start. This ensures that in the
event of an unintentional permutation of a drawer the bus address stays in place and does not move with
the drawer.
A precondition for this function is the separation of FieldBusPlug and UMC. In MCCs the FieldBusPlug is
usually mounted in the cable chamber whereas the UMC is mounted in the withdrawable unit. This means
that even if the withdrawable is removed the FieldBusPlug stays active, keeps the bus address and can
send an error message (missing device) to the control system.
The following cases can occur:
1. Neither the UMC100 nor the FieldBusPlug contains a valid address: The UMC does not start to communicate.
. Only the UMC100 contains a valid address: The FieldBusPlug receives the address and saves it. Then
the bus communication starts automatically.
3. Only the FieldBusPlug contains a valid address (e.g. a new spare UMC is connected) The UMC gets
the address from the FieldBusPlug and saves it. Then the communication starts.
4. The UMC100-FBP and the FieldBusPlug contain the same address: Operation and communication
starts.
5. The UMC100-FBP and the FieldBusPlug contain different addresses (e.g. unintentional permutation
when installing a drawer): The behaviour of the UMC100-FBP depends on the setting of the parameter
Address check.
Case 5a: Address check = Off (= 0) (default)
FieldBusPlug / Issue: 11.2009
- 77 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
The FieldBusPlug stores the address received from the UMC100 and communication starts.
Case 5b: Address check = On (1)
- The communication does not start. In the LCD control panel an address fault is displayed
- To start the bus communication the correct address must be selected in the UMC100
- Enter the fault menu with the left hot-key (Addr)
- Click "Fix" (right hot-key) to select the correct bus address
- After saving the correct bus address the communication starts immediately
- Both the FieldBusPlug and the UMC100-FBP store the adjusted address.
Related Parameter: Address Check
Defining the Bus Fault Reaction
Depending on the application the UMC is used in you might configure the reaction to a bus fault in a different way. The bus fault reaction can be set the following way:
Retain the present state (either running or stopped)
Stop the motor immediately
Start the motor in a forward direction (if actually in stop mode). If it is already running in a reverse or a
forward direction the motor keeps running.
Start the motor in a reverse direction (if actually in stop mode). If it is already running in a reverse or a
forward direction the motor keeps running.
Relevant parameter: Bus Fault Reaction
Ignore Block Parameters
Block parameters can be used to parameterise a device from within the PROFIBUS master using the GSD
file. The PROFIBUS master then sends the parameters in one block (this where the name came from) to
the device. The block parameters are sent under certain conditions:
Bus master start-up
Device start-up
During normal operation in case of parameter changes
If the UMC shall be parameterized via LCD panel or using the PBDTM the block parameters should not be
sent. As it is not possible to stop the bus master from sending the block parameters the FieldBusPlug can
be configured to stop forwarding these parameters to the UMC (i.e. ignore them). To do so set parameter
"Ignore Block Parameter" to "Ignore".
UMC100-FBP
- 78 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
A typical customer error message if this parameter was not set is as follows: "We set up
everything correctly and the plant worked for weeks without problems. But then suddenly the UMC lost its parameters."
What happened: The UMC was configured e.g. via LCD panel during commissioning.
Then weeks later the bus master or controller was restarted for whatever reason and
therefore sent the default UMC block parameters as they were never set.
If you are unsure if the parameter was set correctly you can also lock the parameters
in the UMC. Then no parameter changes are possible anymore until the lock is reset. If
locked the small "lock" icon
is set in the LCD display.
Relevant parameter:
Ignore Block Parameters.
FieldBusPlug / Issue: 11.2009
- 79 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
UMC100-FBP
V6
- 80 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
7 Using Expansion Modules
In this chapter you learn how to use the UMC expansion modules. Expansion modules allow you to
increase the number of usable inputs and outputs. For information on how to connect the IO modules to
the UMC read the Installation chapter. The IO module's status messages are described in the chapter '
Error Handling, Maintenance and Service'.
Activating a Digital IO Module (DX111/122)
To activate a digital IO module set parameter DX1xx Enabled to On. If a module is enabled the UMC
monitors the presence of the module and creates by default a fault in the event that the module is missing
(-> parameter 'Missing Module Reaction').
Using the Digital Inputs
By default all eight digital inputs are available in the fieldbus monitoring telegram. They can thus be directly used in the PLC/DCS application.
For inputs 1DI0 to 1DI5 the following additional options exist:
Each input can separately trigger a fault or warning with a unique error code and error message that is
shown on the UMC's LCD panel.
A fault can be automatically cleared when the cause of the fault is rectified.
Each input can optionally be delayed. (see parameter DX1xx DI delay for details)
The following figure shows the internal data flow of the inputs 1DI0 - 1DI5.
Generate Warning
Ton
Generate Fault
Full
Functionality of the six digital inputs 1DI0 - 1DI5 of the DX111 and DX122 modules.
Using the Relay Outputs
The 4 relay outputs are connected to the fieldbus command telegram and can be freely used by the control system. By default they are not used by the UMC in any way. See the fieldbus command telegram for
the relevant bit positions.
The inputs and outputs of the modules DX122 and DX111 can be freely used in the Custom Application Editor. Consult the editor's manual if you plan to use the inputs or outputs
directly in the UMC.
Using the Analogue Output
The The analogue output can be used to drive an analogue instrument to e.g. display the motor current. It
can work in the following modes: 4-20mA, 0-20mA, 0-10V
Relevant Module Parameters:
DX1xx Enabled
Aux. Inp 1 - 6 Acknowledge Mode
Aux. Inp 1 - 6 Delay
Aux. Inp 1 - 6 Reaction
DX1xx DI Delay (Delay for all inputs)
Aux. Inp 1 -6 Message Line 1 / Line 2
Analog Out0 Type
Missing Module Reaction
Analog Out0 Error Reaction
FieldBusPlug / Issue: 11.2009
- 81 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
UMC100-FBP
V6
- 82 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
8 The LCD Control Panel UMC100-PAN
Overview
The UMC100-PAN provides a easy to use multi-language user interface for the UMC100. In this chapter
you will find the following information:
menu structure
how to operate the UMC100 with the LCD panel
how to acknowledge faults
how to watch process data
how to configure the UMC100 using the LCD panel
See chapter the "Installation" chapter if you are looking for information on how to connect and wire the
LCD panel.
The UMC100-PAN can be either plugged directly on the UMC or mounted on the switchgear door using
the door mounting kit. The following diagram shows the LCD panel with its buttons, LEDs and LCD area.
This chapter describes how the parameters can be accessed from the UMC100-PAN.
Please look into section "Parameters and Data-Structures on a Fieldbus" for an explanation of the parameters and also for an alphabetical list.
Status LEDs:
Green: Ready
Yellow: Running
Red Fault
LCD with background
lightning
Right hot key: Context
- specific function: e.g
"Enter Configuration Menu"
Left hot key: Context
- specific function: e.g.
"Enter Control Menu"
CDC 34015F0009
Scroll upwards
Stop motor
FieldBusPlug / Issue: 11.2009
- 83 -
Scroll downwards
Start motor
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Monitoring Status Information
On the top level of the menu tree which is entered after powering on, several information masks show the
overall status of the UMC and connected IO. To switch between the different masks, use the scroll up or
scroll down keys. The LCD is split into the following different logical areas:
Header: At the top of the LCD the tag name or the submenu title is shown.
Main Area: Main display area to display process data or configuration data etc.
Icon Line: At the bottom of the LCD the actual function of the hot keys (left / right) is shown. In the
middle further status information is displayed as icons. The table below shows the different icons and
their meaning.
Header: e.g. tag name
Main area to display
process values etc ...
Icon bar, hot keys
Left hot key Status Icons Right hot key
function
function
Icon
Meaning
Warnings available. Go into submenu Maintenance/Service->Diagnosis->Present Warnings to find out the reason for the warning.
Motor stopped
Motor running forwards / fast forward
Motor running backwards / fast backwards
LOC
Local control mode 1/2 active
REM
Remote (auto) control mode active
Parameters unlocked / locked: If parameters are locked (indicated with the closed lock in
the icon bar) they cannot be changed either by the fieldbus or using the panel. To change
parameters you have to unlock them first. If password protection is enabled the password has to be typed in first before a parameter can be changed.
Cooling time running. Motor cannot be started until the cooling time is over.
Reverse lockout time is running. The motor cannot be started in opposite direction until
the reverse lockout is over.
Pressing the up/down keys brings you to the next/previous menu on the same level. Pressing Menu enters the first menu level. Pressing Cntrl brings you into the motor control menu.
The figure on the next page shows the top level menu structure and the main configuration menu.
The Menu Tree
If you press
you enter the main configuration menu. The parameters are organised into groups as
described in the section "Parameters and Data Structures on a Fieldbus->Parameter Organisation" and
as shown in the diagram on the following page.
The scroll bar on the right indicates the present location in a configuration menu with several menu items.
On the top of the mask the active menu name (parent menu) is shown.
UMC100-FBP
- 84 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Masks on the top level and the main configuration menu masks.
Top Level Menu
Main Configuration Menu
From any
top mask
Fieldbus
Address
Motor
Current [%]
(right hot key)
From any
mask
(left hot key)
1: Motor management
related settings
(e.g. control function)
2: Motor protection
related settings
(e.g. trip class)
Motor
Current [A]
3: Fieldbus related
settings (e.g. bus
address)
Status UMC
Digital Inputs
4: IO module
related settings
(e.g. DI function)
Status UMC
Digital Outputs
5: Display related
settings
(e.g. Language)
User-defined
mask (1-5)
6: Maintenance
and service
settings and tasks
(e.g. Trip History)
With the right soft key
sections.
FieldBusPlug / Issue: 11.2009
you can enter the selected submenus which are described in the following
- 85 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Motor Management Parameters
Within this submenu all motor management related parameters can be configured. The diagram below
shows the organisation of the different parameter masks in the menu tree.
The parameters are described in details in the section "Parameters and Data Structures on a Fieldbus->Parameter Organisation-> Motor Management Parameters". A
description of the parameters of the menu entry "Auxiliary inputs" can be found in the
section "Parameters and Data-Structures on a Fieldbus->Parameter Organization->
Function Block Related Parameters".
