BEXIMCO PHARMACEUTICALS LIMITED
TONGI, GAZIPUR
Unit-03 CS of Package-02 (HVAC Control)
ITEM
URS
Offer
Telstar
Remarks
Offer
Cord 01(Clean Air Innovation)
Remarks
BMS System
Cord 02(MPEL)
Offer
Remarks
Offer
Brand
Siemens or similar
Siemens
Siemens
Schneider
Country Of Manufacturing
European
European
France
PC
-Personal computer HP or similar
Comply
-Processor Intel Quad Core 2.33GHz
-Ram memory 4Gb DDR2
-Hard disc 500Gb
-LAN card 1000Mbps
-Monitor 19" TFT
-Mouse & Keyboard
-License MS Windows 2008 Server
Germany (for CPU) China European origin preferred
(Others)
Comply
Elomatic
Remarks
Offer
Sunscape
Remarks
Offer
QTS
Remarks
Rockwell
Software Packages
Communication Protocol
Thir Party Integration
Individiual BMS SCADA for HVAC
System & PW System.
All related software for
BMS/SCADA/Control system with
license will be provieded by
supplier. (BPL-800898-TC-CO01 &
TD-CO01).
Not mentioned
1. Ethernet protocol between
SCADA & PLC
2. Profinet protocol between PLC
CPU to HMI/VFD/ Distributed ET200S, (BPL-800898-TD-CO01.)
Comply
Singapore
Manual need
to be
provided.
Comply
Comply(Supl
lier's quote)
Need to include &
provide detail
information.
WIN CC
WIN CC only for
graphics.Other control
system software details
with licencse & backup
need to include with
detail information.
Offer is based on DDC
system whereas BPL
design is based on PLC
control system.
System software with
Specific software name
unlimited tag license and with license is needed.
21CFR Part 11 compliant.
Not Comply with BPL
requirements.
Comply (Supplier's quote)
Offer is based on DDC
system whereas BPL
design is based on PLC
control system.
Not Comply with BPL
requirements.
Specific
software
Comply(Supl
with license
lier's quote)
need to
mention.
Yes confirmed (Supplier's
Quote)
Comply(Supl
lier's quote)
Need integration for some signal
Included (Supplier's
from Chiller,Cooling
Quote)
tower,Compressor & Fire prvention
system.(Please see BPL-800898-LISCO01/03 & TD-CO01)
Comply (Supplier's quote)
Yes confirmed (Supplier's
Quote)
Comply(Supl
lier's quote)
Control Wire
Brand
Need to mention
Not mentioned
To be mentioned
Link
KEI
Country Of Manufacturing
Need to mention
Not mentioned
To be mentioned
Taiwan
India
Cooper wire RC4Z1 2x1mm
free halogen
Quantity: As per BOQ.
Comply
Cooper wire RC4Z1 5x1mm
free halogen
Quantity: As per BOQ.
Cable UTP Cat.6, 4 pairs LSZH 5
Comply
Comply(Supplier's quote)
Yes confirmed(Supplier's
quote)
Offer is based on DDC
system whereas BPL
design is based on PLC
control system.
Comply(Supplier's quote)
Comply
Comply (Supplier's quote)
Yes confirmed (Supplier's
quote)
Yes confirmed (Supplier's
quote)
Quantity: As per BOQ.
RJ45 Plug connector Siemens
10/100/1000MB/s.
Quantity: As per BOQ.
Comply
Comply(Supplier's quote)
Brand
CONTROLLI-DELTA or similar
Controlli
Siemens
Country Of Manufacturing
PDS (Differential pressure switch)
European
Range 5..500 Pa.
Include pipe and accessories for
assembly.
Environment: -20C to +85C
European
Model: DBL 205B
Quantity as per BOQ
TT (Temperature transmitter)
Selectable range -10..110C or
Model: TT 322/CVO
-10..40C. PT100 sensitive element. Quantity as per BOQ
Output: two-wire 4..20mA or
0..10Vdc.
