Standard
Title:
RTV Silicone Rubber Insulator
Coating and Shed Extender
Supplier Standard
Technology
Unique Identifier:
240-56062705
Alternative Reference Number:
TSP 41-223
Area of Applicability:
Engineering
Documentation Type:
Standard
Revision:
Total Pages:
10
Next Review Date:
November 2015
Disclosure Classification:
CONTROLLED
DISCLOSURE
Compiled by
Approved by
Authorised by
..
..
..
K. Kleinhans
K. Kleinhans
R. Cormack
Chief Engineer
Chief Engineer
Senior Manager HV Plant
Date:
Date:
Date:
Supported by TDAC
..
D. Odendaal
TDAC Chairperson
Date:
RTV Silicone Rubber Insulator Coating and Shed Extender
Supplier Standard
Unique Identifier:
Revision:
Page:
240-56062705
1
2 of 10
CONTENTS
Page
1. INTRODUCTION ...................................................................................................................................................... 3
2. SUPPORTING CLAUSES ........................................................................................................................................ 3
2.1 SCOPE .............................................................................................................................................................. 3
2.1.1 Purpose ..................................................................................................................................................... 3
2.1.2 Applicability................................................................................................................................................ 3
2.2 NORMATIVE/INFORMATIVE REFERENCES .................................................................................................. 3
2.2.1 Normative .................................................................................................................................................. 3
2.2.2 Informative ................................................................................................................................................. 3
2.3 DEFINITIONS .................................................................................................................................................... 3
2.3.1 Disclosure Classification ........................................................................................................................... 5
2.4 ABBREVIATIONS .............................................................................................................................................. 5
2.5 ROLES AND RESPONSIBILITIES .................................................................................................................... 5
2.6 PROCESS FOR MONITORING ........................................................................................................................ 5
2.7 RELATED/SUPPORTING DOCUMENTS ......................................................................................................... 5
3. RTV SILICONE RUBBER INSULATOR COATING AND SHED EXTENDER SUPPLIER STANDARD ............... 5
3.1.1 Substation Insulation Evaluation/Site Severity Assessment by Eskom ................................................. 5
3.1.2 Product Approval ....................................................................................................................................... 6
3.1.3 Shed Extenders ......................................................................................................................................... 6
3.1.4 Application of RTV Silicone Rubber Coatings and Shed Extenders ......................................................... 6
3.1.5 Life Expectancy ......................................................................................................................................... 7
3.1.6 Tests .......................................................................................................................................................... 7
3.2 MARKING, LABELING AND PACKAGING ....................................................................................................... 7
3.3 SPARES ............................................................................................................................................................ 7
3.4 KEYWORDS ...................................................................................................................................................... 7
4. AUTHORISATION .................................................................................................................................................... 7
5. REVISIONS .............................................................................................................................................................. 8
6. DEVELOPMENT TEAM ........................................................................................................................................... 8
7. ACKNOWLEDGEMENTS ........................................................................................................................................ 8
APPENDIX A : SCHEDULE A/B: DETAILS OF ESKOMS TECHNICAL REQUIREMENTS .................................... 9
APPENDIX B : SUBSTATION INSULATION ASSESSMENT CHECKLIST ............................................................ 10
FIGURES
Figure 1: Insulator Shed Parameters............................................................................................................................ 4
CONTROLLED DISCLOSURE
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
RTV Silicone Rubber Insulator Coating and Shed Extender
Supplier Standard
Unique Identifier:
Revision:
Page:
240-56062705
1
3 of 10
1. INTRODUCTION
This specification outlines the requirements for room temperature vulcanized (RTV) silicone rubber
coatings and shed extenders for application on ceramic HV equipment insulation in Eskom substations
for the purpose of upgrading and hence improving their pollution performance.
2. SUPPORTING CLAUSES
2.1 SCOPE
2.1.1 Purpose
This specification sets out Eskoms minimum requirements for RTV silicone rubber insulator coatings
and shed extenders for application on ceramic insulation in Eskom substations.