1 Motor Management
1.9 Local control mode 1
Control function
1.9.1 Loc1 start bus cyc.
Reverse lockout time1
1.9.2 Loc1 stop bus cyc.
YD changeover mode2
1.9.3 Loc1 start LCD
YD starting time2
1.9.4 Loc1 stop LCD
Time limit actuator3
1.9.5 Loc1 start bus acyc.
Fault output
1.9.6 Loc1 stop bus acyc.
Checkback
1.9.7 Loc1 start DI
Inching DI start input
1.9.8 Loc1 stop DI
Local ctrl mode 1
Auto ctrl mode
Local ctrl mode 2
1.10 Auto ctrl mode
Invert ctrl inputs
Multifunction inputs
1.10.1 Auto start bus cyc.
Enable custom logic
1.10.2 Auto stop bus cyc.
Extended
1.10.3 Auto start LCD
1.10.4 Auto stop LCD
1.10.5 Auto start bus acyc.
1) Only for control function REV
1.10.6 Auto stop bus acyc.
2) Only for control function YD
3) Only for control function Actuator
1.10.7 Auto start DI
1.10.8 Auto stop DI
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
1.10
1.11
1.12
1.13
1.14
1.15
1.15 Extended
1.15.1
1.15.2
1.15.3
1.15.4
1.15.5
Checkback time
Emergency start
Fault auto reset
Custom app parameter
Auxiliary inputs
1.11 Local control mode 2
1.11.1
1.11.2
1.11.3
1.11.4
1.11.5
1.11.6
1.11.7
1.11.8
Loc2 start bus cyc.
Loc2 stop bus cyc.
Loc2 start LCD
Loc2 stop LCD
Loc2 start bus acyc.
Loc2 stop bus acyc.
Loc2 start DI
Loc2 stop DI
1.13 Multifunction inputs
1.13.1
1.13.2
1.13.3
1.13.4
1.13.5
1.13.6
1.13.7
1.13.8
1.13.9
1.13.10
1.13.12
1.13.14
Multifunction 0
Multifunction 1
Multifunction 2
Multif. 0 delay
Multif. 1 delay
Multif. 2 delay
Multif. 0 autoreset
Multif. 1 autoreset
Multif. 2 autoreset
Multif. 0 fault text L1/2
Multif. 1 fault text L1/2
Multif. 2 fault text L1/2
1.12 Invert ctrl inputs
1.12.1
1.12.2
Invert DI start inp.
Invert DI stop inp.
1.15.5 Auxiliary inputs
1.15.5.1 Aux inp 1 ack mode
1.15.5.2 Aux inp 1 reaction
1.15.5.3 Aux inp 1 delay
1.15.5.4 Aux inp 1 message L1
1.15.5.5 Aux inp 1 message L2
...
(Same repeats for Aux 2 ... 6)
UMC100-FBP
- 86 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Motor Protection Parameters
Within this submenu all motor protection related parameters can be configured. The diagram below
shows the organisation of the different parameter masks in the menu tree.
The parameters are described in detail in the section "Parameters and Data Structures
on a Fieldbus->Parameter Organisation-> Motor Protection Parameters".
2 Protection
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
2.10
2.11
2.12
2.13
Setting Ie 1
Setting Ie 2
Trip class
Current factor
PTC
Cooling mode
Cooling time
Restart level %
Locked rotor (LR)
Thermal load warnlev
Phases
Over/under current
Voltage DIP
2.9 Locked Rotor
2.9.1 LR trip level
2.9.2 LR trip delay
2.11 Phases
2.11.1
2.11.2
2.11.3
2.11.4
2.11.5
Phase loss protect.
Phase imb. trip lev.
Phase imb. warn lev.
Phase reversal
Check phase sequence
2.12 Over / under current
2.12.1
2.12.2
2.12.3
2.12.4
2.12.5
2.12.6
2.12.7
2.12.8
Low curr trip level
Low curr trip delay
Low curr warn level
Low curr warn delay
High curr trip level
High curr trip delay
High curr warn level
High curr warn delay
2.13 Voltage DIP
2.12.1
2.12.2
2.12.3
2.12.4
2.12.5
FieldBusPlug / Issue: 11.2009
- 87 -
Enable voltage DIP
Voltage DIP duration
Autorestart enable
Autorestart window
Autorestart delay
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Communication Parameters
Within this submenu all communication related parameters can be configured. The diagram below shows
the organisation of the different parameter masks in the menu tree. The parameters are described in
details in the section "Parameters and Data Structures on a Fieldbus->Parameter Organisation->Communication Parameters".
3 Communication
3.1
3.2
3.3
3.4
Address check
Busfault reaction
Busaddress
Parameter lock
IO Module Parameters
Within this submenu all IO module related parameters can be configured. The diagram below shows the
organisation of the different parameter masks in the menu tree. The parameters are described in details in
the section "Parameters and Data Structures on a Fieldbus->Parameter Organisation->IO Module Parameters".
4 IO Modules
4.1
4.2
4.31
4.41
4.51
4.3 DX1xx settings
Missing module react.
DX1xx enabled
DX1xx settings
DX1xx monitoring
DX1xx HW+SW version
4.3.1 DX1xx DI delay
4.3.2 DX1xx AO type
4.3.3 DX1xx AO err reac.
1) Only shown if DX1xx is enabled
Display Parameters
Within this submenu all LCD display related parameters can be configured. The figure below shows the
organization of the different parameter masks in the menu tree. The parameters are described in details
in the section "Parameters and Data Structures on a Fieldbus->Parameter Organization->Display Parameters".
5 Display
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
5.10
5.11
5.12
UMC100-FBP
5.11 Password protection
5.11.1 Password enabled
Language
5.11.2 Change password
Tag name
Backlight
User display 1
User display 2
User display 3
User display 4
User display 5
User display 4 text
User display 5 text
Password protection
Panel HW + SW Version
- 88 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Maintenance and Service Parameters/Actions
Within this submenu all maintenance and service related parameters / actions can be configured. The
figure below shows the organisation of the different parameter masks in the menu tree.
Menu point 6.3.1 shows the list of errors and their occurrence in seconds since the start-up of the UMC.
After a power cycle the history buffer is cleared. Use the up/down keys to scroll within the list.
Menu point 6.3.2 shows present warnings. The "i" in the icon bar on the top level masks indicates the
presence of warnings. Use the up/down keys to scroll within the list.
Menu point 6.4 lists all changed parameters. This is useful if you want to verify the parameterization was
carried out correctly or when calling a technical specialist who wants to know what has been configured.
6.1 Maintenance counters
6 Maintenance / service
6.1
6.2
6.3
6.4
6.5
Maintenance counters
Service tasks
Diagnosis
Changed parameters
UMC100 SW version
6.1.1 Motor operation hours
6.1.2 Number of starts
6.1.3 Number of trips
6.2 Service Tasks
6.2.1
6.2.2
6.2.3
6.2.4
Reset parameters
Reset oper. hours
Reset num. of starts
Reset num. of trips
6.3 Diagnosis
6.3.1 Error history
6.3.2 Present warnings
FieldBusPlug / Issue: 11.2009
- 89 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Adjusting Parameters
Adjusting a Numerical Value
This type of dialog allows a numerical value to be specified within the given limits. The single digits must
be defined from right to left. If the last digit was reached the right hot key changes from 'Next' to 'Save'.
When pressing 'Save' the specified value is stored in the UMC. The mask can be exited at any time with
the Cancel button (left hot key). In this case the changes are discarded.
The following example shows how to set the nominal motor current Ie1.
To change the digit use the up/down keys. As it is not possible to enter a value outside the given limits
start editing the first digit by pressing the up button. If you reach 10, a 0 is displayed in the first digit and a
1 in the second digit. Press the left hot key now to go to the next digit.
Last digit to edit
Min/max
value
Next digit
Cancel
editing
Save
changes
Increment digit
Decrement digit
Selecting an Option from a List
This type of dialog allows an item to be selected from a given list of options. With the up/down keys
you can scroll through the list. The slider on the right shows the current position within the list. Pressing
'Select' chooses the currently marked item (inverted). Pressing 'Cancel' exits the dialog and discards the
selection.
Selected option
Slider indicates
position within the
given options
Select option
Previous option in list
Next option in List
Cancel editing
UMC100-FBP
- 90 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Specifying a Text String
This type of dialog allows a character string to be specified e.g. an error message. With the up/down keys
you can scroll through the alphabet and several special characters. Pressing 'Next' selects the next character to edit. When the last character is reached you can save the text string by pressing 'Save' or discard the
changes pressing 'Cancel'.
Last character to edit
Next character
Cancel
editing
Save
changes
Previous character
in ABC
Next character in ABC
FieldBusPlug / Issue: 11.2009
- 91 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Starting and Stopping the Motor
If control via LCD panel was enabled, it is possible to start/stop the motor from the 'Control' menu which
can be accessed from the top level menu when pressing the left hot key (Cntrl). Depending on the selected control function a list of possible start directions is displayed. Pressing the green start button starts
the motor in the selected direction. Pressing the red stop button stops the motor. The motor status icons
show you the present status of the motor.
Main Menu
Cntrl
(left hot key)
Motor Control Menu
Available start
directions depend
on configured
control function
Actual motor state
(here stopped)
Back to
main menu
Select previous option
Start motor in selected
direction (if possible)
Stop motor
(if enabled)
Select next option
UMC100-FBP
- 92 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Acknowledge a Fault
If a fault is present the 'Cntrl' menu is replaced with the menu to acknowledge faults (top level menu, left
hot key). While a fault is present it is not possible to enter the Motor Control menu until the fault has been
acknowledged. When entering the error menu the latest fault message is displayed. By pressing the right
hot key Reset you acknowledge the fault.
If there is another fault pending it is displayed and can also be acknowledged until there is no further fault
pending. Using the up/down keys it is possible to scroll through the list of present faults before acknowledging them. If the last fault was acknowledged the main menu is automatically entered.
The menu can be exited at any time pressing the left hot key Back without resetting any faults.
Error
indication
Enter fault
reset menu
Left hot key
pressed
Automatically
if the last error
was acknowleged
Reset
Previous fault
Back to
main menu
Next fault
The table in the section "Error Handling, Maintenance and Service->Error Handling of
the UMC" lists all diagnosis and fault messages and potential root causes for the fault.
It gives you a first indication of where to look for a fault and how to fix it. Use the error
number shown in the heading (Error 83 in the example) for the look-up table.
FieldBusPlug / Issue: 11.2009
- 93 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
UMC100-FBP
V6
- 94 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
9 Error Handling, Maintenance and Service
Within this chapter you will find the following information
Error handling of the UMC
Detailed explanation of all error and diagnosis messages
Functions related to maintenance and service
Error Handling of the UMC
When the UMC detects a fault condition the fault becomes latched. Once a fault becomes latched, it
remains latched - even if the underlying fault condition is eliminated - until acknowledged by a fault reset
command.
Automatic Reset of Protection Faults
The setting of the "Fault autoreset" parameter determines how the UMC manages protection trips.
Off (the default setting): A protection trip must be acknowledged by the user. This can be done via LCD
panel, fieldbus or the multifunction inputs DI0-DI2 if configured.
On: A protection trip is automatically acknowledged without intervention of either a human operator or
the remote PLC if the trip condition has gone (e.g. cooling time over).
Fault History
The DTM provides access to the fault history. The last 16 faults and their arrival time in seconds since
power on are displayed. If the UMC is switched off the fault history is cleared.
UMC100 Fault Indication
The UMC offers the following possibilities for indicating a fault.
Fault indication via digital outputs: The outputs DO2 and DO3 can be used to signal a summary fault.
