Instrument transformers | Outdoor medium voltage
1. CURRENT TRANSFORMERS
Dry insulation
Instrument transformers | Outdoor medium voltage
OUTDOOR MEDIUM VOLTAGE TRANSFORMERS > Current transformers
INTRODUCTION
Current transformers are designed to provide
a scaled down replica of the current in the MV
line and isolate the measuring instruments,
meters, relays, etc. from the power circuit.
CR model transformers with epoxy resin
internal insulation, cycloaliphatic resin
external insulation and active parts located
in the central part of the transformer. Up
to 72.5 kV.
CE model transformers with epoxy resin
internal insulation, cycloaliphatic resin
external insulation and active parts located
in the top part of the transformer. Up to
72.5 kV.
CX model transformers with epoxy resin
internal insulation, porcelain or silicone
rubber external insulation and active
parts located in the central part of the
transformer. Up to 72.5 kV.
CPE model transformers with epoxy
resin internal insulation, cycloaliphatic
resin external insulation and active parts
located around the pass-through primary
conductor. Up to 36 kV.
Model CX
Model CX up t
o 72,5 kV.
Model CR
Model CE
Model CR up to 72,5 kV.
Model CPE
Model CE up to 72,5 kV.
Model CPE up to 36 kV.
5
Instrument transformers | Outdoor medium voltage
OUTDOOR MEDIUM VOLTAGE TRANSFORMERS > Current transformers
SECTIONS
1. Primary terminals.
2. Equipotential ring.
3. Porcelain or silicone rubber insulator
4. Cycloaliphatic resin insulator.
5.
6.
7.
8.
Epoxy resin.
Primary windings.
Cores and secondary windings.
Secondary terminal box.
1
2
3
4
5
6
Model CX
Model CR
36 kV Current
transformers (CR).
Electronet Services.
(New Zealand)
Instrument transformers | Outdoor medium voltage
OUTDOOR MEDIUM VOLTAGE TRANSFORMERS > Current transformers
APPLICATIONS
Current transformers for outdoor service have
several applications.
Examples of applications:
1. Revenue metering.
2. Protection for substations and distribution
lines.
3. Protection for power transformers.
4.Protection for capacitor banks.
24 kV Current
transformers (CX).
protection for
substation. Iberdrola
(Spain).
5. Outdoor-outdoor wall bushings (model CPE).
36 kV Current
transformers (CR) and
voltage transformers
(UR). Revenue
metering. Electronet
Services (New
Zealand).
72.5 kV Current
transformer (CX)
used for wind farm
substation protection.
Iberdrola (Spain)
7
Instrument transformers | Outdoor medium voltage
OUTDOOR MEDIUM VOLTAGE TRANSFORMERS > Current transformers
DESIGN AND MANUFACTURE
ARTECHE current transformers with dry
insulation are vacuum cast with epoxy resin,
which x and isolates the active parts, creating
a rigid body with high mechanical resistance,
excellent thermal performance and dielectric
withstand capability.
CR, CE and CPE models are housed in a
cycloaliphatic resin body. This insulator
provides for long creepage distance, robust
mechanical strength, excellent arc tracking
properties and resistance to UV exposure.
CX models have a resin body inside a hollow
porcelain or silicone rubber insulator which
provides for long creepage distance and
superior resistance to the elements. The
chamber between the resin body and the
insulator is hermetically sealed with nitrile
rubber gaskets; this space is lled with oil for
insulation levels above 36 kV.
For CE models, the active parts are located
in the top part of the transformer, which is
coated with an external metallic layer for a
better electrical eld control.
For CPE models, the active parts form a toroidal
transformer around the primary conductor.
Its a wall bushing current transformer with or
without integrated primary bar.
The active parts in models CR and CX are
located approximately in the center of the
resin body.
For all models, the secondary outputs are
located in the bottom part. Rings or deector
shields are used to properly distribute the
electrical eld throughout the insulator.
THE ELECTRICAL FIELD IN A CURRENT TRANSFORMER
WITHOUT EQUIPOTENTIAL RING
0,6
0,7
0,8
WITH EQUIPOTENTIAL RING
0,9 0,9
0,8
0,5
The equipotential ring signicantly extends
the service life of the transformer by
preventing the deterioration of the resin
in the transformer head because the ring
prevents the resin from bei
ng subjected to
0,4
0,7
0,6
0,5
0,3
0,4
0,3
0,2
any potential gradient. This can be seen in
the gure included here, which shows the
distribution of the eld lines with or without
equipotential ring.