2.1.2 Applicability
This document shall apply throughout Eskom Holdings Limited Divisions.
2.2 NORMATIVE/INFORMATIVE REFERENCES
Parties using this document shall apply the most recent edition of the documents listed below (list the
references below):
2.2.1 Normative
International document(s):
[1]
IEC 60815, Guide for the Selection of Insulators in Respect of Polluted Conditions,1986.
[2]
IEC 62073, Guidance on the Measurement of Wettability of Insulator Surfaces, 2003
Eskom National document(s):
[3]
32-9: Definition of Eskom documents.
[4]
32-644: Eskom documentation management standard.
[5]
474-65: Operating Manual of the Steering Committee of Wires Technologies (SCOWT)
Eskom Divisional documents(s):
[6]
240-56063877, RTV Silicone Rubber Insulator Coating and Shed Extender Application
Specification, Eskom Transmission.
[7]
SCSASABI7, Standard for the Maintenance of Insulators, Eskom Distribution.
[8]
TRMASADL3, Pollution Mitigation Techniques for Transmission Substation Ceramic Outdoor
Insulation, Eskom Transmission.
2.2.2 Informative
None
2.3 DEFINITIONS
Definition
Description
Arcing distance
Shortest distance in air external to the insulator between metallic parts which
normally have the operating voltage between them. Note: The term dry
arcing distance is also used.
CONTROLLED DISCLOSURE
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
RTV Silicone Rubber Insulator Coating and Shed Extender
Supplier Standard
Unique Identifier:
Revision:
Page:
240-56062705
1
4 of 10
Definition
Description
Creepage distance
The shortest distance, or sum of the shortest distances, along the surface of
an insulator between those parts which normally have the operating voltage
between them. Note: Only the insulating dielectric should be measured (end
fittings are excluded).
Creepage factor
Is the creepage distance divided by the arcing distance of the insulator.
Hydrophobicity
Relates to the wettability of an insulating surface. Hydrophobic and
hydrophilic describe the two extreme levels of wettability of a surface by
water. A hydrophobic surface has low surface tension and is water-repellent.
The opposite of this is a hydrophilic surface, which has a high surface tension
and is thus wetted by water (in the form of a film). The actual wetting
appearance on the insulator is identified according to one of seven wettability
classes (WC 1 to WC 7), as per IEC 62073.
Insulator
A device intended for electrical insulation and mechanical fixing of equipment
or conductors which are subject to potential differences.
Insulator Set
An assembly of one or more insulator strings suitably connected together,
complete with fixing and protective devices as required in service.
Intershed spacing-to-projection
ratio
Defined as the ratio of S/P, where:
P, P1, P2 = Shed projection and represents the horizontal distance measured
from the rod to the end of the shed.
S = Shed spacing, which is the vertical distance between two similar points of
successive sheds.
Figure 1: Insulator Shed Parameters
Room Temperature Vulcanised
(RTV) silicone rubber insulator
coating
A hydrophobic (water repellent) compound system which typically consists of
a base silicone polymer, alumina trihydrate or alternative fillers for increased
tracking and erosion resistance, a catalyst, reinforcing filler or a pigment and
a cross linking agent.
Shed extender
A polymeric disc-shaped device which is attached to the perimeters of an
insulator shed, thus changing the profile and creepage distance of the
insulator.
Specific creepage distance
(mm/kV)
The specific creepage distance is defined as the total creepage distance
divided by the highest phase to phase system voltage (Umax).
Unified creepage distance
(mm/kV)
The unified creepage distance is defined as the total creepage distance
divided by the highest phase to earth system voltage (Umax).
CONTROLLED DISCLOSURE
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
RTV Silicone Rubber Insulator Coating and Shed Extender
Supplier Standard
Unique Identifier:
Revision:
Page:
240-56062705
1
5 of 10
2.3.1 Disclosure Classification
Controlled Disclosure: Controlled Disclosure To External Parties (either enforced by law, or
discretionary).