DO2 is a relay output that uses the same supply as DO0 and DO1. DO3 is a 24VDC output and can be
used to drive a signal lamp as an example. The fault outputs can be configured with the parameter Fault
Outputs.
Fault indication via LEDs on the UMC: The red fault LED is switched on in the event of a fault and remains on until the fault is acknowledged.
Fault messages on the LCD panel: See the table below.
Signalling via fieldbus: In the event of a fault the "Fault Bit" in the cyclic communication telegram is
set to logical-1. Furthermore a diagnosis telegram (if supported by the used fieldbus) is generated that
describes the fault details.
Fault Messages
The following table lists all diagnosis and fault messages and potential root causes for the fault. It gives
you a first indication of where to look for a fault and how to fix it.
Indicator
Code
Source / Root Cause
Possible Cause / Suggested Action
Thermal overload trip
Load side
Trip because of thermal overload of
the motor.
Check process conditions
Check if the cooling time is too short
Check Ie and trip class settings
Check current factor if configured
Phase loss
FieldBusPlug / Issue: 11.2009
Supply side
Load side
Contactors
- 95 -
At least one phase current is below
the phase loss threshold
Check for blown fuse
Check for loose contacts
Check contact wear
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Indicator
Code
Source / Root Cause
Possible Cause / Suggested Action
Phase imbalance
Supply side
Load side
Contactors
The current in one phase is below the
adjusted threshold.
Check supply side
Check for loose contacts
Check contact wear
Locked Rotor
Load Side
The rotor is locked. Load too heavy
for motor.
Thermal model reached
warning level
Load Side
Thermal model reached warning
level. If overload condition remains a
trip soon follows.
Check motor load condition
Check for mechanical problems
PTC overtemperature
Load side
Environment
PTC element indicated that motor
temperature is too high
Check motor environment and load
conditions
PTC wiring problem
Summary message. See
detailed messages for
more information.
See codes 83/84
Check-back error
Summary message. See
detailed messages for
more information.
See codes 80...82
Motor current below low
current trip threshold
Process
Load side
Load side mechanics
Motor current is below user-defined
threshold e.g. motor running idle, dry
running pump, conveyer belt broken
...
Check motor load and motor / process conditions. Wait until cooling
time is over.
Motor current below low
current warning threshold
Process
Load side
Load side mechanics
Motor current is below user-defined
threshold e.g. motor running idle, dry
running pump, conveyer belt broken
...
Check motor load and motor / process conditions
Motor current above high
current trip threshold
10
Load side
Motor current above threshold
caused e.g. by jammed equipment
Check process conditions (remove
blocking cause). Wait until cooling
time is over.
Motor current above high
current warning threshold
11
Load side
Motor current above user-defined
threshold.
Check motor load and motor / process conditions.
UMC100-FBP
Earth fault (external or
12
internal sensor) above trip
threshold
Load side electrical
Earthfault current above
warning threshold
Load side electrical
13
Connection between one or more
phases and ground
Check wiring / motor (isolation problem)
- 96 -
See above
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Indicator
Code
Source / Root Cause
Possible Cause / Suggested Action
UMC self-test error
14
Electronics
Hardware fault detected
Replace UMC
Actuator problem
15
Load side mechanics
Open/close time of actuator exceeded because of tight valve or other
mechanical reasons.
Check runtime parameter and limit
and torque switch wiring
IO module missing
16
Electronics, Wiring
Communication cable not connected.
Cable break or IO module hardware
error.
Custom application error
(e.g. download incomplete)
17
Configuration
An unrecoverable error was detected
while processing the custom application (e.g. checksum error)
The version of application editor and
UMC are not compatible
IO module error
18
Electronics
A self-test error was detected in an
IO module.
Check the LEDs on the module
Replace the module
Aux1: Error or warning
triggered from auxiliary
function block input 0
19
User-defined
The digital input of an IO module has
created a trip/warning.
Aux2: Error or warning
triggered from auxiliary
function block input 1
20
User-defined
Aux3: Error or warning
triggered from auxiliary
function block input 2
21
User-defined
Aux4: Error or warning
triggered from auxiliary
function block input 3
22
User-defined
Aux5: Error or warning
triggered from auxiliary
function block input 4
23
User-defined
Aux6: Error or warning
triggered from auxiliary
function block input 5
24
User-defined
Multifunction input 0
25
User-defined
Multifunction input 1
26
User-defined
Multifunction input 2
27
User-defined
Cooling time running
45
Process, Load side
Motor was tripped due to thermal
overload. Restart is possible after
cooling time is over
Parameter out of range
54
Electronics, Configuration
Someone tried to write a parameter
which is outside the specifications
Reason depends on what you have
connected to the input.
Note: If the "AuxWarnFault" function
block is used in a different way than
in the predefined applications also
other inputs than the DX1xx can be
the fault source.
A multifunction input of the UMC has
triggered a trip.
The reason depends on what you
have connected to the input.
Check the parameter number that is
causing the problem and change the
value.
When writing parameters from within
a a PLC check your program.
FieldBusPlug / Issue: 11.2009
- 97 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Indicator
Code
Source / Root Cause
Possible Cause / Suggested Action
Torque open in intermediate position
64
Actuator mechanics
Tight operation or wiring problem.
Torque close in intermedi- 65
ate position
Actuator mechanics
Tight operation or wiring problem.
Pos. open and closed at
same time
66
Actuator mechanics
Wiring / position switch problem
End pos. open not left
within specified time
67
Actuator mechanics
Wiring / position switch problem or
wrong adjustment of position switch.
End pos. closed not left
within specified time
68
Actuator mechanics
Wiring / position switch problem or
wrong adjustment of position switch.
End position open without command
69
Actuator mechanics
Wiring / position switch problem.
End position closed without command
70
Actuator mechanics
Wiring / position switch problem.
Left pos. open without
command
71
Actuator mechanics
Wiring / position switch problem.
Left pos. close without
command
72
Actuator mechanics
Wiring / position switch problem.
Motor operation hour
exceeded
74
Load side mechanical
Max. motor operation hours reached.
Wrong password
76
Electronics
Line frequency out of
range
77
Supply side
Check supply
Wrong phase sequence
(reversal)
78
Supply side,
Load side
Phase order is not L1/L2/L3.
CB relay 0
80
Wiring,
Contactors
Expected feedback from a contactor
is missing after checkback time was
over.
Perform motor maintenance
Reset counter
Check wiring of auxiliary contact to
the correct UMC input.
Check contactor
Increase checkback time
CB current
82
Contactors,
Supply side,
Load side
No motor current after motor was
switched on and checkback time was
over. Or motor current falls below
20% while motor is running.
Check supply side
Check that Ie was set correctly
Check current factor if set
Increase checkback time
UMC100-FBP
PTC wire break
83
Wiring
Check between UMC and motor
PTC short-circuit
84
Wiring
Check between UMC and motor
- 98 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Indicator
Code
Source / Root Cause
Possible Cause / Suggested Action
DX111/DX122 module
missing
85
Electronics
An IO module does not respond
during start-up of UMC. See detailed
diagnosis byte to find out which
module is missing.
Check wiring between UMC and
mod.
Check supply of module
Check status LEDs of the module
Overload analog output
DX111/DX122
92
Wiring, connected meter
has a defect
Check wiring, short circuit at analogue output
Wire break analogue
output DX111/DX122
93
Wiring
Check Wiring
Self-test failure DX111/
DX122
94
Wiring
Check Wiring
Resetting Parameters to Factory Defaults
It is possible to reset all parameters to the factory default settings. The fieldbus address is not affected
from the reset command. Also the different maintenance counters are not affected but must be resetted
manually at the UMC100-PAN.
The reset command can be activated via:
UMC100-PAN
Resetting the Password
The password can always be set or disabled using the UMC100 DTM (PBDTM) or using the UMC100PAN.
Reading and Resetting Maintenance Counters
Preventive maintenance is the best way to ensure the long service life of any equipment.
The UMC provides several counters which help to better plan maintenance activities or to track down an
existing problem.
Number of motor starts can help to identify worn-out power contacts or to determine on contactor wear
Number of protection trips
Motor operation hours can help to assess the bearing status and its lubrication
The maintenance counters are available at the UMC100-PAN and in the PBDTM.
FieldBusPlug / Issue: 11.2009
- 99 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
DX1xx Status Codes
Three LEDs show the module status. The following table explains the status messages.
Status
Explanation
Green LED
Yellow LED
Red LED
On
On
On
Self-test during start-up
Flashing
Off
On
Communication with UMC was interrupted. Relay outputs
switched off.
Possible cause: Wiring between UMC and IO module broken.
Possible corrective measure: Check wiring and check that the
module was activated in the UMC configuration.
Flashing
Off
Off
Waiting for communication with UMC. Module is ready.
Possible cause: Wiring between UMC and IO module broken.
Possible corrective measure: Check wiring and check that the
module was activated in the UMC configuration.
On
Off
Off
Cyclic data exchange with UMC. No diagnosis.
On
Flashing
Off
Cyclic data exchange with UMC. Diagnosis exists.
Flashing
Hardware defect.
Flashing
Possible corrective measure: Replace module.
Irrelevant
Replacing a UMC100
The UMC and the current transformer are calibrated together in the ABB factory. Therefore the UMC must
be completely replaced.
The UMC can be disconnected from the FieldbusPlug without disturbing the fieldbus communication and
the other slaves. The FieldbusPlug is supplied via the voltage conducted together with the bus lines. The
FieldbusPlug keeps the actual slave address and informs the control system that the connected device is
disconnected.
Set the parameters in the new UMC depending on your parameterisation concepts.
After mounting and connecting a new UMC, the communication starts up again.
Replacing a DX1xx IO Module
DX1xx modules are automatically parameterized by the UMC if the communication between UMC and IO
module has been established. No further user actions are required.
Requesting Support
If you need support we kindly ask you to contact your local ABB representative using the template provided at the end of this manual.
UMC100-FBP
- 100 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
A1 Parameters and Data Structures on a Fieldbus
In the following chapter you find a detailed description of all UMC parameters, the format of the command monitoring and diagnosis telegrams. Furthermore the information is provided of how the UMC data
is mapped to the different FieldbusPlugs
Monitoring Data
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit1
Bit 0
Summary
Warning
Summary
Fault
Local
Control3
Overload
warning
UMC100
DI5
UMC100
DI4
UMC100
DI3
Run Forward1,3 /
Opening2,3
UMC100
DI0
Run Reverse1,3 /
Closing2,3
-
Reverse
Lockout
Time3
UMC100
DI2
Off
0
0
UMC100
DI1
2, 3
Motor Current in % of Ie (0% - 800%)
4, 5
Analogue Word (Thermal Load: 0% - 100%)
6, 7
Analogue Word (Time to trip in seconds)
8, 9
Analogue Word (Time to restart in seconds)
10.11
Analogue Word
Run
Fast
Forward4)
12
DX1xx
DI7
DX1xx
DI6
DX1xx
DI5
DX1xx
DI4
DX1xx
DI3
DX1xx
DI2
DX1xx
DI1
DX1xx
DI0
13
14
15
The table above represents the data allocation as realised with the built-in standard applications. It may differ for customer-specific applications!