This equipotential ring is a standard accessory
in all ARTECHE MV Current transformers
with either cycloaliphatic resin, porcelain or
silicone rubber insulation.
0,2
0,1
0,1
Instrument transformers | Outdoor medium voltage
OUTDOOR MEDIUM VOLTAGE TRANSFORMERS > Current transformers
ADVANTAGES
Variety of designs for greater adaptation to
client needs.
Cast in high dielectric strength resin.
Very high and invariable accuracy (up to
0.1%) for the service life of the equipment.
Ratio change by primary or the secondary
tapping.
Primary winding with spark gap for
overvoltage protection (CX, CR).
Compliance with a wide range of creepage
distances,
depending
on customer
specications.
Excellent response under extreme weather
conditions such as temperatures of -55C
or +50C; UV radiation; altitudes over 1000
m.a.s.l., saline or polluted environments,
earthquakes, seismic hazard areas, etc
Compact design for easy handling.
May be transported, stored and installed
vertically or horizontally.
OPTIONS:
Wide range of primary and secondary
terminals.
Brown or gray insulators.
Porcelain or silicone rubber insulators
(model CX).
Sealable secondary box.
Corrosion-resistant metallic components,
and stainless steel washers, nuts and bolts.
Different cable glands available in the
secondary terminal box.
Maintenance free. No spare parts needed
throughout its lifespan.
The materials used for construction are
recyclable and resistant to the elements,
adhering to environmental regulations.
Each transformer is routine tested for partial
discharges, tangent delta (DDF), insulation
and accuracy. Designed to withstand all the
type test included in the standards.
Compliance to any international standard:
IEC, IEEE, UNE, BS, VDE, SS, CAN, AS, NBR,
JIS, GOST, NF and others.
Officially homologated In-house testing
facilities.
con
tor.
Detail of cable
glands designed
based on customer
Wide range of
Detail of the spark gap
primary terminals.
in a CX for protecting
the primary winding.
specications.
9
Instrument transformers | Outdoor medium voltage
OUTDOOR MEDIUM VOLTAGE TRANSFORMERS > Current transformers
RANGE
ARTECHE current transformers with dry
insulation are named using three letters and
two numbers, which indicate their maximum
service voltage.
The rst two letters indicate the type of
transformer and the third letter indicates
the model within the product line. Current
transformers are named using the letters CX
(porcelain or silicone rubber insulator), CR
(cycloaliphatic resin insulation), CE (inverted,
cycloaliphatic resin insulation) or CPE
(cycloaliphatic resin insulation with toroidal
transformer).
Current ratios: all types of combinations
possible in a single device. Secondary
windings for:
Protection: all protection types, including:
low induction linear cores, etc.
Metering: accuracy classes for any type of
metering and billing (including extra-high
accuracy class 0.1 / 0.15 with extended
current range).
Number of secondary windings: as per
customer needs, up to 4 secondary windings
are possible in a single device.
The following tables show the range currently
available. These characteristics are merely
indicative; ARTECHE can manufacture these
transformers to comply with any domestic or
international standard.
H
H
T
A
Fig. 2 - Models CX / CR
Fig. 3 - Model CPE
Fig. 1 - Model CE
Fig.
