HFS R 146 (1627)

The document provides information about fire and smoke dampers including the Holyoake series HFS, IBD, IBD-FS and LR. It describes the damper types, materials, fire ratings, mounting options, dimensions and technical specifications.

Uploaded by

MoriyasuNguyen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 22

Fire Dampers &

Smoke Dampers

Series HFS, IBD, IBD - FS & LR.


HFS

Fire and Leakage Rated Smoke Damper.

322 - 325H

Multileaf Blade Design.


Range of Electrical On/Off, Spring Return and Pneumatic Actuators.

IBD

Interlocking Curtain Blade Fire Damper.

307 - 321H

HFS & IBD Vertical and Horizontal Mounting.

IBD - FS

Fire Seal Fire and Leakage Rated Damper.

HFS, IBD & IBD - FS.

Roll Formed Blades and Frame.

HFS, IBD & IBD - FS. Universal Mounting Sleeve and Angles.
IBD & IBD - FS.
IBD & IBD - FS.

329 - 340H
314 - 317, 323, 334 - 336H

Safe Test Test Latch Fitted as Standard


Electro Thermal Resettable Link Option, (Allows remote activation via Smoke Detectors,
or Alarm System).

LR

Low Heat Radiation Fire/Smoke/Control Damper.

326 - 328H

Innovative Low Radiation, Low Leakage, Insulated Single Damper Blade.


Mounting Flanges, Pre-Insulated Sleeve and Air Balancing Damper.
IBD - FS & LR.

Vertical (Wall Mounting Only).

All Products

4 Hour Fire Rated, (subject to wall/floor thickness and construction).


71 Degrees C Fusible Link (Standard).
Ordering Key and Specification

321, 325, 328 & 340H

307H

Fire & Smoke Dampers

Series IBD Fire Dampers


Holyoake Curtain-type fire dampers are designed to maintain the
integrity of the fire resistance of a wall, or floor, in which a hole has
been formed to permit the passage of air, ducted or otherwise, to
enable an air distribution system to function. The arrangement of
interlocking blades mounted in a guide channel frame, minimizes
space requirements and facilitates ease of installation in ductwork.
Fire Rating:
All Holyoake Series IBD units carry up to a 4 HOUR rating to
AS 1530.4 as determined by the following testing Authority.
For the purposes of the Australian and New Zealand
Building Code they have an FRL/FRR of / 240 / .
UBRANZ
Assessment Report Certificate No.1
IBD Damper mounted in a concrete wall, or floor.
(Certified for 240 minute fire rating).
UBRANZ

Model IBD-B-V Illustrated.


Mounting Sleeve Omitted for Clarity,
refer to Pages 313H - 317H for details.

Fire Test Certificate No. FTC 392


IBD Damper mounted in a plasterboard wall.
(Certified for 30 or 60 minute fire rating).
(Certificates are available upon request).

Standard Construction
Frame:

110 mm x 1.2 mm galvanised steel, roll formed guide


channel.

Blades:

70 mm x 1.0 mm galvanised steel, roll formed


inter-locking profile.

Springs:

Blade End: stainless steel.


Retraction: stainless steel.
Note: Horizontal dampers with a duct B dimension
of less than 180 mm have all blades fitted with end
springs only. Above 180 mm constant force springs
only are fitted. All vertical dampers have the bottom
blade only fitted with end springs.

Style-B

Alternate
Activation:

Electro-Thermal Resettable Link


This device can be activated by smoke detectors of
compatible design, (Supply and fit by others).
By definition, a fire damper provides an effective
barrier to the passage of fire and products of
combustion, but when its operation is initiated by the
detection of smoke, or other products of combustion
it may then be termed smoke damper.
The difference between a fire damper and a smoke
damper is not a physical one, but is in the method of
initiating the operation. (AS 1682.1-1990).
Series IBD fire dampers must be installed in sleeves
(refer to Pages 313H - 317H). These sleeve
assemblies are available, please consult the sales
office.

Stainless
Steel:

Construction in stainless steel is available for both


IBD and mounting sleeves.

Style-C

Style-CR

H
B
(Duct)

Vertical or horizontal, but in all cases the blades must


be horizontal.

Mounting
Sleeves:

Fusible Links: Safe Test Test latch Model IBD-TL fitted as standard,
complete with 71 C Fusible Link.
See page 318H for more details.
(Other ratings available on request).
Please contact your local Holyoake branch.

Duct Connection
Style-A

Mounting:

H
B
(Duct)

B H
(Duct)

H
A
(Duct)
A + 64

B
(Duct)
D + 64

A
(Duct)
A + 64

Style-CO

Single Section Maximum Dimensions


DUCT CONNECTION STYLE

Alternative Max.
Dimension Combinations
Vertical
Horizontal

CR

838
1219
838
1016

1828
762
965
762

838
1219
838
1016

1600
654
835
654

774
1155
774
952

1568
622
803
622

Mounting Sleeves
omitted for clarity.

CO

774

774
1155
774
952

1568
622
803
622

Notes

Horizontal

Vertical

1. In specifying a fire damper the width should always be stated first and the height second.
2. Nominal dimensions are opening sizes and allow clearance for insertion into mounting sleeve:
6 mm Duct Connection Style A & B. 3 mm Duct Connection Style C, CR & CO.
Where this allowance is not required specify exact size.

308H

Holyoake Air Management Solutions 2013

Fire Dampers Series IBD


Assembly and Dimensional Information
(A & B Dimensions allow 6 mm clearance for mounting sleeve of
nominated size)

Model: IBD-A-V
B

Interlocking blade, vertical (wall) mounting damper, gravity operated,


spring loaded initial movement, blade stack located
within air stream.

IBD-A-V

Air
Flow
Either
Way
77
110
189
150

Minimum size A 100 x B 63 mm.


Maximum size combinations:
A 838 x B 1828, or A 1219 x B 762 mm (Single Section).

Model: IBD-B-V

Interlocking blade, vertical (wall) mounting damper, gravity operated,


spring loaded initial movement, blade stack located out of air stream.

Air
Flow
Either
Way

Minimum size A 100 x B 83 mm.


Maximum size combinations:
A 838 x B 1600, or A 1219 x B 654 mm (Single Section).

IBD-B-V

77
110

Mounting Sleeve omitted for clarity - refer to Pages 313H - 317H for details.

Model IBD-A-V (Multiple)

Model: IBD-A-V (multiple)

See above for details on individual IBD-A-V dampers

IBD-A-V

IBD-A-V

IBD-A-V
B

IBD-A-V

IBD-A-V

IBD-A-V

Model IBD-B-V (Multiple)

Model: IBD-B-V (multiple)


Where opening is larger than maximum single section size, an assembly
of equal size single section dampers is used. Style B assemblies where
more than one unit high, would consist of B type units in the top row
only and A type elsewhere. Multiple assemblies are shipped in sections
for field assembly. Adequate fire rated bracing must be provided by the
installer to prevent collapse of multiple unit assemblies when closed,
even under relatively low pressure differential conditions.

IBD-B-V

IBD-B-V

IBD-B-V
B

IBD-A-V

IBD-A-V

Maximum multiple unit module for vertical dampers is 3 wide by 2 high


single sections as shown.

IBD-A-V

A
Mounting Sleeve omitted for clarity - refer to Pages 313H - 317H for details.