Accuracy: 0.2C at 25C
Power Supply: 24Vac or dc
Environment: -30C to +70C
HT-TT (Temperature and humidity
transmitter )
Yes confirmed (Supplier's
quote)
Mounted in air duct.
Model: EE 160
Range: temperature -20C.. 50C
Quantity as per BOQ
and humidity 0..100%. Output: twowire 4..20mA or 0-10Vdc. IP65
enclosure.
Environment: -40C to +60C
HVAC Instrumentation
TS provided for Huba
control instrumentation
which doesn't comply
European
with
the offer & excel
Repalced by Siemens P/N TS
needed.
sheet.
QBM81-5
TS needed.
Page 1 of 9
Offer is based on DDC
system whereas BPL
design is based on PLC
control system.
Not Comply with BPL
requirements.
Comply(Supl
lier's quote)
Comply(Supl
lier's quote)
Canada
Specific
model
Comply(Supl number &
lier's quote) manual are
not
provided.
Yes confirmed (Supplier's Specific model number is
quote)
needed
Yes confirmed (Supplier's Specific model number is
quote)
needed
Comply(Supl
lier's quote)
Greystone
Europe
Yes confirmed (Supplier's Specific model number is
quote)
needed
Offer is based on DDC
system whereas BPL
design is based on PLC
control system.
Need to
mention
Need to
mention
Comply(Supl
lier's quote)
Danfoss/E+H
Repalced by Siemens P/N TS needed.
QAE2164 (IP54)
Repalced by Siemens P/N
QFM3171
Not
mentioned
Not
mentioned
Offer is based on DDC
system whereas BPL
design is based on PLC
control system.
Not Comply with BPL
requirements.
Specific
model
Comply(Supl number &
lier's quote) manual are
not
provided.
Specific
model
Comply(Supl number &
lier's quote) manual are
not
provided.
BEXIMCO PHARMACEUTICALS
TONGI, GAZIPUR
PDT (Differential pressure
transmitter.)
Range 0..50/100/300.
Model: PA 699/100
Output two-wire 4..20mA or 0Quantity as per BOQ
10Vdc. IP65 enclosure.
Power Supply: 13.5-33Vac or 24Vdc
Environment: 0C to +70C
PDT (Differential pressure
transmitter.)
Range 0..300/500/1000.
Model: PA 699/500
Output two-wire 4..20mA or 0Quantity as per BOQ
10Vdc. IP65 enclosure.
Power Supply: 13.5-33Vac or 24Vdc
Environment: 0C to +70C
Brand
Siemens or similar
Offer is based on DDC
system whereas BPL
design is based on PLC
control system.
Offer is based on DDC
system whereas BPL
design is based on PLC
LIMITED control system.
Not Comply with BPL
requirements.
TS needed.
Yes confirmed (Supplier's Specific model number is
quote)
needed
Specific
model
Comply(Supl number &
lier's quote) manual are
not
provided.
TS needed.
Yes confirmed (Supplier's Specific model number is
quote)
needed
Specific
model
Comply(Supl number &
lier's quote) manual are
not
provided.
Repalced by Siemens P/N
QBM3020 (IP54)
Repalced by Siemens P/N
QBM3020 (IP54)
HVAC Control Boards
Siemens
Schneider make
switchgear and local
panel mgf.
Country Of Manufacturing
European
Switchboard cabinet
Include: Thermal magnetic circuit
Comply
breaker,DC 24V power
supplies,relays,emergency pilots &
push buttons etc.
Comply(Supplier's quote).
