Manual
F5021B
Lift controller 32 bit system
version E02.2(MA)
Directory
Table of Contents
1. F5021 Mainboard..........................................................................................1
Product characteristics.......................................................................1
Scope of operation...............................................................................1
2.System overview..............................................................................................3
Main module SM01.............................................................................3
Car module SM02................................................................................3
Command Modue SM03.....................................................................3
Floor module SM04.............................................................................3
Special module SM09..........................................................................4
funktional overview.............................................................................4
3. Operation equipment....................................................................................7
Operation of the system:.....................................................................8
Log - in:................................................................................................8
Menu.....................................................................................................8
Window with status in the submenu Monitor..............................8
Adjusting Parameters in submenu Para.Select................................9
different functions (Func.Select)......................................................11
4.Menu tree & parameter...............................................................................13
Basic parameters (Main Para.)........................................................14
Inspection parameter (Insp.Option)................................................14
Driving cycle parameter (S-Curve).................................................14
Multistep-parameter (Multi Speed).................................................15
Door parameter (Door Control).......................................................16
Adjusting floor display (Flr.Disp.)...................................................17
Enabling floors (Service Flr.)...........................................................18
Blocking florrs (Floor Block)...........................................................18
Defining coercive stop (Comp. Stp.)................................................18
Defining the building fill-up/dump (Heavy Traf.)..........................18
5.Shaft copy......................................................................................................21
re-levelling sensor:.............................................................................22
Contactor:..........................................................................................22
Adjusting switch................................................................................22
Inspection end switch........................................................................22
Intelligent magnetic sensor iMS45...................................................23
Design and functionality...................................................................23
Assembly diagram iMS45_POS.......................................................24
Assembly diagram iMS45_SPD (only for controller without a
machine room)...................................................................................24
6.SM01 F5021 main board..............................................................................25
Directory
SM01 circuit points:..........................................................................25
7.SM02/SM03 carmodule................................................................................29
reference note:...................................................................................29
SM02 circuit Points...........................................................................29
SM03 Push button module...............................................................31
8.SM02/H Controlcabinet module.................................................................33
9.SM09IO/B Expansion board.......................................................................35
10.SM02/G Car box module...........................................................................37
11.SM04HRF floor module.............................................................................39
12.Security........................................................................................................41
Security circle....................................................................................41
optional security switches.................................................................41
circuit of security...............................................................................42
Components.......................................................................................42
Functionality:.....................................................................................43
Possible sources of error:..................................................................43
Additional controll by the controller...............................................43
Scan-circuit of the security circle.....................................................43
N-type.................................................................................................44
Checking:...........................................................................................44
Relay for precontrolling....................................................................44
Trip monitoring.................................................................................44
Checking:...........................................................................................44
Complementary notes for inspection:.............................................44
Generally:...........................................................................................45
Isolation reading:...............................................................................45
13.Triggering of the frequency inverter........................................................47
Generally............................................................................................47
Triggering Multistep binary.............................................................47
Driving cycle......................................................................................48
speed and distances for brake..........................................................48
14.List of parameter........................................................................................49
15.Error codes..................................................................................................59
Manual F5021B - F5021 Main board
1. F5021 Main board
Product characteristics
32bit processor ARM7 industrial
standard
Doubble-processor-architektur for
extended security needs
2x CAN interfaces separate for internal
and external communication
high EMV-stability (EFT-4000V)
high ESD- stability (ESD 8000V)
certified for EN81, GB7588, CE
Functionallity area
For rope- and hydraulik-lifts
A lot of functions possible to parametize for nearly all kinds of lifts.
Lifts from 0,63m/s to 4m/s.
Up to 64stops, also with selective door controlling
Replace the 16bit-board F2021 (longtime supply with replacement parts is secured)
Analoge or digital triggering of the frequency inverter respectively chopper.
Shaftdetection via incremental shaft encoder (RS422, HTL, SSI)
Duplex groupe function integrated, possible to exted up to group times 8
Weight compensation at start-up with according weight measuring system.
ID-card system (credit card -transponder) possible to integrate.
Remote control locally and globally
Graphical LCD direct on board or a separate controller.
Description of Drive cycle, on- and off- activities, status information etc.
Error information memory (20 digits) with real-time coverage and full text advice.
As standard are 2 cabine doors, possible to expand for 3 doors.
Lot of special features, e.g. automatical evacuation with choose of direction conditioned to the weight.
Page 1
Manual F5021B - System overview
2.System overview
SmartCom is a modern, based on newest technology controller
system, especially for elevators.
The system basically composed of following components:
Main module SM01
Car module SM02
Command-module SM03
Floor module SM04
Expansion module SM09
Different variations of the serveral modules make the best and
optimized adjustment of the controller system possible for the
respective lift and the requested functionallity area.
Based on the never changing CAN-journal its possible to realize
controller for simple and complex lifts.
All components are, due to the CAN-systems, nearly in any order
possible to be combined, and after all possible to be extended.
Main module SM01
The main module is in the Controlcabinet and is the heart of the
controller. It contains all functions, especially trigging the handler,
recognitize the possition of the lift and lots of special features, which are normally directed to the
shaft and the engine room. It is communicating with the other modules via CAN-Bus.
Car module SM02
All functions, which are directed to the car, are done by the car module. It is linked via CAN with
the main module.
There are two possible options, the classic with only one module SM02/03, and from now on the,
with 32bit Board F5021 established spreaded option. In this case there are each a SM02/H in the
Inspection box and a SM02/G in the car operation panel (COP) used. Due to this, the till now
needed 36pin cable from the Inspection box to the COP, is reduced to a maximum of 12 pins. Now
the connection for up to 3 cabinet tableas (2nd door side, console panel via CAN is really easy.
Command-module SM03
This module is connected with the cabinet module. It is possible to connect 8 of these modules with
one SM02. One command module allocate 8 entrances for inside commands and 8 outputs for the
respective indication.
Floor module SM04
Modules of this kind of art can be used as well as floor display in the car or as floor module with
floor display and driving display at the floors. The addressing is really simple without any tools, by
settings via the floor push buttons or via the DIL-switches.
The SM04 is available in different forms: horizontal, vertikal and vertikal slim. The Displays are
different in their kind of art and coverage and it is also possible to be manufactered client-specific.
They are all communicating via CAN-Bus and can be teamed together nearly in any order.
Page 3
Manual F5021B - System overview
At the floors, the Exterior call buttons and key buttons will be conected with the AM04 modules
(Display + CAN-module) for special features. Newer modules also allow the conection of a speaker
to make possible the, in EN81-70 required, tones.
Extra module SM09
Via this module client specific special features can be complemented without changing the central
module. For example the conection to lift-maintenance-systems of the client or additional alerts,
etc.
Function overview
Standardfunktionen
1
Collectioncontrolling
2
Inspection Drive
3
Self liberation with slow drive
Test dive
Real time clock
Time to keep doors open
Door opening by lokal call
Early door closing
Forced opening of doors
10
Controlling of door closing.
11
(return motion automatic)
Controlling of door opening
12
13
Call cancel
Terminal stops
14
Direct drive
15
16
Cabinet full
Cabinet light cut off
17
Park drive
18
LCD controller
19
Analoge speed control
Page 4
Collecting hall calls with respect on the given direction
Manual drive up and down. Within the area of doors, the door open
button can be used for opening the door.
In case of missing the door area within the normal mode, the lift is
driving slowly with closed safets circuit into flush position and open the
door.
For Testcases, the lift can do a indicated number of accidentally test
drives.
Errors are registred with date and time. Time-dependent funktions can
be activated.
Dependent of the kind of call(interior, exterior, service, special call), the
time to deep doors open can be indicated.
Is the lift allready in the floor from which the call comes, the door
opens. With the Door open button, the door can be keept in open
position
With the Close door button, the door can be closed, earlier than the keep
door open time frame.
Inside the door area, with the Door open botten, the door opening can be
forced for closed doors or doors which are actually close.
In case the bar is not closed within 15 sec. after arrival at the door-closeendswitch, the door open again for a new try.
In case that 15 seconds after the door opened and the door-opendendswitch is not activated, the door is closing until further command.
By doubble-pushing a call button, the call is canceled.
At paramount stage the up command gets canceled, at the lowermost
stage the down command gets canceled.
Direct drive without rat run. This function is activated at standard when
incremental detection and analog trigger of the inverter.
The driving cycle is preset by the controller. There are no special
demands on the inverter.
If full load, the cabinet do not stop anymore for hall calls.
After 5 minutes without any activity, the cabinet light will be switched
off.
After an indicated time without any activity, the lift drives to the main
purchase postion.
Graphical display with comprehensive status informations and menu
navigation.
The rotation speed of the frequency inverter is triggered by the analog
output
Manual F5021B - System overview
20
21
Digitale speed control
Error memory
22
Learn trip for schaft information
23
24
Floor approval
Adjustment of the floor display
25
Liftboy control
26
Priority inside
27
LED-dot matrix-display,
LCD graphic-display
Display with roll function
Automatic schaft data correction
Remote off
28
29
30
31
32
Door only opens inside the door
areas
Safty light barrier/ light gate
33
34
Overload
Abuse recognition
35
36
Stop in case of wrong agitator
direction
Drive inspection (skidding)
37
38
Inspection of traction
Inspections end switch
39
Contactor monitoring
40
41
Speed monitoring
CPU monitoring
Optionale functions
1
preopening doors
2
relevelling with open doors
3
Fire controll
Alternatively the speed can be controlled via contactors
The last 20 Errors get saved and displayed with information of time,
floor and error code.
The controller is learning with encoders and floor flags the bulk of the
schaft and stopping distance. After that, the lift can merge into standard
mode.
Free adjustments of floors, which can be departed.
The icons, which should appear in the respective floors, can be free
adjusted to a large extent.
The lift gets drived via interior control manually. Hall calls will be
served.
Hall calls are deactivated only interior calls are effective. The door must
be closed with the door-close-button. The Push-button have to be
compressed until the close-door-end-switch is activated.
At every stop there ist a dot matrix display with floor update, direction
and status. The user can see that there is something going on.
Respectively to the drive direction, the display is rolling.
Continously the schaft datas gets corrected
The lift can be shut down, but before all still open cabinet commands
need to be completed.
Outside the door areas, the cabinet doors can not be opened.
The safty light barrier/ light gate gets evaluated by the controller. In case
of activation, the controller avoids closing the door.
In case of overload, the door stay open and an alert sounds (buzzer)
If the cabinet is empty (empty load) the number of cabinet calls is
bordered.
In case the controller recognize a wrong agitator direction the handler
gets stopped.
