Technical Specifications:
120/240V Single Phase, pass-through kWh meter
Rated Voltage: 120/240 volts
Rated current: 5(100)A
Works with wires up to 3/8 in diameter
Pulse output impulse constant: 800imp/kWh
Range of allowable environmental conditions: Pollution Degree 2,
Measurement Category III, Altitude rating 2000 meters max. Maximum
Temperature Range: -30 Deg. C to 70 Deg. C.
The equipment is protected throughout by
double insulation as indicated by this symbol:
Accuracy Class: 1 (Fig 3)
Rated Frequency: 50Hz/60Hz
Creep: Logical design of anti-creep
Start current: 0.4% Ib. (1.0)
Power consumption: 1W (when 220V, 20A)
Tamper Detection Class 1.
Weight: 0.32kg
Outside dimensions: 78x100x65mm (Fig 1)
Safety Precautions:
Meter should be installed by a qualified electrician.
Turn o all power supplying the equipment before preforming any
installation or service. Use a volt meter to confirm power is o.
Use of this device inconsistent with this manual can cause permanent
damage to the unit and/or serious harm to the installer or operator.
Tools/Materials List:
Volt meter
Small standard screwdriver
DIN-Rail
UL Listed Type 4 Enclosure (with appropriately rated conduit and
fittings) is required if meter will be installed outdoors
Functions:
Long-term active electricity measuring without adjustment.
Meets IEC 62053-21 and IEC 62052-11 standards (static AC active meter)
Installation Instructions:
1. Use a volt meter to confirm that you have 240 volts between L1 and L2.
This meter will not function correctly unless this is the case. For 120V
systems, use our EKM-15IDS v.2, EKM-15E, or any Omnimeter model.
2. Disconnect or switch power o before attempting to install, connect,
disconnect, or service the meter. ALL POWER MUST BE TURNED OFF!
3. IMPORTANT: Distinguish and then identify the 2 hot Lines and the
neutral line. Label all 3: L1, L2, N.
4. Once the power has been turned o, pass line 1 and line 2 through the
two holes in the meter. (for a retrofit installation this may first require
disconnecting the ends of L1 and L2 from a breaker or junction box)
5. Once the wires are through the meter, the ends should be reconnected
in their original positions. On the meter, tighten down the tap screws
for each line that passes through the meter. The tap screws penetrate
the wire insulation and power the meter once the power is turned on.
6. Mount the meter using 35mm DIN Rail in a protected indoor location.
If installing outdoors, a UL Listed Type 4 Enclosure is required.
7. Once the above steps are completed, and you are ready, you can turn
the power back on and begin to read your meter.
SO
+ _
1 2 3 4 5 6
(Fig 2)
Power
factor
COS
1.0
1.0
0.5(L)
0.8(C)
0.5(L)
0.8(C)
Basic error %
Class 0.5
Class 1
Class 2
+
1.0
+
0.5
+
1.0
+
1.0
+
0.5
+
0.5
+
1.5
+
1.0
+
1.5
+
1.5
+
1.0
+
1.0
+
2.5
+
2.0
+
2.5
--+
2.0
---
(Fig 3)
120V
120V
240V
L1
1
2
3
4
5
6
L2
L1
+
SO
L2
(Fig 4)