10
Instrument transformers | Outdoor medium voltage
OUTDOOR MEDIUM VOLTAGE TRANSFORMERS > Current transformers
Current transformers
Model
Highest
voltage
(kV)
Rated insulation level
Power
Lightning
frequency
(kV)
Impulse
(kVp)
Standard
creepage
distance
(mm)
Dimensions
(mm)
B
(mm)
H
(mm)
Weight
(kg)
Cycloaliphatic resin insulation
CRB-17
17.5
38
95
420
219
254
335
22
CRE-17
17.5
38
95
440
219
254
300
35
CRB-24
24
50
125
590
219
254
371
24
CRE-24
24
50
125
620
219
254
370
40
CRF-24
24
50
125
810
219
254
370
45
CRE-36
36
70
170
925
219
254
475
45
CRF-36
36
70
170
915
219
254
440
50
CRH-36
36
70
170
1250
250
250
625
115
CRK-36
36
70
170
1135
350
350
551
146
CRH-52
52
90
250
1785
250
250
797
135
CRK-52
52
90
250
1815
350
350
690
185
CRH-72
72.5
140
325
1785
250
250
797
135
CRK-72
72.5
140
325
1815
350
350
877
235
CE-034
36
70
170
920
250
250
1135/855*
265
CE-046
52
90
250
1300
250
250
1340/1070*
270
CE-069
72.5
140
325
1815
350
350
1576/1305*
350
Porcelain or silicone rubber insulation
CXD-24
24
50
125
744
210
210
462
43
CXE-36
36
70
170
900
250
250
532
80
CXE-52
52
90
250
1440
250
250
712
111
CXG-52
52
90
250
1560
250
250
798
186
CXH-52
52
90
250
1560
330
330
800
263
CXG-72
72.5
140
325
1860
250
250
918
190
CXH-72
72.5
140
325
1860
330
330
920
305
Cycloaliphatic insulation
CPE-36
36
70
170
1080
500
460
1395
270
* T dimension.
Approximate dimensions and weights. For special requirements, please consult.
72,5 kV Current
transformer (CX).
Yuandon Textil Co.
(Taiwan).
72,5 kV Current
transformer (CX). Nuon
(the Netherlands).
11
Instrument transformers | Outdoor medium voltage
2. INDUCTIVE VOLTAGE
TRANSFORMERS
Dry and oil-paper insulation
12
Instrument transformers | Outdoor medium voltage
OUTDOOR MEDIUM VOLTAGE TRANSFORMERS > Voltage transformers
INTRODUCTION
Inductive voltage transformers are designed
to provide a scaled down replica of the voltage
in the MV line and isolate the measuring
instruments, meters, relays, etc. from the
power circuit.
UR model are single-phase transformers
with epoxy resin internal insulation and
cycloaliphatic resin external insulation. Up
to 72.5 kV.
VR model are two-phase transformers
with epoxy resin internal insulation and
cycloaliphatic resin external insulation. Up
to 52 kV.
UJ model are single-phase transformers
with epoxy resin internal insulation, a
metal-covered main body and silicone
rubber insulators. Up to 36 kV.
VJ model are two-phase transformers with
epoxy resin internal insulation, a metalcovered main body and silicone rubber
insulators. Up to 36 kV.
UZ and UT model are single-phase
transformers with oil-paper internal
insulation and porcelain or silicone rubber
insulators. Up to 72 kV.
VZ model single-phase transformers with
oil-paper internal insulation and porcelain
or silicone rubber insulators. Up to 36 kV.
Model UR
Model VZK
Model VJ
Model UTB
Models UR/UT up to 72,5 kV.
Model VR up to 52 kV.
Models UJ/VJ up to 36 kV.
Models UZK/VZK up to 36 kV.
SECTION
5
6
7
6.
7.
Secondary windings.
Magnetic core.
Model VZK
13
Instrument transformers | Outdoor medium voltage
OUTDOOR MEDIUM VOLTAGE TRANSFORMERS > Voltage transformers
APPLICATIONS
Voltage transformers for outdoor service have
several applications.
Examples of applications:
1. Revenue metering.
2. Protection for substations and distribution
lines.
3. Protection for capacitor banks.
4. Discharge of lines and capacitor banks.
72.5 kV Current
transformers (CX) and
voltage transformers
(UT) for power
transformer protection.
Iberdrola (Spain).
5. Power supply for auxiliary services.
6. Power supply for switching equipment
in distribution automation (reclosers,
disconnects or switches).
24 kV Voltage
1.
2.
3.
4.
5.
Primary terminals.
Porcelain or silicone rubber insulator.
Oil-paper insulation.
Secondary terminal box.
Primary windings.
transformers
(VJ). Auxiliary
power supply for
switching equipment
in distribution
automation.
36 kV Current
transformers (CR) and
voltage transformers
(UR). Revenue
metering. Electronet
Services (New
Zealand).
ARTECHE instrument
transformers are installed
in over 150 countries.