If the cabinet is not moving despite active handler, the handler gets
stopped after 40 seconds (drive inspection). New drives only possible
after Reset.
In case of cabinet is moven despite deadlock, alarm get raised.
The inspections end switch avoid, that the lift drives to the emergency
limit switch during inspections, return motion drives or learn trip.
The controller check at every drive the correct functionallity of the main
contactors and brake contactor .
If over speed is detected an emergency stop will be effected
The processor is monitored by watchdog, if needed restarted.
Using safty circuit
Using safty circuit. At hydraulic lifts standard function
In case of fire signal the lift drive to the fire floor and stay there with
open door.
All commands get canceled and the lift drives to the fire floor stage.
Now the firemen can use the lift. The door is not open atuomatically, but
have to be opened with the door-open-button. Unhand the button makes
the doors closing immediatelly.
Fireman control
5
6
Additional COP
COP for 2nd door
European (EN81) und Russian (PUBEL) variant.
It is easy to install a second car operation panel
Selective door control
Disabled COP
Particular COP (e.g. desk COP) for disabled people (longer door
Page 5
Manual F5021B - System overview
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
opening times)
Via the second CAN-Bus 2 lifts can be conectetd to a two- groupe. The
lifts than parting calls respective to the actual situation; so it can be
achieved that the times of waiting can be reduced to a minimum. In
addition there can be activated a function, that, if there are no more open
calls, the one of the lifts which is nearer the main stop position, gets
driven there an keep it prepared there.
Group function
With a optional group controler board, lift groups with up to 8 lifts can
be realized. The group control collects the hall calls and allocate these
respectivlly to the condition of the several lifts in order to reach short
time of waiting.
Rush hour handling fill up
Via internal time frame inputs, the capacity can be adapted to the
building
building. (type office buildings)
Rush hour handling clear building Via internal time frame inputs, the capacity can be adapted to the
building. (type office buildings)
Distribution of waiting lifts
If there are no more open calls, the lifts of the groupe get distributed
after 1 min. in the buildding, means one drives to main stop position, the
others disperse themself, in order to achieve shorte waiting times.
Interface to building control service RS485 interface for connection to a PC of the building control service
engineering
engineering.
Remote control
The lift can be integrated into a region comprehensive remote control
system.
Lift arrival gong
During the drive in, the gong on the cabin roof or under the cabin floor,
about the arrival of the lift.
direction indicator HOP
Inside the exterior panels it is possible to instal an optical and akustical
continued travel display.
Floor gong
For every stop an lift arrival gong can be arranged.
Card reader in the cabin
With a transponder card, either a specific call can be activated or
defined calls can be approved.
Card reader at the floor
Approval of exterior calls
Selective door triggering
Frontside and backside of the lift can be controlled seperatly.
Scramble
After one minute the door is closing slowling despite of the safty light
barrier.
VIP Service
A key switch in exterior panels cancels all hall calls and fetches the
empty cabin. Now multiple interior calls can be done. After these calls
are done, the lift change back to standard handling.
PIN entry via Push buttons
For certain floor approvals the Push buttons can be used for entering a
PIN.
Local controlled floor approval
For several and duplex lifts a changed floor approval via key switch can
be activated.
Via group controlled floor approval Floor approvals can be temporary changed via the group add-on.
Temporary block of sereral floors
Temporary, the user can block floors
Automatic evakuation
In case of black out with following auxiliary power supply, the cabine
will be driven to the next stop.
Auxiliary power supply evakuation For lift groups an evakuation will be done separate one after another
Earthquake function
Lift get stopped during the drive and will be driven to the evaktuaion
stop.
Voice message
Serial and parallel access for voice message
Duplex-function
Page 6
Manual F5021B - Operation equipment
3. Operation equipment
Overview of push button functions:
Next parameter/ menu item
Increase the number of selected decimal
Former parameter/ menu item
Decrease the number of selected decimal
Jump 10 parameters back,
one decimal place to the left
Jump 10 parameters forward,
one decimal place to the right
ENTER Access parameter menu
D1:driving
D2: up
D3: down
D4: error
Floor or
error code
LCD
with status
Menu, etc.
parameter set/adopt
ESC
Parameter/menu item leaving
F1
Hot key: change from status-window to
error display, to encoder diagnostic and
to CAN-diagnostic
2x F1
3x F1
F2
2x F2
F3
Hot key: change to call entry and to
status display of in-/outputs.
keypad
CAN
RS485
Hot key: to travel cycle display
All functions from F1 to F3 also accessable via the
menu!
Optional a control element can be directly inserted
on board F5021B, or the external control element
can be connected with a special cable with the 9pin
Sub-D-linkage JP15. The USB-plug of the cable
have to be pluged in the left plug (RS485). A plugin into the right plub by mistake arose no claims,
the control element is just not working.
Attention! Never use the special cable to link with
the PC. The PC can be damaged!
Again Attention!
The inserted control element and the external
control element may not be connected at the same
time! In case this occurs, there wont be any damage, but the parameter are not possible to be setted
because two control elements at one time are not allowed to access the parameter memory!
Page 7
Manual F5021B - Operation equipment
Handling:
The handling via the inserted control element and the external
control element are identical. The external control element processes
additionally to the shortcuts F1, F2 and F3 whereby assinged
diagnostic-windows directly can be recalled. At the inserted control
element all windows only accessable via the menu.
Log-in:
Start window
In order to see the status and for setting parameters, first you have to
log-in. In case you are not logged in yet, it is displayed after pushing
the ENTER button the window for log-in. By default the password is 1234.
After log-in it is possible to change this in Chg.Password. Attention! Do not
forget the password!. The controller can without password only in the factory be
unlocked!
Log-in
Menu
The complete menu tree you can find in: Menu tree & parameter.
The start window shows mode, group status, journey counter, floor, speed and the
actual activity. With Enter you can change to the main menu. Repushing Enter
show you the monitor-menu auf, which occupies all diagnostic windows.
Status window in Submenu Monitor
Run State is the start window.
In the first line you can see the mode (Normal, Inspection, Fire Return,
Firemen, Park) and the group status (Simplex, Group).
Among the journey counter, floor, speed and actual activity.
In Call. Func. are displayed the actuall calls and it is also possible to enter
calls (with the arrow buttons on the respective call and Enter).
Cabin call, hall calls for up and down.
Speed Curve is the graphical display of the as-is-value (of the encoder) of the
speed.
Above it is displayed the actual speed value and the time of journey.
At the window Input&Output it is possible to display all outputs and inputs.
With the up/down-buttons you can switch between the several 16fold groups.
With the right/left-buttons a single input/output can be marked. Than in the
line among is shown the function of the input/output.
The marking X (inputs SM01) and Y (outputs SM01), also TX (inputs SM02)
and TY (outputs SM02) you can find again in the diagram.
Page 8
Main menu
Manual F5021B - Operation equipment
In the error memory (Fault Record) there are displayed the last 20 errors with
date, time and floor.
The latest error is displayed at first.
With up/down you can move between the items in the list. With Enter an
additional window pops up, in which date, time and full-text-error message is
displayed.
The list Shaft Data contains the floor postions in mm which were identified at
the learn trip. If there are problems in the shaft selection you can really fast
identify if the floors were learned correctly.
The two windows Encoder Eva and Communication are helpful if you have
problems with the encoder or the CAN-bus.
In the version window are shown date and version number of the firmware.
Before doing an update it should be checked if the new software is really
more active than the allready existing version.
Parameter setting in the sub menu Para.Select
Via the parameter menu you can access to the numerous parameters. There are
parameter groups, in which the parameters combined thematically (e.g. engine
or door parameter), as well as a list in which all parameters are sorted by
numbers.
Most of the parameters can only be setted in the inspection or return motion
mode. If the alert window shows up, switch to inspection.
All parameter are achived as 16bit integer. Most of them are shown as
decimal, with adjustment value (e.g. means the value 50 at a device of 0,1s a
parameter value of 5 seconds).
Page 9
Manual F5021B - Operation equipment
Some parameters are available as bitmask. Indeed is shown the decimal, at
once you want to set the value, it will be shown as bitmask and you can set it
with right/left button (move between the bits) and up/down button (* means
setted/ - means canceled).
In the line below shows up the description of the bit.
Thus you can configure e.g. for every several input the logic (*NC/-NO)
Lvl.Mic.Adj. allows you the correction of serverl precisions in all floors.
Normally this is not necessary as the floors get messured at the learn trip.
Multi Speed contains all parameters, which are necessary for the handling of
the frequency inverters in multistep-mode (prallel control).
Door Control allows you to set parameter for the lift-door-control.
Flr.Disp. Guides you to the list with floor displays. For every floor it is
possible to do the settings for the displayed letter-combination. (at Step SM04
displays). At the same time, the display code configure the voice message,
which get annouced at the respective floor when lift drives in.
The display codes are configured in a table in the attachment.
Service Floor configure the floors, which are approved. Furthermore floors
can be configured, which are only can be unblocked via key-switch.
Block Floor allow the locking of a floor by time or key-switch.
Comp. Stop (forced stop) define stops, at which the lift by passing enforced
stops. In some cases it make sence for hotels.
Heavy Traf. Allows the configuration of the function fill-up building and
clear building. By this, especially for office buildings, it is possible to
improve the hoisting capacity.
In Test Run it is possible to configure the parameter F34 to a number of
journeys, the lift have to do test journeay without any commands
(accidentially).
Para. Setup is the access to the complette parameter list.
Page 10
Manual F5021B - Operation equipment
Reset restores all parameters to factory setting. This should only be done if
absolutly necessary. Before Reset there have to be entered a number in order
to avoid to do a reset by mistake.
Attention! After entry of the number the reset of all parameters starts without
any further query!
F146 necessarily have to be setted to 0!
Different functions (Func.Select)
Time Setup: Configuration of the real time clock. This is used for Error
recording and the time relevant floor approvals and the functions fill-up
building and clear building.
Door Teach: Detect by opening and closing the function of the door-endswitches.
Shaft Teach:learn trip, have to be done before switch to standard mode (after
installation or change of door positions).
Door, bus, shaft selection and cabine light have to operate correctly.
After activation of the learn trip, the lift is driving self-consistent to the
lowermost stop and starts the learn trip. As soon as the learn trip is finished,
the lift can be switched to standard mode. If an Error occours, the learn trip is
stopped with an error message.
Reset Para.F: Restore to factory setting!!!
Reset Errco.: Clearance of the error memory!
Error Reset: Reset after Lift Error (fatal error) as e.g. drive monitoring,
contactor monitoring, brake monitoring, etc.