Command Data
Word
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit1
Bit 0
Fault
Reset
Auto
Mode3
Prepare
Emergency
Start
Run Forward1.3 /
Opening2,3
Off
Run Reverse1,3 /
Closing2,3
UMC100
DO2
UMC100
DO1
UMC100 UMC100
DO0
24VDC Out
Run
Fast
Forward 4)
DO1xx
DO3
DX1xx
DO2
DX1xx
DO1
DX1xx
DO0
0
0
1
2
3
4, 5
Analogue Word
6, 7
Analogue Word
8,9
Analogue Word
10,11
Analogue Word
1)
Not for Actuator 1 ... 4
Only for Actuator 1 ... 4
3)
Not for Overload Relay and Transparent
4)
Only for Pole-Changing Starter
2)
FieldBusPlug / Issue: 11.2009
- 101 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
The table above represents the data allocation as realised with the built-in standard applications. It may differ for customer-specific applications!
Diagnosis Data
Word
Byte
0
0
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit1
Bit 0
Checkback
missing
PTC wiring
failure
PTC hot
Prewaring
thermal
model
Locked
rotor during startup (stall)
Phase
imbalance
Phase
loss
Thermal
overload
trip
Actuator
problem1
UMC selftest error
Earth fault
pre-warning
Eart
fault trip
(internal or
externally
triggered)
I above
high
current
warning
threshold
I above
high current trip
threshold
I below low
current
warning
threshold
I below
low current trip
threshold
Trip/Warning from
AuxFault
function
block input
52)
Trip/Warning from
AuxFault
function
block input
42)
Trip/Warning from
AuxFault
function
block
input 32)
Trip/Warning from
AuxFault
function
block
input 22)
Trip/Warning from
AuxFault
function
block
input 12)
HW fault
on IO
module
Custom
application error
IO
module
missing
Trip triggered
from
Multifunction input
DI2
Trip triggered from
Multifunction input
DI1
Trip triggered from
Multifunction
input DI0
Trip /
Warning from
AuxFault
function
block
input 62)
Extended
diagnosis
is available1).
Parameter out of
range
Fault code. See section "Error Handling, Maintenance and Service-> Fault Messages" for a description
of the code.
UMC100-FBP
1)
For details see extended diagnosis byte
2)
By default these diagnosis bits are triggered from the digital inputs of the DX111/DX122 IO module. If you have
created an own custom application these diagnosis bits might be triggered for other reasons (see handbook
"Custom Application Editor" for more details).
- 102 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Accessing Data on PROFIBUS
On PROFIBUS the device parameters, monitoring data and the command data size is described in the
GSD file and mapped to the data telegrams cyclically exchanged between the PROFIBUS master and
the UMC. The diagnosis data is transferred if needed via the extended PROFIBUS diagnosis also described in the GSD file. Device parameters are transferred in one block during bus start or UMC start from
the PROFIBUS master to the UMC. See also the sections "Configuring the Fieldbus Configuration" and
"Commissioning->Configuration from within the control system".
Accessing Data on Modbus
On Modbus the data is provided in so-called registers. A Modbus master can read and write data on
these registers. UMC data is accessible on the following registers:
Modbus Function Code
Register Address
Content
0x0000
Monitoring Data Bytes 0,1
0x0200 (hex)
Monitoring Data Words 1 - 7.
15
0x0100 (hex)
Command Data Bytes 0,1,2,3
16
0x0300 (hex)
Command Data Words 1 - 5
0x2000 (hex)
Diagnosis Data
Plesae note that words 6 and 7 contain
binary data but are read as words!
Plesae note that diagnosis data is
transmitted as words but contains bit
information!
For more information about integrating the UMC in a Modbus network please refer to the MRP21-FBP
(Modbus plug) technical manual.
Accessing Data on DeviceNet
On DeviceNet the device parameters, monitoring data and the command data size is described in the
EDS file. Monitoring, command and diagnosis data is mapped to the data telegrams which are cyclically
exchanged between the DeviceNet master and the UMC. For more information about device parameterisation in DeviceNet networks please refer to the DNP21-FBP (DeviceNet plug) technical manual.
Accessing Data on CANopen
On CANopen the device parameters, monitoring data and the command data size is described in the
CANopen EDS file.
By default
command data is mapped to RPDO1 for binary data and RPDO3 for analogue data.
monitoring data is mapped to TPDO1 for binary byte 0 and 1
analogue monitoring data words 1-5 are mapped to TPDO3/4 . In addition the remaining binary data
(byte 12 - 15) are mapped to TPDO4 too!
Parameters can be set/read using SDO (Service Data Object) communication.
For more information about the CANopen FieldbusPlug please refer to the technical manual of COP21FBP (CANopen plug).
FieldBusPlug / Issue: 11.2009
- 103 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Parameter Organisation
The UMC parameters are described in groups reflecting the major function blocks of the UMC. The figures in braces (e.g. 1.1) provide the link the menu strucutre i.e. where it is displayed.
Motor Management lists all parameters related to motor management i.e. starting and stopping the motor and the control function
Protection lists all parameters related to the motor itself (e.g. nominal current) and the motor protection
functions
Communication lists parameters related to the fieldbus communication
IO Module lists all parameters related to the optional IO expansion modules
Display lists all parameters directly related to the LCD panel
Function block lists all parameters related to a specific function block.
The column "Adjustable via" shows the possible options to adjust a parameter. "All" means the parameter
can be set via UMC100-PAN, GSD-PDP22, GSD-PDQ22, EDS CANopen, EDS DeviceNet and PBDTM.
Otherwise the available options are listed.
Motor Management Parameters
Parameter
Parameter
Description, Explanations
Options
Adjustable via
General motor management parameters
20
Control function Defines the type of starter function
All
Transparent (1),
Overload relay (2),
Direct starter (3),
Reverse starter (4)
Star-delta starter (5),
Pole-changing starter (7),
Actuator_1 (9),
Actuator_2 (10),
Actuator_3 (11),
Actuator_4 (12)
21
Rev lock-out
time
Interlocking time before a start command in the opposite direction is accepted
1-255 s
24
YD changeover
mode
Time (0),
The UMC switches from star to delta
either after a defined time or if the motor Current (1)
current has decreased to 90% of Ie1
25
YD starting
Time switching from star to delta. If the
time (Time Limit changeover mode is set to 'current' this
Actuator)
time defines when the motor current
must be below 90% of Ie.
Defines the maximum travel time from
one end position to the opposite end
position.
27
UMC100-FBP
Fault output
All
All
1s to 360s in steps of
0,1s.
Default: 60s
Unscaled: 10 ... 3600
Example: A value of 10
means 1s
Behaviour of DO2 or DO3 in the event of Off (0),
a trip or fault.
Flashing DO2 (1),
On DO2 (2),
Invert DO2 (3),
Flashing DO3 (4),
On DO3 (5),
Invert DO3 (6)
- 104 -
All
All
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Motor Management Parameters Continued
Parameter
Number
Parameter
Description, Explanations
Options
Adjustable
via
22
Checkback
Selection of the checkback
supervision method.
Contact DI0 (1),
Current (2),
Simulation (3)
All
86
Inching DI
start input
(Jog)
Enables inching (i.e. jogging)
of the start signal originating
from a digital input.
No (0),
Yes (1)
All
19
Enable custom Enable the execution of a
logic
customer defined application
No (0),
Yes (1)
All
All
Local Control Mode 1
90
Loc 1 start
bus cyclic
Allow the motor to be started
via cyclic bus command in
local mode 1
No (0),
Yes (1)
91
Loc 1 stop
bus cyclic
Allow the motor to be stopped via cyclic bus command
in local mode 1
No (0),
Yes (1)
94
Loc1 start
LCD
Allow the motor to be started
via LCD panel in local mode
1
No (0),
Yes (1)
95
Loc1 stop
LCD
Allow the motor to be stopped via LCD panel in local
mode 1
No (0),
Yes (1)
96
Loc1 start bus
acyclic
Allow the motor to be started
via acyclic bus command in
local mode 1 (e.g. from DTM)
No (0),
Yes (1)
97
Loc1 stop bus
acyclic
Allow the motor to be stopped via acyclic bus command in local mode 1 (e.g.
from DTM)
No (0),
Yes (1)
92
Loc1 start DI
Allow the motor to be started
via digital input in local mode
1
No (0),
Yes (1)
93
Loc1 stop DI
Allow the motor to be stopped via digital input in local
mode 1
No (0),
Yes (1)
Local Control Mode 2
FieldBusPlug / Issue: 11.2009
- 105 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Motor Management Parameters Continued
Parameter
Number
Parameter
Description, Explanations
Options
Adjustable
via
106
Loc 2 start bus Allow the motor to be started
cyclic
via cyclic bus command in
local mode 2
No (0),
Yes (1)
All
107
No (0),
Loc 2 stop bus Allow the motor to be stopcyc
ped via cyclic bus command Yes (1)
in local mode 2
110
Loc2 start LCD Allow the motor to be started
via LCD panel in local mode
2
No (0),
Yes (1)
111
Loc2 stop LCD Allow the motor to be stopped via LCD panel in local
mode 2
No (0),
Yes (1)
112
Loc2 start bus
acyclic
Allow the motor to be started
via acyclic bus command in
local mode 2 (e.g. from DTM)
No (0),
Yes (1)
113
Loc2 stop bus
acyc
Allow the motor to be stopped via acyclic bus command in local mode 2 (e.g.
from DTM)
No (0),
Yes (1)
108
Loc2 start DI
Allow the motor to be started
via digital input in local
mode 2
No (0),
Yes (1)
109
Loc2 stop DI
Allow the motor to be stopped via digital input in local
mode 2
No (0),
Yes (1)
Auto Control Mode
UMC100-FBP
98
Auto start bus
cyclic
Allow to start the motor via
cyclic bus command in auto
mode
No (0),
Yes (1)
99
Auto stop bus
cyclic
Allow to stop the motor via
cyclic bus command in auto
mode
No (0),
Yes (1)
102
Auto start LCD
Allow to start the motor via
LCD panel in auto mode
No (0),
Yes (1)
103
Auto stop LCD
Allow to stop the motor via
LCD panel in auto mode
No (0),
Yes (1)
104
Auto start Bus
Acyclic
No (0),
Allow to start the motor via
acyclic bus command in auto Yes (1)
mode (e.g. from DTM)
105
Auto stop Bus
Acyclic
No (0),
Allow to stop the motor via
acyclic bus command in auto Yes (1)
mode (e.g. from DTM)
100
Auto start DI
Allow to start the motor via
digital input in auto mode
No (0),
Yes (1)
101
Auto stop DI
Allow to stop the motor via
digital input in auto mode
No (0),
Yes (1)
- 106 -
All
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Motor Management Parameters Continued
Parameter
Number
Parameter
Description, Explanations
Options
Adjustable
via
All
Invert control (ctrl) Inputs
82
Inv DI start
input
If inverted (Yes) the DI is normally closed. If not inverted
(No) it is normally open.