14
Instrument transformers | Outdoor medium voltage
OUTDOOR MEDIUM VOLTAGE TRANSFORMERS > Voltage transformers
DESIGN AND MANUFACTURE
ARTECHE voltage transformers with dry
insulation are vacuum cast with epoxy
resin, which x and isolates the active parts,
creating a rigid body with high mechanical
resistance, excellent thermal performance
and dielectric withstand capability.
UR/VR models are housed in a cycloaliphatic
resin body. This insulator provides for long
creepage
distance, robust mechanical
strength, excellent arc tracking properties and
resistance to UV exposure.
72.5 kV UT
UJ/VJ have their resin body coated with a
grounded external metallic layer to control
their electrical elds. The pole(s) have external
silicone rubber insulation with superior
resistance to the elements.
Transformers
Panama.
36 kV UZK
.
Transformers
Transpower.
(New Zealan
d).
ARTECHEs voltage transformers with oilpaper insulation (UZ/VZ, UT) have their core
and windings (active parts) inside a metal
tank. The internal insulation is made by oil
impregnated paper. The external insulator
may be porcelain or silicone rubber. The
voltage transformer is hermetically sealed.
The U models have one single pole for phaseearth connections while the V models have
two poles for phase-phase connection.
Instrum
ent tran
sformer
s | Outd
oor med
ium volt
age
15
OUTDOOR MEDIUM VOLTAGE TRANSFORMERS > Voltage transformers
ADVANTAGES
Variety of designs for greater adaptation to
client needs.
Cast in high dielectric strength resin (UR/
VR, UJ/VJ).
Very high exact and invariable accuracy
(up to 0.1%) for the service life of the
equipment.
Option for double primary ratio.
Compliance with a wide range of creepage
distances,
depending
on customer
specications.
Excellent response under extreme weather
conditions such as temperatures of -55C
or +50C; UV radiation; altitudes over 1000
m.a.s.l., saline or polluted environments,
earthquakes, seismic hazard areas, etc
Compact design for easy handling.
May be transported, stored and installed
vertically or horizontally.
Maintenance free. No spare parts needed
throughout its lifespan.
The materials used for construction are
recyclable and resistant to the elements,
adhering to environmental regulations.
Each transformer is routine tested for partial
discharges, tangent delta (DDF), insulation
and accuracy. Designed to withstand all the
type test included in the standards.
Compliance to any international standard:
IEC, IEEE, UNE, BS, VDE, SS, CAN, AS, NBR,
JIS, GOST, NF and others.
Officially homologated In-house testing
facilities.
OPTIONS:
Wide range of primary and secondary
terminals.
Brown or gray insulators.
Porcelain or silicone rubber insulators
(models UZ/VZ, UT).
Sealable secondary box.
Corrosion-resistant metallic components,
and stainless steel washers, nuts and bolts.
Different cable glands available in the
secondary terminal box.
Oil sampling valve for periodic analysis
(models UZ/VZ, UT).
Detail of cable
glands designed
based on customer
specications.
36 kV Voltage
transformers (URS)
installed horizontally.
Oil sampling valve
for quick and safe
operation.
16
Instrument transformers | Outdoor medium voltage
ARTECHE transformers
are installed in over 150
countries.
OUTDOOR MEDIUM VOLTAGE TRANSFORMERS > Voltage transformers
RANGE
ARTECHE voltage transformers with dry or
oil-paper insulation are named using three
letters and two numbers, which indicate their
maximum service voltage.
The rst two letters indicate the type of
transformer and the third letter indicates the
model within the product line.
Voltage transformers with the letters VR, VJ or
VZ are for phase-phase connections; and those
with UR, UJ, UZ or UT are for phase-earth.
Standard accuracy classes and burdens:
In accordance with IEC standards:
100 VA Class 0.2 / 3P
250 VA Class 0.5 / 3P
In accordance with IEEE standards:
0.3 WXYZ
1.2 WXYZ, ZZ
Higher accuracy classes and burdens available.
The following tables show the range currently
available. These characteristics are merely
indicative; ARTECHE can manufacture these
transformers to comply with any domestic or
international standard.
A
A
Fig. 5 - Model UR
Fig. 6 - Model VR
Fig. 7 - Model UJ
Fig. 8 - Model VJ
H
Fig.