Relogin: Log out and if so new log in. Normally after 10 minutes without
operation the log out is automatically.
Chg.Password: Changing password. Attention! Do not forget password! Only
possible to can be restored without password in the factory!
Page 11
Manual F5021B - Menu tree & parameter
4.Menu tree & parameter
Func.Selec Monitor
t
Run State
Status of the lift (Floor, speed,. etc.)
Call Func
Enter and display calls
Speed Curve
Graphical display of the speed curve
Input&Output Status of the inputs and outputs
Fault Record
Error memory
Shaft Data
List of floor values
Encoder
Analysis of encoder
Communicat. Analysis of CAN-system
Para.Select
Version
Display of software version
Main Para.
Basic parameter
Insp.Option
Inpection parameter
S-Curve
Travel cycle parameter
Lvl.Mic.Adj
Fine adjustment precision
Multi Speed
Parameter for multistep operation
Door Control Door-parameter
Func.Select
Flr.Disp.
Adjustment of floor display
Service Flr.
Floor approval
Block Flr.
Floor blocking (access control)
Comp.Stop
Define forced stops
Heavy Traf.
Fill-up building/ clear building
Test Run
Number of accidential test drives
Para.Setup
All parameters in one list
Reset
Restore to factory setting!
Time Setup
Configure time
Door Teach
Learns door-end-switches
Shaft Teach
learn trip shaft
Reset Para.F
Parameter to factory setting
Reset Errco.
Reset Error memory
Error Reset
Reset from error mode
Relogin
Again log-in
Chg.Password
Password change
Page 13
Manual F5021B - Menu tree & parameter
Basic-parameter (Main Para.)
No.
Standard
Description
Advise
F6
1m/s
Nominal speed lift
F7
1450rpm
Nominal rotation speed engine
F8
1024ppr
Encoder pulses
F24
Trigger of FU analog
F11
18
Number of floors
F182
Number of delay switches
F60
motor contactors : 3= K1 and K2 after the
inverter and monitored
F36
Break-monitoring-switch, 0= no monitoring
F153
Door lock det. type
F156
Safety loop type
F62
32
Journey time monitoring. For test set to 2s.
F25
35296
F26
83
Configureing, if the several inputs wired as
closer (NO=normally open) or as opener
(NC=normally closed).
F27
835
F28
F23
Group function
0Simplex, or rather Duplex-master
1Duplex Slave
2for external groupe processor
3at group-ring (look at F181)
F181
Lift number within a group: minimum value have 0~7; for F23=3
most priority. (F32=3)
Bitmasks
Depends on the diagram and the conected
switches
Inspections-parameter (Insp.Option)
No.
Value
Description
Advise
F201
at 1 it is possible to drive above the reference-journey-end-switch
For test purpose
F200
Distance for early stop at paramount stop (headgear)
mostly UK
F40
Top Access Dis.
F42
Bot.Access Dis.
F64
0= no door operation for inspection
F165
Bit 1=0
Bit 1 avoid movements of door at inspection (door B)
Travel cycle parameter (S-Curve)
No.
Value
Description
F0
0,55m/s
Acceleration
F1
0,55m/s
Deceleration
F2
1,3s
Rounding at start
Page 14
Advise
Manual F5021B - Menu tree & parameter
No.
Value
Description
F3
1,1s
Rounding at the change to constant drive
F4
1,1s
Rounding at leaving of constant drive
F5
1,3s
Rounding at stopping
F12
0,25m/s
Inspection speed VI
F13
0,06m/s
Levelling speed VN
F48
Advise
Down Rev. Speed
F183
0,8m/s
learn trip speed (for analog-trigger)
F21
6mm
V0 stop distance
F175
0,06m/s
Creep speed at start
F186
0,5s
Time of creep speed at start
F180
100,00%
Analog value at nominal speed (Vmax)
F16
0,2
Time between inverter run signal and break release
F58
0,5
Deceleration of the driving cycle at start
F17
0,6
Deceleration of break after rotation speed Zero
F122
0,3s
Time between break off and direction off
F141
0,5s
Time between inverter run signal off and motor contactors
off
F144
Time between inverter direction off and inverter run signal
off
F56
50
Stopping distance up, >100 stop with creep speed
F57
50
Stopping distance down, >100 stop with creep speed
F126
300mm
Short-journey deceleration distance
F193
Empty load-compensation
F194
Full load compensation lowmost stop
F195
Full load compensation paramount stop
Only relevant for very high
assets in order to balance
the weight of the ropes.
Multistep-parameter (Multi Speed)
No.
Value
Description
F32
Type of frequency inverter:
0: YASKAWA,CT,FUJI,iAStar
1SIEMENS
2: KEB
3: MICO
4: SIEI
5: Dietz
6: NEW FUJI
7: user-defined (look at F240F249)
F63
Number of drive positions at Multistep-controler of inverter
F16
0,2s
Deceleration between inverter run signal and break contactor on.
F17
0,6s
Deceleration between inverter stop command and break
contactor off
Advise
Page 15
Manual F5021B - Menu tree & parameter
No.
Value
Description
F58
0,5s
Deceleration between FU run signal and start of drive cycle
F122
0,3s
Time between break off and FU drive signal off (speed and
direction) .
F141
0,5s
Follow-up time of the engine-schuetze: approval off=>Schuetze
off.
F144
0,000s
Follow-up FU-approval after switch off the direction signal.
F21
6mm
V0 stop distance
F45
1,300m
Breaking distance for V1 (floor drive)
F46
2,900m
Breaking distance for V2 (2 floors drive)
F47
4,000m
Breaking distance for V3 (more floors drive)
F157
5,500m
Breaking distance for V4 at 4 floors drive (for fast lifts)
F158
6,500m
Breaking distance for V5 at 5 floors drive (fast lifts)
F126
300
Short drive deceleration distance
F143
spare
F147
spare
F56
Fine adjustment for stopping upwards: 50 for direct drive in,
>100 with creep speed
F57
Fine adjustment for stopping downwards: 50 for direct drive in,
>100 with creep speed
F240
Release brake
F241
Inspection slow
F242
Releveling
F243
Creep speed
F244
Inspection fast
F245
Speed floor-drive-in
F246
Speed 2-floor-drive-in
F247
Speed 3-floor-drive-in
F248
Speed 4-floor-drive-in
F249
Speed 5-floor-drive-in
Advise
User defined Multistep
control of the frequency
inverter:
F24 = 0F32 = 7
door Parameter (Door Control)
No.
Value
Description
F50
65535
Door A approval floor 1 to 16
F51
65535
Door A approval floor 17 to 32
F52
65535
Door A approval floor 33 to 48
F191
65535
Door A approval floor 49 to 64
F53
Door B approval floor 1 to 16
F54
Door B approval floor 17 to 32
Page 16
Advise
Manual F5021B - Menu tree & parameter
F55
Door B approval floor 33 to 48
F192
Door B approval floor 49 to 64
F128
0= charging, 1 = selective door control
F130
Door control (keep closed/keep open):
0no keeping of closed/open
Bit 1keep door open (in case cabin door get drawed back
from shaft door)
Bit 2keep door closed (in case door-bracing opens without
keep-shut moment)
Bit 3keep shut during travel (in case door-braking would
bump against the bar)
Bit 4no door-close-end-switch
Bit 5AT120 door control
Bit 6manual door
F140
At door open, second doorzone active:
0X9/X10 configures door opening.
1X18 configures door opening
F129
re-levelling with open door/ in advance door opening (require
safety circuit):
0no safety circuit
1preopening door
2re-levelling with open door
3both
F14
Door-open-time frame after hallr call
F15
Door-open-time frame after car call
F121
Door scramble:
0on, 1off
F115
15
Run-time at door closing (in case there is no end-switch)
F116
15
Run-time at door opening (in case there is no end-switch)
F117
60s
Door open time frame after confirmation keep-door-openbutton.
F118
30s
Door open time frame after confirmation open-door for
disabled person.
F165
Door opening functionallity:
Bit 1: no opening/ closing during inspection.
Bit 2: no opening of doors during test mode
Bit 3: Door A basic postion open at main stop
Bit 4: Door A basic postion open at every stop
Bit 5: Door B basic postion open at main stop
Bit 6: Door B basic postion open at every stop
F142
0,1s
Follow-up time of the door-engine-contactors (after end-switch
confirmation)
F145
spare
F119
Door mode when priority inside
0keep close-door-button pushed for closing the door
1Door is closing after command
Floor display adjustment (Flr.Disp.)
No.
F65
Value
49
Description
Advise
Display Code for floor 1
Page 17
Manual F5021B - Menu tree & parameter
F66
Display Code for floor 2
F67
etc.
Display-codes in respect to the table in the attachment.
Floor approval (Service Flr.)
No.
Value
Description
Advise
F29
65535
Approval floors 1 - 16
F30
65535
Approval floors 17 - 32
F31
65535
Approval floors 33 - 48
F190
65535
Approval floors 49-64
F137
65535
Defines floors, which can be blocked with key-switch:
Bitmask 1-16
F138
65535
Bitmask 17-32
F139
65535
Bitmask 33-48
F199
65535
Bitmask 49-64
F236
65535
NS-CB Floor 1-16
F237
65535
NS-CB Floor 17-32
F238
65535
NS-CB Floor 33-48
F239
65535
NS-CB Floor 49-64
Enter as bitmask!
Floor blocking (Floor Block)
No.
Value
Description
Advise
F161
Floor blocking (F137,F138,F139)
0: no block
1: block by time F131
2: block by key-switch
F131
Floors able to block
0: inactive
164: number of the floor to block.
F132
Time from when floor <F131> have to be blocked: e.g. 730 for
7:30.
F133
Time from when floor <F131> have to be un-locked. e.g.: 930 for
9:30.
Forced stop definition (Comp. Stp.)
No.
Value
Description
Advice
F134
65535
Bitmask floors 1 - 16
F135
65535
Bitmask floors 17 - 32
When crossing the setted floors, the lift mandatory
stops, even without command.
F136
65535
Bitmask floors 33 - 48
Makes only sence in hotels.
Fill-up building/clear building definition (Heavy Traf.)
No.
Page 18
Value
Description
Advice
Manual F5021B - Menu tree & parameter
F231
Approval for function fill-up building/ clear building
0: no function
1: fill-up building
2: clear building
3: both functions
F232
730
Starting time for fill-up building: e.g. 730 means 7:30
F233
930
Finish time for fill-up building: e.g. 930 means 9:30
F234
1700
Starting time for clear building: z.B. 1700 means 17:00
F235
1830
Finish time for clear building: z.B. 1830 means 18:30
Page 19
Manual F5021B - Menu tree & parameter
Page 20
Manual F5021B - Shaft selection
5.Shaft selection
The shaft selection consists of a incremental encoder and
solenoid switches, respectiveley sensors.