Digital Input: 16384
Digital Output: 16384
Analogue Input: 1024
Analogue Output: 1024
Temp.: -20C to +70C
Qunatity: As per BOQ
Comply
Comply(Supplier's quote)
Digital Input: 65536
Digital Output: 65535
Analogue Input: 4096
Analogue Output: 4096
Temp.: -20C to +70C
Qunatity: As per BOQ
Comply
Input: 32(24Vdc)
Temp: -20C to +70C
Qunatity: As per BOQ
Comply
Digital Output Module for CPU-317 Output: 16(24Vdc)
Temp: -20C to +70C
Qunatity: As per BOQ
Comply
Analogue Input Module for CPU-317 Input: 8(0-10Vdc or4-20mA)
Temp: -20C to +70C
Qunatity: As per BOQ
Comply
Analogue Output Module for CPU317
Output: 4(0-10Vdc or4-20mA)
Temp: -20C to +70C
Qunatity: As per BOQ
Comply
Power Module For CPU-317
Input: 230Vac
Output: 24Vdc
Temp: 0C to +60C
Comply
Model: ET-200S
Digital Input: 62
Digital Output: 51
Analogue Input: 36
Analogue Output: 62
Temp.: 0C to +60C
Qunatity: As per BOQ
Comply
Input: 8(24Vdc)
Temp: -20C to +70C
Qunatity: As per BOQ
Comply
Output: 8(24Vdc)
Temp: 0C to +60C
Qunatity: As per BOQ
Comply
Analogue Input Module for ET-200S Input: 4(4-20mA)
Temp: 0C to +60C
Qunatity: As per BOQ
Comply
Analogue Output Module for ET200S
Comply
CPU-315-PN/DP
CPU-317-PN/DP
Digital Input module for CPU-317
Remote I/O
Digital Input module for ET-200S
Digital Output Module for ET-200S
Output: 2(0-10Vdc or4-20mA)
Temp: 0C to +60C
Qunatity: As per BOQ
European
Siemens
China
Should be European.
Switchgear - Europe
(France, Schneider);
Panel Mgf local india
Manual need
1769-L30ER to be
provided.
Yes confirmed (Supplier's Specific model number is
quote)
needed
Manual need
1769-L30ER to be
provided.
Yes confirmed (Supplier's Specific model number is
quote)
needed
Comply(Supplier's quote).
Yes confirmed (Supplier's Specific model number is
quote)
needed
Comply(Supplier's quote).
Comply(Supplier's quote).
Comply(Supl
lier's quote)
Yes confirmed (Supplier's Specific model number is
quote)
needed
Comply(Supplier's quote).
Comply(Supplier's quote).
Singapore
Yes confirmed (Supplier's
quote)
Comply(Supplier's quote)
Comply(Supplier's quote).
Rockwell
Offer is based on DDC
system whereas BPL
design is based on PLC
control system.
Yes confirmed (Supplier's Specific model number is
quote)
needed
Yes confirmed (Supplier's Specific model number is
quote)
needed
Yes confirmed (Supplier's Specific model number is
quote)
needed
Offer is based on DDC
system whereas BPL
design is based on PLC
control system.
Not Comply with BPL
requirements.
1769-IQ32
Manual need
to be
provided.
1769-OB16
Manual need
to be
provided.
1769-IF8
Manual need
to be
provided.
1769-OF8C
Manual need
to be
provided.
1769-PA2
Manual need
to be
provided.
Yes confirmed (Supplier's Specific model number is
quote)
needed
Manual need
1734-AENTR to be
provided.
Comply(Supplier's quote).
Comply(Supplier's quote).
Comply(Supplier's quote).
Comply(Supplier's quote).
Page 2 of 9
Yes confirmed (Supplier's Specific model number is
quote)
needed
Yes confirmed (Supplier's Specific model number is
quote)
needed
Yes confirmed (Supplier's Specific model number is
quote)
needed
Yes confirmed (Supplier's Specific model number is
quote)
needed
1734-IB8
Manual need
to be
provided.
1734-OB8
Manual need
to be
provided.
1734-IE4C
Manual need
to be
provided.
1734-OE2V
Manual need
to be
provided.