A
A
Fig. 11 - Model UT
Fig. 10 - Model VZK
Fig. 9 - Model UZK
18
Instrument transformers | Outdoor medium voltage
OUTDOOR MEDIUM VOLTAGE TRANSFORMERS > Voltage transformers
Voltage transformers
Model
Highest
voltage
(kV)
Rated insulation level
Power
Lightning
frequency
(kV)
Impulse
(kVp)
Standard
creepage
distance
(mm)
Thermal
burden
(VA)
Dimensions
(mm)
B
(mm)
H
(mm)
Weight
(kg)
Cycloaliphatic resin insulation
URJ-17
17.5
38
95
550
400
254
219
453
41
URL-17
17.5
38
95
545
450
254
219
453
33
URN-17
17.5
38
95
570
1500
254
219
500
55
URJ-24
24
50
125
910
400
254
219
575
43
35
URL-24
24
50
125
765
450
254
219
533
URN-24
24
50
125
800
600
254
219
570
57
URN-36
36
70
170
1340
600
254
219
708
60
URS-36
36
70
170
1260
1500
350
200
715
68
URU-52
52
90
250
1640
2500
500
400
1030
152
URU-72
72.5
140
325
2360
2500
500
400
1130
173
VRJ-17
17.5
38
95
615
400
254
219
450
43
VRL-17
17.5
38
95
610
600
254
219
435
38
VRN-17
17.5
38
95
620
1500
254
219
570
59
VRJ-24
24
50
125
955
750
254
219
560
45
VRL-24
24
50
125
955
750
254
219
515
40
VRN-24
24
50
125
790
750
254
219
570
59
VRN-36
36
70
170
1055
750
254
219
630
60
VRS-36
36
70
170
1140
1500
350
200
696
83
VRU-52
52
90
250
1552
4000
500
400
986
179
Silicone rubber insulation
UJL-24
24
50
125
760
450
220
320
565
UJN-36
36
70
170
1360
600
220
320
787
49
85
VJL-24
24
50
125
760
500
220
320
550
60
VJN-36
36
70
170
1360
600
220
320
765
100
17.5
38
95
790
1500
300
300
970
85
85
Oil-paper insulation
UZK-17
UZK-24
24
50
125
790
1500
300
300
970
UZK-36
36
70
170
790
1500
300
300
970
85
UTB-52
52
90
250
2355
1500
11
300
300
1340
100
UTD-52
52
90
250
2355
2500
11
300
300
1410
150
100
UTB-72
72.5
140
325
2355
1500
11
300
300
1340
UTD-72
72.5
140
325
2355
2500
11
300
300
1410
150
UTE-72
72.5
140
325
2355
3000
11
450
450
1425
250
VZK-17
17.5
38
95
790
1500
10
300
300
940
100
VZK-24
24
50
125
790
1500
10
300
300
940
100
VZK-36
36
70
170
790
1500
10
300
300
940
100
UTD-72
72,5
140
325
1.825
2.000
300
300
1.395
150
Approximate dimensions and weights. For special requirements, please consult.
19
Instrument transformers | Outdoor medium voltage
3. COMBINED TRANSFORMERS
Dry insulation
20
Instrument transformers | Outdoor medium voltage
OUTDOOR MEDIUM VOLTAGE TRANSFORMERS > Combined transformers
INTRODUCTION
Combined instrument transformers contain a
current transformer and a single-pole voltage
transformer within the same resin body.
KM model transformers with epoxy resin
internal insulation and cycloaliphatic resin
external insulation. Up to 36 kV.
Model KM up to 36 kV.
Model KM
APPLICATIONS
Combined transformers for outdoor service
are ideal for use at metering points.
They are particularly useful in installations
with space or cost limitations.
Examples of applications:
ARTECHE offers three-phase metering units
for pole mounting.
Model MK. Three combined transformers in a
single metal structure.
Model ME. Three current transformers and
three voltage transformers in a single metal
Model MK.
Metering unit
structure.
Model ME.