NEO
(Emergency stop TOP)
IEO
(Inspection stop TOP)
Car
The incremental encoder optinally is positioned on the
engine or in the shaft.
(Downslow switch TOP)
NEO
L.KO
L.IEO
Especially for rope lifts it is used the encoder of the
engine, which can hand over at the most of the frequency
inverters via encoder output (encoder simulation) to the
controller.
IEO
L.NEO
KO
Downslow switch v>2.5m/s
In this case it is entered the effectiv datas for the
parameters F6 (nominal speed), F7 (engine speed) and F8
(encoder release).
KO
L.KO1
KO1
For slowly running synchronous motors it mostly have to
be juggeled with the parameters nominal-rotation-speed
and encounter-puls-rate. E.g. 150U/min at 2048ppr
changed to 600U/min (*4) and 512 ppr.
KO1
only if v>2.5m/s
v
Distance (mm)
L.KO L.KO1
950
If the encoder is assembled in the shaft (rotating string) for
the nominal-rotation-speed have to be entered an
equivalence-rotation-speed (equates encoder-rotationspeed).
0,63m/s:
1,0m/s:
1,6m/s:
1,8m/s:
2,0m/s:
2,5m/s:
For the system used by us with carbon cord show up the
following values:
KU1
v>2.5m/s
1300
2400
2600
2400
2400
3800
5600
0,8 1
1,2
(F8)
294 367 441
1,4
1,6
514 588
m/s
L.KU1
KU1
(F7)
Downslow switch v>2,5m/s
RPM
C
D
KU
L.NEU
L.IEU
KU
Downslow switch
DOWN
D
C
IEU
Inspection switch
DOWN
EmergencyStop
DOWN
L.KU
Car
IEU
NEU
re-levelling sensors:
As the shaft selection is done with the engine encoder, the slip of the tractions sheave have to be
compensated. For this, there are in every floor re-levelling-plates installed with about 220mm length. (The
Page 21
Manual F5021B - Shaft selection
12
50
length is not important, but it have to be identic in all floors).
220
200
This plate will be evaluated by two inductiv sensors C and D. C is the upper, D the
lower.
Solenoid switch:
Additionally there are in the shaft ceiling and in the shaft pit each 2 bi-stable solenoidswitches (there could also be roller-switches with repective curves at the cabin). Correction
above and below, as well as inspection-end above and below.
It is important, that the switches are installed as opener. By crossing the above correction- and inspectionswitch they have to be open on the upper side and closed on the lower side. For the lower positioned ones,
the same is valid respectively contrairiwise.
Correction switch
The correction switches serve the deceleration at the termian end stops in case of error (blackout of
incremental encoder) and for learn trip. They are also used for correction of the incremental-encoder-datas.
In the set of drawings, page 50 you can find these respectivly to the speed recommendet distances. The
exact pitch for the braking distance which is choosen by the controller is not important, as this is assigned
by the chossen parameters. However, braking distance and pitch should not have a bigger difference than
45cm.
Inspection end switch
The lower inspection end switch have to be installed in that way, that it opens right before the emergency
limit switch is activated, but after the re-levelling-sensor D lower the precision plate is freed. C is
mentionend in the plate.
For the upper inspection switch it is in the respective way, means IEO will be activated (open contact) if
the sensor C is upper the precision plate and D is still at the plate. Also in this case the emergency limit
switch should be a bit away, that the lift stops before the emergeny limit switch is activated.
The inspection end switches are important for the learn trip.
Page 22
Manual F5021B - Shaft selection
Intelligent magnetic sensors iMS45
Meanwhile, all above mentioned switches are integrated in one compact
sensor-system. Due to this the montage and adjustments are made really easy.
The iMS45 have up to 4 solenoid sensors, which are together with a
programm able analysis-electric can generate up to eight switching signals. For a complete shaft selection
one iMS45-POS is enough. Especially for machineroomless an additonal iMS45-SPD sensor will be
attached, which detect the speed and rotation of the driving wheel. This is displayed at the Drive monitor,
which is the display and analysis unit.
The sending of datas itself will be done via a serial conection without malfunction rate RS485-connection.
Assembly and function
Assembly
The sensor is in a stable aluminium housing, which is also available as IP54-version which is used in
firefighter lifts.
The solenoids are flat solenoids with 15mmx7mm of cross-section and a variable length. The solenoids are
installed at the button of the arrester rails.
Function
In the iMS45 are 4 solenoid sensors, which are measuring the strengh and polarity of the magnetic field.
An analysis unit detect the respective switching signals and send these serial to the cabine, respectively to
the drive (driving wheel) for controlling/ stearing. Additionally the iMS45-POS have an independent
transistor output for e.g. contacting a chanel of a security circuit.
different detections:
* Single magnet north
* Single magnet south
* Doubble magnet upper north/ lower south
* Doubble magnet upper south/ lower north
* Tripple magnet north in the middle
* Tripple magnet south in the middle
* Crossing direction
* Crossing speed
* North/south transition is detected exactly of each milimeter, mostlikely independent on the distace
sensor/ magnet
Page 23
Manual F5021B - Shaft selection
Montage scheme iMS45_POS
1
short magnet south
Track Pos (Levelling X9/10, Doorzone
Slowdown X7/8 and X3/X4
Learntriplimit X5/6)
distance by speed = 1.6 m/s
2,8m
long magnet south
Top Floor
S
Reference point
slowdown up (X7)
double magnet short
north below
S
N
Slowdown magnet up
doublemagnet round
with north magnet below south magnet
Levelling and Doorzone:
N
Floor 2....
distance by speed = 1.6 m/s
2,8m
distance by speed = 1.0 m/s
1,4m
reference point
slowdown X8
slowdown X8
double magnet north above south
flat magnet
Width 10, Depth 8, Length 150mm
southmagnet (marked with white)
N
S
10..30V
brown
RS485
white
1
2
4
5
E
0V 3
black
gray
blue
+10...30VDC
D+
sLink
D-
Out E NPN 200mA
0V
POS
position sensor
Slowdown magnet down (only bottom floor)
doublemagnet round
with north magnet above south magnet
LED2
Polarity North or South means the pole which
shows to the sensor.
South is marked with white.
4
5
1
3
2
4
5
3
2
N long magnet north
triple magnet (south in middle)
defines learntrip limit x6
double magnet north above south
Ub
GND
D+
DE
brown
blue
white
black
gray
LED1
Bottom Floor
S
N
floor 2 ...n-1: no slowmagnets required!
flat magnet
Width 10, Depth 8, Length 150mm
Northmagnet (blank)
Reference point floor level
N
S
Attention!
Sensor POS is asymetrical! The active Sensor element
must show to the guiding rail (marked).
Pos sensor must be always right from rail.
Wrong installation may cause malefunction.
Sensor
distance by speed = 1.0 m/s
1,4m
reference point floor level
Top Floor
Triple magnet (North in the middle)
defines Learntriplimit up (X5, IEO)
S
N
short magnet north
+5
-5
shortmagnets length 20mm
longmagnets length 150mm
reference point floor level
S short magnet south
LED1: Sensor is online (connection to DriveMonitor Ok)
LED2: Sensor is detecting magnet
N short magnet north
created
last modif.
name
M.Aicher
date
09.11.2009
No:
magnetic sensor, shaft selector
Page
Ver.
50
Montage scheme iMS45_SPD (only for machine room less lifts)
1
traction wheel
polarity and
number of
magnets not
important.
5 or 6 magnets
around the wheel
are ok
magnets round D=6mm
LED1: Sensor is online (connection to DriveMonitor Ok)
LED2: Sensor is detecting magnet
4
1
5
+5
-5
Position of sensor important for speed
and direction detection!
In case of wrong direction on DriveMonitor
turn sensor 180.
Ub
GND
D+
D-
LED2
1
3
2
4
LED1
check that sensor is in right position,
because for correct function
the sensors must be mounted
in the right way!
Speed-Sensor MS485 SPD at traction wheel
SPD
speed sensor
10..30V
brown
RS485
yellow
Sensor
1
2
4
5
E
0V 3
green
white
+10...30VDC
D+
D-
sLink
0V
created
last modif.
Page 24
name
M.Aicher
date
09.11.2009
magnetic sensor, Speed Sensor
No:
Page
52
Ver.
Manual F5021B - SM01 F5021 main board
6.SM01 F5021 main board
SM01 F5021 Mainboard Terminals
1
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
JP9
JP10
D12
Y10
D13
Y11
D14
Y12
D15
Y13
analog output
10
X26
X27
X28
X29
JP12
JP11
0V(AGND)
encoder input
Speed 0-10V
sym.
encoder input
speed governor
Y15
CAN 2 TXV(group)
TXV+
inputs 230VAC
see LED X26,X27,X28,29
D16
Y14
TXATXA+
shutdown
motor temperature
monitoring safety circuit
Autotuning is active
FireStop2
FireStop1
D11
Y9
CAN1
(car, shaft)
D10
Y8
JP8
A+
D9
Y7
error inverter
down levelling
slow down switch up
D8
Y6
A-
D7
Y5
B+
D6
Y4
B-
D5
Y3
limit switch up (learn trip)
down limit switch (v>2m/s)
manual down
D4
Y2
10
B>
D3
Y1
A>
D2
Y0
V+:15V
D1
X26
X27
X28
X29
X25
JP5
X24
X23
X22
X21
JP6
X20
TXV-
X19
TXV+
10
X18
TXA-
X17
TXA+
X16
automatic
evacuation
X15
brake opened
X14
brake abrasion
monitoring
X13
brake monitoring
X12
brake closed
X11
inverter RUN
X10
contactor monitoring
brake contactor
X9
contactor monitoring
motor contactor 1
10
fire return home
9
X8
up levelling
8
X7
slow down switch down
7
X6
limit switch down (learn trip)
6
X5
up limit switch (v>2m/s)
5
X4
manual up
4
X3
0V
0V
+24V
+5V
0V
0V
JP4
3
X2
normal/inspection
6
5
4
3
2
1
JP3
2
X1
JP20
200
100
JP2
1
X0
V-: 0V
JP1
JP7
Configuration of inputs and outputs:
The in- and outputs are limited free configurable. The following table shows the basic settings which are
ok in the most of cases. Some signals have a different configuration in some special cases. These specials
you can find in the electrical drawing of each case. Thus significant is the electrical drawing.
