Product data sheet
Characteristics
XCKN0118P20
limit switch XCKN - thermoplastic roller lever 1NC+1NO - snap - M20
Range of product
OsiSense XC
Series name
Standard format
Product or component
type
Limit switch
Device short name
XCKN
Sensor design
Compact form A
Body type
Fixed
Head type
Rotary head
Material
Plastic
Body material
Plastic
Head material
Plastic
Fixing mode
By the body
Movement of operating
head
Rotary
Type of operator
Spring return roller lever thermoplastic
Type of approach
Lateral approach 2 directions
Cable entry
1 entry tapped for M20 x 1.5 cable gland, cable outer diameter: 7...13 mm
Number of poles
Contacts type and composition
1 NC + 1 NO
Contacts operation
Snap action
Complementary
Tracks
24/40 mm
Switch actuation
By 30 cam
Electrical connection
Screw-clamp open terminals, clamping capacity: 1 x 0.34...2 x 1.5 mm
Contacts insulation form
Zb
Positive opening
With
Positive opening minimum torque
0.15 N.m
Minimum torque for tripping
0.1 N.m
Maximum actuation speed
1.5 m/s
Contact code designation
R300, DC-13 (Ue = 250 V, Ie = 0.1 A) conforming to EN/IEC 60947-5-1 appendix
A
A300, AC-15 (Ue = 240 V, Ie = 3 A) , Ithe = 10 A conforming to EN/IEC
60947-5-1 appendix A
[Ui] rated insulation voltage
300 V conforming to CSA C22.2 No 14
500 V degree of pollution 3 conforming to IEC 60947-1
300 V conforming to UL 508
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-1
6 kV conforming to IEC 60664
Short circuit protection
10 A cartridge fuse type gG
Electrical durability
5000000 cycles, DC-13, 48 V, 7 W, operating rate: <= 60 cyc/mn, load factor: 0.5
conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13, 24 V, 10 W, operating rate: <= 60 cyc/mn, load factor:
0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13, 120 V, 4 W, operating rate: <= 60 cyc/mn, load factor:
0.5 conforming to IEC 60947-5-1 appendix C
Mechanical durability
10000000 cycles
Width
30 mm
Apr 1, 2016
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Main
Height
108 mm
Depth
44.5 mm
Product weight
0.175 kg
Terminals description ISO n1
(13-14)NO
(21-22)NC
Environment
Shock resistance
50 gn (duration = 11 ms) conforming to IEC 60068-2-27
Vibration resistance
25 gn (f = 10...500 Hz) conforming to IEC 60068-2-6
IP degree of protection
IP65 conforming to IEC 60529
IK degree of protection
IK04 conforming to EN 50102
Class of protection against electric shock
Class II conforming to NF C 20-030
Class II conforming to IEC 61140
Ambient air temperature for operation
-25...70 C
Ambient air temperature for storage
-40...70 C
Protective treatment
TC
Product certifications
CCC
CSA
UL
Standards
EN 60204-1
EN 60947-5-1
IEC 60204-1
IEC 60947-5-1
UL 508
CSA C22.2 No 14
Offer Sustainability
Sustainable offer status
RoHS (date code: YYWW)
Green Premium product
Compliant - since 0953 -
Schneider Electric declaration of conformity
REACh
Reference not containing SVHC above the threshold
Product environmental profile
Available
Product end of life instructions
Need no specific recycling operations
Download Product Environmental
Product data sheet
Dimensions Drawings
XCKN0118P20
Dimensions
(1)
(2)
1 tapped entry for M20 x 1.5
: 2 elongated holes 4.3 x 6.3 on 22 mm centres, 2 holes 4.3 on 20 mm centres.
Product data sheet
Mounting and Clearance
Mounting with Cable Entry
Position of Cable Gland
(1)
(2)
Recommended
To be avoided
XCKN0118P20