Leak Detection - DC Pipe
Leak Detection - DC Pipe
INSTALLATION
AND
OPERATION MANUAL
PAGE 3-26 CWA 9000 START-UP AND OPERATION
28 TYPICAL INSTALLATION CWA 900
29 BLOCK SCHEMATICS
30 COMPONENT PLACEMENT
31 DIMENSIONS
32 TERMINALS
34 HEATER
35-40 MATCHING BOX CWA 9092
41-49 SENSOR WIRES
50-55 PLANNING OF ALARM SYSTEM
56-63 INSTALLATION OF SENSOR WIRES
65-65 WORK SHEET
66-69 ELECTRICAL TEST
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
Operation instructions
CWA 9000
Also refer to project manual for specific data.
Start up
Monitoring
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
NOTE:
before THE START-UP, it is necessary to have checked the
whole pipesection according to the installation/testing
instructions.
It is also advised that all reference-points have been established
and the appropriate forms have been filled-in.
Make sure that all as-built-drawings are properly up-dated with
all
Compensators, Tees and Elbow marked, all distance measurements are noted on the same. All drawings should be available
during start-up.
It is also advised that the TDR is available if there should occur
any problems. The LCD screen on the LD Unit will instruct you
on the proceedings step by step and it will be simple to follow
the instructions.
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
eo553
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
Selfcheck
VER. 4.20
COMADS. xx
ANY KEY TO PROCEED
COPYRIGHT
CWA SYSTEM AB
1988 - 1993
PRESS:
SETTING UP CHANNEL
NUMBER 1
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
Sensitivity setting
The unit has four different sensitivity levels. The sensitivity level
that shall be used depends on what kind of liquids that are to be
monitored and the type of sensor cable/wire that is being used.
Sensitivity <1> is most sensitive and <4> least sensitive.
[For District Heating sensitivity <4> is recommended.]
For other applications, refer to project manual.
The unit will ask for the sensitivity setting for each channel
installed individually.
Example: PRESS:
CHANNEL 1
SENSITIVITY <4>
M/R TO ACCEPT
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
Propagation speed
The unit has to know the propagation speed for each installed
channel and its cable.
For District Heating with direct applied foam, propagation speed is
usually 91%.
SET PROPAGATION
SPEED FOR CHANNEL 1
ENTER 3 DIGITS
REL. SPEED =
Example: 91%
PRESS:
SET PROPAGATION
SPEED FOR CHANNEL 1
ENTER 3 DIGITS
REL. SPEED = 0,910
to get accurate
readings in case of a
leak.
INITIALIZING ch:1
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
Cable end
CHANNEL 1:
SET UP TO MONITOR
860 METERS
<F> TO PROCEED
NOTE:
Later on in the start-up procedure, it is possible to adjust the
propagation speed to get the exact cable length corresponding to
the physical length of the pipe system.
Differences greater than + 10% at this stage are unusual. If the value
is drastically shorter than expected, a break is present.
Check with TDR.
If the value is much longer, you may not have an open end of the
cable.
Check with TDR.
The echo from the open end can also be too small, due to impedance
mismatches on the cable.
Check with TDR.
Example:
Physical length = 860 meters
Given value = 530 meters
Check with TDR and repair.
After having the right distance displayed:
PRESS:
F
EO557
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
Measuring Line
Here, the cable is also being checked for acceptance of use. You
will be notified if so.
This is a slow procedure; it can take about 1 min./ 100 meters of
wire.
MEASURING LINE 1
COMPUTING LIMITS
CH. 1
OFFSET ZERO ?
<F>=YES <R>=NO
EO558
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
Offset zero
The OFFSET ZERO function is used when you have the Leak
Detector unit installed far away from the startpoint of the sensor
wire and a Jumper Cable RG 58 C/U is used between the Leak
Detector Unit and the matchingbox CWA 9091. The Jumper
Cable can be max. 100 m. long. The OFFSET ZERO function
enables the Jumper Cable to be integrated into the unit so that
the measuring starts at the connection point at the pipe.
NOTE:
A Break or a Short along the Jumper Cable will be displayed as a
negative value on the LCD display.
Example: [ BREAK AT -47 m ] means that the break is at 47 m
from the desired ZERO POINT towards the Leak Detector.
CH. 1
OFFSET ZERO ?
<F>=YES <R>=NO
PRESS:
PRESS:
ALT. B:
B: YES: Go to next page.
Let the unit measure from the
pipe-end.