SM01 terminals:
Terminal
JP1
Name
Description
Function
X0
Signal inspection on, respectively normal operation
input N
X1
Inspection/return motion up
input N
X2
Inspection/return motion down
input N
X3
Delay switch upwards/above for v>2,5m/s,
input N
Advise
F24=5
at short stop in the upmost stop.
Counting impulse B (hydraulic lift with magnet switch)
5
X4
Delay switch downwards for v>2,5m/s,
F24=3
input N
F24=5
at short floor in the lowest stop.
Counting impulse A (hydraulic lift with magnet switc)
F24=3
X5
learn trip -end-switch upwards/top
input N
X6
learn trip -end-switch downwards/down
input N
X7
Delay switch upwards/top
input N
X8
Delay switch downwards/down
input N
10
X9
re-levelling upwards (levelled)
input N
X10
re-levelling upwards (levelled)
input N
X11
Converter error signal or ready signal
input N
Monitoring approval-relay of the downwards valve
Rope lift
Hydraulic lift
X12
Firedepartement-controlling on
input N
X13
Fire stop 1
input N
X14
Fire stop 2
input N
X15
Motor contactor K1 Monitoring
input N
X16
Motor contactor K2 Monitoring
input N
Page 25
Manual F5021B - SM01 F5021 main board
Terminal
8
Name
X17
Description
Break contactor K8 Monitoring
Function
input N
Monitoring of the valve approval relay
9
X18
Door-zone-signal/ monitoring of safety circuit
input N
10
X19
Inverter RUN signal (open breaks signal)
input N
X20
Monitoring of the engine temperature
input N
X21
Lift shutdown at the next stop
input N
X22
Monitoring open breaks
input N
Monitoring minimum preasure
X23
Monitoring closed breaks
input N
JP5
JP6
X24
Anti surf (shaft door monitoring) deactivation
input N
X25
automatical evacuation on
input N
COM
common mass for inputs
COM
COM
Feed-in mass of the optocoupler
0V feed-in
10
+24V
Supply of the optocoupler
24V feed-in
TXA1+ CAN_H of CAN-Bus 1 inside the lift
datas
TXA1- CAN_L of CAN-Bus 1 inside the lift
datas
0V
GND
+24V
+24V
TXA2+ CAN_H of CAN-Bus 2 for lift groups
datas
TXA2- CAN_L of CAN-Bus 2 for lift groups
datas
0V
GND
+24V
+24V
AI1
JP7
JP8
Analog output current 4...20mA
AGND Feed-in mass for analog output
Use Twisted Pair
lines!
Use Twisted Pair
lines!
output AI
supply
AVS
Analog output power 0...10V speed set point FU
output AV
AVL
Analog output power 0...10V torque set point FU
output AV
B-
Encoder input channel B symmetric
input RS422-
B+
A-
A+
+15V
Page 26
Rope lift
Hydraulic lift
Rope lift
Hydraulic lift
Monitoring preasure relief
JP4
Rope lift
Hydraulic lift
Rope lift
Hydraulic lift
Softstart RUN signal (Approval for drive upwards)
JP3
Advise
input
RS422+
Encoder input channel A symmetrisch
input RS422input
RS422+
Powersupply for HTL encoder!!
supply output Attention! Do not
conect 5V encoder!
Manual F5021B - SM01 F5021 main board
Terminal
JP9
Name
0V
Y0
Description
Function
HTL inputs A and B (Open Collector) 0-100kHZ
Pre-controller-relay break contactor K8
relay-output
Valve-approval-relay
2
Y1
Pre-controller-relay break contactor High voltage for
arround 2s
JP10
relay-output
Y2
motor contactor K1
relay-output
Y3
motor contactor K2
relay-output
COM1 COM of relay-contacts Y0-Y3
Y4
Door-open relay door A
relay-output
Y5
Door-close relay door A
relay-output
Y6
Door-open relay door B
relay-output
Collected malfunction message
Y7
door-close relay door B
Circuit plan!!
relay-output
Engine tuning FUJI Gearless with incremental encoder
5
JP11
Circuit plan!!
COM2 COM of relay-contacts Y4-Y7
Y8
Trigger K14 (bypass door switch)
relay-output
Y9
End of automatical evacuation
relay-output
3
4
Y10
Trigger frequency inverter upwards
relay-output
Y11
Trigger frequency inverter downwards
Y12
Inverter Run-signal
relay-output
Y13
Multi-Step 1 speed signal
relay-output
Y14
Multi-Step 2 speed signal
relay-output
Y15
Multi-Step 3 speed signal
relay-output
JP12
Rope lift
Hydraulic lift
relay-output
LRV additional speed
10
Rope lift
Hydraulic lift
LRV inspection
9
Rope lift
Hydraulic lift
valve slow down
8
Rope lift
Hydraulic lift
valve fast down
7
Rope lift
Hydraulic lift
valve slow open
6
For Safety circuit
COM3 COM of relay-contacts Y8-Y9
valve fast open
Rope lift
Hydraulic lift
Rope lift
Hydraulic lift
Approval-relay downwards-valve
Advise
Rope lift
Hydraulic lift
COM4 COM of relay-contacts Y10-Y15
N-wire of the input terminals
X26
Scan emergency stop sector of the safety loop
X27
scan end of safety loop
inputs
230VAC for
scan of the
Page 27
Manual F5021B - SM01 F5021 main board
Terminal
JP20
JP15
Description
X28
scan revolving door contacts
X29
additional highvoltage input
N-type to the engine and break contactor
GND
Voltage supply contact of the main board
GND
+24V
GND
GND
DCD
RS232 interface
RXD
RS232 interface
TXD
RS232 interface
DTR
RS232 interface
JP22
Name
SGND RS232 interface
+5V
GND
D+
RS485-A
D-
RS485-B
Page 28
Only active if jumper J2 is installed. (hand terminal)
Function
security
circuit
Advise
Manual F5021B - SM02/SM03 cabin module
7.SM02/SM03 cabin module
JP8
JP7
JP6
JP5
JP4
JP3
JP2
JP1
1.
8
7
6
5
4
3
2
1
2.
16
15
14
13
12
11
10
9
3.
24
23
22
21
20
19
18
17
4. SM-03
32
31
30
29
28
27
26
25
JP10
JP4
JP3
SM-03
JP2
JP9
JP1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
JP8
JP7
JP6
JP5
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
JP7
20
19
18
17
16
15
14
13
12
11
10
TX18: not used
arrow UP TY0
TX17: fireman keyswitch
2
3
TX16: car light monitoring
arrow down TY1
TX15: Button Inspection fast
car light off TY2
TX14: keep door open (handicaped)
TX13: light gate B
gong TY3
TX12: door close limit B
overload indicator
TX11: door open limit B
TY4
TX10: insp. door open
10
11
buzzer
TY5
TX9: priority
12
13
TX8: insp. door close
14
SM-02
3
2
TX4: full load
19
20
TX3: overload
door close btn TX20
door close indic.
TX1 door close limit A
TX0: door open limit A
COM (0V) TX0 -TX18
com+
com+
CAN
TX2: light gate A
4
3
2
1
JP1
jp3
18
+24V
+0V
door open btn
com+
com+
4 TXA-
17
TX5: safety edge door A
jp2
16
j1
TX6: safety edge door B
3 TXA+
RS485
2 TXV-
15
TX7: empty load
1 TXV+
door open indic.
4
3
2
1
to Voice Announcer
Advise:
This SM02 will be replaced in future by SM02/H (in the cartop box) and SM03/G (in the COP). The
trigger of the doors (open and close) wont be done anymore by SM01 in the control cabinet; this will be
done by SM02/H in the cartop box. (changed configuration)
SM02 Anschlsse
Terminal
JP2
1
2
3
4
5
6
Name
TY0
Descripion
direction upwards
Function
Advise
relay-output
C.TY0 COM TY0
TY1
direction downwards
relay-output
C.TY1 COMTY1
TY2
Cabin light switch off
relay-output
C.TY2 COMTY2
Page 29
Manual F5021B - SM02/SM03 cabin module
Terminal
Name
TY3
Descripion
Gong (acustic signal)
Function
relay-output
C.TY3 COM TY3
TY4- Overload indicator -
Transistor NPN
10
TY+
+24V
11
TY5- Buzzer- (acustic signal)
Transistor NPN
12
TY5+ Buzzer+ (acustic signal)
+24V
13
AV+ Analog input 0..10V (weight measurement)
14
AV-
Analog input GND
15
D+
RS485-A
datas
16
D-
RS485-B
datas
17
18
19
Overload indicator +
+24V Power supply optocoupler
20
0V
TY
Indicator door-open-button -
Transistor NPN
C+
Indicator door-open-button -
+24V . R
C+
Door-open-button contact
+24V . R
JP3
4
JP4
TX19 Door-open-button contact
input P
TY
Indicator door-close-button -
Transistor NPN
C+
Indicator door-close-button -
+24V . R
C+
Door-close-button contact
+24V . R
TX20 Door-close-button contact
input P
COM COM for the inputs from TX0 till TX18
GND
TX0
Door-open-end-switch door A
input N
TX1
Door-close-end-switch door A
input N
TX2
Light gate door A
input N
TX3
Over load switch
input N
TX4
Full load switch
input N
TX5
Return motion switch door A
input N
TX6
Return motion switch door B
input N
TX7
Empty load-switch
input N
10
TX8
Door-open-button inspection
input N
11
TX9
Priority inside
input N
12
TX10 Door-close-button inspection
input N
13
TX11 Door-open-end-switch door B
input N
14
TX12 Door-close-end-switch door B
input N
JP5
Page 30
Advise
Manual F5021B - SM02/SM03 cabin module
Terminal
JP6
JP15
Name
Descripion
Function
15
TX13 Light gate door B
input N
16
TX14 button door keep open
input N
17
TX15 button inspection fast
input N
18
TX16 Cabin light monitoring
input N
19
TX17 Firedepartement-key-switch
input N
20
TX18 Free
input N
TXV+ +24V supply SM02
TXV- GND supply SM02
TXA+ CAN_H
TXA- CAN_L
D0
output to control of a voice announcement up to 255
annoucements.
D1
D2
output NPN
D3
output NPN
D4
output NPN
D5
output NPN
D6
output NPN
D7
output NPN
GND Voltage supply voice message
10
+24V
JP1
Jumper for CAN Bus termination. Only if the termination
is not activated yet in the cabin indicator board. (SM04)
JP7
Connector for button-connection-module SM03
J2/J3
Advise
output NPN
output NPN
In case voltage supply is only via JP6 install both bridges.
In no case install if JP2.19 and JP2.20 get supplied in
separate!