No (0), Yes (1)
83
Inv DI stop
input
If inverted (Yes) the DI is normally closed. If not inverted
(No) it is normally open.
No (0), Yes (1)
Multifunction Inputs: The following parameters are all related to DI0-DI2 which are called
multifunction inputs as their function can be adjusted in a wide range.
(1.13)
117,
118,
119
Multif. 0,1,2
delay
Delay until the function of
DI0,1,2 is triggered
0...25,5 in steps of 0,1s
120,
121,
122
Multif. 0,1,2
auto reset
If DI0,1,2 is configured as
external fault an auto reset
can be enabled.
No (0),
Yes (1)
135/136
137/138
139/140
Multif. 0,1,2
fault text
Line 1, Line 2
If DI0,1,2 is configured as an
external fault a text message
can be defined which is
shown on the LCD panel.
Line one and line two with 8
characters each.
Default: Fault DIx where
x=0,1,2
PBDTM,
LCD Panel
UMC100PAN
114,
115,
116
Multifunction
0,1,2
Function of DI0/1/2.
Off (0):
Stop NC (1),
Stop NO (2),
Ext. Flt NC always1 (3),
Ext. Flt NO always1 (4),
Ext. Flt NC Motor on (5),
Ext. Flt NO Motor on (6),
Prep. emergency start NC (7),
Prep. emergency start NO (8)
Test position NC (9),
Test position NO (10),
Force local NC (11)
Force local NO (12)
Fault reset NC (13),
Fault reset NO (14),
Voltage DIP NC (15),
Voltage DIP NO(16),
CEM11 always2 (Warn) (17),
CEM11 after startup (Warn) (18),
CEM11 always2 (Fault) (19),
CEM11 after startup (Fault) (20)
All
0.1, 0.2, 0.3, 0.4 ,0.5 ... 25.5
in steps of 0.1s
All excluding GSDPDQ22
NC: Normally closed
NO: Normally open
Motor running or stopped
Always when the motor is
running
1)
2)
All
Unscaled: 0...255
Example: A value of 5 means
500ms
Extended
23
Checkback
time
FieldBusPlug / Issue: 11.2009
The maximum delay between
the output relay was closed
until the checkback signal is
present (signal at DI0 present
or motor current > 20 %
depending on parameter
Check-back)
- 107 -
Unscaled: 0...255
Example: A value of 5 means
500ms
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Motor Management Parameters Continued
Parameter
Number
Parameter
Description, Explanations
Options
Adjustable
via
15
Emergency
Start
To allow start-ups even if the
thermal overload protection
would prevent them.
Off (0), On (1)
All
14
Fault auto
reset
Automatically reset of selected protection faults (PTC,
Overload (EOL), Unbalance).
Off (0), On (1)
All
0 ... 255
All
Faults triggered from the
UMC100 multifunction inputs
and the IO module are not
automatically reset.
81
UMC100-FBP
Custom app
parameter
Allows to specify a value
which is available in the custom application.
- 108 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Protection Parameters
Parameter
Number
Parameter
Name
Description, Explanations
Options
Adjustable via
0.24...3200A in steps of
0.01A
Default: 0.50A
All
Protection Parameters
29
Setting Ie 1
Nominal current of motor for speed
1.
Unscaled: 24...320000
Example: A value of 24
means 240mA
30
Setting Ie 2
Nominal current of motor for speed
2.
See above
All
28
Trip class
Class according to EN/IEC
60947-4-1
Class 5 (0),
Class 10 (1),
Class 20 (2),
Class 30 (3),
Class 40 (4)
All
31
Current factor Current factor when using an external CT or when the motor wires
are fed through the UMC CTs more
than once.
2,3,4,5, 100 ... 64000
All
Examples:
3: motor wires are fed
through 3 times
100: internal CT, no multiple feed-throughs
12500 means a factor of
125:1
Disabled (0),
Trip(1),
Warning(2)
All
Cooling mode After a thermal overload trip which
was triggered through the thermal
motor model the cooling duration
can be defined as fixed time or as
a percentage of the thermal load
level (0%=cold, 100% = trip)
Time (0),
Restart Level (1)
All
49
Cooling time
The time a restart is inhibited following a thermal overload trip triggered by the thermal motor model
30 ... 64000s
Default value: 120s
All
50
Restart level
in %
Below this threshold a motor restart is accepted.
10...100%
Default value: 30%
All excluding
GSDPDQ22
PTC, Thermistor
48
FieldBusPlug / Issue: 11.2009
Setting for the built-in PTC (Thermistor) protection. The reaction to
hardware cannot be set separately.
- 109 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Protection Parameters Continued
Parameter
Number
Parameter
Name
Description, Explanations
Options
Adjustable via
146
Thermal load
warning level
If the thermal model reaches
the warning level a warning is
generated.
20 ... 100
All excluding
GSDPDQ22
Current in percentage that
should trigger a locked rotor
fault during motor start-up. A
value of 800% (160) switches
off the function.
100% ... 800% in steps of 5%
All
The time the motor current
must exceed the adjusted
threshold before a fault is triggered.
0, 0.1, 0.2, 0.3, 0.4, 0.5 ... 25.5s
in steps of 0.1s
Locked Rotor
40
41
Locked rotor
trip level
Locked rotor
trip delay
800% disables the function
Unscaled: 20 ... 160
Example: 100 means 500%
All
Unscaled: 0...255
Example: 5 means 500ms
Phases
42
Phase loss
protection
Trips the motor depending of
the trip class within 1.5 -12
seconds in case of a phase
loss. This parameter must be
set to On during regular operation.
Off (0), On (1)
All
43
Phase imb
trip level
Phase imbalance trip threshold.
Above this value a trip is generated. A value of 100 disables
the trip.
0...100%
100% disables the function
All excluding
GSDPDQ22
Phase imb
warn level
Phase imbalance warning
threshold. Above this value a
warning is generated. A value
of 100 disables the warning.
0...100%
45
Phase
reversal
If enabled the three phases
must be fed through the UMC
CTs in the correct order (L1 left,
L2 middle, L3 right).
L1L2L3 (0),
L3L2L1 (1)
All excluding
GSDPDQ22
46
Check phase
sequence
Enables supervision of phase
sequence (L1/L2/L3)
Disabled (0),
Trip (1),
Warning (2)
All excluding
GSDPDQ22
44
Default value: 50
100% disables the function
All excluding
GSDPDQ22
Over - and Undercurrent
32
Low curr trip
level
Value in % of I/Ie. Below this va- 0...100% in steps of 5%
lue a trip is generated. A value
Default: 0%
of 0% disables the trip.
0% disables the function
All
Unscaled: 0 ... 20
Example: 10 means 50%
UMC100-FBP
- 110 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Protection Parameters Continued
Parameter
Number
Parameter
Name
Description, Explanations
Options
Adjustable via
34
Low curr
warn level
Value in % of I/Ie. Below this
value a warning is generated.
A value of 0% disables the
warning.
0...100% in steps of 5%
Default: 50%
0% disables the function
All
Delay time until a low current
trip is triggered.
0...25.5s in steps of 0.1s
Default: 0.5s
33
Low curr trip
delay
Unscaled: 0...20
Example: 10 means 50%
Unscaled: 0...255
Example: 20 means 2s
35
Low curr
warn delay
Delay time until a low current
warning is triggered.
0...25.5s in steps of 0.1s
Default: 0.5s
Unscaled: 0...255
Example: 20 means 2s
36
38
37
High curr trip
level
High curr
warn level
High curr trip
delay
Value in % of I/Ie. Above this
value a trip is generated. A
value of 800% (160) disables
the trip.
100...800 in steps of 5%
Default: 800%
800% disables the function
Value in % of I/Ie. Above this
value a warning is generated.
A value of 800% (160) disables
the warning
100...800% in steps of 5%.
Default value is 150%.
800% disables the function
Delay time until a high current
trip is triggered..
0...25.5s in steps of 0.1s
Default: 0.5s
High curr
warn delay
Delay time until a high current
warning is triggered.
All excluding
GSDPDQ22
All
Unscaled: 20...160
Example: 100 means 500%
(100% is nominal current)
All
Unscaled: 20...160
Example: 100 means 500%
(100% is nominal current)
Unscaled: 0...255
Example: 20 means 2s
39
All excluding
GSDPDQ22
0...25.5s in steps of 0.1s
Default: 0.5s
Unscaled: 0...255
Example: 20 means 2s
All excluding
GSDPDQ22
All excluding
GSDPDQ22
Voltage Dip/Load Shedding
142
Dip Enable
Enable / Disable function
Off (0),
On (1),
On + Rapid Cycle Lockout (2)
UMC100PAN
PBDTM
143
Voltage Dip
Duration
Max. voltage dip duration time
before a trip is signalled.
0...25.5s in steps of 0.1s
Default: 0.5s
All excluding
GSDPDQ22
Unscaled: 0...255
Example: 5 means 0.5s
144
Autorestart
Window
FieldBusPlug / Issue: 11.2009
If the voltage dip ends within
this time window an autorestart
is triggered (if enabled).
- 111 -
0.1 ... 1s in steps of 0.1s
Unscaled: 1...10
Example: 5 means 0.5s
UMC100PAN
PBDTM
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
145
Autorestart
Delay
Delay until the motor is restarted
0 ... 255s
UMC100PAN
PBDTM
147
Enable Autorestart
Enables the autorestart of the
motor after end of the voltage
dip
Off (0)
On (1)
UMC100PAN
PBDTM
Communication Parameters
Parameter
Number
Parameter Name
Description, Explanations
Options
Adjustable via
17
Address
check
Enable check if bus address stored in
the UMC is the same as the one stored
in the FieldbusPlug.
Off (0), On (1)
All
18
Busfault
reaction
UMC behaviour in the event of a bus
fault.
Motor Off (0),
Retain (1),
Start For (2),
Start Rev (3)
All
Bus
address
Fieldbus address. Depending on the
FieldbusPlug used, the permitted address range is smaller than the one
allowed here.
0,1,2,3 ...255
UMC100PAN
PBDTM
Parameter
lock
Prevents any parameter changes if set
to On.
Unlocked (0), Locked (1)
UMC100PAN
IO Module Parameters
DX111 / DX122 Parameters
Param- Parameter
eter
Name
Number
Description, Explanations
Options
Adjustable via
Missing
Module
Reaction
Defines if the UMC creates a
fault or a warning in case of a
missing IO module.
Error (0)
Warning (1)
All
DX1xx Enabled
Specify if the module is connected to UMC
Off (0), On (1)
All
151
DX1xx DI
delay
Input delay in ms assuming a
line frequency of 50Hz
DX111: 3...200ms
All excluding
GSD-PDQ22
Values are rounded up to the
next multiple of 3.