Dimension B

From
To

63
15*

64
183
30*

184
303
42*

DUCT CONNECTION STYLE A (Single Section)


304
424
544
664
784
904 1024 1144 1264 1384 1504 1624 1744
423 543 663 783 903 1023 1143 1263 1383 1503 1623 1743 1828
54*
66*
78*
90
102
114
126
138
150
162
174
186
198

From
To

83
29*
824
883
129

84
143
29*
884
943
129

144
178
54*
944
1003
129

DUCT CONNECTION STYLE B (Single Section)


179
239
299
359
394
454
238 298 358 393 453 513
54*
54*
54*
79*
79*
79*
1004 1039 1099 1159 1219 1254
1038 1098 1158 1218 1253 1313
154
154
154
154
179
179

Dimension X

Dimension B
Dimension H = B +
Dimension B
Dimension H = B +

From
To

514
573
79*
1314
1373
179

574
608
104
1374
1433
179

609
668
104
1434
1468
204

669
728
104
1469
1528
204

729
788
104
1529
1588
204

789
823
129
1589
1600
204

* Minimum of 85 mm
when fitted with
IBD - ETR, refer to Page 318H.

309H

Fire & Smoke Dampers

Series IBD Fire Dampers


Assembly and Dimensional Information

Model: IBD-A-H
B

Interlocking blade, horizontal (floor) mounting fire damper,*


spring loaded for complete travel, blade stack located
within air stream.
*Where dimension B exceeds 180 mm, two constant
force springs anchored to the frame and attached to
the last blade draw the blade curtain closed. Where
dimension B is less than 180 mm, all blades are fitted
with omega springs at blade ends, which drive the
curtain to the closed position.

IBD-A-H

IBD-B-H

Minimum size A 100 x B 70 mm.


Maximum size combinations:A 838 x B 965, or A 1016 x B 762 mm (Single Section).

Model: IBD-B-H
Interlocking blade, horizontal (floor) mounting fire damper,*
spring loaded for complete travel, blade stack located
out of air stream.

150 189

110 77

110 77

Air
Flow
Either
Way
H
Mounting Sleeve omitted for clarity, refer to Pages 313H - 317H for details.
Air
Flow
Either
Way

Spring arrangement similar to IBD-A-H.


Minimum size A 100 x B 35 mm.
Maximum size combinations:A 838 x B 835, or A 1016 x B 654 mm (Single Section).

Model: IBD-A-H (multiple)


Model: IBD-B-H (multiple)

(A & B Dimensions allow 6mm clearance for duct of nominated size).

Model IBD-B-H (Multiple)

Model IBD-A-H (Multiple)

Where opening is larger than maximum single section


size, an assembly of equal size single section dampers
is used. Blade stacks for assemblies two sections
across the B dimension are normally installed
as illustrated, with blade stacks outermost, thus
improving access and minimising air flow interference.
Multiple assemblies are shipped in sections for field
assembly.

IBD-A-H

IBD-B-H

IBD-A-H

IBD-B-H

A
IBD-A-H

IBD-B-H

IBD-A-H

IBD-B-H

Maximum multiple unit module for horizontal dampers


is 2 wide and 2 high single sections as shown.

Mounting Sleeve omitted for clarity, refer to Pages 313H - 317H for details.

Dimension B

From
To

70
26*

71
100
42*

101
150
56*

DUCT CONNECTION STYLE A (Single Section)


151
181
244
364
484
604
180 243 363 483 603 723
70*
40*
52*
64*
76*
88

724
843
100

844
965
112

From
To

35
54*

36
85
54*

86
110
54*

DUCT CONNECTION STYLE B (Single Section)


111
161
181
239
299
359
160 180 238 298 358 393
54*
54*
54*
54*
54*
79*

394
453
79*

454
513
79*

Dimension X

Dimension B
Dimension H = B +

310H

* Minimum of 85 mm
when fitted with IBD - ETR, refer to Page 318H.

514
573
79*

574
608
104

609
668
104

669
728
104

729
788
104

789
823
129

824
835
129

Holyoake Air Management Solutions 2013

Fire Dampers Series IBD


Assembly and Dimensional Information

Model: IBD-C-V
Interlocking blade located out of airstream, vertical (wall) mounting
damper, gravity operated, spring loaded initial movement, fitted
with enclosure plates and square, or rectangular spigots to suit duct
connections.

Air Flow
Either Way

H
B
(Duct)

IBD-C-V

32
40

77
110

A (Duct)
A + 64

40

Model: IBD-CR-V
Interlocking blade located out of airstream, vertical (wall) mounting
damper, gravity operated, spring loaded initial movement, fitted with
enclosure plates and round spigots to suit duct connections.

Air Flow
Either Way

H
B
(Duct)

IBD-CR-V

32
50

77
110

B + 64

50

Model: IBD-CO-V
Interlocking blade located out of airstream, vertical (wall) mounting
damper, gravity operated, spring loaded initial movement, fitted with
enclosure plates and oval spigots to suit duct connections.

Air Flow
Either Way

H
B
(Duct)

IBD-CO-V
32
50

77
110

A (Duct)
A + 64

50

32

32

A or B
(Duct)

Typical Multiple Assembly


Where opening is larger than maximum single section size,
an assembly of equal size single section dampers is used.
Where H requires more than one section, the blade stack
for the lower section will be in the air stream. The extent of
this obstruction may be determined by dimension X on
Model IBD-A-V, of the appropriate size.

IBD-CR-V
MULTIPLE
ASSEMBLY

B
(Duct)

32
A or B+ 64

Mounting Sleeves omitted for clarity, refer to Pages 313H - 317H for details.

A & B Dimensions allow 3 mm clearance for duct of nominated size

Dimension B

From
To

Dimension H = B +
Dimension B
Dimension H = B +

From
To

51
61*
792
851
161

52
111
61*
852
911
161

112
146
86*
912
971
161

DUCT CONNECTION STYLE C, CR & CO (Single Section)


147
207
267
327
362
422
482
206 266 326 361 421 481 541
86*
86*
86* 111
111
111
111
972 1007 1067 1127 1187 1222 1282
1006 1066 1126 1186 1221 1281 1341
186
186
186
186
211
211
211

542
576
136
1342
1401
211

577
636
136
1402
1436
236

637
696
136
1437
1496
236

697
756
136
1497
1556
236

757
791
161
1557
1568
236

* Minimum head height


with IBD - ETR is 85 mm,
refer to Page 318H.

311H

Fire & Smoke Dampers

Series IBD Fire Dampers


Assembly and Dimensional Information
Typical Section Styles C, CR & CO, Horizontal.

*50 mm for
IBD-CR-H or
IBD-CO-H.

IBD-C-H
Air Flow
Either Way
40*
77110
40*

32

Model: IBD-C-H
Interlocking blade located out of airstream, horizontal (floor) mounting
fire damper, *spring loaded for complete travel, fitted with enclosure
plates and square, or rectangular spigots to suit duct connections.

H
B (Duct)

A + 64

A
(Duct)

IBD-C-H

32

H
B (Duct)

Model: IBD-CR-H
Interlocking blade located out of airstream, horizontal (floor) mounting
fire damper, *spring loaded for complete travel, fitted with enclosure
plates and round spigots to suit duct connections.

B+ 64

IBD-CR-H

32

H
B (Duct)

Model: IBD-CO-H
Interlocking blade located out of airstream, horizontal (floor) mounting
fire damper, *spring loaded for complete travel, fitted with enclosure
plates and oval spigots to suit duct connections.

A + 64

A
(Duct)

* Where B, or D dimension exceeds 148 mm, two constant force


springs anchored to the frame and attached to the last blade draw the
blade curtain closed. Where B, or D are less than 148 mm, all blades
are fitted with omega springs at blade ends, which drive the curtain
to the closed position.