BEXIMCO PHARMACEUTICALS LIMITED
TONGI, GAZIPUR
Power Module For ET-200S
Output: 24Vdc
Temp: 0C to +60C
Comply
Comply(Supplier's quote).
Brand
Siemens or similar
Siemens
Siemens
Yes confirmed (Supplier's Specific model number is
quote)
needed
1794-PS13 / Manual need
1734to be
EP24DC
provided.
Frequency Inverters
Country Of Manufacturing
Model
European
Sinamics G120C or similar
European
Offer is based on DDC
system whereas BPL
design is based on PLC
control system.
UK
Sinamics G120C
See attached TS
Sinamics G120C
Schneider
Offer is based on DDC
system whereas BPL
design is based on PLC
control system.
Schneider France
Yes confirmed (Supplier's Specific model number is
quote)
needed
Not Comply with BPL
requirements.
Rockwell
Manual need
to be
provided.
Singapore
Manual need
to be
provided.
PowerFlex
525
Manual need
to be
provided.
Supply Voltage
380-480Vac
Comply
Comply(Supplier's quote).
Specific model number is
needed
Manual need
380-480Vac to be
provided.
Range
0.55-18.5 Kw
Comply
Comply(Supplier's quote).
Specific model number is
needed
Manual need
0.55-18.5 Kw to be
provided.
Communication
Profinet protocol
Comply
Comply(Supplier's quote).
Operator Display
With keypad
Needed Keypad included
Intelligent Operating
Panel (IOP)
Yes confirmed (Supplier's Specific model number is
quote)
needed
Yes confirmed (Supplier's Specific model number is
quote)
needed
Quantity
As per BOQ
As per BOQ
As per BOQ
As per BOQ
Manual need
Comply(Supl
to be
lier's quote)
provided.
Brand
Country Of Manufacturing
Screen Diagonal
Siemens or similar
European
3.8"
Siemens KTP400
European
Comply
Siemens KTP400
China
4.0
Siemens
India
Should be European.
Yes confirmed (Supplier's Specific model number is
quote)
needed
Rockwell
USA
Ethernet/IP
Not comply
Manual need
With keypad to be
provided.
HMI
Should be European
Offer is based on DDC
system whereas BPL
design is based on PLC
control system.
Resolution
320 pixel horizontal,240pixel
vertical,4 Grayscale
Comply
320 x 240 Pixel Greyscale
Specific model number is
needed
Protection
IP20
Comply
IP20
Specific model number is
needed
Communication
Profinet protocol according to BOQ
& TD-CO-01
Comply
As per BPL-800898-TC-CO01
1. cGMP
2. ISO 14644 Standards
3. 21 CFR: Code Of FEDERAL
Regulations Title 21
4. US FDA Regulation
5. GAMP-5 Regulation for
automation
As per URS(Supplier's
Quote)
Qualification,Validation & FAT
Validation & Qualification
(DQ,IQ,OQ etc.) must be done by
supplier.
Comply(Supplier's quote)
Confirm as
Requirement(Supplier's
Quote)
Comply(Supplier's quote)
Equipments Calibration
All equipments must have
calibration certificates & these are
in supplier's scope.
Comply
Confirm as
Requirement(Supplier's
Quote)
Yes confirmed (Supplier's
quote)
Disaster Recovery & Software
upgradation
Need information .
Please Clarify
Need to be discussed
Yes confirmed (Supplier's
quote)
Safety Requirements
Comply
All safety requirements will be
fulfilled by contractor.Safety
equipments during construction
must be provided by contractors.
(see BPL-800898-TC-CO01). Details
safety plan & program is required.