E.g.:
7,8,9 -> 9 ms delay
In addition to the software
delay a fix hardware delay of
about 4ms must be considered.
DX122: 3...200ms
Values are rounded to the next
multiple of 10. Values below 20
are rounded up to 20.
E.g.:
3...20: 20 ms delay
81...90: 90 ms delay
UMC100-FBP
- 112 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
152
DX1xx AO
type
Hardware type of the analogue output on the DX1xx
module.
0 - 20mA (0),
4 - 20mA (1),
0 - 10mA (2),
0 - 10V (3)
All excluding
GSD-PDQ22
153
DX1xx AO
error
reaction
Reaction if the AO detects
a short-circuit or wire break
condition.
Disabled (0),
Trip (1),
Warning (2)
All excluding
GSD-PDQ22
UMC Display Parameters (5)
Parameter
Number
Parameter Name
Description, Explanations
Options
Adjustable
via
123
Language
Language used on the LCD
panel
English (0), German (1), ... All
124
Tagname
String that is displayed on
the LCD panel
String with 8 chars.
Default: "UMC"
PBDTM
UMC100PAN
125
Backlight
LCD backlight
Off (0), On (1)
All excluding
GSDPDQ22
128
User display 1
Process value shown on the
top level menu.
Thermal Load (0)
DX1xx DI (1)
DX1xx DO (2)
Operating Hours (3)
Number of Trips(4)
Number of Starts (5)
Max. Startup Current (6)
Real Startup Time (7)
All excluding
GSDPDQ22
129
User display 2
Process value shown on the
top level menu.
see above (default is
'Max startup current')
130
User display 3
Process value shown on the
top level menu.
see above (default is
'Real startup time')
131
User display 4
Process value shown on the
top level menu.
Binary 1 (0)
Binary 2 (1)
Analog 1 (2)
Analog 2 (3)
Time to Trip (4)
Time to Cool (5)
132
User display 5
Process value shown on the
top level menu.
see 'User display 4'. Default is 'Time to Cool'.
133
User display 4
text
See custom application
manual for more details.
Text string with 8 characters describing the
displayed value (default
text 'TTT')
134
User display 5
text
See custom application
manual for more details.
Text string with 8 characters describing the
displayed value (default
text 'TTC')
PBDTM
UMC100PAN
Password Protection
126
Password Protection
Change Password Password that permits parameters to be changed
FieldBusPlug / Issue: 11.2009
Enables the motor control /
parameters to be passwordprotected
- 113 -
Off (0), On for Parameters All exclu(1), On for Param. + Mo- ding GSDtor Control (2)
PDQ22
0000 ... 9999
UMC100PAN
PBDTM
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Function Block Related Parameters
Aux Input Block
In the standard built-in applications the inputs of this function block are connected to the digital inputs of
the DX1xx module (see section 'Using Expansion Modules').
Parameter
Number
Parameter Name
Description, Explanation
Options
Adjustable
via
51 - 56
Aux inp 1-6 ack
mode
Definition of the fault reset
behavior
Manual Reset (0)
Auto Reset (1)
All
57 - 61
Aux Inp 1-6 reaction
Definition of the input
function
Disabled (0)
Fault (NC) Motor in On/Off (1)
Fault (NO) Motor in On/Off (2)
Fault (NC) Motor in On (3)
Fault (NO) Motor in On (4)
Warning (NC) Motor in On/Off (5)
Warning (NO) Motor in On/Off (6)
Warning (NC) Motor in On (7)
Warning (NO) Motor in On (8)
All
DTM,
UMC100PAN
NC: Normally closed
NO: Normally open
UMC100-FBP
63/64
65/66
67/68
69/70
71/72
73/74
Aux Inp 1-6 message Line 1/Line 2
Message text line 1 and
line 2
Free text with 8 characters
for each line. Default: Aux
DIx with x=1...6
75 - 80
Aux Inp 1-6 delay
Input delay time in multiples of 100ms
0 ... 255 in multiples of 0.1s
- 114 -
All excluding GSDExample: A value of 5 means
PDQ22
500ms
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
All Parameters Sorted by Parameter Number
No
Name
Parameter Group
No
Name
Parameter Group
DX1xx Enabled
IO Module Parameters
57
Aux Inp 1 Reaction
Aux Input Block
58
Aux Inp 2 Reaction
Aux Input Block
59
Aux Inp 3 Reaction
Aux Input Block
60
Aux Inp 4 Reaction
Aux Input Block
61
Aux Inp 5 Reaction
Aux Input Block
62
Aux Inp 6 Reaction
Aux Input Block
63
Aux Inp 1 Message L1
Aux Input Block
Missing Module React.
IO Module Parameters
PTC, Thermistor
Protection
14
Fault Auto Reset
Motor Management
15
Emergency Start
Motor Management
17
Address Check
Communication
18
Busfault Reaction
Communication
19
Enable Custom Logic
Motor Management
20
Control Function
Motor Management
21
Rev Lock-Out Time
Motor Management
22
Check-Back
Motor Management
23
Check-Back Time
Motor Management
24
YD Change-Over Mode
Motor Management
25
YD Starting Time
Motor Management
27
Fault Output
Motor Management
28
Trip Class
Protection
29
Setting Ie 1
Protection
30
Setting Ie 2
Protection
31
Current Factor
Protection
32
Low Curr Trip Level
Protection
33
Low Curr Trip Delay
Protection
34
Low Curr Warn Level
Protection
35
Low Curr Warn Delay
Protection
36
High Curr Trip Level
Protection
37
High Curr Trip Delay
Protection
38
High Curr Warn Level
Protection
39
High Curr Warn Delay
Protection
40
Locked Rotor Level
Protection
41
Locked Rotor Delay
Protection
42
Phase Loss Prot.
Protection
43
Phase Imb Trip Level
Protection
44
Phase Imb Warn Level
Protection
45
Phase Reversal
Protection
46
Check Phase Sequence
Protection
64
Aux Inp 1 Message L2
Aux Input Block
65
Aux Inp 2 Message L1
Aux Input Block
66
Aux Inp 2 Message L2
Aux Input Block
67
Aux Inp 3 Message L1
Aux Input Block
68
Aux Inp 3 Message L2
Aux Input Block
69
Aux Inp 4 Message L1
Aux Input Block
70
Aux Inp 4 Message L2
Aux Input Block
71
Aux Inp 5 Message L1
Aux Input Block
72
Aux Inp 5 Message L2
Aux Input Block
73
Aux Inp 6 Message L1
Aux Input Block
74
Aux Inp 6 Message L2
Aux Input Block
75
Aux Inp 1 Delay
Aux Input Block
76
Aux Inp 2 Delay
Aux Input Block
77
Aux Inp 3 Delay
Aux Input Block
78
Aux Inp 4 Delay
Aux Input Block
79
Aux Inp 5 Delay
Aux Input Block
80
Aux Inp 6 Delay
Aux Input Block
81
Custom App Parameter Motor Management
82
Invert DI Start Inp.
Motor Management
83
Invert DI Stop Inp.
Motor Management
86
Inching DI Start Inp
Motor Management
90
Loc 1 Start Bus Cyc
Motor Management
91
Loc 1 Stop Bus Cyc
Motor Management
92
Loc 1 Start DI
Motor Management
93
Loc 1 Stop DI
Motor Management
94
Loc 1 Start LCD
Motor Management
95
Loc 1 Stop LCD
Motor Management
96
Loc 1 Start Bus Acyc
Motor Management
97
Loc 1 Stop Bus Acyc
Motor Management
Auto Start Bus Cyc
Motor Management
48
Cooling Mode
Protection
98
49
Cooling Time
Protection
99
Auto Stop Bus Cyc
Motor Management
50
Restart Level
Protection
100
Auto Start DI
Motor Management
51
Aux Inp 1 Ack Mode
Aux Input Block
101
Auto Stop DI
Motor Management
52
Aux Inp 2 Ack Mode
Aux Input Block
102
Auto Start LCD
Motor Management
Auto Stop LCD
Motor Management
53
Aux Inp 3 Ack Mode
Aux Input Block
103
54
Aux Inp 4 Ack Mode
Aux Input Block
104
Auto Start Bus Acyc
Motor Management
Auto Stop Bus Acyc
Motor Management
Loc 2 Start Bus Cyc
Motor Management
55
Aux Inp 5 Ack Mode
Aux Input Block
105
56
Aux Inp 6 Ack Mode
Aux Input Block
106
FieldBusPlug / Issue: 11.2009
- 115 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
UMC100-FBP
V6
No
Name
Parameter Group
No
Name
Parameter Group
107
Loc 2 Stop Bus Cyc
Motor Management
132
User Display 5
Display
108
Loc 2 Start DI
Motor Management
133
User Display 4 Text
Display
109
Loc 2 Stop DI
Motor Management
134
User Display 5 Text
Display
110
Loc 2 Start LCD
Motor Management
135
Multif In 0 Message L1
Motor Management
111
Loc 2 Stop LCD
Motor Management
136
Multif In 0 Message L2
Motor Management
112
Loc 2 Start Bus Acyc
Motor Management
137
Multif In 1 Message L1
Motor Management
113
Loc 2 Stop Bus Acyc
Motor Management
138
Multif In 1 Message L2
Motor Management
114
Multif In 0
Motor Management
139
Multif In 2 Message L1
Motor Management
115
Multif In 1
Motor Management
140
Multif In 2 Message L2
Motor Management
116
Multif In 2
Motor Management
142
Dip Enable
Protection
117
Multif In 0 Delay
Motor Management
143
Dip Duration
Protection
118
Multif In 1 Delay
Motor Management
144
Dip Autorestart Window
Protection
145
Dip Autorestart Delay
Protection
146
Thermal Load Warnlev
Protection
147
Dip Autorestart Enable
Protection
151
DX1xx DI Delay
IO Module Parameters
152
DX1xx AO Type
IO Module Parameters
153
DX1xx AO Err Reac
IO Module Parameters
1000
Parameter Lock
Communication
1001
Busaddress
Communication
119
Multif In 2 Delay
Motor Management
120
Multif In 0 Autoreset
Motor Management
121
Multif In 1 Autoreset
Motor Management
122
Multif In 2 Autoreset
Motor Management
123
Language
Display
124
Tagname
Display
125
Backlight
Display
126
Password Protection
Display
128
User Display 1
Display
129
User Display 2
Display
130
User Display 3
Display
131
User Display 4
Display
- 116 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
All Parameters Sorted Alphabetically
No
Name
Parameter Group
20
Control Function
Motor Management
17
Address Check
Communication
48
Cooling Mode
Protection
Cooling Time
Protection
Current Factor
Protection
104
Auto Start Bus Acyc
Motor Management
49
98
Auto Start Bus Cyc
Motor Management
31
100
Auto Start DI
Motor Management
81
Custom App Parameter
Motor Management
102
Auto Start LCD
Motor Management
145
Dip Autorestart Delay
Protection
105
Auto Stop Bus Acyc
Motor Management
147
Dip Autorestart Enable
Protection
Dip Autorestart Window
Protection
99
Auto Stop Bus Cyc
Motor Management
144
101
Auto Stop DI
Motor Management
143
Dip Duration
Protection
Dip Enable
Protection
103
Auto Stop LCD
Motor Management
142
51
Aux Inp 1 Ack Mode
Aux Input Block
153
DX1xx AO Err Reac
75
Aux Inp 1 Delay
Aux Input Block
IO Module Parameters
63
Aux Inp 1 Message L1
Aux Input Block
152
DX1xx AO Type
IO Module Parameters
64
Aux Inp 1 Message L2
Aux Input Block
151
DX1xx DI Delay
57
Aux Inp 1 Reaction
Aux Input Block
IO Module Parameters
52
Aux Inp 2 Ack Mode
Aux Input Block
DX1xx Enabled
76
Aux Inp 2 Delay
Aux Input Block
IO Module Parameters
65
Aux Inp 2 Message L1
Aux Input Block
15
Emergency Start
Motor Management
66
Aux Inp 2 Message L2
Aux Input Block
19
Enable Custom Logic
Motor Management
58
Aux Inp 2 Reaction
Aux Input Block
14
Fault Auto Reset
Motor Management
53
Aux Inp 3 Ack Mode
Aux Input Block
27
Fault Output
Motor Management
77
Aux Inp 3 Delay
Aux Input Block
37
High Curr Trip Delay
Protection
67
Aux Inp 3 Message L1
Aux Input Block
36
High Curr Trip Level
Protection
68
Aux Inp 3 Message L2
Aux Input Block
39
High Curr Warn Delay
Protection
59
Aux Inp 3 Reaction
Aux Input Block
38
High Curr Warn Level
Protection
54
Aux Inp 4 Ack Mode
Aux Input Block
86
Inching DI Start Inp
Motor Management
78
Aux Inp 4 Delay
Aux Input Block
82
Invert DI Start Inp.