SM03 button module
It is possible to connect up to eight SM03 each with 8 buttons (up to 64 floor buttons)
Plug
SM03 Nr.1
SM03 Nr.2
...
SM03 Nr.8
JP1
floor 1
floor 9
...
floor 57
JP2
floor 2
floor 10
...
floor 58
JP3
floor 3
floor 11
...
floor 59
JP4
floor 4
floor 12
...
floor 60
JP5
floor 5
floor 13
...
floor 61
JP6
floor 6
floor 14
...
floor 62
JP7
floor 7
floor 15
...
floor 63
Page 31
Manual F5021B - SM02/SM03 cabin module
Plug
JP8
Page 32
SM03 Nr.1
floor 8
SM03 Nr.2
...
SM03 Nr.8
floor 16
...
floor 64
Manual F5021B - SM02/H cartop box module
8.SM02/H cartop box module
Terminal
Name
JP1
TXV+ +24V
TXV- GND
TXA+ CANH
TXA- CANL
COM COM for TY0,TY1
TY0
Drive-in-gong down
output TU
TY1
Drive-in-gong up
output TU
GND GND
+24V +24V
COM COM for TX0,TX1
TX0
End-switch door open door A
input N
TX1
End-switch door close door B
input N
COM COM for TY2-TY4
TY2
Scrambling door A
output TU
TY3
Door A closing
output TU
TY4
Door A opening
output TU
COM COM for TX2,TX3
TX2
Return motionswitch door A
input N
TX3
Light grid door A
input N
COM COM TX4-TX6
TX4
JP3
JP4
JP5
JP6
Description
Monitoring cabin light
Function
Advise
input N
Page 33
Manual F5021B - SM02/H cartop box module
Terminal
Name
TX5
Full load
input N
TX6
Over load
input N
COM COM TY5
COM
TY5
output relay
JP8
Description
Switch of cabin light
JP2
Connection for SM09IO/B add-on module
DB1
RS232 serial interface
SW1
Function
SW1.1 Both on for CAN-Bus scedulling
SW1.2
SW2
SW2.1 Both on for programm opload.
SW2.2 Both on for standard operation.
JP7
D0
Voice annoucement bit0
output TN
D1
Voice annoucement bit1
output TN
D2
Voice annoucement bit2
output TN
D3
Voice annoucement bit3
output TN
D4
Voice annoucement bit4
output TN
D5
Voice annoucement bit5
output TN
D6
Voice annoucement bit6
output TN
D7
Voice annoucement bit7
output TN
GND
10
+24V
Page 34
Advise
Manual F5021B - SM09IO/B Add-on module
9.SM09IO/B Add-on module
Terminal
Name
Description
JP1
Connection to SM02/G or SM02/H
JP2
Connection for additional SM09IO/B add-on module
JP3
JP4
JP5
JP6
JP7
JP8
JP9
JP10
Function
EY0
Open door B
output relay
EY1
Close door B
output relay
EY2
Scramble door B
output relay
COM COM for EY0-EY2
EY3
COM COM EY3
EY4
COM COM EY4
EY5
COM COM EY5
EX0
End-switch-door open door B
input N
EX1
End-switch-door close door B
input N
COM COM EX0,EX1
EX2
Light gate door B
input N
EX3
Return motion switch door B
input N
COM COM EX2,EX3
EX4
COM COM EX4
EX5
COM COM EX5
Free
Free
Free
Free
Free
Advise
output relay
output relay
output relay
input N
input N
Page 35
Manual F5021B - SM02/G car panel board-module
10.SM02/G car panel board-module
Terminal
Name
JP1
TXV+ +24VDC
TXV- GND
TXA+ CANH
TXA- CANL
TX16 button door keep open (HOLD)
input N
TX17 Free
input N
TX18 Priority inside
input N
TX19 Free
input N
TX20 Firedepartment control key-switch
input N
COM COM 0V, TX16-TX20
JP5
JP6
JP7
TY
Description
LED door-open-button minus
LED+ LED door-open-button plus
GND Door-open-button
TX21 Door-open-button
TY
LED door-close-button Minus
LED+ LED door close button Plus
GND Door-close-button
TX22 Door-close-button
JP2
Connection for SM03 call module
JP3
Connection for SM09IOB add-on module
DB1
RS232 serial interface
Function
Advise
Relay-output
Relay-output
output N
input N
output N
input N
Page 37
Manual F5021B - SM02/G car panel board-module
Terminal
SW1
Name
SW1.1
Description
Both on for turning on CAN scedulling resistor.
SW1.1
SW2
SW3
Page 38
SW2.1
Both on for programm upload.
SW2.2
Both off for standard operation
SW3.1 SW3.2 SW3.3 SW3.4 Type cabin indicator board
ON
OFF
OFF
OFF
Standard-indicator board
OFF
ON
OFF
OFF
Indicator board B-flip side
(selective door)
OFF
OFF
ON
OFF
Operator indicator board
OFF
OFF
OFF
ON
Additional indicator board
Function
Advise
Manual F5021B - SM04HRF floor module
11.SM04HRF floor module
GND
5V
24V
-A0
A1
A2
A3
A4
rolling
down
up
GND
2
4
6
8
10
12
14
16
18
20
22
24
26
JP11
program
down call
up call
keylock
free
VIP
door lock monitoring
nu
SW2
2
JP9
ON
SET ADR
display mode
down indicator
up indicator
dwn arrow
up arrow
SW1
additional
door lock switch
TxA-
TxA+
bus termination
TxV-
TxV+
ON
GND
+24V
6 5 4 3 2 1
+24V
JP6
8 7 6 5 4 3 2 1
JP10
JP1
JP2
1 2 3 4
1 2 3 4
Pin
Description
Function
JP1
TXV+ +24V
JP2
TXV- 0V
TXA+ CAN_HI
datas
TXA- CAN_LO
datas
+24 for button (COM)
Hall call downwards
input P
Hall call upwards
input P
input Parking
input P
Firedepartement control
input P
VIP Control
input P
Door-locking-bolt-monitoring at anti-surf
input P
Not used
input P
0V output
+24V output
Indicator Hall call down
output NPN
Indicator Hall call up
output NPN
Continued travel arrow downwards
output NPN
Continued travel arrow upwards
output NPN
JP10
JP9
Advise
For specail versions it is
possible that there is a
different assignment, e.g.
In-use-light, cabine here,
etc.
For spare part oder,
please always mention the
construction number
Belegung kann
abweichen.
Page 39
Manual F5021B - SM04HRF floor module
Pin
JP11
SW2
Page 40
Description
Function
Advise
GND
+5V output (max. 50mA)
+24V output (max.50mA)
Free
10
A0
output NPN
Instead of STEP LED
dot-matrix-display it is
possible to connect at this
interface a display of
other manufacturer with
binary control, COM
Anode.
12
A1
output NPN
Switch SW2-1 to ON!
14
A2
output NPN
16
A3
output NPN
18
A4
output NPN
20
In use/ lift in operation
output NPN
22
down
output NPN
24
up
output NPN
26
GND
OFF: standard; ON: with call up or down you could set
the adresse on the LED display.
OFF: STEP LED-display, ON: external display binary.
Manual F5021B - Security
12.Security
2
Lx
mark if safety switch is connected.
S17
X20 1
X21 1
S50
11
Inspectionswitch
12
X51.1
S11
.2
X51.3
X10.5
X51.2
emergency
stop (pit)
X11.3
X10.1
.4
22
32
44
X11.1 X10.2
S35
X51 .5
.6
S27
9 X47 8
X46 8
S31.n
S32.n
S31.1
S32.1
S60
speed
governor
11
23
12
24
13
S61
X60.15
K10
emergency control bypass
13
14 13
K12
14 21
K14
22
13
X60.12
emergency stop
X60.7
S501
14
.8
.7
17
12
X60.13
JP11.1
.6
A1: safety loop modul on SM01 mainboard
JP11.5
C
K01
K02
K08
JP16.3
JP16.4
JP16.1
open/hold
.5
Nx
safety loop
JP11.3
B
K08a
V8
JP11.6
JP11.2
motor contactor 1
A1
K.RF A1 K1
A1
K2
K1
JP16.2
motor contactor 2
Page 1
JP16.6
Y.FR Y.FA
X11
11
12
11
S510
16
K11
S502
C
X11
14
door zone bypass (optional)
Speed Governor
Y.FA: coil for remote trip
X60.9
insp.
down
X60.11
S26
S60
5
S53
.7
X11.2
53
54
Inspection switch
S36
X60.14
4
43
X51.4
X10.7 and .8 only
if oil dampers are
installed!
(v=1.6 m/s)
oildamper
switch
switch at
safety gear
tension weight
.6
31
S52
accelerate
S10
.4
S25
brake control
X10.3
S20
S19
S18
door lock
car B-side
21
insp.
up
door lock shaft
B-side (option)
S40
emergency
stop cabinet
door
lock car
door lock shaft
XES.1
final limit
switch
safety
gear
emergency
stop
inspection
XES.2
emergency
stop B-side
roof
exit
optional
S50
emergency operation
1
Page 1
K8
A2
A2
A1
A2
K8
S501 K8 6
S502 K8 4
X60.6
15
14
41
The safety loop modul is built of 3 inputs 230VAC
and 4 relays for controlling main contactors.
This part of PCB is certified according to EN81.
Important! The neutral wire N to the main contactors
must be connected via PCB as shown!
created
last modif.
name
M.Aicher
date
29.10.2009
M.Aicher
07.01.2010
X60.5
A2
X60.4
X59
42
.5
Y1
Safety-Loop
.6
40
.7
Y2
200VDC Brake (2 circuits)
No
Page
03
Vers.
Security circuit
The safety circuit always builded up in the same way and is devided into 3 sections for security switches:
Emergency stop
contains all security switches, which are always activ, thus never are allowed to
be by-passed. This affects all emergency stop switches, the counterweight
switch, maintenace openings, etc.
emergency control bypass
contains all security switches, which get by-passed in return motion control,
thus safty gear, emergency-end-switch, speed restrictor.
doorzonenbypass
contains all blocking switches of the shaft doors and the door contacts of the
cabin doors.
At the end of the security circuit conditioned the inspections- and return motion control.
Optional security switch
In the connection scheme all popular security switches drawn in. Security switches which are not always
necessary, like blocking switch of the B-door, are drawn in as optional. If it is availble it have to be marked
on the connection scheme and certainly also connected.
The terminals for optional security switches are factory-provided by-passed with wire-bridge. So it is
secured, that the bridge get removed by connection of a switch.