Confirm as
Requirement(Supplier's
Quote)
Yes confirmed (Supplier's
quote)
Hand Tools & Necessary
equipments for installation &
Commissioning are In supplier's
scope.(BPL-800898-TC-CO01)
Confirm as
Requirement(Supplier's
Quote)
Yes confirmed (Supplier's
quote)
Confirm as
Requirement(Supplier's
Quote)
Yes confirmed (Supplier's
quote)
Regulation
Hand tools
Commisssioning & Training Details Need total planning about
commissioning & training.
Profinet Protocol
4.3"
Offer is based on DDC
system whereas BPL
design is based on PLC
control system.
Not Comply with BPL
requirements.
Specific model number is
needed
General Requirements
Confirm as
Requirement(Supplier's
Quote)
Offer is based on DDC
system whereas BPL
design is based on PLC
control system.
Yes confirmed (Supplier's
quote)
Offer is based on DDC
system whereas BPL
design is based on PLC
control system.
Not Comply with BPL
requirements.
Included
Comply
480 x 272
Manual need
WQVGA, 18to be
bit color
provided.
graphics
IP54
Manual need
to be
provided.
Ethernet/IP
Manual need
to be
provided.
Comply(Supl
lier's quote)
Comply(Supl
lier's quote)
Comply(Supl
lier's quote)
Comply(Supl
lier's quote)
Comply(Supl
lier's quote)
Page 3 of 9
Manual need
to be
provided.
Comply(Supl
lier's quote)
Comply(Supl
lier's quote)
BEXIMCO PHARMACEUTICALS LIMITED
TONGI, GAZIPUR
Warranty
12 Months warranty from the date
of handover.
12 months from the date Not Comply
of
acceptance of the
starting-up of the
installation.
Confirm as
Requirement(Supplier's
Quote)
Spare Parts Mangements
Probable list for 1 year spare parts
Excluded from the offer.
Need to be discussed
Needed
Comply(Supplier's quote)
Drawings & Documents
All documents & drawings as per
TC-CO01 have to be provided.
Included
Not mentioned
Need to included.
Yes confirmed (Supplier's
quote)
Accessories
All necessary related accessories
for control system work are in
supplier's scope.
Comply
Confirm as
Requirement(Supplier's
Quote)
Needed
Yes confirmed (Supplier's
quote)
Yes agreed and
confirm(Supplier's Quote)
Page 4 of 9
Comply(Supl
lier's quote)
Comply(Supl
lier's quote)
Comply(Supl
lier's quote)
Comply(Supl
lier's quote)
BEXIMCO PHARMACEUTICALS LIMITED
TONGI, GAZIPUR
Package - 02 (HVAC and Clean Room)
Technical Findings' Summary
2.1. Cleanroom & Architectural Observations' Summary
Telstar
Cord-1 (Square Panel)
Cord-2 (Blueseal)
QTS
1. Telstar quoted at the end of Excel sheet as "Telstar have reserved its' right to change the brand or country of origin in
procurement phase". We do not accept any such conditions from any vendors. But, for exceptional cases, with prior approval from
client (BPL), it can be changed.
2. Telstar's offer met all the criterias in the cleanroom and architectural section (2.1.).
3. Fire door, metallic door, mesh door, glass door, sliding door, rolling door and ebonite door are not offered by Telstar. These items will
either have to be offered by Telstar, or will have to be purchased from separate sources.
1. Load bearing capacity of ceiling panel offered is 150 kg/m2, but BPL requirement is 200 kg/m2. So, Cord-01 need to comply with
this requirement.
2. Fire door, metallic door, mesh door, glass door, sliding door, rolling door and ebonite door are not offered by Cord-1. These items will
either have to be offered by Cord-01, or will have to be purchased from separate sources.
1. Load bearing capacity of ceiling panel offered is 100 kg/m2, but BPL requirement is 200 kg/m2. So, Cord-2 need to comply with this
requirement.
2. Their panel door is not ramp hinged, which is a major disadvantage for long term operation.
3. Fire door, metallic door, mesh door, glass door, sliding door, rolling door and ebonite door is included in the offer but brand and
country of manufacturing is not mentioned.