IBD-CO-H

H
B (Duct)

A or B
+ 64

IBD-CR-H

A or B
(Duct)

Typical Multiple Assembly

MULTIPLE
ASSEMBLY

Where opening is larger than maximum single section size, an assembly


of equal size single section dampers is used. Where H requires two
sections, the blade stacks are located out of the air stream on opposite
sides of the opening.
A & B Dimensions allow 3 mm clearance for duct of nominated size.

Dimension B +
Dimension H = B +

From
To

53
86

54
78
86

79
128
86

Duct Connection Style C, CR, & CO (Single Section)


129 149 207 267 327 362 422 482
148 206 266 326 361 421 481 541
86
86
86
111 111 111 111
86

542
576
136

577 637
636 + 696
136 136

697
756
136

757 792
791* 803*
161 161

* Maximum Single Section for DuctConnection


Style CR is 774 mm Diameter.
+ Dimension B is a Maximum of 622 mm if
Dimension A = 774 - 952 mm.

312H

Holyoake Air Management Solutions 2013

Fire Dampers Series IBD


Fire Damper Installation
The following installation method and diagrams (shown on the next
page) are presented as the method by which
Holyoake fire dampers must be installed.

(VI) When installed and closed, the blade and pivots must be fully
contained within the penetrated element and within the casing
(AS 1682.2 - 1990).

It draws upon SMACNA fire, smoke and radiation damper installation


guide for HVAC systems, third edition, 1986, and is intended to meet
the requirements of Australian Standard 1682, Part 2, 1990.

(VII) Fire dampers may not be used as control dampers.


i.e. They must be installed fully open.

The casing shall completely penetrate the fire barrier and be retained:

(VIII) All Holyoake IBD type fire dampers must be sleeve mounted.5,6,7
See details on following pages.

(a) on both sides by means of mounting flanges in such a manner that


it can expand in a fire without distorting the blades in a closed
position; or

(IX) Series IBD vertical (wall) mounted fire dampers must not be
installed either with blades vertical (on end), with the blade stack
below the opening, or horizontally.

(I)

(b) on the accessible side by means of one mounting flange only,


which can be fixed to the fire damper and to the fire barrier through
oversized holes and penny washers. Fixings should be finger tight
(to allow movement for thermal expansion), but locked, i.e. with
double nut (lock nut).
Mounting flanges 5, 6, 7 shall be butted against the face of the fire
barrier and fixed to the fire damper casing. The width of the angle
section of the flange shall be not less than twice the clearance
between the fire damper body and the penetration.
(II) The fire damper shall be installed so that the airflow2 does not
impede its closure, and air velocities3 do not exceed the dampers
limit (10 m/s).
(III) The method of attachment of ductwork to the fire damper must
be such that any deformation, or collapse of the ductwork in a
fire, does not dislodge the fire damper, or affect its performance.
This is best achieved by the use of breakaway joints which will
allow damaged ductwork to fall away. e.g. Slip Joints, Proprietary
Duct Flange Systems, etc.
(IV) Clearance between sleeve and penetration should be
packed with compressible, non-combustable4 materials and
generally be such that the hole size may be no less than
overall sleeve size + 1% + 10 mm, both width and height.
However, in no case should total clearance be less than the tested
prototype (12 x 2 = 24), or exceed 50% of the flange face width.
(V) Access doors, or removable pressed panels, must be provided
for duct entry, to test and reset release mechanisms and for
inspection.

Vertical in wall

Vertical in wall

This is the correct position

Vertical in wall

(X) Ensure damper is square and free from racking, that there are
no obstructions in the centre track, and that it is installed in
accordance with the this way up arrow on every damper, both
vertical and horizontal.
(XI) For Special Applications and Installation Methods, please contact
your local Holyoake Branch.

Notes
1 AS 1682.1 - 1990 requires the casing to be no less than 1.6 mm in thickness.
Australian Standards Association allow that the combination of casing and
sleeve in this case satisfies this requirement. In keeping with SMACNA
recommendations, minimum sleeve thickness is 0.45mm which augments
the roll-formed section to provide a total of 1.6 mm for the smallest duct
size, and greater for larger sizes. Holyoake sleeves are a minimum thickness
of 0.55 mm.
2 Air flow may be from either direction for Holyoake Series IBD.
3 While damper size influences acceptable velocities (i.e. the larger the
damper the lower the velocity), Holyoake Industries suggests a maximum of
10 m/s on vertical gravity dampers. If velocities are expected to exceed this,
it is suggested that spring closure (type H) dampers be specified, even for
vertical mounting. Pressure differential across the closed damper should
not exceed 750 Pa.

4 Material capable of resisting high temperatures, fusing at not less than


1000C, such as high temperature mineral wool, may be accepted for this
purpose. Prototypes were tested with a High Temperature Loose Wool.
5 SMACNA requires the damper and retaining flanges to be secured to the
sleeve, with 6 mm bolts and nuts, 12 mm welds, 4.7 mm steel rivets, or
No. 10 steel screws. (Optional fixing screws can be provided).
6 Retaining flanges must be of minimum thickness 2.5 mm for face area
> 2 m2, or 2.0 mm for face area < 2 m2 (AS 1682.1 - 1990).
They are mandatory on all four sides, but need not be welded to form a frame.
7 Materials for sleeves and retaining flanges must comply with
AS 1682.1 - 1990, which allows galvanised steel with a coating class not
less than Z275.

313H

Series IBD Fire Dampers


Fire Damper Installation
Installation in a Masonry Wall,
(refer to notes on previous page).

Typical Fire Damper Installation Various Styles


Fixing (Note 7 on page 313H).
Clearance & Packing
(IV on page 313H).

Mounting Angles
& Fixing.

Fire & Smoke Dampers

Duct Connections
Style CR & CO.

Duct Connections
Style C.

Duct Connections
S Cleat - Typical
Style B.
Breakaway Joint (III on page 313H).

Sleeve
(VIII on page 313H).

Plasterboard Wall.
Plasterboard as per
wall lining. Attached
to stud*.

Installation in a Plasterboard Wall,


(refer to notes on previous page).
* = Wall opening to be lined with
the same quantity and thickness
of plasterboard, as per wall lining.
Plasterboard packer not required
if double layer wall linings used.

Duct Connections
Style A.

Keep track clear


of fastenings and
other obstructions.

Clearance & Packing


(IV on page 313H).
Sleeve
(VIII on page 313H).

Steel retaining angles


not fixed to wall.
Fire rated mastic
sealant.

SafeTest
Test latch.
Damper.
Duct.
S Cleat
(III on page 313H).
Timber or Steel stud
framing the opening
all round, screwed at
the corners and to the
vertical studs.

Fixing to sleeve
(Note 5 on page 313H).
Plasterboard packer all round
(as per wall lining), attached
to wall.

Keep track clear


of fastenings and
other obstructions.

Joining of
Multiple Sections.

Joining of multiple sections.

300 Typ.
50 Typ.

314H

Holyoake Air Management Solutions 2013

Fire Dampers Series IBD


Installation Details and Sleeve Mounting Dimensions
Model: IBD-B -V

Model: IBD-A-V

H (x A)
B (x A)

B (x A)

150 Max 6

150 Max 6

150 Max 6

150 Max 6

Model: IBD-A-H
Model: IBD-B -H
150 Max 6

150 Max 6

150 Max 6

150 Max 6
B (x A)
B (x A)
H (x A)

For H dimension refer to table, page 309H.

Reset and Release Microswitches


Optional Release and/or Reset Microswitches are available,
factory fitted. Contact your local Holyoake branch for details.

Note
Standard Switches are not fire rated.