EO559
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
10
Alternative B:
If you have an installation where different cabletypes with different propagation speeds are used, (usually coax RG 58 as a
jumper cable ) between the unit and the detector cable, you may
choose to integrate the jumper cable into the unit.
This is advantageous because the two cables have different
electrical characteristics and propagation speeds and therefore
will give erroneous distance values in case of a Leak/Break
alarm.
DISCONNECT CABLE 1
AT THE DESIRED ZERO
POINT THEN PRESS
ANY KEY TO PROCEED
any
RECONNECT CABLE
AT ZERO POINT THEN
ANY KEY TO
CONTINUE
PRESS:
any
Go to page LE. 9: 14 and proceed from there.
EO5510
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
11
Cable End
Offset Zero
Normal
1. Normal
The normal position. Check that the switch is set in this position
before the start up procedure is started.
The switch shall also be in this position in monitoring mode.
CWA 9000
Closed
Open
Cable End
Offset Zero
Normal
2. Offset Zero
The switch makes a break at the beginning of the leak detection
loop. Used when the Offset Zero point shall be detected.
When the unit prompts you to "disconnect the cable at desired
zero point", set the switch in this position.
When the unit prompts you to "reconnect the cable", set the
switch back to Normal position.
CWA 9000
Open
Open
Cable End
Offset Zero
Normal
Do NOT forget to
set switch in
"NORMAL"
position.
3. Cable End
The switch makes a short at the end of the leak detection loop. Used
when the Propagation speed shall be adjusted.
When the unit prompts you to "short the far end of the cable(s)to
be adjusted", set the switch in this position.
When the unit prompts you to "remove the shorts at cable
ends", set the switch back to Normal position
CWA 9000
Closed
Closed
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
12
LE.9:17:
Adjust propagation
speed
ADJUST PROPAGATION
SPEED FOR CABLES
<F>=YES <R>=NO
If no adjustment is desired
PRESS:
If adjustment is desired
PRESS:
PRESS:
any
ALT. B:
If, for example, the propagation
speed for channel 1 shall be
adjusted:
Make a temporary short at the
far end(s) of the cable(s).
NOTE:
It is recommended to make a
short at all wires/cables at the
same time.
<F> TO PROCEED
EO5511
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
13
Adjust propagation
speed
PRESS:
SET PROPAGATION
SPEED FOR CHANNEL 1
ENTER 3 DIGITS
REL. SPEED = 0.
Example: 9
SET PROPAGATION
SPEED FOR CHANNEL 1
ENTER 3 DIGITS
REL. SPEED = 0.910
MEASURING LINE
CHANNEL 1:
CABLE END FOUND AT
733meters
ANY KEY TO PROCEED
PRESS:
any
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
14
Adjust propagation
speed
The read-out from the display was a little to long and therefore it
is necessary to make a new adjustment.
For the calculation of the right propagation speed the following
rule can be used.
Displayed length < The correct length : Use a higher propagation
speed.
Displayed length > The correct length : Use a lower propagationspeed.
In our example we shall accordingly use a slower propagation
speed.
PRESS:
SET PROPAGATION
SPEED FOR CHANNEL 1
ENTER 3 DIGITS
REL. SPEED = 0.
PRESS:
REMOVE SHORTS AT
CABLE ENDS
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
15
Level
USER
NUMBER
00
ACCESS TO
<1>:DISABLE CHANNEL
<2>:ENABLE CHANNEL
<3>:SET CLOCK
<MR>:EXIT,<F>:MORE
01
<1>:SET PASSWORD
<2>:CLEAR ALARMTABLE
<3>:SET COLDSTART
<MR>:EXIT
02
03
04
05
06
07
08
09
<1>:DISABLE CHANNEL
<2>:ENABLE CHANNEL
<3>:SET CLOCK
<MR>:EXIT
10
3
Reset
Read Memory
50
Open
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
16
PRESS:
Normal display.
Background light on
ENTER USER NO. 00
ENTER ACCESS CODE
Default.
<1>:DISABLE CHANNEL
<2>:ENABLE CHANNEL
<3>:SET CLOCK
<MR>:EXIT ,<F>:MORE
Choose function.
MENU 1
PRESS:
<1>:SET PASSWORD
<2>:CLEAR ALARMTABLE
<3>:SET COLDSTART
<MR>:EXIT
Choose function 1.
MENU 2
PRESS:
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
17
Set password
The security levels are divided into three groups and one free
which is open for all persons. The USER NO. gives the
accessible security levels. See page LE. 9: 23.