1. QTS's offer met all the criterias in the cleanroom and architectural section (2.1.).
2. Fire door, metallic door, mesh door, glass door, sliding door, rolling door and ebonite door are not offered by QTS. These items will
either have to be offered by QTS, or will have to be purchased from separate sources.
1. Minimum load bearing capacity of ceiling panel, unit of glass panel thickness for window and material and polishing of wall
protection panel is not mentioned in Excel sheet.
Sunscape
2. Fire door, metallic door, mesh door, glass door, sliding door, rolling door and ebonite door are not offered by Sunscape. These items
will either have to be offered by Sunscape, or will have to be purchased from separate sources.
1. Load bearing capacity of ceiling panel offered is 150 kg/m2, but BPL requirement is 200 kg/m2. So, Elomatic need to comply with
this requirement.
2. Infill media of glass panel is silicon, but as per our specification infill media should be silica gel. Offer does not comply.
Elomatic
Gusu
Nicomac
3. Frame of emergency exit door does not comply with our specification. Our requirment is Aluminium, where as they have offered
Galvanised Polished Skin Pass (GPSP).
4. Fire door, metallic door, mesh door, glass door, sliding door, rolling door and ebonite door are not offered by Elomatic. These items
will either have to be offered by Elomatic, or will have to be purchased from separate sources.
Excel sheet is not received. Provided offer is not sufficient to retrieve any data.
Excel sheet is not received. Provided offer is not sufficient to retrieve any data.
2.2. Special Equipment Observations' Summary
Page 5 of 9
BEXIMCO PHARMACEUTICALS LIMITED
TONGI, GAZIPUR
Telstar
Cord-01 (Square Panel)
Cord-02 (Blue Seal)
1. Telstar quoted at the end of Excel sheet as "Telstar have reserved its' right to change the brand or country of origin in
procurement phase". We do not accept any such conditions from any vendors. But, for exceptional cases, with prior approval from
client (BPL), it can be changed.
2. Country of manufacturing of Pass Through Box is not specified. Need to specify.
1. Material of Construction of weighing booths is mentioned as SS 304, but our requirement is SS 304L. Needs to comply.
2. Chilled water system for temperature control is not present in dispensing booth as per URS.
1. Material of Construction of weighing booths is mentioned as SS 304, but our requirement is SS 304L. Needs to comply.
2. Touch Screen HMI and PLC are not included as per URS.
3. Dispensing booths (weighing booth) for ATEX areas are not considered in the offer.
2.3. HVAC Observations' Summary
Telstar
Cord-01 (Clean Air
Innovation)
Cord-02 (Confidence
Trade Limited)
QTS
Elomatic
1. Telstar quoted at the end of Excel sheet as "Telstar have reserved its' right to change the brand or country of origin in
procurement phase". We do not accept any such conditions from any vendors. But, for exceptional cases, with prior approval from
client (BPL), it can be changed.
2. Brand for AHU, swirl diffuser, supply grill, return grill, CAV, VAV, terminal filtration box is not specified.
3. Brand of FCU and heat exchanger needs to be specified and confirmed.
4. Country of manufactring of Constant Air Volume (CAV) & Variable Air Volume (VAV) is not specified.
5. Filter type of terminal filtration box is not specified.
6. Ductwork should follow SMACNA standard, which they did not confirm in the offer/excel sheet.
1. Cord-01 (Clean Air Innovation) is yet to submit the filled up excel sheet for HVAC package. Thus, all the data could not be retrieved
from offer. The excel file should be provided to confirm the data.
2. AHU brand, origin and country of manufacturing are not specified.
3. Brand, and/or origin, and/or country of manufacturing of Make Up Air Unit (MAU), Fan Coil Unit (FCU), ventillation fan, terminal
filtration box, heat exchanger are not specified.