2.4 ABBREVIATIONS
Abbreviation
HV
Description
High Voltage
IEC
International Electrotechnical Commission
IEEE
Institute of Electrical and Electronics Engineers
QITP
Quality Inspection Test Plan
RTV
Room Temperature Vulcanized
SCD
Specific Creepage Distance
USCD
Unified Specific Creepage Distance
2.5 ROLES AND RESPONSIBILITIES
None
2.6 PROCESS FOR MONITORING
None
2.7 RELATED/SUPPORTING DOCUMENTS
None
3. RTV SILICONE RUBBER INSULATOR COATING AND SHED EXTENDER SUPPLIER
STANDARD
3.1.1 Substation Insulation Evaluation/Site Severity Assessment by Eskom
The following information, specific to each substation where insulation is to be upgraded, shall be
supplied to the product supplier by Eskom for tender purposes. This will be done in accordance to IEC
60815 and the insulation assessment checklist (see Addendum). Items to be noted per insulator product
include:
Photograph and/or drawing of each insulator product to be upgraded
Condition of existing insulator surface
Insulation material
Shed profile
Creepage distance
Dry arcing distance
Diameter of insulator trunk and sheds
Surface area of insulator (to be calculated by supplier)
Intershed spacing
CONTROLLED DISCLOSURE
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
RTV Silicone Rubber Insulator Coating and Shed Extender
Supplier Standard
Unique Identifier:
Revision:
Page:
240-56062705
1
6 of 10
Shed projection
Site severity pollution level of substation (if previously measured)
3.1.2 Product Approval
a. Only RTV silicone rubber coatings and shed extenders that have been technically evaluated by
Eskom are permitted for use.
b. Suppliers shall provide proof, in the form of a test certificate, that their products have been tested in
accordance with IEC 587 Class 1A 4.5.
c.
Eskom reserves the right to perform in-house testing using its test facilities as part of product
evaluation.
d. Suppliers shall provide Eskom with information on the service experience of their products.
Information supplied as such shall be verifiable. Therefore, suppliers shall supply Eskom with the
names and contact details of utilities where their products have been applied.
3.1.3 Shed Extenders
a. The need for shed extenders shall be determined by the supplier on the basis of information
supplied to him by Eskom for tender purposes. The quantity and placement of shed extenders must
be such that the Eskom required minimum creepage distance is attained, and comply with all the
requirements as stipulated in IEC 60815 and Section 2.4 of 240-56063877.The position of the shed
extenders shall be indicated in the applicators QITP.
Note: The insulator with installed shed extenders shall fully comply with IEC 60815. However, a
minimum shed spacing to projection ratio of 0.5 and a maximum creepage factor of 4 will be accepted.
b.
The entire porcelain and shed extender surfaces need to be coated with an Eskom approved RTV
silicone rubber coating.
3.1.4 Application of RTV Silicone Rubber Coatings and Shed Extenders
In addition to the requirements herein, the applicator is to apply the guidelines as outlined in 24056063877. The position of all shed extenders shall be approved by Eskom prior installation
a. Prior to application of an RTV silicone rubber coating onto a ceramic insulator, the surface must be
cleaned and de-greased with a suitable de-greaser. The de-greasing material used should be an
environmentally friendly product and should have the following characteristics:
Non-corrosive
Should not leave a conductive layer on the insulator surface
Should not damage the insulator surface and surrounding hardware
b. After cleaning, the insulators must be rinsed thoroughly to ensure no conductive residue remains on
the surface.
c.
Cleaning and degreasing agents used should not damage the porcelain, metalware, galvanising or
cementing materials.
d. Cleaning should include removal of all conductive contaminants and loose material on the ceramic
surface.
e. All surfaces are to be RTV silicone rubber coated including the breaker chamber porcelains of circuit
breakers.
CONTROLLED DISCLOSURE
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
RTV Silicone Rubber Insulator Coating and Shed Extender
Supplier Standard
f.
Unique Identifier:
Revision:
Page:
240-56062705
1
7 of 10
RTV silicone rubber coating shall be applied by supplier accredited persons, in accordance with
supplier specifications.
g. Shed extenders, where necessary, shall be installed by supplier accredited persons according to the
manufacturers installation procedure.