USER NUMBER: 00, 01, 02 have access to all functions and
commands including setting USER NUMBERs and ACCESS
CODEs.
USER NUMBER: 03, 04, 05, 06, 07, 08, 09 have a limited
access but can handle the following:
DISABLE/ENABLE CHANNEL, SET CLOCK and RESET
ALARM.
USER NUMBER: 10 - 49 can only RESET ALARM.
ENTER:
ENTER:
1
As an example.
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
18
Set clock
PRESS:
Background light on
<1>:DISABLE CHANNEL
<2>:ENABLE CHANNEL
<3>:SET CLOCK
<MR>:EXIT ,<F>:MORE
PRESS:
=+ =-,<MR>=EXIT
Set day 26
=+ =-,<MR>=EXIT
Set hour 14
=+ =-,<MR>=EXIT
SetMinutes
=+ =-,<MR>=EXIT
Background light off
TIME: 25 FEB 13:41
MONITORING CHAN. 1
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
19
Alarm test
A/I
PRESS:
<R> RESET
will Reset the alarm.
PRESS:
1
PRESS:
PRESS:
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
20
Alarm memory
All alarms are stored in the battery backed memory and can be
recalled whenever needed.
The ALARM TABLE can also be erased and we advise you to
do so before turning over the installation to the owner, thereby
ensuring that all future alarms are ALARMS trigged after
installation.
PRESS: M/R
Background light is on
EXAMINE WHICH
CHANNEL
PRESS:
PRESS: M/R
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
21
Clearing alarmtable
If the unit shall be able to monitor the entire length of the cable,
it is necessary to clear the alarmtable after the fault is repaired.
PRESS:
To clear an alarmtable.
Background light is on
ENTER USER NO.
PRESS:
PRESS:
1
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
22
Clearing alarmtable
<1>:DISABLE CHANNEL
<2>:ENABLE CHANNEL
<3>:SET CLOCK
<MR>:EXIT ,<F>:MORE
Menu 1
PRESS:
<1>:SET PASSWORD
<2>:CLEAR ALARMTABLE
<3>:SET COLDSTART
<MR>:EXIT
Menu 2
PRESS:
PRESS:
The alarmtable is now empty and the unit is monitoring the entire
length.
If the fault that caused the alarm is not repaired, a new alarm will
be trigged.
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
23
Disable channel
PRESS:
Background light is on
<1>:DISABLE CHANNEL
<2>:ENABLE CHANNEL
<3>:SET CLOCK
<MR>:EXIT,<F>:MORE
PRESS:
MONITORING
NELS
1,2
CHAN-
CHANNEL TO DISABLE
PRESS:
MONITORING
NELS
2,
CHANNEL TO DISABLE
NOT MONITORING
ALL CHANNELS DISABLE
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
24
Enable channel
After having disabled any channel for some reason, you have to
enable the channel again.
This shall also be done after you have received an ERROR
message on the display and found out what caused the error and
repaired the same.
Time: 26 Feb 14:27
MONITORING CHAN. 2
PRESS:
Background light is on
<1>:DISABLE CHANNEL
<2>:ENABLE CHANNEL
<3>:SET CLOCK
<MR>:EXIT,<F>:MORE
PRESS:
MONITORING
CHANNELS
2
CHANNEL TO DISABLE
PRESS:
MONITORING
NELS
1,2
CHAN-
CHANNEL TO ENABLE
Background light is off
Time: 26 Feb 14:28
MONITORING CHAN. 1
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
25
Error codes
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
26
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
27
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
28
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
29
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
30
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
31
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
32
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
33
Application: Heating element for use in Leak Detectors whenever the environmental temperature is
expected to be lower than 0 C.
Space is reserved on mounting plate. Thermostat is included.
115 x 70 x 50 mm
300 grams
230 VAC
33 Watt
Connect to mains terminal block and
thermostat.
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
34
MATCHINGBOX
1. Matchingbox CWA 9091
2. Block schematics
3. Mechanical
In any piping system, above or below ground, there is always a
risk of for earth currents and transients. Those signals can
damage electronic parts and systems.
CWA 9091 MATCHINGBOX is designed to drain such signals
to ground and also to match the signals from the Leak Detector
to smoothly pass over to the sensor wires or cables. It is a small
but important unit.
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
35
CWA 9092
Not applicable
180 x 80 x 56 mm
750 grams
-10 - +70 C.
