MCCBs for motor protection
Electrical characteristics
Frame size
[AF]
Rated current, In
[A]
TS100
TS160
TS250
100
160
250
1.6, 3.2, 6.3, 12, 20,
32, 50, 63, 80,
32, 50, 63, 100
No. of poles
Rated operational
AC
voltage, Ue
DC
Rated impulse withstand voltage, Uimp
Rated insulation voltage, Ui
[V]
690
690
690
[V]
500
500
500
[kV]
[V]
Rated ultimate short-circuit breaking capacity, Icu
AC 50/60Hz
100, 160, 220
100, 160
750
750
750
L
220/240V
[kA]
100
120
200
100
120
200
100
120
200
380/415V
[kA]
50
85
150
50
85
150
50
85
150
440/460V
[kA]
50
70
130
50
70
130
50
70
130
480/500V
[kA]
42
65
85
42
65
85
42
65
85
660/690V
[kA]
Rated service breaking capacity, Ics [%Icu]
10
15
20
10
15
20
10
15
20
100%
100%
100%
100%
100%
100%
100%
100%
100%
Rated short-circuit making capacity, Icm
AC 50/60Hz
220/240V
[kA]
220
264
440
220
264
440
220
264
440
380/415V
[kA]
105
187
330
105
187
330
105
187
330
440/460V
[kA]
105
154
286
105
154
286
105
154
286
480/500V
[kA]
88
143
187
88
143
187
88
143
187
660/690V
[kA]
17
30
40
17
30
40
17
30
40
Category of utilization
Isolation behavior
front-connection
rear-connection
front-connection
rear-connection
Trip unit (release)
magnetic only
Connection
fixed
plug-in
MTU
Mechanical life
[operations]
25000
25000
25000
Electrical life @415 V AC
[operations]
10000
10000
10000
10516086
10516086
10516086
IEC60947-2
IEC60947-2
IEC60947-2
Basic dimensions, WHD
3-pole
[mm]
3-pole
[kg]
(front connection)
Weight
(front connection)
Reference standard
22
MCCBs for motor protection
TS400
TS630
TS800
400
630
800
320
500
630
690
690
690
500
500
500
750
750
100
120
200
100
65
85
150
65
65
85
130
42
65
85
750
L
120
200
100
120
200
85
150
65
100
150
65
85
130
65
100
130
42
65
85
42
85
100
10
20
35
10
20
35
10
20
35
100%
100%
100%
100%
100%
100%
100%
100%
100%
220
264
440
220
264
440
220
264
440
143
187
330
143
187
330
143
220
330
143
187
286
143
187
286
143
220
286
88
143
187
88
143
187
88
187
220
17
40
74
17
40
74
17
40
74
20000
20000
10000
6000
6000
3000
140260110
140260110
210320135
5.4
5.4
15.1
IEC60947-2
IEC60947-2
IEC60947-2
23
MCCBs for motor protection
Magnetic only trip unit
MTU for TS100, TS160, TS250, TS400, TS630, TS800
For the protection of motors from 1.6 to 250kW(400V), TS100 to
TS800 circuit Breakers must be equipped with a special trip unit
MTU adjustable thresholds.
L1
L2
L3
This assembly ensures: Short-circuit protection (magnetic trip unit
with adjustable thresholds); Suitability for isolation. For the TS100
to TS800 circuit breakers, trip unit MTU is interchangeable.
5
Breaker
The circuit breakers presented here: Provide protection against
short-circuits; Are suitable for isolation as defined by IEC60947-2
standard.
Contactor
O/L
T1
T2
T3
M
Magnetic only
release
Motor
Configuration
Trip unit identification
Trip unit rating, In
and reference temperature
Magnetic setting for short-circuit
protection
Catalogue numbering system
TS250
MTU
Magnetic only release
MCCB frame type
- TS100: TS100N, TS100H, TS100L
- TS160: TS160N, TS160H, TS160L
- TS250: TS250N, TS250H, TS250L
- TS400: TS400N, TS400H, TS400L
- TS630: TS630N, TS630H, TS630L
- TS800: TS800N, TS800H, TS800L
24
MCCBs for motor protection
Characteristics
Magnetic trip units(MTU)
Rating(A)
N/H/L
In
TS100 to TS800
1.6
3.2
6.3
12
20
32
50
63
100
160
220
320
500
630
TS100
TS160
TS250
TS400
TS630
TS800
Short - circuit protection(magnetic)
Pick - up
Im
setting
6..12In (6 Point)
Setting details
MTU In
6In
..
..
..
..
12In
..
..
..
1.6
10
12
14
16
18
20
MTU In
100
6In
600
720
840
960
1080
..
12In
1200
3.2
20
24
28
32
36
40
160
960
1152
1344
1536
1728
1920
6.3
40
48
56
64
72
80
220
1320
1584
1848
2112
2376
2640
12
70
84
98
112
126
140
320
1920
2304
2688
3072
3456
3840
20
120
144
168
192
216
240
500
3000
3600
4200
4800
5400
6000
32
190
228
266
304
342
380
630
3780
4536
5292
6048
6804
7560
50
300
360
420
480
540
600
63
400
480
560
640
720
800
TS100MTU
- Adjustable magnetic only unit
TS100MTU
560
480
400
640
720
800
Im
63A
3P
TS160MTU
- Adjustable magnetic only unit
TS160MTU
1344
1152
960
1536
1728
1920
Im
160A
3P
TS250MTU
- Adjustable magnetic only unit
TS250MTU
1848
1584
1320
2112
2376
2640
Im
220A
Im = 6...12In
3P
14
12
TS400 MTU, TS630MTU, TS800MTU
- Adjustable magnetic only unit
TS630MTU
4200
3600
3000
Im
10
4800
5400
16
18
20
500A
6000
Im
25