3.1.5 Life Expectancy
The life expectancy for both the RTV silicone rubber coating and shed extenders, where applicable,
should be 15 years.
3.1.6 Tests
Hydrophobicity test
Coating Thickness test
3.2 MARKING, LABELING AND PACKAGING
None
3.3 SPARES
None
3.4 KEYWORDS
RTV Silicone, Rubber, Insulator, Shed Extender, supplier
4. AUTHORISATION
This document has been seen and accepted by:
Name & Surname
Designation
This Document has been approved by TDAC ROD 13 February 2013
CONTROLLED DISCLOSURE
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
RTV Silicone Rubber Insulator Coating and Shed Extender
Supplier Standard
Unique Identifier:
Revision:
Page:
240-56062705
1
8 of 10
5. REVISIONS
Date
Rev.
Compiler
Remarks
November 2012
K. Kleinhans
Draft Document for Review created from TSP 41-223
June 2013
K. Kleinhans
Final Document for Publication
6. DEVELOPMENT TEAM
The following people were involved in the development of this document:
Kevin Kleinhans
Technology
Lester Geldenhuis
Transmission
Dr. Wallace Vosloo
Resources and Strategy Division
Raphael Swinny
Resources and Strategy Division
7. ACKNOWLEDGEMENTS
None
CONTROLLED DISCLOSURE
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
RTV Silicone Rubber Insulator Coating and Shed Extender
Supplier Standard
Unique Identifier:
Revision:
Page:
240-56062705
1
9 of 10
APPENDIX A: SCHEDULE A/B: DETAILS OF ESKOMS TECHNICAL REQUIREMENTS
Item
number
Description
Schedule A
Eskoms minimum
requirements
1.
1.1
1.2
Coating
Coating material
Minimum coating thickness (dry)
2.
2.1
2.2
2.3
2.4
3
Shed extenders (if required)
Shed material
Shed profile
Minimum shed thickness
Adhesive material
Degreasing material (if required)
Primer material (if required)
Silicone based
Aerodynamic
3mm
Silicone based
Eskom approved (toluene),
compliant with SABS 1365
Spraying preferred.
Method of application of coating
WC 1
Hydrophobicity (IEC 62073)
Cleaning of existing insulation
Schedule B
Equipment
Guarantees and
Particulars.
Silicone based
0.3mm
CONTROLLED DISCLOSURE
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
RTV Silicone Rubber Insulator Coating and Shed Extender
Supplier Standard
Unique Identifier:
Revision:
Page:
240-56062705
1
10 of 10
APPENDIX B: SUBSTATION INSULATION ASSESSMENT CHECKLIST
Addendum: Substation Insulation Assessment Checklist (checklist to be completed for each insulator
component of the HV equipment, where applicable)
Substation Insulation Assessment Checklist
Substation
Bay
Phase (R, W or B)
Equipment / item
System maximum voltage (Umax) (kV)
Insulator component type
Number of insulator components in series per phase (Insulator Set)
Material
Condition of insulator surface
Creepage from top to first shed (mm)
Creepage per shed pair (mm)
Number of shed pairs per insulator component
Creepage from bottom to last shed pair (mm)
Creepage distance (mm) per insulator component
Total creepage distance (mm) of insulator components in series per phase
Dry arcing distance (mm) per insulator component
Total dry arcing distance (mm) of insulator components in series per phase
Alternating sheds (Yes/no)
Under ribs present (Yes/no)
Number of Large sheds
Large shed projection (mm)
Large shed circumference (mm)
Number of small sheds
Small shed projection (mm)
Small shed circumference (mm)
Large shed spacing (mm)
Minimum distance between sheds (mm)
Large shed spacing to large shed projection ratio
Trunk diameter Top (mm)
Trunk diameter Bottom (mm)
Site pollution severity level (if measured)
Additional comments:
Name:
Date:
Signature:
Note: The above checklist is an example for typical insulator types and does not cover insulators with
barrel or beehive shapes, nor non-consistent tapers or varying shed projections.