Page 41
Manual F5021B - Security
Matter: By-passing of security circuits!
Basically it is not allowed to make security circuits effectless per by-passing.
But it is not possible to install a lift without by-passing temporary parts of the security circuits.
Only use wire-bridges for by-passing, which you install at the terminals for the security switches.
With this handling in any case the bridge will be removed when you install the switch. Never use
shorting plug bridges you might forget these conventionally! As wire, please use an eye-catching
one, but not the greenyellow colored one! Please also avoid to have these too long (they should not
loll out of the cabinet in worst case somebody is closing the door and you may have 230V of the
Security circuit at the cabinet).
Security circuit
K178
B
The security circuit is only needed, if re-levelling with
open or pre-operating doors is required! For hydraulic lifts
is due to the re-levelling the security circuit mandantory!
-X52
door zone sensor 2
door zone sensor 1
safety circuit (only when preopening doors
or relevelling with open doors)
K179
B
-X52
11
178
The assignment of the security circuit are two sensors,
which are operating independent one from the other, to
recognize where the door zones are, to compare the datas
and respectivley make it possible to by-pass the door
contacts within the door zones or not. For instance it
should be attained the security of a castor security switch.
The security circuit is based on the common principle of
the strip circuit. Every circuit switch part have to change it
s attitude in order to make an alliance possible.
12
179
100
43
21
100(+24V)
K10
13
K12
14
33
K10
K11
44
43
K12
34
21
33
K11
44
22
K10
34
22
33
K12
34
V12
A1
A1
-K10
-K11
A2
release delay
appr. 100ms
A1
R12
220R
470/63V
-K12
A2
C12
A2
200(GND)
door zone bypass
K10
The used security circuit is on a seperate board and is typeexamination tested.
13
K11
14 13
K12
14 21
K14
22
13
14
KoSi81-3
Components
K11
K10, K11 und K12 are contactor or security-relays with positively
driven contacts. If a closer bonds, the opener stay open and
contrariwise.
K10
K12
K14
K10
allocated to the sensor B178 of door zone 1
K11
allocated to the sensor B179 of door zone 2
K12
monitoring of K10/B178 and K11/B 179
K14
relay without security function, allows the controller the disconnection of the bypass.
S 50
security contact in the inspections switch avoid bypassing during inspection.
JP1
1
JP3
JP4
1 2
1 2
Functionality:
Initial position:
Lift outside of the doorzone, K10 and K11 dropped-out, K12 tightened.
Lift runs in door zone:
B178 and B179 get closed successive or simultaneous.
First K10, than K11 activates. K12 drop-out after activation of K11. by-pass
completed.
R12 and C12 delay the depression of K12 for max. 100ms, in order to make
lock K11 possible.
Page 42
Manual F5021B - Security
Lift is leaving door zone:
B178 and B179 opens, K10 and K11 depresses, K12 activate.
The circuit is ready for the next switching cycle.
Possible sources of error:
Error
Simulation
Action at early opening door
(door opens in doorzone)
No hand-off. Lift stops in door zone
No hand-off. Lift stops in door zone
No hand-off. Lift stops in door zone
While leaving the door zone K11 is depressing, K12
do not activate anymore. At the next run-in K11 is
not activating anymore. Lift make stop by open the
door emergency stop
B179 hot-wired/K11 do not depress
While leaving door
While leaving the door zone K10 is depressing, K12
zone, restrain K11
do not activate anymore. At the next run-in K10 is
festhalten until next
not activationg anymore. Lift makes stop by open the
run-in.
door emergency stop
K12 do not activate anymore
Disconnect K12.A1
K10 and K11 do not activate anymore. Lift stop
while open the door in the door zone emergency
stop
According to EN81 14.1.1 one single error do not lead to a dangerous operating conditon and will be
recognized, as the lift will make an emergency stop by disconnecting the security circuit while opening the
door within a door zone.
B178 discontinued/K10 no activation
B179 discontinued/K11 no activation
K12 do not depress
B178 hot-wired/K10 do not depress
Pinch off B178
Pinch off B179
Restrain K12
While leaving door
zone, restrain K10
until next run-in.
In addition there is existing a further monitoring done by the controller.
Dependent up on the re-levelling sensors, which are independent from the door zone sensors, K14 is
activated.
In the unlikely case, that both door-zone-sensors by leaving the door zone would be hot-wired, a by-pass
outside of the door zone will be avoided by the circuit via K14.
Additional monitoring by controller
The controller is monitoring via K10, K11, and K12 the security circuit. During the journey the contact
chain have to be closed once inside the door zone and have to be opend once outside the door zone. In case
of an error, the installation will be shut down at the next stop with error message. Part of encoder
Scan control at security circuit
On the board SM01 F5021 there are 3 inputs for 230V. These are installed according to the requirements of
EN81 at scan controls for security circuits. This is confrimed by TV with a confirmation assessment.
Basically the circuit consist of pre-resistors, protection diodes and optocoupler with VDE-approbation.
It is executed the terms accourding to EN81 for a secure disconnection of the 230VAC-page from the
24VDC-page as well as for exclusion of errors.
N-Wire
The N-wire of the security contactor , means motor contactor K1 and K2, as well the break contactor K8
and maybe K8a have to be controlled via the board!
At a N-wire-breakage the contactor than have the necessity of drop-out, independent of the theoretical
possible chance of a hot-wire in the optocouplers which may make a partial by-pass of the security circuit
possible.
Page 43
Manual F5021B - Security
Check:
Connect the controller free of voltage!
With the continuity checker between N-input terminal and A2 (N-terminal) of security contactor (K1, K2,
K3, K8), check the run.
With a pluged JP11(main board) you have a run, with pultruded JP11 there must not be any run..
Pilot relay
On the board SM01sup (F5021) there are also 4 pilot relays for security contactors . This part of circuit is
also confirmation checked, means it is possible to connect directly the end of the security circle, the
security contactore sources their controller voltage directly out of the security circle.
The security contactors, motor contactors K1 and K2, as well the break contactor K8 are seperatly
monitored. If there is one of the contactors is not depressed before a journey, the control gets blocked and
have tho be reseted manually.
Monitoring of journey
SmartCom F5021 is monitoring via the encoder of the engine and the re-levelling-sensons the reaktions of
the lift in regards on the driving commands to the inverter. If there are signals missing, the drive gets shutdown, latest after 20sec. .
Restart of journey only possible after reset of the main board.
Check:
1. Advise the lift to drive from the lowest to the topmost stop and do the unplug JP7 respectively JP8 (Encoderinputs) at the main board. The lift have to be shut dwon after arround 20 sec.
2. Uninstall 170 or 171 (re-levelling-sensors). After arround 20sec. re-levelling the lift get shut dwon.
You easily can set diving commands via the status window Call.Func.
For short lifts 20sec. may be a long time frame. In this case you could reduce temporarily the parameter
Monitoring of journey via the menu parameter-group F in order to simplify the checking.
Subsidiary advises for inspection:
Lift controller of STEP Sigriner Elektronik GmbH are manufactured and checked with EN81 and VDEstandards. The used components, especially the main- and auxiliary contactore are selected respectively to
the requirements of EN81, VDE0100, VDE0660.
All adjustable components, like engine-security-switch, frequency inverter etc. are allready pre-adjusted by
us as far as possible. It is incumbent upon the installing company to adjust these components before
implementation with respect to the resources..
By default the security cycle is fused with a power protection switch with F2 (2A Charakteristik C). As a
maximum a power protection switch with 4A can be used.
gernerally:
Keep door closed:
In order to be able to check without any interruption, it is possible to block the
door in the menu under subtitle Test Run and unter subtitle Reg it is possible to
make calls.
Inspection travel:
always have priority before return motion and is also possible with activated
Page 44
Manual F5021B - Security
return motion control. The by-pass of the security switch is raised. With
reaching the correction switch above or below, the speed is reduced. At the
inspections-end-switch will be stopped. Inside of the door zone the function of
the door can be checked with door open/close. Otherwise during inspection
the door is always closed.
Retrun motion drive:
this is only possible with deactivated inspection control. Appropriate security
switches, like emergency-end-switch, arrester-switch etc. will be by-passed.
Also the return-motion-drive is stopped at the inspection-end-switches. These
have to be by-passed for testing the driving-ability.
Cabin light:
If blackout of cabin light (simulation with F02) the lift will be shut down in the
next stop and the door will be opened.
Temperature of engine:
A PTC thermistor switch-off leads as well to a shut down in the next possible
stop.
Isolation measurement:
By default the controller undergo a isolation masurement in the factory. The at face arranged measurement
refers only to the connected resources of the lift.
Absolutely consider the valid security instruction for at face isolation measurement. There is a danger for
humans and technique!
In order to avoid damages of the controller, switch off the respective fuse F2 at the controller for
measurements.
Connection of frequency inverter, USV-systems and other systems with power semiconductors and filter,
most likely have to be disconnected or hot-wired according to manufactures for testing purpose. For this
follow the advises of the manufactures.
Incorrect done isolation measurement can lead to extensive damage. In this case STEP Sigriner Elektronik
Gmbh explicit do not guarantee!
Page 45
Manual F5021B - Triggering of frequency inverter
13.Triggering of frequency inverter
SmartCom have 2 kinds of triggering a frequency inverter available:
1. Analog: The converter is triggered via the analog output. The travel curve at this will be created by the
controller, whereby direct drive-in makes possible with every converter with analog input.
2. Multistep binary: The converter provides dependent of 3 binary signals, up to 6 steps of driving. The
travel cycle mostly defined by the converter.Direct drive-in is not possible. Through ideal choice of speed,
it is however possible to reach minimal creep ways. Binary triggering is for most of the industry converters
possible.
Generally
Before start of a journey for all controllers the erroroutput and the ready message of the converter have to
be inactive, also all security contactors (K1, K2, K8) have to be depressed. First of all, after a driving
command the main contactors K1 and K2 will be activated. Via the feedback (contactor monitoring)
SmartCom is checking the activation. If this is effective, the conrol of the converter will be activated. Now
a RUN-signal is happen from the converter to the control. After that the break is opening. The triggering of
the contactore always have to be happen from the controller, as otherwise the timing of the contactor
monitoring would not work.
If you buy the controller completly with converter or provide the converter, it will be pre-programmed and
adjusted with intelligent values at our testbed. Than the normal case you just need to do at face adapting
the motor datas and maybe have to do a auto-tuning.
Triggering Multistep binary
At nearly all industrie-converters it is possible to choose more speeds binary, means e.g. with 3 control
cables it is possible to choose 8 speed variants.
