Generator set data sheet
Model:
Frequency:
Fuel Type:
C275 D5
50
Diesel
Spec sheet:
SS8-CPGK
Noise data sheet (Open/enclosed):
ND50-OS550 / ND50-CS550
Airflow data sheet:
AF50-550
Derate data sheet (Open/enclosed):
DD50-OS550 / DD50-CS550
Transient data sheet:
TD50-550
Standby
Prime
Fuel consumption
kVA (kW)
kVA (kW)
Ratings
275 (220)
Load
1/4
1/2
3/4
Full
1/4
1/2
3/4
Full
gph
3.7
6.6
10.1
13.7
3.1
5.7
8.4
11.5
L/hr
16.7
30.0
45.8
62.5
14.2
25.8
38.3
52.5
250 (200)
Engine
Standby Rating
Engine manufacturer
Cummins
Engine model
QSL9 G5
Configuration
4 Cycle; In-line; 6 Cylinder Diesel
Prime Rating
Aspiration
Turbo Charged and Charge Air Cooled
Gross engine power output, kWm
310
268
BMEP at set rated load, kPa
2785
2413
Bore, mm
114
Stroke, mm
145
Rated speed, rpm
1500
Piston speed, m/s
7.2
Compression ratio
16.8:1
Lube oil capacity, L
26.5
Overspeed limit, rpm
1800 50
Regenerative power, kW
47
Governor type
Electronic
Starting voltage
24 Volts DC
Fuel flow
Maximum fuel flow, L/hr
165
Maximum fuel inlet restriction, mm Hg
203
Maximum fuel inlet temperature (C)
70
2012 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and Our energy working for you. are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
Document no. DS22-CPGK-RevD - 24/2/2012
Air
Standby Rating
Prime Rating
Combustion air, m 3/min
20.30
18.70
Maximum air cleaner restriction, kPa
6.2
Exhaust
Exhaust gas flow at set rated load, m3/min
53.0
44.9
Exhaust gas temperature, C
560
500
Maximum exhaust back pressure, kPa
10.2
Standard set-mounted radiator cooling
Ambient design, C
50
Fan load, KW m
10
Coolant capacity (with radiator), L
15
Cooling system air flow, m3/sec @ 12.7mmH2O
7.93
Total heat rejection, BTU/min
10190
Maximum cooling air flow static restriction mmH2O
19.1
8415
Weights*
Open
Enclosed
Unit dry weight kgs
2295
3872
Unit wet weight kgs
2347
4511
* Weights represent a set with standard features. See outline drawing for weights of other configurations
Dimensions
Length
Width
Height
Standard open set dimensions
3135
1100
1928
Enclosed set standard dimensions
4254
1424
2215
Genset outline
Open set
Enclosed set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
2012 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and Our energy working for you. are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
Document no. DS22-CPGK-RevD - 24/2/2012
Alternator data
Connection 1
Temp rise C
Duty2
Alternator
Voltage
Wye, 3 Phase
163/125
S/P
UCD274K
380-415V
WYE
125/105
S/P
HC4D
380-440V
Ratings definitions
Emergency Standby
Power (ESP)
Limited-Time running
Power (LTP):
Prime Power (PRP)
Base Load (Continuous)
Power (COP)
Applicable for supplying power to
varying electrical load for the
duration of power interruption of a
reliable utility source. Emergency
Standby Power (ESP) is in
accordance with ISO 8528. Fuel
Stop power in accordance with ISO
3046, AS 2789, DIN 6271 and BS
5514.
Applicable for supplying power to a
constant electrical load for limited
hours. Limited Time Running Power
(LTP) is in accordance with ISO
8528.
Applicable for supplying power to
varying electrical load for unlimited
hours. Prime Power (PRP) is in
accordance with ISO 8528. Ten
percent overload capability is
available in accordance with ISO
3046, AS 2789, DIN 6271 and BS
5514.
Applicable for supplying power
continuously to a constant electrical
load for unlimited hours. Continuous
Power (COP) in accordance with ISO
8528, ISO 3046, AS 2789, DIN 6271
and BS 5514.
Formulas for calculating full load currents:
Three phase output
kWx1000
Voltagex1. 73x0.8
Single phase output
kWxSingleP haseFactor x1000
Voltage
See your distributor for more information.
Cummins Power Generation
Manston Park, Columbus Avenue
Manston, Ramsgate
Kent CT12 5BF, UK
Telephone: +44 (0) 1843 255000
Fax: +44 (0) 1843 255902
E-Mail:
[email protected]Web: www.cumminspower.com
2012 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and Our energy working for you. are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
Document no. DS22-CPGK-RevD - 24/2/2012