Duct attachment method for the IBD Type B in Sleeve


NC
NO
C

Damper Open
(Blades Stacked)

Damper Closed
(Blades Released)

Top Switch
(Blade Stack)
NC
C
NO

Brown
Green

Blue

NC

NO

NO

Blue

1
2

Green

NC
C
5
NO
E

Brown

Green

Blue

S Cleat

Bottom Switch

Brown

Blue

Brown
Green

C
3

Bottom Switch
NC

Duct
Sealer

Top Switch
(Blade Stack)
1

Sleeve
Connecting Duct

NC
NO
C

Notes
1. Above details are intended as a guide for field installation of sleeves.
2. Refer to Pages 313H - 317H for full sleeve information.

315H

Series IBD Fire Dampers


Installation Details and Sleeve Mounting Dimensions
Model: IBD-C-V

Model: IBD-CR-V

Fire & Smoke Dampers

(IBD-CO-V Similar)

H (x B + 64)
H (x A + 64)

B
B

150 Max 6

150 Max 6

150 Max 6

150 Max 6

Model: IBD-CR-H

Model: IBD-C-H

(IBD-CO-H Similar)

150 Max 6

150 Max 6

150 Max 6

150 Max 6

B
H (x A + 64)

BD
H (x D
B + 64)

For H dimension refer to table on page 311H.


Guide Product Weights
IBD Curtain Fire Dampers
IBD-A-V 200 x 200
IBD-A-V 600 x 400 (Inc Sleeve)

Approximate Weight in Kg
2
16.4

IBD-B-V 250 x 250


IBD-B-V 206 x 500
IBD-B-V 760 x 560
IBD-B-V 1050 x 700
IBD-B-V 350 x 350 (Inc Sleeve)
IBD-B-V 400 x 375 (Inc Sleeve)
IBD-B-V 500 x 350 (Inc Sleeve)

3.5
4.5
12.7
11.5
16
16.26
19.64

IBD-CR-V 150 Diameter


IBD-CR-V 200 Diameter
IBD-CR-V 250 Diameter
IBD-CR-V 450 Diameter
IBD-CR-V 400 Diameter (Inc Sleeve)

3.1
4.08
5.12
10.45
23.62

IBD-A-H 580 x 480


IBD-A-H 1000 x 680

8.03
16.22

IBD-B-H 600 x 600

11.5

Notes
1. Above details are intended as a guide for field installation of sleeves.
2. Refer to Pages 313H - 317H for full sleeve information.

316H

IBD-CR-H
IBD-CR-H
IBD-CR-H
IBD-CR-H

150 Diameter
200 Diameter
300 Diameter
350 Diameter

3.7
4.43
6.54
8.02
Holyoake Air Management Solutions 2013

Selection Data Series IBD


Universal Mounting Sleeve IBD-MSU
(Factory Furnished)

Typical IBD Installation


60

Holyoake Fire Damper Sleeves


Model IBD-MSU fire damper mounting sleeves are constructed to meet
the requirements of AS 1682, Parts 1 & 2 - 1990 (refer also page 313H,
Damper Installation and Notes). They are of a standard length
(450 mm), sufficient for all wall thicknesses up to 290 mm.
However, optional extended length sleeves are available upon request.
Mounting angles are supplied. One set is fixed on one end of the sleeve
and the other set is supplied loose, for final fixing of these to the
sleeve, on site, by others.

40
450*
H (ID)

Loose
Retaining
Flanges

(Note: Both sets may be provided loose, due to handling and transport
considerations).

W (ID)

All factory sleeves are supplied fixed to the appropriate fire damper.

Minimum Wall, Or Floor Thickness:

60

Standard Sleeve 100 mm.


Optional Extended Sleeve 291 mm.

Maximum Wall, Or Floor Thickness:

Factory Fixed
Retaining Flanges+
* Standard length. Specify alternative if required.
+ May be supplied loose due to handling considerations.

Standard Sleeve 290 mm.


Optional Extended Sleeve 690 mm

Typical Assembly - Standard Damper Sleeve


(B Type Damper Illustrated)

Material:
Galvanised Steel Type Z275.
Maximum Dimensions per Side Sleeve Thickness
0 - 300
301 - 762
763 - 1371
1372 - 1828

80
Max.

Factory
Fitted
Angles+

0.55
0.55
0.75
0.95

100 Min.
Wall or
Floor

150
Max.

Field Fixed
Angles

*This
area
within
wall, or
floor
depth.

Flanges
40 x 60 x 2 mm galvanised steel angle. (x4 per side, x 2)

Construction:
Sleeves are corner lapped and spot-welded, then attached to the
damper frame on all four sides, to form a rigid assembly.
c
All damper sleeves come with raw edges.
d
Optional S cleats on all edges (Typical Breakaway Joint).
e
Optional 25, or 35 mm Breakaway flange on all edges.
Do NOT use bolts, or no bolt corner clips for Fire Damper
Breakaway Joints, (Optional PVC cleats are available).
(Typical Breakaway Joint refer to Section K Accessories).
f
Type B damper sleeves are fitted with a duct bridging piece.
g
An extended damper sleeve is available for wall depths
291 690 mm, (specify length required when ordering).
Supplied only as part of a complete unit.
h
Casing sleeve may only be extended 150 mm from the face of the
wall on each side, if slip joint or S cleat is used; or 80 mm each side
if Breakaway flange is fitted.

60

Typical Assembly - Optional Extended Damper Sleeve


(A Type Damper Illustrated)

Factory
Fitted
Angles+

80
Max.

291 Min.
Wall or
Floor

CR

CO

Width

A-3

A-3

A + 67

B + 67

A + 67

Height

B-3

H+3

H+3

H+3

H+3

150
Max.
6

Field Fixed
Angles

*This
area
within
wall, or
floor
depth.

60

28
Packing Material.
See Installation
(IV on page 313H).

450

Standard, or Extended Sleeve


A

290 Max.
Wall or
Floor

40

If in excess of these dimensions sleeve should be trimmed back to the


appropriate lengths. This then complies with AS 1682, Parts 1 & 2, 1990.
Note: Factory Fitted Mounting Angles are positioned 150 mm from the
end of the sleeve, unless specified at 80 mm.

Style

40

690 Max.
Wall or
Floor
850 Max

28
Packing Material.
See Installation
(IV on page 313H).

317H

Fire & Smoke Dampers

Series IBD Fire Dampers - Testing


Safe Test - Test Latch Model IBD-TL
O
O
O

IBD-TL

Safe and Simple Testing Method.


Test and Reset in minutes.
AS 1851 - 2012 (Section 13) requires that you annually test Fire
Dampers.
To ensure the Life and Property saving function for which they are
designed, all fire dampers should be drop tested after installation.
All IBD dampers are fitted with Safe Test Test Latch links.

Each Holyoake Series IBD Fire Damper is mechanically tested


before it is allowed to leave the factory. In the event of damage
occurring during transit, on site, or during installation, rendering any
fire damper ineffective, failure to function will reveal any warping,
track obstruction, or spring failure that may have occurred. This will
require rectification, cleaning and removal of the obstacle, prior to
retesting and handover.
The Holyoake Safe Test IBD-TL Test Latch, is a latching device with
a specially made fusible link, which, when the latch is released,
swings clear and allows the curtain to close as if the link had parted
under the influence of flame. After testing, the curtain can be
re-stacked and the same link clipped back into the latch, where it is
again ready to be released in the event of a fire.

