0% found this document useful (0 votes)
109 views1 page

Motor Test Report for Engineers

This document provides a test report for a 3-phase electric motor. It includes specifications such as voltage, frequency, power output, efficiency class, temperature measurements, and test results. Key details include: - Motor type: 3~Motor, 22kW output, 1480 rpm, insulation class F, IP55 protection. - Testing included no load test, locked rotor test, overload tests at 130% voltage and 160% current, and thermal test at rated load up to 93% efficiency. - Temperature measurements taken of stator winding, frame, and bearing during thermal test were within specified limits. - Tests were carried out according to IEC 60034 standards and manufacturer certified motor meets efficiency

Uploaded by

suinpe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
109 views1 page

Motor Test Report for Engineers

This document provides a test report for a 3-phase electric motor. It includes specifications such as voltage, frequency, power output, efficiency class, temperature measurements, and test results. Key details include: - Motor type: 3~Motor, 22kW output, 1480 rpm, insulation class F, IP55 protection. - Testing included no load test, locked rotor test, overload tests at 130% voltage and 160% current, and thermal test at rated load up to 93% efficiency. - Temperature measurements taken of stator winding, frame, and bearing during thermal test were within specified limits. - Tests were carried out according to IEC 60034 standards and manufacturer certified motor meets efficiency

Uploaded by

suinpe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Date of issue:

1.9.2015

Type Test Report


Serial No.:
Customer:
Type:
Product Code:

M3AA 180MLB 4
3GAA182420-ADK

Customer ref.:
Rating:
V
690
400
660
380
415
460

3~Motor
Insul.cl.F
IP55

Y
D
Y
D
D
D

Hz
50
50
50
50
50
60

kW
22,0
22,0
22,0
22,0
22,0
22,0

r/min
1480
1480
1477
1477
1482
1783

cos j
0,82
0,82
0,84
0,84
0,80
0,82

A
24,1
41,5
42,7
42,7
40,9
35,8

Duty
S1
S1
S1
S1
S1
S1

Eff class IE3


50Hz :
60Hz :
Resistance
Line
U1 - V1
U1 - W 1
V1 - W 1

Ambient:
0,1964
0,1952
0,1953

IE3 - 93,3(100%) - 94,1(75%) - 94,1(50%)


IE3 - 93,8(100%)

22,4 C
W
W
W

Insulation resistance at
R > 2000 Mohm

High-voltage test winding

Test

Torque
[Nm]

No load test
Locked rotor test

Line
U[V]
401,2
80,7

Overload
Volt.
130 %
Curr.
160 %
Speed 120 %

1000 V

D
D

f[Hz]
50
50

Input
I[A]
15,3
41,8

P1 [kW]
0,50
1,80

2400 V

60 s

Output
P2 [kW] n[r/min]
1500

cos j
0,05
0,31

h [%]

Thermal test ( 100% load )

141,7

400

50

41,3

23,70

22,00

1482

0,83

93,00

Partial load points:


~75% load
~50% load
~25% load

105,8
70,3
35,1

400
400
400

D
D
D

50
50
50

32,4
24,5
18,2

17,60
11,80
6,10

16,50
11,00
5,50

1489
1493
1498

0,79
0,69
0,48

93,60
93,30
90,40

[oC]

[K]
62,8

Temperature rise at rated load.


Stator winding :
Frame :
Bearing D-end :

64
67

Method
1
2
2

Ambient Temperature :

25

Measurement method
1 Resistance
2 Thermometer
3 Thermocouples

These tests have been carried out on motor no. 3GV13 11256351 001 , on date 2013-10-02
which is identical in electrical design with the above.

Manufactured and tested in accordance with rules of IEC 60034-1 and IEC 60034-2-1.
PLL determined from residual loss.
On behalf of customer
On behalf of manufacturer

Date of test
Telephone

Tested by ABB AB, LV Motors, 721 70 Vsters, Sweden


Computer print-out valid without signature.

ABB, Motors and Generators


www abb.com/motors&generators

Telefax

+46 (0)21 32 90 00
+46 (0)21 32 90 22

60s