BNC connector 50 Ohm
Connection cable 1,25m, mounted
IP 65
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
36
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
37
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
38
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
39
This side is by intention left blank for your notes and future use.
Cable End
Offset Zero
Normal
1. Normal
The normal position. Check that the switch is set in this position
before the start up procedure is started.
The switch shall also be in this position in monitoring mode.
CWA 9000
Closed
Open
Cable End
Offset Zero
Normal
2. Offset Zero
The switch makes a break at the beginning of the leak detection
loop. Used when the Offset Zero point shall be detected.
When the unit prompts you to "disconnect the cable at desired
zero point", set the switch in this position.
When the unit prompts you to "reconnect the cable", set the
switch back to Normal position.
CWA 9000
Open
Open
Cable End
Offset Zero
Normal
3. Cable End
The switch makes a short at the end of the leak detection loop. Used
when the Propagation speed shall be adjusted.
When the unit prompts you to "short the far end of the cable(s)to
be adjusted", set the switch in this position.
When the unit prompts you to "remove the shorts at cable
ends", set the switch back to Normal position
CWA 9000
Closed
Closed
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
40
SENSOR WIRES IN
PIPES,
JOINTS AND FITTINGS
1. CWA Crimp Connector
CWA Sensor Wire
CWA Joint Activator
2. Design Guide
3. Planning Guide
4. Installation
5. Testing
Test Format
The Leak Detection / Location system consists of TWO
important parts: The SENSOR WIRE and LEAK DETECTORS.
The installation and connection of the sensorwires is very
important as they are placed underground inside the insulation,
mistakes here can be difficult to repair.
The instructions and methods in this part is the result of over 20
years of experience and have proven to be reliable.
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
41
CWA Crimp
Connector
Specification:
Uninsulated, fully annealed, solid, pure copper wire.
1,5 or 1,7 sq. (1,3 - 1,5 mm dia)
Connected by crimping and soldering with CWA Crimp
Connector.
Delivered from CWA or Local.
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
42
L = 400 mm
W = 100 mm
T = 10 mm
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
43
Production
Production of pipes and fittings with CWA Sensor Wires is quite
simple and economical. Moreover, very few additional equipment is necessary to run a smooth and effective production line.
The layout and design can be fully implemented into any existing
production-line.
Investments are minimized and require no extra tooling except
for the wire supports that should be integrated in the present
centering pieces that are being used in current production.
The use of specified copper wires, which are available as
standard from local suppliers, reduces the cost/pipe to minimum.
All pipes and fittings are fully symmetrical and can be tailored to
any measurement or produced as standard parts that are interchangeable with each other and within wide ranges of pipediameters.
Pipesizes over 250 mm are recommended to have 4 sensor wires
for maximum safety and ease of handling at site.
It is recommended that one wire is tinned and the other is blank
copper just for identification purpose. That will also minimize the
risk for crossed wires in field-joints.
Specification:
Uninssulated, fully annealed, solid, pure copper wire.
1,5 or 1,7 sq (1,3-1,5 mm dia.).
Connected by crimping and soldering with CWA Crimp Connector.
Delivered from CWA or Local.
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
44
Straight Pipes
Elbows
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
45
T-pieces
Compensators
NOTE:
Important
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
46
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
47
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
48
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
49
Planning Guide
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
50
Planning of an
Alarmsection
There are some very simple rules when working with and planning for a pipe-installation with CWA Alarm System:
1. The alarmwire is connected in each fieldjoint in such a way
that the wire is forming a loop. That requires that the two wires
are kept strictly LEFT and RIGHT without crossing each other
at any point (fig 1).
2. The left wire is ALWAYS on the left side of the pipe and
keeping that position throughout the entire system.
The same is valid for the right hand wire.
3. The above is valid at any of the pipesection and at all start/
endpoints.
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
51
Expansion of a
system
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
52
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
53
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
54
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
55
Pipe Ends
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
56
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
57
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
58
Installation
Important Notes
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
59
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
60
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
61
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
62
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
63
Testing of installed
alarm wires
200000
xL
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
64
TESTCERTIFICATE
Pipe section identification ..................................................
Pipe identification ..............................................................
Test of loop resistance ....................................................... Ohm
Test of insulation resistance ............................................... kOhm Left wire
Test of insulation resistance ............................................... kOhm Right wire
TDR testing performed (if appl.) .......................................
Tested by: .......................................................................... Date .... / .... / ....