IBD-TL2
Latch Assy
(Galvanised Steel)

IBD-TL
Fusible
Link 71C

Locking Pin

To Operate IBD Dampers


1. Remove the duct access door (refer to Section K accessories
section of this manual).
2. Using this access, reach in and remove the locking pin from the
nearest latch.
3. Check that the locking pin is still in place on the other latch, so that
the fusible link is retained by it, when released.
4. Check that the track is clear of any obstruction and keep hands clear.
5. Lift the latch lever, and the curtain will rapidly close.
6. Reload the curtain and swing the fusible link back into place in the latch.
7. Replace the locking pin in the latch.
8. Replace the duct access door.

Electro Thermal Resettable Links


Model: IBD-ETR
All Holyoake IBD type fire dampers, are available with optional
Electro Thermal Resettable Link mechanisms. (subject to minimum
duct heights, see table below).
Contact your local Holyoake branch for details.
24 V AC or DC Supply Electro Thermal Resettable Release.
Max 30 Sec Release and 60 Sec Reset, with integral 71 Degrees C
Thermal Resettable Release.

To Operate IBD Dampers below minimum heights shown.


1. Remove the duct access door (refer to Section K accessories
section of this manual).
2. Remove locking pin from both sides.
3. Check that the track is clear of any obstruction and keep hands clear.
4. Support the blade pack, lift both latch levers and remove fusible link.
5. Release the blade pack and the curtain will rapidly close.
6. Reload the curtain and support the blade pack, whilst replacing the
fusible link locating pins into both latches.
7. Replace both locking pins.
8. Replace the duct access door.

Blade Support/
Locating Bar

Combined
Electro/Thermal
Release
Type A

Minimum Duct Height for dampers fitted with Electro Thermal


Resettable Links
Duct Connection Style
Minimum Duct Height
A
210
B

150

150

CR

150

CO

150

MIN 85

Combined
Electro/Thermal
Release
Blade
Support/
Locating Bar

100

For testing purposes, all dampers below these heights will require removal of
link and blades dropped manually.
Note: Take suitable safety precautions for Hand and Eye Protection.
Type B

318H

Holyoake Air Management Solutions 2013

Fire Dampers, Performance Data Series IBD


Model: IBD-A-V, or H
Dim. B
(mm)
184
304
424
544
664
784
904
1024
1144
1264
1384
1504
1624
1744

100

200
55.90
29.00
19.60
14.80
11.80
9.90
8.50
7.45
6.63
5.97
5.43
4.98
4.60
4.27

82.70
55.80
42.10
33.80
28.20
24.20
21.20
18.90
17.00
15.50
14.20
13.10
12.20

300
33.90
17.60
11.90
8.95
7.18
6.00
5.15
4.51
4.02
3.62
3.29
3.02
2.79
2.59

400
24.30
12.60
8.51
6.42
5.15
4.31
3.70
3.24
2.88
2.60
2.36
2.17
2.00
1.86

AREA FACTOR TABLE DUCT CONNECTION - STYLE A


Dimension A Width (mm)
500
600
700
800
19.00
15.60
13.20
11.40
9.83
8.06
6.83
5.92
6.63
5.44
4.61
3.99
5.01
4.10
3.48
3.01
4.02
3.29
2.79
2.42
3.36
2.75
2.33
2.02
2.88
2.36
2.00
1.74
2.53
2.07
1.75
1.52
2.25
1.84
1.56
1.35
2.02
1.66
1.41
1.22
1.84
1.51
1.28
1.11
1.69
1.38
1.17
1.02
1.56
1.28
1.08
0.94
1.45
1.19
1.01
0.87

900
10.10
5.23
3.53
2.66
2.14
1.79
1.53
1.34
1.19
1.08
0.98
0.90
0.83
0.77

1000
9.00
4.68
3.16
2.38
1.91
1.60
1.37
1.20
1.07
0.96
0.88
0.80
0.74
0.69

1100
8.18
4.24
2.86
2.16
1.73
1.45
1.24
1.09
0.97
0.87
0.79
0.73
0.67
0.62

1200
7.47
3.87
2.61
1.97
1.58
1.32
1.13
0.99
0.88
0.80
0.72
0.66
0.61
0.57

(All dimensions include 6 mm clearance total between outside of damper frame and inside of duct).

For pressure drop through an open IBD-A-V, or IBD-A-H fire damper use the
following procedure:
1. Find the Area Factor from the above table enter duct height and width.
2. Determine Conversion Velocity (CV) by multiplying Area Factor by flow in
m3/s (CV = Area Factor x m3/s).
3. Enter pressure drop chart with Area Factor and establish intersection
with Conversion Velocity (CV) line just determined. Read pressure drop
on left hand side of the chart.

Note: Interpolations while not precise, are adequate for most calculations.
EXAMPLE:
Find the pressure drop across a 900 wide x 1504 high model IBD-A-V fire
damper, passing 11 m3/s.
1. From the table using interpolation, the Area Factor is 0.9.
2. CV = 11 x 0.9 = 10.
3. From pressure drop chart, pressure drop is 9 Pa.

200
150
125

30C

100
90
80
70
60
50

V
25C
V
20C

40

V
15C

30
20

V
10C

Static
Pressure
(Pa)

10
9
8
7
6
5

V
7.5C

5.0C

V
3.5C

1
0.1

.2

.3

.4

.5 .6

.8 1.0

1.5 2.0 2.5 3.0

4.0 5.0 6.0 8.0 10

15

20

30

40 50

70

100

Area Factor (From Table)

Notes
1. Static Pressure and Conversion Velocities are correct for 1.2 kg/m3 air density.
2. Ratings are based on dampers installed in accordance with details in this catalogue, with ductwork upstream and downstream.

319H

Fire & Smoke Dampers

Series IBD Fire Dampers, Performance Data


Model: IBD-B-V, or H
Dim. B
(mm)
84
179
299
394
514
609
729
824
944
1039
1159
1254
1374
1469
1589

100

200

67.80
50.30
37.90
31.80
26.30
23.20
20.20
18.30
16.30
15.10
13.80
12.80
11.80

42.40
23.80
17.60
13.30
11.10
9.24
8.14
7.07
6.41
5.73
5.29
4.82
4.50
4.15

300
67.90
25.70
14.40
10.70
8.07
6.75
5.60
4.93
4.29
3.89
3.47
3.21
2.92
2.73
2.52

400
48.70
18.50
10.40
7.68
5.79
4.85
4.02
3.54
3.08
2.79
2.49
2.30
2.10
1.96
1.81

AREA FACTOR TABLE DUCT CONNECTION - STYLE B


Dimension A Width (mm)
500
600
700
800
38.00
31.10
26.40
22.90
14.40
11.80
9.99
8.67
8.07
6.61
5.60
4.86
5.99
4.91
4.16
3.60
4.51
3.70
3.13
2.72
3.78
3.10
2.62
2.27
3.13
2.57
2.18
1.89
2.76
2.26
1.92
1.66
2.40
1.97
1.67
1.44
2.17
1.78
1.51
1.31
1.94
1.59
1.35
1.17
1.79
1.47
1.25
1.08
1.63
1.34
1.13
0.98
1.53
1.25
1.06
0.92
1.41
1.15
0.98
0.85

900
20.20
7.65
4.29
3.18
2.40
2.01
1.67
1.47
1.28
1.16
1.03
0.95
0.87
0.81
0.75

1000
18.10
6.85
3.84
2.85
2.15
1.80
1.49
1.31
1.14
1.03
0.93
0.85
0.78
0.73
0.67

1100
16.40
6.20
3.48
2.58
1.94
1.63
1.35
1.19
1.03
0.94
0.84
0.77
0.70
0.66
0.61

1200
14.90
5.66
3.17
2.35
1.78
1.49
1.23
1.09
0.94
0.86
0.76
0.71
0.64
0.60
0.55

(All dimensions include 6 mm clearance total between outside of damper frame and inside of duct).