4. Filter type of terminal filtration box is not specified.
5. Duct insulation material and thickness didn't follow URS.
6. Material of flexible duct insulation didn't follow URS.
7. Ductwork should follow SMACNA standard, which they did not confirm in the offer/excel sheet.
1. Cord-02 (CTL) has not yet submitted the filled up excel sheet for HVAC package. Thus, all the data could not be retrieved from offer.
The excel file should be provided to confirm the data.
2. Country of manufacturing of ventillation fan was not specified.
3. Filter type of terminal filtration box was not specified.
4. Duct insulation material and thickness didn't follow URS.
5. Ductwork should follow SMACNA standard, which they did not confirm in the offer/excel sheet.
1. Brand of swirl diffuser, supply grill and return grill isn't specified.
2. Ductwork should follow SMACNA standard, which they did not confirm in the offer/excel sheet.
1. Specific country of origin and manufacturing of AHU and MAU is not mentioned.
2. Country of origin and country of manufacturing of FCU is India, which is not technically accepted in terms of quality and performance.
3. Filter type of terminal filtration box is not specified
Page 6 of 9
BEXIMCO PHARMACEUTICALS LIMITED
TONGI, GAZIPUR
Elomatic
4.
5.
1.
2.
3.
Evercool
Brand of heat exchanger is not specified.
Ductwork should follow SMACNA standard, which they did not confirm in the offer/excel sheet.
Duct insulation material and thickness didn't follow URS.
Filter type and brand aren't mentioned.
Ductwork should follow SMACNA standard, which they did not confirm in the offer/excel sheet.
2.4. HVAC Control Observations' Summary
1. Telstar quoted at the end of Excel sheet as "Telstar have reserved its' right to change the brand or country of origin in
procurement phase". We do not accept any such conditions from any vendors. But, for exceptional cases, with prior approval from
client (BPL), it can be changed.
2. Software packages with license and detail information is not provided.
1. Some of the equipment (PLC/Input output modules and HMI) are offered from China. We prefer these items from EU origin.
Telstar
Cord-1 (Clean Air)
2. Software packages with license and detail information are not provided.
3. Technical Specification (TS) for HVAC instrumentation is not provided.
4. Disaster Recovery and software upgradation information are not provided.
5. Information about drawings and documents according to Technical Condition (TC) & Technical Description (TD) are not included in
offer.
6. Spare parts support service information is not provided.
Direct Digital Control (DDC) based control system is offered. Doesn't comply with URS.
Cord-2 (MPL)
QTS
Evercool
Elomatic
1. Software packages with license and detail information are not provided.
2. Technical Specification (TS) and for HVAC instrumentation,BMS,PLC & other related equipments are not provided.
3. Specific model number for HVAC instrumentation are not provided.
3. Brand & Country of manufacturing of cable are not mentioned.
Direct Digital Control (DDC) based control system is offered. Doesn't comply with URS.
1. Specific model for different equipment is not mentioned. Elomatic denied to specify the model number unless they are
selected.
2. Software packages with license and detail information are not provided.
Page 7 of 9
BEXIMCO PHARMACEUTICALS LIMITED
TONGI, GAZIPUR
2.5. Chiller, Cooling Tower and Chilled Water Distribution Observations' Summary
Telstar
Cord-01 (Clean Air
Innovation)
Cord-02
(ConfidenceTrading
Limited)
QTS
Elomatic
Brownfield
1. Telstar quoted at the end of Excel sheet as "Telstar have reserved its' right to change the brand or country of origin in
procurement phase". We do not accept any such conditions from any vendors. But, for exceptional cases, with prior approval from
client (BPL), it can be changed.
