0% found this document useful (0 votes)
47 views2 pages

Troubleshooting 110 KV Current Transformer

Representatives from M/S Tulsyan and M/S Lamco met on September 24, 2015 to troubleshoot issues with a 110 KV current transformer. They tested the insulation resistance values of the transformer cores and found that core No. 5 had a low value. After replacing the secondary terminal bushing for that core, the insulation resistance value was within normal range. They also observed an oil leak in a separate current transformer that was purchased two years ago and tightened the secondary terminals.

Uploaded by

Dhilip An
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
47 views2 pages

Troubleshooting 110 KV Current Transformer

Representatives from M/S Tulsyan and M/S Lamco met on September 24, 2015 to troubleshoot issues with a 110 KV current transformer. They tested the insulation resistance values of the transformer cores and found that core No. 5 had a low value. After replacing the secondary terminal bushing for that core, the insulation resistance value was within normal range. They also observed an oil leak in a separate current transformer that was purchased two years ago and tightened the secondary terminals.

Uploaded by

Dhilip An
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd

Date: 24.09.

15

Minutes of meeting held between M/S Tulsyan and M/S Lamco


Industrial (P) Ltd at Tulsyan site on 24/09/15 regarding
troubleshooting in 110 KV current transformer (New)
M/S Lamco Engineer Mr [Link] attended M/S Tulsyan site
on 24/09/15 for current transformer trouble shooting. C.T SI.NOCD3822
Following activities were carried out:
1. Tested that CT IR value in the CT (300/1A, 3 core & 600/1A, 2
core)
2. In CT core No-5 IR value is Low.
3. Replaced the secondary terminal bushing for core No-5
4. After replaced the bushing the IR value is ok (), Resistance
value-2.66
5. Another one New CT (Purchased before 2 Years) oil leak
observed and secondary terminals tightened .CT oil leak is
observation CT SI NO-CD 3511, 200/1A-3 Core, 600/1A-2 Core
[Link] PO/ CWPP11/1213/0220 Date: 06/03/2013.

TULSYAN
LAMCO

ENMAS O & M