For pressure drop through an open IBD-B-V or IBD-B-H fire damper use the
following procedure:
1. Find the Area Factor from the above table enter duct height and width.
2. Determine Conversion Velocity (CV) by multiplying Area Factor by flow in
m3/s (CV = Area Factor x m3/s).
3. Enter pressure drop chart with Area Factor and establish intersection
with Conversion Velocity (CV) line just determined. Read pressure drop
on left hand side of the chart.

Note: Interpolations while not precise, are adequate for most calculations.
EXAMPLE:
Find the pressure drop across a 500 wide x 514 high model IBD-B-V fire
damper, passing 2.2 m3/s.
1. From the table using interpolation, the Area Factor is 4.51.
2. CV = 2.2 x 4.5 = 10.
3. From pressure drop chart, pressure drop is 8 Pa.

200
150
125
100
90
80
70
60
50
40

CV

30

30

C
25

Static
Pressure
(Pa)

C
20

20

C
15
10
9
8
7
6
5

CV
10
C
7.5

CV
5.0

C
3.5

1
0.1

.2

.3

.4

.5 .6

.8 1.0

1.5 2.0 2.5 3.0

4.0 5.0 6.0 8.0 10

15

20

30

40 50

70

100

Area Factor (From Table)

Notes
1. Static Pressure and Conversion Velocities are correct for 1.2 kg/m3 air density.
2. Ratings are based on dampers installed in accordance with details in this catalogue, with ductwork upstream and downstream.

320H

Holyoake Air Management Solutions 2013

Interlocking Blade Fire Damper - Series

IBD

Product Ordering Key and Suggested Specifications


IBD

Interlocking
Curtain Blade
Fire Damper

A
B
C
CR
CO
Duct
Connection
Style

V
H

Vertical,
or
Horizontal
Mounting.

WIDTH (A)mm
x
HEIGHT (B) mm

Nominal
Duct Size,
(A Width
Dimension
First).

TL
ETR

TL = Test Latch with


71 C Link,
ETR = Electro Thermal
Resettable Link.

MSU

Universal
Mounting
Sleeve

SPECIAL
OPTIONS

Single Pole
Micro Switch
(For Release Position).
2 x Single Pole
Micro Switch
(For Reset And
Release Position).
Extended Damper Sleeve,
(Specify Wall Thickness).

Fire dampers shall be interlocking blade, curtain type, conforming to the requirements of the Australian and N.Z. Building Code and
shall be built to comply with construction details proven by prototype tests conducted in accordance with AS 30, AS 1682, or UL 555,
to withstand exposure to controlled flame for no less than 4 hours before failure of the assembly as a whole, or any of its components
and shall qualify for a 4 hour fire resistance rating, in terms of Australian Standard AS 1530, Part 4, fire resistance test of structures.
Fire dampers shall be equipped for either vertical, or horizontal mounting and shall close by release of a fusible link at a temperature of 71C,
or by means of an Electro Thermal Resettable Release device incorporating a 71 C Thermal Resettable Release.
Safe Test Test latches and access doors shall be provided for all fire dampers, so that they may be test operated at any time after
installation without destroying fusible links and annually in accordance with AS 1851 - 2012 ( Section 13 ), Routine service of fire
protection systems and equipment.
Fire dampers shall be installed in wall, or floor openings utilizing factory fitted galvanised steel mounting sleeves and angles, other
materials and practices required to satisfy the Australian and N.Z. Building Code and AS 1682 Parts I & II and as shown in the manufacturers
installation instructions.
Fire dampers shall be Holyoake Series IBD, with sleeves Holyoake Model IBD-MSU, all as manufactured and supplied by Holyoake.

321H

Fire & Smoke Dampers

Series HFS Fire & Leakage Rated Smoke Damper


Model: HFS-R-146
The Holyoake HFS-R-146 is a fire and leakage rated multi-leaf steel
damper, for the prevention of the spread of fire and/or smoke through
ducted air systems, or between plenums. Self contained as a fire
damper and externally operable by electric, or pneumatic actuator;
constructed to comply with AS 1668.1, 1998 and AS 1682.1, 1990.
Fire Rating: Tested in accordance with AS 1530.4,1990, integrity was
maintained for a minimum of 4 hours. For purposes of the
Australian and New Zealand Building Code they have a
F.R.L./F.R.R. of / 240 /
Tests:

Mounting:

Actuators:

HFS-R-146
With Sleeve
and Actuator.

BRANZ Fire Test Certificate No. FTC 390,


HFS-R-146 mounted in a concrete wall, or floor.
(Certified for 240 minute fire rating).
BRANZ Fire Test Certificate No. FTC 391,
HFS-R-146 mounted in a plasterboard wall.
(Certified for 30 and 60 minute fire rating).

Latch:

Stainless steel with 71C fusible link.

(Certificates are available upon request).

Axles:

84 mm long hex, M.S. bright zinc-plated pins,


mechanically locked and welded to half hex blade
channel.

Cranks:

6 mm M.S. bright zinc-plated, force fitted to hex pin and


S.S. link bar pin.

Sleeve mount in accordance with AS 1682 - 1990, Part 2,


and generally as described on pages 313H - 317H and
323H, with blade axles located within the fire partition.
Sleeves and mounting angles are furnished as standard.
Holes through walls, or floors must be sized to provide
room for expansion in accordance with AS 1682.1 - 1990.
HFS-R-146 requires a 12 mm tolerance gap on all four sides.
Because of critical fitting requirements, actuators must
be factory fitted. Factory supplied make may vary from
time to time.
Specify: (a) Make.
(b) Voltage (if electric).
(c) Pressure range (if pneumatic).
(d) Spring, or non-spring return (if electric).
(e) Fail open, or closed (if spring).
(f) Temperature rating.

Blade Rotation: Parallel only.


Finish:
Maximum
Velocity:

Nominal Size is sleeve ID, always stated as W x H, in


that order
Note: Add 6 mm to Nominal W (Width) and
Nominal H (Height) for Internal Duct size

10m/s

Frame Bracing: Diagonal corner braces on all dampers above 300 x300.
Handing:
Remote
Indication:

Standard Construction
Dimensions:

Mill.

Standard left hand as illustrated. Alternative right hand


is available, specify when ordering.
All units are fitted with a normally open single pole limit
switch activated by the blade. Standard is set to close
circuit on damper closure. Alternative (close circuit on
damper opening) is available, specify when ordering.

Sleeve Material: Galvanised Steel Type Z275.


Maximum Dimensions
Per Side mm
0-300
301-762
763-1113

Sleeve Thickness mm
0.45
0.55
0.75

Minimum
Nominal Size:

200 mm Wide x 230 mm High.

Maximum
Nominal Size:

Mounting Angles: 40 x 60 x 2 mm galvanised steel angle,


(x4 per side, x2).

900 mm Wide x 1113 mm High.

Installation:

Frame:

Mild steel grade G250 galvanised to Z275,


167 x 23 x 1.15 mm roll formed hat section,
with machine notched joints and corner gussets.

Blades:

Mild steel grade G250 galvanised to Z275,


157 x 1.15 mm roll formed double vee and hex,
on 146 mm shaft centres.

Blade Seals:

Silicon seal on blade edge.

Side Seals:

Stainless steel type 301.

HFS-R-146 dampers must not be installed


with the axles vertical.
They may be used in either vertical, or horizontal
planes, with air flow and fire exposure from either
direction.
Dampers must be fixed square and free from racking.
Duct Connection: Mounting Sleeves are supplied raw edged. Duct Joints
to the damper must be Break-away type e.g. S cleat.