2. Chiller is offered from China. We prefer from Europe/USA/Japan/Malaysia.
3. Specific country of origin for sand filter, valves, fittings and instruments is not mentioned.
1. Brand and country of manufacturing of expansion vessel and sand filter is not mentioned.
1. Chiller is offered from China. We prefer from Europe/USA/Japan/Malaysia.
2. Country of origin of fittings is not mentioned.
3. Electromagnetic flow switch is preferred from USA/EU origin, instead of China.
1. Excel sheet is yet to receive.
1. Brand and country of manufacturing of chiller is offered from Thermex, India; which is not equivalent to York, USA in
terms of material of construction, controlling system, longevity, performance and efficiency. As such, they didn't comply
with URS. We prefer from Europe/USA/Japan/Malaysia.
2. Cooling tower is not offered.
3. Origin of valves and electromagnetic flow switch is offered from India. We prefer from Europe/USA/Japan/Malaysia.
1. Country of manufacturing of chiller is not mentioned.
2. Expansion vessel and sand filter are not offered.
3. Origin of valves and instrumentation is India, which is not technically acceptable. We prefer from USA/EU origin.
2.6. HVAC Heating Water Generation and Distribution Observations' Summary
Telstar
Cord-01 (Clean Air
Innovation)
Cord-02
(ConfidenceTrading
Limited)
QTS
Elomatic
Brownfield
1. Telstar quoted at the end of Excel sheet as "Telstar have reserved its' right to change the brand or country of origin in
procurement phase". We do not accept any such conditions from any vendors. But, for exceptional cases, with prior approval from
client (BPL), it can be changed.
2. Specific country of origin of valves and instrumentaions isn't mentioned.
1. Brand and country of manufacturing of hot water generation plant and pumps aren't specified.
1. Country of manufacturing of pipe fittings is not specified.
2. Country of manufacturing of centrifugal pump is Indonesia. We prefer from Europe/USA/Japan.
1. Excel sheet is yet to receive.
1. Elomatic have offered hot water generation plant, expansion vessel and valves from India, which is not technically acceptable in
terms of quality and performance. We prefer from EU/USA/Japan/Malaysia.
1. Brownfield have offered hot water generation plant, pump, expansion vessel, valves and instrumentation from India, which is not
technically acceptable in terms of quality and performance. We prefer from EU/USA/Japan.
Page 8 of 9
BEXIMCO PHARMACEUTICALS LIMITED
TONGI, GAZIPUR
Recommendations of Package-02 (HVAC and Clean Room)
1. Complying with URS requirements and the deficiencies mentioned above, Telstar and Cord-01 may be selected as a short listed vendor for package 02.
2. QTS didn't provide all necessary information (Filled up Excel Sheet) needed for technical evaluation and draw conclusion.
3. Cord-02, Sunscape, Brownfield, Elomatic, Nicomac and Gusu are not recommended to be shortlisted beacuse of following major technical reasons:
a. Cord-02. DDC based HVAC control system, ramp hinged clean room doors not offered.
b. Sunscape and Evercool. DDC based HVAC control system, didn't offer special equipment (pass box, dispensing booth), chiller, cooling tower, chilled water
and HVAC heating water generation and distribution.
c. Brownfield. Didn't offer clean room, special equipment (pass box, dispensing booth), HVAC and HVAC control system. Their offered majority of the
components (valves, electromagnetic flow switch, hot water generation system, pumps, pressure gauge, pressure transmitters etc.) are from India, which is not
technically acceptable in terms of quality, performance, longevity and reliability.
d. Elomatic. Offered chiller didn't comply with URS, didn't offer cooling tower and special equipment (pass box, dispensing booth). Their offered majority of the
components (valves, electromagnetic flow switch, hot water generation system, FCU, heat exchanger etc.) are from India, which is not technically acceptable in
terms of quality, performance, longevity and reliability. Elomatic is mainly a design, consultancy and engineering firm, with very limited project execution
experience.
e. Nicomac and Gusu. Initially offered partially, later they didn't respond.
Note to Vendors: After being short listed, vendors should agree to modify the design (where needed) as per our changed layout and they should review the design
to optimize as per current scope of work.
Page 9 of 9