Motor Management
69
Aux Inp 4 Message L1
Aux Input Block
83
Invert DI Stop Inp.
Motor Management
70
Aux Inp 4 Message L2
Aux Input Block
123
Language
Display
60
Aux Inp 4 Reaction
Aux Input Block
96
Loc 1 Start Bus Acyc
Motor Management
55
Aux Inp 5 Ack Mode
Aux Input Block
90
Loc 1 Start Bus Cyc
Motor Management
79
Aux Inp 5 Delay
Aux Input Block
92
Loc 1 Start DI
Motor Management
71
Aux Inp 5 Message L1
Aux Input Block
94
Loc 1 Start LCD
Motor Management
72
Aux Inp 5 Message L2
Aux Input Block
97
Loc 1 Stop Bus Acyc
Motor Management
61
Aux Inp 5 Reaction
Aux Input Block
91
Loc 1 Stop Bus Cyc
Motor Management
56
Aux Inp 6 Ack Mode
Aux Input Block
93
Loc 1 Stop DI
Motor Management
80
Aux Inp 6 Delay
Aux Input Block
95
Loc 1 Stop LCD
Motor Management
73
Aux Inp 6 Message L1
Aux Input Block
112
Loc 2 Start Bus Acyc
Motor Management
74
Aux Inp 6 Message L2
Aux Input Block
106
Loc 2 Start Bus Cyc
Motor Management
62
Aux Inp 6 Reaction
Aux Input Block
108
Loc 2 Start DI
Motor Management
125
Backlight
Display
110
Loc 2 Start LCD
Motor Management
1001
Busaddress
Communication
113
Loc 2 Stop Bus Acyc
Motor Management
18
Busfault Reaction
Communication
107
Loc 2 Stop Bus Cyc
Motor Management
46
Check Phase Sequence
Protection
109
Loc 2 Stop DI
Motor Management
22
Check-Back
Motor Management
111
Loc 2 Stop LCD
Motor Management
23
Check-Back Time
Motor Management
41
Locked Rotor Delay
Protection
FieldBusPlug / Issue: 11.2009
- 117 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
UMC100-FBP
V6
40
Locked Rotor Level
Protection
126
Password Protection
33
Low Curr Trip Delay
Protection
43
Phase Imb Trip Level
Protection
44
Phase Imb Warn Level
Protection
Display
32
Low Curr Trip Level
Protection
35
Low Curr Warn Delay
Protection
42
Phase Loss Prot.
Protection
Phase Reversal
Protection
Protection
34
Low Curr Warn Level
Protection
45
Missing Module React.
IO Module Parameters
PTC, Thermistor
50
Restart Level
Protection
114
Multif In 0
Motor Management
21
Rev Lock-Out Time
Motor Management
120
Multif In 0 Autoreset
Motor Management
29
Setting Ie 1
Protection
117
Multif In 0 Delay
Motor Management
30
Setting Ie 2
Protection
135
Multif In 0 Message L1
Motor Management
124
Tagname
Display
136
Multif In 0 Message L2
Motor Management
146
Thermal Load Warnlev
Protection
115
Multif In 1
Motor Management
28
Trip Class
Protection
121
Multif In 1 Autoreset
Motor Management
128
User Display 1
Display
118
Multif In 1 Delay
Motor Management
129
User Display 2
Display
137
Multif In 1 Message L1
Motor Management
130
User Display 3
Display
138
Multif In 1 Message L2
Motor Management
131
User Display 4
Display
116
Multif In 2
Motor Management
133
User Display 4 Text
Display
122
Multif In 2 Autoreset
Motor Management
132
User Display 5
Display
119
Multif In 2 Delay
Motor Management
134
User Display 5 Text
Display
139
Multif In 2 Message L1
Motor Management
24
YD Change-Over Mode
Motor Management
140
Multif In 2 Message L2
Motor Management
25
YD Starting Time
Motor Management
1000
Parameter Lock
Communication
- 118 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
A2 Examples of Circuit Diagrams
K2
N/-
24
A2
Y22
Y21
Y11
Fwd Stop
k1*
18
17
16
15
13 14
DI0
UMC100
DI1 DI2 DI3 DI4 DI5
9
8
7
5
K1
DO1
DOC DO0
0V 24VDC
Fieldbus
Plug
UMCPAN
10 11
12
24VDC
DO3
Fault /
Fehler
ILim
GND
(24VDC)
(N/-)
DO2
k1
k1
k2
L1, L2, L3
24VDC
0V
A1
C577
Y33
Y12
K1
K2
Y34
EIN/ON
Fault Reset
Fehler Quitt.
23
13
L/+
14
Direct Starter, Category 4
Circuit diagram showing safe-tripping with the help of an emergency stop relay. Carefully read the C577
manual on how to use this device.
FieldBusPlug / Issue: 11.2009
- 119 -
UMC100-FBP
UMC100-FBP
- 120 -
Fieldbus
Plug
UMCPAN
0V 24VDC
10 11
24VDC
Out
12
max.
200mA
Fault /
Fehler
GND
(24VDC)
k1
15
17
DO1
K2
18
k2
Start Start
Rev For
DO2
DI1 DI2 DI3 DI4 DI5
13 14
DI0
16
UMC100
DO0
DOC
K1
N/-
k1
k2
reverse
rckwrts
forwards
vorwrts
k3
690V/400V
Y21
Y11
Y22
Y12
A2
Y34
24VDC
A1
C577
0V
Y33
K1
K2
EIN/ON
Fault Reset
Fehler Quitt.
N/-
K3
23
13
L/+
24
14
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Reversing Starter, Category 4
Circuit diagram showing safe-tripping with the help of an emergency stop relay. Carefully read the C577
manual on how to use this device.
FieldBusPlug / Issue:11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
A3 Technical Data
UMC100
Main Power Lines
Voltage (three-phase systems)
Max. 1000 V AC
Attention: For an Uimp of 6 kV and a voltage of
1000 V the device must be used according to
Annex H EN60947-1 in the range 600 V < Ue <=
1000 V.
(IT Network) only for overvoltage category II. Otherwise overvoltage category III applies.
Conductor holes in the current transformers
Max. 25 mm
(max. diameter incl. insulation 11 mm)
Set current range for overload protection
UMC alone: 0.24-63 A
UMC with provided current transformer: 50-850 A
(see chapter 'Connecting External Current Transformers')
Overload protection for three-phase motors
Acc. to EN/IEC 60947-4-1
Trip classes, selectable by parameter
5, 10, 20, 30, 40* (acc. to EN/IEC 60947-4-1)
*) for over-currents > 6xIe the trip time is 10%
faster than specified in the standard.
Tolerance of tripping time (incl. total ranges of current, temperature 0-60C, frequency 45-65 Hz)
UMC alone: +/- 10 %
Tripping time for phase loss
Trip class:
5 approx. 1.5 s
10 approx. 3 s
20 approx. 6 s
30 approx. 9 s
40 approx. 12 s
Accuracy class of the monitored current (range 50
to 200 % of Ie)
UMC alone 3%
Load per phase:
Approx. 30 milli
Frequency range
45-65 Hz. Protection of frequency converters is
not allowed.
Short-circuit protection
Provided by external short-circuit protection device), e.g. MO, MCB, MCCB or fuse. Refer also to
ABB coordination tables available here:
http://www.abbcontrol.fr/coordination_tables/
TABLES5.asp
Cross-section of lines
Acc. to the rated motor current referring EN/IEC
60947-1 and the specific installation condition in
EN/IEC 60204 or VDE 298-4 resp.
Vibration according IEC 60068-2-6
Shock according IEC 60068-2-27
1g
15 g / 11 ms
FieldBusPlug / Issue: 11.2009
- 121 -
UMC with provided current transformer: +/- 14 %
UMC with provided external
current transformer: 4%
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Tripping time for warm motor for 3-phase
symmetrical loads
Tripping time for cold motor for 3-phase
symmetrical loads
(motor current Ic/Ie = 100 % for long time before
overloading
10000
10000
1000
1000
Clas s 10
100
Clas s 20
Clas s 30
Clas s 5
Triptime
Triptime
Clas s 5
Clas s 10
Clas s 20
100
Clas s 30
Clas s 40
Clas s 40
10
10
1
0
I/Ie
I/Ie
Controller Unit
Supply voltage
24 V DC (+30 % ... -20 %)
(19.2 ... 31.2 V DC) including ripple
Supply current (incl. DIs, relays activated, transistor output loaded with 200mA)
Max. 360 mA (at 19.2 ... 31.2 V DC)
Total power dissipation
Max. 9 W
Reverse polarity protection
Yes
LEDs: Red/yellow/green
Red: Motor has been tripped due to a thermal
overload condition or another fault.
Yellow: Motor is running
Green: Ready for operation
Digital Inputs
Number of digital inputs
6 (DI0 ... DI5)
Type 1 accord. to EN 61131-2
Supply for digital inputs
24 V DC
Note: Input value of the UMC100 DIs is undefined
if the UMC supply is outside the specified limits.