Blade Linkage: External in frame, concealed between frame and


mounting sleeve.
Bearings:

12.5 mm I.D. x 28 mm O.D. grease-packed ball races,


pressed into frame.

Control Shaft:

12.5 mm O.D. x 1.2 mm wall 304 stainless steel tube.

Control Linkage: 71C fusible link driven crank type, with integral
constant force return spring.

322H

Holyoake Air Management Solutions 2013

Dimensional Data Series

HFS

Model: HFS-R-146
m).
0.900N0o)
(M(aMxa9x
WW

For maximum open free area, select exact modular height.


Exact modular height is where H = H Min.
Latch With
Fusible Link.

For non modular height use the following:


Determine number of blades from Table 1, then:
Top + Bottom Blade Centres

Blade Stop Heights

A = H - H Min + A Min
2

B = H - H Min + B Min
2

SS 301
Side Seal.

71C
Fusible Link.
Grease
Packed
& Sealed Ball
Bearings.

Jack Shaft Centre From Top of Casing


SS 304
Tubular Shaft.

C = H - H Min + C Min
2

167
22

e.g. 300 Height

A 300 = 300 - 230 = 35 + 115 = 150


2

Blade Edge Seals.

40

Limit Switch.

HFS-R-146

B 300 = 300 - 230 = 35 + 33 = 68


2
C 300 = 300 - 230 = 35 + 175 = 210
2

(Mounting Sleeve
and Actuator
Omitted for Clarity).

55
146
15

H
(Max
1113
Nominal)

TABLE 1 - NOMINAL DIMENSIONS


No. of Blades

H Min

230

376

522

668

814

960

1106

H Max
A Min
B Min
C Min

375
115
33
175

521
115
33
175

667
115
33
175

813
115
33
321

959
115
33
467

1105
115
33
613

1113
115
33
759

A
B

Note: Add 6 mm to Nominal W (Width) and Nominal H (Height) for Internal Duct Size.

4 Slotted For
M6 Bolts*.

60 x 40 x 2 GMS
Fixed MTG Angle

H
(Nominal)

60 x 40 x 2 GMS

55
200 Max
80Min

450

100

W (Nominal)

60

165
Min
125

Notes
1 Standard sleeve length of 450 mm will accommodate walls 80 - 200 mm thick. For other wall depths, specify special length.
2 Limit switch tails.
3 Typical actuator. For smallest damper, fits within overall damper and mounting angle height.
4 M6 galvanised bolts (* Refer to page 313H Fire Damper Installation Notes).
5 Packing in the expansion gap, High Temperature Mineral Wool, (Supply and fit by others ).
6 Multiple assemblies need to be individually operated and separated by a minimum of 200 mm of structural support,
(in either width, or height); of the same fire rating and structural integrity as the surrounding wall.
7 Illustration details an example of arrangement to be supplied and is as tested.
8 Trim sleeves as per note 6 on page 317H, to comply with AS 1682, Part 2, 1990.

323H

Fire & Smoke Dampers

Series HFS Performance Data


Model: HFS-R-146
Nom Ht.
(mm)
230
376
522
668
814
960
1106

No. of
Blades
1
2
3
4
5
6
7

200
66.56
29.31
18.79
13.83
10.94
9.05
7.72

250
48.91
21.54
13.81
10.16
8.04
6.65
5.67

300
38.66
17.02
10.91
8.03
6.35
5.26
4.48

350
31.97
14.07
9.02
6.64
5.25
4.35
3.71

AREA FACTOR TABLE


Nominal Width (mm)
450
500
550
23.74
21.03
18.88
10.45
9.26
8.31
6.70
5.94
5.33
4.93
4.37
3.92
3.90
3.46
3.10
3.23
2.86
2.57
2.75
2.44
2.19

400
27.24
12.00
7.69
5.66
4.48
3.70
3.16

600
17.13
7.54
4.84
3.56
2.81
2.33
1.99

650
15.67
6.90
4.42
3.26
2.58
2.13
1.82

700
14.45
6.36
4.08
3.00
2.37
1.96
1.67

750
13.40
5.90
3.78
2.78
2.20
1.82
1.55

800
12.49
5.50
3.53
2.59
2.05
1.70
1.45

850
11.70
5.15
3.30
2.43
1.92
1.59
1.36

900
11.00
4.84
3.11
2.29
1.81
1.50
1.28

Note: Add 6 mm to Nominal W (Width) and Nominal H (Height) for Internal Duct Size.

Use the table and chart to determine the pressure drop through
HFS R 146 Fire / Smoke Dampers.

EXAMPLE:
Find the pressure drop across a 350 wide x 814 high model HFS-R-146
Fire/Smoke Damper handling 1.3 m3/s.

1. Determine area factor for damper by entering the area factor table with
duct width and height.

1. From the table the area factor is 5.25.

2. Find conversion velocity (CV) by multiplying area factor for selected size
damper by flow rate in m3/s. CV = Area Factor x m3/s.

2. CV = 1.3 x 5.25 = 6.825.


3. From pressure drop chart, Pressure Drop is 12Pa.
(Note: Interpolations while not precise, are adequate for most calculations).

3. Enter pressure drop chart with area factor and proceed up to the
appropriate conversion velocity (CV) line.
Read the pressure drop (Pa) on the left hand side of the chart.

Notes

1000

500
400
300
200

25CV
100

15CV

50
40
30

10CV

Static
Pressure
(Pa) 20

7.5CV

5CV
4CV

10

5
4
3
2

1
1

10

20

30

40

50

60 70 80

100

Area Factor (From Table)

Notes
1. Static Pressure and Conversion Velocities are correct for 1.2 kg/m3 air density.
2. Pressure drop data is for dampers tested with ductwork on both the up and downstream sides.These values need to be suitably increased where dampers
are mounted with ductwork on one side only, or when mounted onto plenum walls. (Refer to SMACNA, or ASHRAE System Design Guides).
3. Data is for the specific sizes listed in the Area Factor table. For other sizes use the next size down and make a proportional adjustment based on the
approximate increase in free area.

324H

Holyoake Air Management Solutions 2013

Fire & Leakage Rated Smoke Damper Series HFS


Product Ordering Key and Suggested Specifications
HFS-R-146

Fire and
Leakage Rated
Smoke
Damper.

WIDTH (W)mm
x
HEIGHT (H)mm
Nominal Size
Sleeve ID
(W Width
Dimension
First).

MSU

Universal
Mounting Sleeve.

OPTIONS

Reverse Handing (Right Hand).


Reverse Switching
(Close Circuit on
Damper Opening).
Extended Damper Sleeve
(Specify Wall/Slab
Thickness).

ACTUATORS

Specify
(a) Make.
(b) Voltage (if electric).
(c) Pressure range (if pneumatic).
(d) Spring, or non-spring return(if electric).
(e) Fail open, or closed (if spring).
(f) Temperature rating.

Fire and Leakage Rated Smoke dampers shall be multi-leaf dampers, constructed to comply with details proven by prototype tests
conducted in accordance with AS 1530.4.
To withstand exposure to controlled flame for no less than 4 hours before failure of the assembly, or any of its components.
Fire and Smoke dampers shall be equipped for either vertical, or horizontal mounting, are complete with a suitable electric, or pneumatic
actuator and shall release by a fusible link at a temperature of 71C.
Alternatively the fire/smoke damper can be activated by a remote signal from a fire alarm panel (supply and fit by others).
Fire and Smoke dampers should be annually, or biannually tested as determined by AS 1851 - 2012 ( Section 13 ), Routine service of fire
protection systems and equipment; in accordance with their design failure position.
Fire and Leakage Rated Smoke dampers, shall be Holyoake series HFS-R-146 with Sleeves, Holyoake Model HFSR146 - MSU and shall be
as manufactured and supplied by Holyoake.