Metering unit
21
Instrument transformers | Outdoor medium voltage
OUTDOOR MEDIUM VOLTAGE TRANSFORMERS > Combined transformers
DESIGN AND
MANUFACTURE
ARTECHE combined transformers with
dry insulation are vacuum cast with epoxy
resin, which x and isolates the active parts,
creating a rigid body with high mechanical
resistance, excellent thermal performance
and dielectric withstand capability. They
are housed in a cycloaliphatic resin body.
This insulator provides for long creepage
distance, robust mechanical strength,
excellent arc tracking properties and
resistance to UV exposure.
ADVANTAGES
Variety of designs for greater adaptation to
client needs.
Cast in high dielectric strength resin.
Very high and invariable accuracy (up to
0.1%) for the service life of the equipment.
Wide range of primary currents.
Current ratio change by primary or
secondary tapping.
Option for double primary ratio.
Compliance with a wide range of creepage
distances, depending on customer
specications.
Excellent response under extreme weather
conditions such as temperatures of -55C
or +50C; UV radiation; altitudes over 1000
m.a.s.l., saline or polluted environments,
earthquakes, seismic hazard areas, etc
Compact design for easy handling.
May be transported, stored and installed
vertically or horizontally.
Maintenance free. No spare parts needed
throughout its lifespan.
The materials used for construction are
recyclable and resistant to the elements,
adhering to environmental regulations.
Each transformer is routine tested for partial
discharges, tangent delta (DDF), insulation
and accuracy. Designed to withstand all the
type test included in the standards.
Compliance to any international standard:
IEC, IEEE, UNE, BS, VDE, SS, CAN, AS, NBR,
JIS, GOST, NF and others.
Officially homologated In-house testing
facilities.
17.5 kV Metering unit (MK)
for revenue metering.
CFE (Mexico).
22
Instrument transformers | Outdoor medium voltage
OUTDOOR MEDIUM VOLTAGE TRANSFORMERS > Combined transformers
RANGE
ARTECHE combined transformers with dry
insulation are named using three letters and
two numbers, which indicate their maximum
service voltage.
The rst two letters indicate the transformers
type and the third letter indicates the model
within the product line.
Current ratios: all types of combinations
possible in a single device.
Secondary windings for:
Protection: all possible types, including:
low induction, linear cores, etc.
Metering: accuracy classes for any type
of metering and billing (including extrahigh accuracy class 0.1/0.15 with extended
current range).
Standard accuracy classes and burdens for
voltage transformer:
According to IEC standards:
100 VA Clase 0,2 / 3P
250 VA Clase 0,5 / 3P
According to IEEE standards:
0,3 WXYZ
1.2 WXYZ, ZZ
Higher accuracy classes and burdens available.
The following tables show the range currently
available. These characteristics are merely
indicative; ARTECHE can manufacture these
transformers to comply with any domestic or
international standard.
Combi
ned tra
nsforme
rs
Fig. 12 - Model KM
Model
Highest
voltage
(kV)
Rated insulation level
Power
Lightning
frequency
(kV)
Impulse
(kVp)
Standard
creepage
distance
(mm)
Thermal
burden
(VA)
Dimensions
(mm)
B
(mm)
H
(mm)
Weight
(kg)
Cycloaliphatic resin insulation
KMB-17
17.5
38
95
577
750
12
219
270
474
60
KMB-24
24
50
125
770
750
12
219
270
582
655
KMF-36
36
70
170
1194
750
12
254
330
638
120
Approximate dimensions and weights. For special requirements, please consult.
23
Instrument transformers | Outdoor medium voltage
4. OTHER TECHNOLOGIES
SRS sensors
PPE wall bushings
High voltage transformers
Fig.
72.5 kV Oil-paper
current transformers
(CA). Endesa (Spain).
24
Instrument transformers | Outdoor medium voltage
OUTDOOR MEDIUM VOLTAGE TRANSFORMERS > Other technologies
SRS SENSORS
The SRS-52 series features dry, outdoorservice voltage sensors. Its components are
completely encapsulated, combining the
technology of two top-quality epoxy resins:
cycloaliphatic resin and type-B resin. In this
way, excellent internal dielectric properties are
achieved, as well as an excellent response to
UV radiation and external insulation erosion.
Thus, this equipment is maintenance-free
and ensures a long mechanical and electrical
life. The SRS-52 is designed to be installed
vertically on poles or substation structures.