UMC100-FBP
Isolation
No
Input signal bounce suppression
Typ. 2 ms
Signal 0 range including ripple
-31.2 ... +5 V
Signal 1 range including ripple
+15 ... +31.2 V
Input current per channel (24 V DC)
Typ. 6.0 mA
- 122 -
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Digital Inputs
Input resistor to 0 V
3.9 k
Cable length
unshielded max. 600 m
shielded max. 1000 m
Relay Outputs
Number of relay outputs
3 x monostable with one common root
Voltage range of contacts
12-250 V AC/DC
Lowest switched power for correct signals
1 W or 1 VA
Switching capacity per relay contact acc. to EN
60947-5-1 (electromagnetic load)
AC-15 240 V AC: max. 1,5 A
AC-15 120 V AC: max. 3 A
DC-13 250 V DC max. 0.11 A
DC-13 125 V DC max. 0.22 A
DC-13 24 V DC max. 1 A
Short-circuit protection
6 A gL / gG
Switching of inductive power
Inductive loads need additional measures for
spark suppression. Diodes for DC voltage and varistors / RC elements for AC voltage are suitable.
Some DC coil contactors contain rectifiers which
suppress sparks perfectly.
Relay contact service life
Mechanical 500 000 switching cycles
Electrical (250 V AC):
0.5 A: 100 000 cycles
1.5 A 50 000 switching
Internal clearance and creepage distances relay
contacts to 24 V circuits
> 5.5 mm (safety insulation up to 250 V AC)
(EN 60947-1, Pollution degree 2)
Supply power down/up, behaviour: Valid for all
motor control functions, but not for transparent
and overload relay.
Whenever the supply voltage of the UMC is
switched off and on, the starting of the motor
needs a new RUN signal.
Digital Output
Max. output current
200mA
Short circuit protected
Yes
Output voltage if high
UMC100 supply voltage, nominal 24VDC
Isolation
No
Thermistor Motor Protection (PTC - binary)
Broken wire resistance
> 4.8 k
Response resistance
3.4 - 3.8 k
Reset resistance
1.5 - 1.8 k
Response time
800 ms
Max. cold resistance of PTC sensor chain
< 1.5 k
Line length
2.5 mm2: 2 x 250 m
1.5 mm2: 2 x 150 m
0.5 mm2: 2 x 50 m
Isolation
No
FieldBusPlug / Issue: 11.2009
- 123 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
Fieldbus Connection
Mounting
Plug connection, fastening with supplied screw
Tightening torque of the fixing screw
0.8 Nm + rotation 90 degree
Suitable ABB FieldBusPlug types for
PROFIBUS: PDP22-FBP or PDQ22
Modbus: MRP21
DeviceNet: DNR21
CANopen: COP21
Environmental and mechanical data
Mounting
On DIN rail (EN 50022-35) or with 4 screws M4
Mounting position
Any
Dimensions (W x H x D)
70 x 105 x 110 mm (incl. FieldBusPlug and Control
Panel)
Net weight
0.282 kg (current transformer + controller unit)
Wire size and tightening torque
0.5 Nm
4.5 in.lb
3,5 mm / 0.138 in
7mm
0.28 in
2x 0.2 ... 2,5mm
2x 28 ... 12 AWG
7mm
0.28 in
2x 0.2-2.5mm
2x 28 ... 12 AWG
Tightening torque for screw mounting
0.8 Nm
Degree of protection
UMC: IP20
Temperature range
Storage -25 ... +70 C
Operation 0 ... +60 C
Marks, Approvals
CE, cUL, Further in preparation. Ask your local
sales representative for other approvals.
Performance Data
UMC100-FBP
Reaction time UMC100 DI to UMC100 Relay Output (incl. hardware delays).
typ. 10ms (Transparent Control Function)
Reaction time UMC100 DI to DX111 Relay Output
(incl. hardware delays)
Reaction time from DX111 DI to UMC100 Relay
Ouput (incl. hardware delays)
typ. 10 ms (Transparent Control Function)
Number of supported function blocks:
See 2CDC 135 014 D02xx
- 124 -
typ. 14 ms (Transparent Control Function)
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
UMC100-PAN
Installation
Installation in a switchgear cabinet door or on a
front panel.
Degree of protection
IP54 (on front side)
LEDs: Red/Yellow/Green
By default the LEDs have the same meaning as
the ones on the UMC100.
Red: Error
Yellow: Motor is running
Green: Ready for operation
Buttons
6 buttons with fixed meaning
Dimensions (WxHxD)
50 x 66 x 15 mm
Net weight
0,039 kg
Temperature range
Storage -25 ... +70 C
Operation 0 ... +55 C
Tightening Torque for screw mounting
0.5 Nm
DX111 and DX122
General
Mounting
Snap-on mounting onto 35 mm standard mounting rails
Mounting position
Any
Dimensions (W x H x D)
45 x 77 x 100 mm
(excluding communication connector)
LEDs: Red/yellow/green
Red: Hardware error of module
Yellow: Diagnosis available
Green: Ready for operation
Supply voltage
24 V DC (+30 % ... -20 %)
(19.2 ... 31.2 V DC) including ripple
Supply current
Max. 90mA (at 19.2 ... 31.2 V DC)
Tightening torque for the input, output and supply
terminals
4,5 mm / 0.177 in / PH 1
0.6 ... 0.8 Nm
5.31 ... 7.08 in.lb
7mm
0.28 in
2 x 0.5 ... 4 mm2
2 x 20 ... 12 AWG
7mm
0.28 in
2 x 0.75 ... 2.5 mm2
2 x 18 ... 14 AWG
7mm
0.28 in
2 x 0.75 ... 2.5 mm2
2 x 18 ... 14 AWG
FieldBusPlug / Issue: 11.2009
- 125 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
V6
General
Tightening torque for the communication terminals
0.22 Nm
1,5 mm
7mm
0.28 in
1 x 0.14 ... 1.5 mm2
28 ... 16 AWG
7mm
0.28 in
1 x 0.14 ... 1.5 mm2
28 ... 16 AWG
7mm
0.28 in
1 x 0.25 ... 0.5 mm2
28 ... 16AWG
Net weight
0.22 kg
Degree of protection
IP20
Temperature range
storage -25 ... +70 C
operation 0 ... +55 C (DX122) / +60 C (DX111)
Marks, Approvals
CE, cUL
Furher in preparation. Ask your local sales representative for other marks/approvals.
Relay Outputs
Number of relay outputs
4
1DO1, 1DO2 with root 1DOC
2DO3, 2DO4 with root 2DOC
Voltage range of contacts
12-250 V AC/DC
Short-circuit protection
6 A gL / gG per root (1DOC, 2DOC)
Lowest switched power for correct signals
1 W or 1 VA
Switching of inductive power
Inductive loads need additional measures for
spark suppression. Diodes for DC voltage and
varistors / RC elements for AC voltage are suitable. Some DC coil contactors contain rectifiers
which suppress sparks perfectly.
Switching capacity per relay contact acc. to EN
60947-5-1 (electromagnetic load)
AC-15 240 V AC: max. 1,5 A
AC-15 120 V AC: max. 3 A
DC-13 250 V DC max. 0.11 A
DC-13 125 V DC max. 0.22 A
DC-13 24 V DC max. 1 A
Relay contact service life
Mechanical 500 000 switching cycles
Electrical (250 V AC):
0.5 A: 100 000 cycles
1.5 A 50 000 switching
Internal clearance and creepage distances of relay
contacts to 24 V circuits
UMC100-FBP
- 126 -
> 5.5 mm (safety insulation up to 250 V AC)
(EN 60947-1, Pollution degree 2)
FieldBusPlug / Issue: 11.2009
V6
Universal Motor Controller
UMC100-FBP
Technical Description
Digital Inputs DX111
Number of digital inputs
8 externally supplied, isolated inputs
Type 1 accord. to EN 61131-1
1DI0 ... 1DI4 with common root 1DIZ
2DI5 ... 2DI7 with common root 2DIZ
Supply for digital inputs
24 V DC
Isolation
Yes
Input signal bounce suppression
Typ. 6ms
Signal 0 range including ripple
-31.2 ... +5 V
Signal 1 range including ripple
+15 ... +31.2 V
Input current per channel (24 V DC)
Typ. 6.0 mA
Input resistor to 0 V
3.9 k
Cable length
unshielded max. 600 m
shielded max. 1000 m
Digital Inputs DX122
Number of digital inputs
8 externally supplied, isolated inputs
Type 2 accord. to EN 61131-1
1DI0 ... 1DI4 with common root 1DIZ
2DI5 ... 2DI7 with common root 2DIZ
Supply for digital inputs
110 V AC - 240 V AC
Isolation
Yes
Input signal bounce suppression
Typ. 20 ms
Signal 0 range including ripple
0 ... 40 V AC
Signal 1 range including ripple
74 ... 265 V AC
Frequency range
45 ... 65 Hz
Input current per channel (230V AC)
Typ. 10 mA
Analogue Output
Type of connection
2-wire connection to display e.g. the motor current
on an analogue meter.
Configurable output range
0-10mA, 0/4 mA - 20 mA, 0-10 V
Cable shielding
Recommended for up to 30 m and outside the
switchgear cabinet; shielding mandatory for
cables over 30 m
Max. output voltage
10V
Accuracy
< 5%
Max. output load
500 (if configured as current output)
Min. output load
1k (if configured as voltage output)
Resolution
8 bit
Short-circuit-proof
Yes
Open-wire detection
Short-circuit detection
Yes, if configured as 0/4-20 mA output
Yes, if configured as 0-10V output
Isolation
No
FieldBusPlug / Issue: 11.2009
- 127 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
UMC100-FBP
V6
- 128 -
FieldBusPlug / Issue: 11.2009
Universal Motor Controller
UMC100-FBP
Technical Description
V6
FAX No.: +49 (0) 6221-701-1382
Detected an Error?
Your feedback helps us to constantly improve our products. We are grateful for your comments and
suggestions. Please provide us with the following information if you have noticed an issue:
Name
Company / Department
Telephone / Email
Problem Description
Steps to reproduce the problem
Version of UMC (Ident number on nameplate and firmware version which is displayed on the UMC100-PAN)
Version of PBDTM (ControlPanel->Sofware) / AssetVisionBasic (Help->About) / Windows (Control->System)
FieldBusPlug / Issue: 11.2008
- 129 -
UMC100-FBP
Universal Motor Controller
UMC100-FBP
Technical Description
UMC100-FBP
V6
- 130 -
FieldBusPlug / Issue: 11.208
11.2009
2CDC 135 013 D0201
Manual No.
ABB STOTZ-KONTAKT GmbH
Eppelheimer Strae 82 Postfach 101680
69123 Heidelberg 69006 Heidelberg
Germany Germany
Telephone
Telefax
E-mail
Internet
+49 (0) 6221 701- 0
+49 (0) 6221 701- 240
[email protected]http://www.abb.de/stotz-kontakt