Guide Product Weights


Fire & Leakage Rated Smoke Dampers
HFS-R-146 200 x 230 (Inc Sleeve, Angles & Motor)
HFS-R-146 250 x 250 (Inc Sleeve, Angles & Motor)

Approximate Weight in Kg
10.1
11.33

Important Note
HFS dampers must be transported with their blades horizontal, not in the vertical position.

325H

Fire & Smoke Dampers

Series LR Low Radiation Fire Damper


Model: LR
The Holyoake Series LR (Low Radiation) Fire Dampers are designed
to impede the spread of fire and heat within building compartments,
whilst maintaining the walls integrity. The low leakage insulated
damper blade assembly with blade tip sealing ring, forms a solid
barrier against flame, smoke and hot gases.
Complying with AS/NZS 1668.1 - 1998 the LR Fire Damper is certified
for a 4 hour rating in a masonry wall and
a 2 hour rating in a plasterboard wall.

4 Hour FRL/FRR and Radiation Protection to AS 1530 part 4.


The Holyoake LR Fire Smoke damper has been designed to provide
premium protection for occupants and building structures in the
event of a fire.
The innovative heat radiation blocking damper blade, will snap closed
within seconds upon the air temperature reaching 71C, providing
rapid temperature response.
Furnace testing to AS 1530.4 - 1997 has proven that the damper will
stop the passage of fire and smoke through a fire rated wall for at
least 4 hours.

>>V}`>i
>`>Li>`i

The LR Damper integrates both a fire, smoke and control damper into
Guide Product Weights
one easy to install, maintain and test unit. It is supplied complete
Low Radiation Fire & Smoke Damper
Approximate Weight in Kg
with external low radiation sleeve and mounting flanges.
LR 150
4.17 Boxed
Fire protection is provided by a fusible link and damper blade that
seals the duct shut in the event of a fire.
The damper blade is designed to reduce the transfer of heat radiation
through the firewall, providing induct heat radiation control, while the
outer solid insulating sleeve ensures minimal conduction of heat into
the wall cavity.
Standard Insulated.
Standard Insulated.
For Plasterboard or Masonry Walls.
Sectional View Through Plasterboard Wall.
The unique Series LR damper design
Minimal Heat
ensures that the damper blade always
Transfer Into
stays within the confines of the wall
Wall Cavity
and provides a cost effective solution.
Non - Conductive
Insulated
Damper Blade

Features:

Ui>,>`>/ii`
Ui>>}i>i` >`i
U1{i,>}
U*i>i`-iii
U >>V} >i
U`>Liv6>>Li7> i

Solid Insulating
Sleeve

Fusible
Link
Blade Tip
Sealing
Ring

Sliding Flange

Permanently
Attached
Flange

Optional Un-insulated.
Sectional View Through Masonry Wall.

Optional Un-insulated.
For Masonry Walls Only.

Insulated
Damper Blade

Galvanised Steel
Sleeve

Fusible
Link
Blade Tip
Sealing
Ring

Permanently
Attached
Flange

326H

Sliding Flange
Fire Proof Sealant
Holyoake Air Management Solutions 2013

Performance and Dimensional Data Series LR


Rating

Dimensions:

FRL/FRR rating:
Exova WarringtonFire Aus Pty Ltd /240/
Heat radiation less than 10 kW/m2
Test Certificate SFC41085.3

Masonry Walls

FRL/FRR rating:
Exova WarringtonFire Aus Pty Ltd /120/ 30 *
Heat radiation less than 10 kW/m2
Test Certificate SFC41084.3

Framed Walls*

(* Includes steel and timber framed walls).


NATA certified testing to AS 1530 part 4, to the requirements of AS 1682 Part 1.
* In accordance with Exova WarringtonFire 45757.1.

Performance Data

Static Pressure Drop When Damper Fully Open


Flow (l/s)

Ps (Pa) fully open

10
20
40
60
80
100
120
140
160
180
200

1
2
5
9
16
24
36
47
61
78
94

LR 150
A

145

110

95 -170

430

137

Note: All Dimensions in mm.

Installation
1 The LR damper has one flange permanently attached. Installation is
simple. A circular hole is made through the wall where the duct is
to penetrate.
Cut Size In Wall mm
Insulated
LR150 180 - 185

Leakage When Damper Shut


Leakage
(l/s)

Un-insulated
LR150 155 - 160

14

2 Mount the LR damper through the hole in the wall.

12

3 Fix the outside flange.


4 On the opposite side of the wall mount the sliding flange over the
LR Damper sleeve and fasten to both the damper and wall.

10
8

In plasterboard walls the weight of the damper must be supported


independently of the wall lining, in accordance with plasterboard
manufacturers specifications.

6
4
2
0
0

500

1000

1500

Pressure Behind Damper (Pa)

Screw Fix
As Provided
1. Cut Hole

Damper Setting
The damper can be used for balancing and set using the attached
external handle. The clamp nut on the handle must be tightened to hold
the damper blade in place. The handle may also be used to check the
functioning of the damper when inspection is due.

Note
Series LR dampers are suitable for Wall Mounting Only.

Fixing
3. Fix attached
flange to wall

2. Insert LR Damper
Through Hole in Wall

Fixing
4. Attach Sliding
Flange & Fix
to Wall

327H

Fire & Smoke Dampers

Series LR Low Radiation Fire Damper

Product Ordering Key and Suggested Specifications


LR150

OPTION

Model

Standard
(Insulated)

LR150

OPTION

Model

Un-insulated

Holyoake LR Low Radiation Fire Dampers shall have a


4 hour rating in a masonry wall and a 2 hour rating in a
steel, or timber framed wall.
The rating shall be certified to AS 1530.4 and to the
requirements of AS 1682.1.
The rating applies to fires on both sides of a fire wall.
Heat radiation emitted during testing to AS 1530.4 was
less than 10 kW/m2.
LR Low Radiation Fire Dampers contain a fusible link
that releases and allows the damper to close upon
reaching 71C.
LR Fire Dampers should be annually tested as
determined by AS 1851 - 2012 ( Section 13 ). Routine
service of fire protection systems and equipment.
An external lockable handle is included as standard
that can be used to position the damper blade to
provide volume control.
No additional insulating material will be needed to
install the Low Radiation Fire Damper.
Low Radiation Fire Dampers shall be Holyoake Series
LR Standard (Insulated) and shall be manufactured
and supplied by Holyoake.

Holyoake LR Low Radiation Un-insulated Fire Dampers


shall have a 4 hour rating in a masonry wall, (not suitable
for steel, or timber framed walls).
The rating shall be certified to AS 1530.4 and to the
requirements of AS 1682.1. The rating applies to fires on
both sides of a fire wall.
Heat radiation emitted during testing to AS 1530.4 was
less than 10 kW/m2.
LR Low Radiation Un-insulated Fire Dampers contain a
fusible link that releases and allows the damper to close
upon reaching 71C.
LR Fire Dampers should be annually tested as
determined by AS 1851 - 2012 ( Section 13 ). Routine
service of fire protection systems and equipment.
An external lockable handle is included as standard that
can be used to position the damper blade to provide
volume control.
No additional insulating material will be needed to install
the Low Radiation Un-insulated Fire Damper.
Low Radiation Un-insulated Fire Dampers shall
be Holyoake Series LR (Un-insulated) and shall be
manufactured and supplied by Holyoake.
Patent Pending

328H

Holyoake Air Management Solutions 2013