Since its stainless steel base is drilled with
standardized holes, it can be replaced if
necessary.
The SRS-52 voltage sensor is a resistor
divider; therefore, the secondary voltage is
proportional to the primary voltage, without
saturation.
The SRS-52 sensor is designed for outdoor
service applications for measurement and/
or protection for generation or distribution
systems with voltages up to 52 kV.
The PPE-36 series features dry, outdoorservice wall bushings. Its components are
completely encapsulated, combining the
technology of two top-quality epoxy resins:
cycloaliphatic resin and type-B resin. In this
way, excellent internal dielectric properties are
achieved, as well as an excellent response to
UV radiation and external insulation erosion.
Thus, this equipment is maintenance-free and
ensures a long mechanical and electrical life.
HIGH
The PPE-36 is designed to be installed
vertically or horizontally on poles or substation
structures. Since its aluminum base is drilled
with standardized holes it can be replaced if
necessary.
s a wide ra
The wall bushing can pass through wall
sections of 320 or 400 mm, and it can include
a primary bar.
The PPE-36 wall bushing is designed for
outdoor service applications for measurement
and/or
protection
for generation
or
distribution systems with primary currents of
up to 6000 amperes.
Instrument transformers | Outdoor medium voltage
VOLT
AGE
ARTECHE ha
nge of high
voltage
transformers
that can be
used in me
dium
voltage outd
oor applicati
ons.
Current tr
ansformers.
Oilpaper insula
tion, topcore type.
Mo
del CA from
36 kV.
Oilpaper insul
PPE WALL
BUSHINGS
ation, hairpi
n type.
Mo
del CH from
36 kV.
SF6 insulation, top-core type. Model
CG from 72.5 kV.
Inductive voltage transformers.
Oil-paper insulation. Model UT from
52 kV.
Capacitive voltage transformers.
Oil-paper insulation. Model
from 72.5 kV.
Combined transformers.
Oil-paper insulation. Model KA from
36 kV.
DDB
For more information, refer to catalog:
INSTRUMENT TRANSFORMERS. HIGH
VOLTAGE.
SRS Sensor
CA
Transformer
25
PPE Wall bushings
5. QUALITY, ENVIRONMENT
AND SERVICE
Exceeding environmental regulations,
ARTECHE has been able to minimize
the use off hazardous materials, energy
consumption and waste generation.
26
QUALITY & ENVIRONMENT
Everyone in the ARTECHE Group works under
Instrument transformers | Outdoor medium voltage
the criteria set out in our environmental and
quality policy.
ARTECHE has the
experience, technology and
capabilities of instrument
transformers. Thus we
provide the best solution
available in the market.
A sum of regulated procedures based on
communication, teamwork, prevention analysis
and continuous improvement, common to the
whole organization.
Advanced
sustainability
criteria
in
production and in the creation and
development of new products.
Compact designs, manufactured with
minimal
energy
consumption
and
enviromental-friendly materials.
Internal and external skill motivation
programs.
Advanced development of knowledge
management.
Quality agreements with utilities.
Physico-chemical and electrical laboratories
for testing under any International
Standard.
Type test reports issued by KEMA, CESI,
LAPEM, RENARDIRES, etc.
Final testing according to specic customer
requirements.
Approvals in more than 100 electricity
companies.
ISO 14001:2004.
ISO 9001:2008.
SERVICE
ARTECHEs service is based on a close
relationship with the customers, reected
in the integrated post-sale assistance plan
and structured client opinion system.
In addition to ensuring rapid response,
ARTECHE developed a continuous service
improvement plan, which sustains an
extensive training program with courses,
publications, conferences, etc.
ARTECHEs focus on service, with a broad
experience leading us to be an active
participant in the electrical organizations
such as: IEC, IEEE, CIGRE, CIRED, ASINEL, etc.
ARTECHE has production facilities in four
continents (North America, South America,
Europe, Asia and Australia) and more than
70 technical/commercial offices. Thus
ARTECHE provides effective responses
to the requirements of any customer and
situation, based on the global knowledge
acquired.
Physical and chemical
laboratories conduct
over 130 tests to certify
the quality of raw
materials.
The solutions ARTECHE has
developed and expanded have
made us an active participant
in the most important electrical
events and organizations.
27