Supervisor: ......................................................................... Date .... / .... / ....
Cheif Supervisor: ............................................................... Date .... / .... / ....
Approved by: ..................................................................... Date .... / .... / ....
Instrument battery and setting is checked
by: ...................................................................................... Date .... / .... / ....
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
65
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
66
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
67
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
68
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
69
CWA SYSTEM AB
P.O. Box 4007, S-131 04 NACKA, SWEDEN
70
CWA 6103
Application: District Heating.
A pipe alarm unit for monitoring 1000 m of
pipe.
Galvanically isolated from carrier pipe and
mains for maximum dependability and reliability over the years.
Measuring method is a combination of Impedance
measurement and resistance measurement which has
proven to be extremely accurate.
3 different alarm levels are available by a toggle-switch,
selectable by customer, due to local requirements.
Equipped with indicating LED for Power, Leak, Fault
(break) and Short-circuit. Buzzer and relay will be
activated upon any of these functions.
Protection: IP 65.
Built-in protection against lightning and transients.
(Patented).
Test switch for all functions 110 or 220 V, 50-60 Hz.
Outgoing relay with NO/NC contacts Capacity 1000 m of
pipe.
Temperature range: -30 - +60o C.
Weight: 0,850 kg
Size:
175
175
75
mm.
MANUFACTURER
CWA SYSTEM AB
S 131 04 NACKA SWEDEN
TEL +46 8 556 15 390, FAX +46 8 556 15 391
The wires in each pipe are then connected to the next pipe till the total
of1000 m of pipe is reached.
The wires are connected in a way that they form a loop, controlling the
entire pipe section including all branches and fittings.
3. In each pipe-joint, the wire is embedded in a "Joint Activator" to assure
the exact distance between wire and pipe before and during foaming as
well as enhancing an eventual leak location with a portable TDR.
MEASUREMENTS:
175 x 175 x 75 mm, Weight 0,85 kg.
ELECTRICAL: 220 V AC, 50-60 Hz connection.
LED for Power, Alarm, Loop break and Short.
Switches for TEST and 3 different alarm levels.
MANUFACTURER
CWA SYSTEM AB
S 131 04 NACKA SWEDEN
TEL +46 8 556 15 390, FAX +46 8 556 15 391
2.
The "Power" and "Break" LEDs should light, the buzzer should sound and the
relay is trigged.
3.
Connect the loop (or a short piece of wire) to connections 4 and 5 in the terminal
marked "LOOP PIPE".
The "Break" LED should go out, the buzzer stop and the relay should go back to
normal position.
4.
5.
Move the test-switch to the "Test Moisture" position. After a few seconds the
"Alarm Moisture" LED should light up. The LED should go off when the switch is
returned. If this does not work, adjust the alarm level according to the instructions
below.
6.
Move the test-switch to the "Loop test"-position. The "Loop Alarm" LED should
light up.
7.
Relay:
By changing a jumper on the PCB, it is possible to switch between
NO and NC functions for the relay. Jumper right equals the NO function and
Jumper left equals the NC function.
8.
Buzzer:
To turn off the buzzer the "I'' jumper below the buzzer is broken.
9.
Connect the loop to the Pipe Connection terminal and set the alarm-level selector
in the 30k position.
MANUFACTURER
CWA SYSTEM AB
S 131 04 NACKA SWEDEN
TEL +46 8 556 15 390, FAX +46 8 556 15 391
If the LED is lit, adjust R31 so that the LED goes off. Move the Test-switch
upwards (Test Moisture) and keep it there. Adjust R31 slowly until the LED is lit
again.
15 and 8 K Ohm
These levels are adjusted from factory and a check is performed in the following
way:
15 K Ohm
Move the Alarm Level Switch to the 15 K Ohm position. Connect an external 15
K Ohm resistor between points 5 and 6 on the plinth for loop-connection. The
Alarm LED should now light up within a second or two. If not, adjust the
potentiometer for 15 K Ohm (R52) until it does.
8 K Ohm
Move the Alarm Level Switch to the 8 K Ohm position. Connect an external 8 K
Ohm resistor between points 5 and 6 on the terminal for loop-connection. The
Alarm LED should now light up within a second or two. If not, adjust slowly the
potentiometer for 8 K Ohm (R53) until it does.
MANUFACTURER
CWA SYSTEM AB
S 131 04 NACKA SWEDEN
TEL +46 8 556 15 390, FAX +46 8 556 15 391