Smartcom is using 3 cables for choosing 6 speeds. Based on this the travel characteristics could be better
optimazed. V1 to V3 intended as follows:
V1: Journey from floor to floor
V2: Journey with a floor in between
V3: Journey with more than one floor in between
In the normal case V1 is enough, but for fast lifts
(V>1,6m/s) or for short stops V1 is needed for Journey
from floor to floor, V2 for long-distance journey. For lifts
faster than that (>3m/s) V3 come into the play.
The proper breaking distances are setted at the encoder
with the speeds, high- respectively lowruntimes and
roundings (S-curve). Which speed is choosen by the
controller depends on the respective prameters in the
controller (F6-F11).
M
ulti
ste
p1
M
ulti
ste
p2
M
ulti
Ste
p3
Y1
3
0
1
0
1
0
1
Y1
4
0
1
0
0
1
1
Y1
5
0
0
1
1
1
1
e.g.
Param
eter
Yaska
wa
speed
Stop
re-levelling
Inspection
V1
V2
V3
D1-01
D1-04
D1-05
D1-06
D1-07
D1-08
Page 47
Manual F5021B - Triggering of frequency inverter
Travel cycle
Speeds and breaking distances
Out of the lift datas result the frequenzes which have to be setted up at the encoder: f = v
f Nenn
v Nenn
For a lift with 1m/s with 50Hz the inspection speed 12,5Hz have to be setted, if 0,25m/s are desired.
The braking distance results out of the desired delay, of the speed and of the rounding.
Approximately we forget about the rounding off and act on the assumption of a middle delay.
The time for the looping floor results out of Vnenn and a as follows: T =
With a deceleration of 0.5m/sit
results a down delay of 2s.
v Nenn
a
v (m/s)
In thes time the lift runs
s = 0,5 v Nenn T
For 1m/s and 2s results a
brakedistance of 1m.
a
Vnenn
s(m)
Brakedistance
Down delay T
Page 48
t (s)
Manual F5021B - Parameter list
14.Parameter list
No.
Marking
Description
Stand.
Area
Unit
Value
F0
acceleration
acceleration
550
2001500
mm/s2
0.55m/s2
F1
deceleration
deceleration
550
2001500
mm/s2
0.55m/s2
F2
S Jerk T0
Rounding off at start
1300
1004000
ms
1.300s
F3
S Jerk T1
Rounding off at crossing to
standard operation
1100
1004000
ms
1.100s
F4
S Jerk T2
Rounding off at the beginning of
the delay phase
1100
1002000
ms
1.100s
F5
S Jerk T3
Rounding off at stopping
1300
1002000
ms
1.300s
F6
Rated speed
Nominal speed of the lift
1750
2006000
mm/s
1.75m/s
F7
Motor speed
Nominal rotation speed of engine
1450
5010000
rpm
1450rpm
F8
Encoder Pulses
Encoder release (Pulse per
rotation)
1024
10020000
ppr
1024ppr
F9
Parking floor
Parking floor
148
F10
Floor offset
Floor offset at lift groups
048
F11
No. of Floor
Number of floors
18
248
F12
Inpection Speed
Speed for inspection
250
10500
mm/s
0.250m/s
F13
Relevel Speed
re-levelling speed
60
10400
mm/s
0.060m/s
F14
Hall call door close
delay
Door-open-time frame after
exterior call
40
0600
0.1s
4.0s
F15
Car call door close
delay
Door-open-time frame after interior
call
25
0600
0.1s
2.5s
Brake open delay
Delay between FU Run signal and
break contactor on.
050
0.1s
0.2s
Softstart Delay
Delay between K1 off and K2 off
F17
Brake close delay
Delay between FU-stop command
and break contactor off
050
0.1s
0.6s
F18
Fire home
fire floor 1
148
F19
Second fire home
fire floor 2 (have priority)
148
F20
Homing Delay
Parking time frame (until journey
to <F9>)
0no parking journey
0600
F21
Level adjust distance
V0 stop Distance
240
mm
F22
Main landing
Main stop at group function, see
(F20F196F197 )
148
F23
Group control mode
Groupfunction
0Simplex or Duplex-Master
1Duplex slave
2at external group processor
3at ring groups (see F181)
03
F24
Drive Mode
Triggering the frequency inverter
0Multistep1Analog
05
F16
0s
6mm
Page 49
Manual F5021B - Parameter list
No.
Marking
Description
Stand.
Area
Unit
Value
3: Hydraulic with solenoid switch,
5: Hydraulic with encoder
F25
Input Type 1
Typ of input closer alternatively
opener for inputs X0-X15
480
065535
F26
Input Type 2
Typ of inputs closer alternatively
opener for inputs X16-X31
83
065535
F27
Input Type 3
Typ of inputs closer alternatively
opener for inputs TX0-TX15
6283
065535
F28
Input Type 4
Typ of inputs closer alternatively
opener for inputs TX16-TX31
065535
F29
Service floor setting 1
Approval floor 1 - 16
65535
065535
F30
Service floor setting 2
Approval floor 17 - 32
65535
065535
F31
Service floor setting 3
Approval floor 33 - 48
65535
065535
F32
Inverter type selection
in Digital control
frequency inverter typ:
0: YASKAWA,CT,FUJI,iAStar
1SIEMENS
2: KEB
3: MICO
4: SIEI
5: Dietz
6: NEW FUJI
7: User defined (look F240
F249)
07
F33
Interval between trips
in automatic running
test
Time between calls at automatic
test (accidental commands)
0: no function
065535
F34
Number of trips in
automatic running test
Number of automatical test drives
0: no test-drive
065535
F35
Fireman mode
0Standard
EN81-71 firedepartment control
2without key in the cabin
3with key in the cabin
Pubel (RUS) firedept. control
4without key in the cabin
5with key in the cabin
0~5
F36
Waiting time for break monitoring
Brake switch detection
switch
time
0no break monitoring
10
0100
Adress for remoute surveillance
via RS485 network:
255 standard for single lift
255
0255
V1 Dec.distance
Breaking distance for V1 (floor
drive)
1300
V2 Dec.distance
Breaking distance for V2 (2-floor
drive)
V3 Dec.distance
Breaking distance for V3 (multiple
floor drive)
F37~F
Spare
43
F44
F45
F46
F47
Page 50
Local address in 485
serial communication
0s
0.1s
1s
2002500
mm
1.300m
2900
5004500
mm
2.900m
4000
5006500
mm
4.000m
Buffer
Manual F5021B - Parameter list
No.
Marking
F48~F
Spare
49
Description
Stand.
Area
Unit
Value
Buffer
F50
Front door-open
allowed 1
approval door A at floors 1-16
65535
065535
F51
Front door-open
allowed 2
approval door A at floors 17-32
65535
065535
F52
Front door-open
allowed 3
approval door A at floors 33-48
65535
065535
F53
Rear door-open
allowed 1
approval door B at floors 1-16
065535
F54
Rear door-open
allowed 2
approval door B at floors 17-32
065535
F55
Rear door-open
allowed 3
approval door B at floors 33-48
065535
Fine settup for stop upwards: 50
for direct drive-in, >100 with creep
drive
50
0200
mm
V0 shut down delay upwards. (at
Hydraulic with solenoid switch)
050
0.1s
Fine settup for stop downwards:
50 for direct drive-in, >100 with
creep drive
50
0200
mm
V0 shut down delay downwards.
(at Hydraulic with solenoid switch)
050
0.1s
050
0.1s
0.5s
1200mm
F56
Leveling adjustment
up
Leveling adjustment
down
F57
F58
Speed curve delay at
start
Delay between FU Run signal and
start of driving cycle
F59
Spare
Buffer
F60
Motor contactor 1
detection mode
Engine contactor arrangement: K1
can be positioned before und
behind the encoder, K2 is always
behind the encoder and always
controlled.
0: Engine contactor K1 before FU
without monitoring.;
1: Engine contactor K1 before FU
with monitoring;
2: Engine contactor K1 behind FU
without monitoring
3: Engine contactor K1 behind FU
with monitoring
03
F61
Gong Output distance
Distance before floor for triggering
the gongs
1200
01500
mm
F62
Traval time limit
time for travel-time-controlling
32
245
F63
Multi-speed setting
Number of travel steps at
Multistep-control of the FU
15
F64
Inspection allowed
door operate
Approval of door movements at
inspection
0doors blocked
1doors enabled
01
50mm
50mm
32s
Page 51
Manual F5021B - Parameter list
No.
Marking
Description
Stand.
Area
Unit
Value
F65
Indication of floors
F112
Configuration of the displays
(display codes) for the floors 1-48
F113~
Spare
F114
Buffer
F115
Door close time limit
Door run time close (in case of no
end-switch)
15
530
15s
F116
Door open time limit
Door run time open (in case of no
end-switch)
15
530
15s
F117
Holding time
Door-open time frame after
pushing the keep-door-openbutton.
60
0255
60s
F118
Holding time for the
handicapped
Door-open time frame after
pushing the keep-door-openbutton for disabled person.
30
0255
30s
Priority Mode
Door mode if priority inside
0Hold door close button for
closing the door
1Door make close after
command
F120
Number of
registrations annuisance
Violation detection interior call
0no function
1Stop without erasing light grid
command
220max. Number of accepted
commands at the same time when
empty load TX7 (cabin empty) is
active.
020
F121
Forced door-closing
enable
Door scrambling:
0off, 1on
01
F122
Run enable delay
Time between break off and FU
drive signal off (speed and
direction).
0100
0.1s
0.3s
Type of existing exterior-calls
0only simple calls ( not
selective)
1Selective doors: SM-04
address 49~96 for B-door exteriorcalls.
2calls for disabled persons: SM04 address 49~96 for disabled
person exterior-call (priority).
3Selective door and disabledperson-calls: SM-04 address
33~64 for B-door calls, 65~96 for
disabled person-calls (priority).
0~3
05
mm
300mm
F119
Call classification
F123
F124
Spare
Buffer
releveling times
Number of failed tries of relevelling until malfunction is
displayed.
F125
F126
Page 52
Short floor
deceleration distance
Short travel delay distance
0255
300
Manual F5021B - Parameter list
No.
Marking
Description
Stand.
Area
01
F127
deceleration switch
distance detect
Monitoring the distance of the
delay switches before terminal
stops (in case of to short)
0no
1yes
F128
Front and rear door
operate mode
Door mode at two doors
0selective door control active
1both doors controlled together
01
Relevelling with door
open and/or pre-open
door Enable
re-levelling with open door/
prerunning door opening (requires
security circuit):
0no security circuit
1prerunning door
2re-levelling with open door
3both
07
Holding dooropening/closing
torque.
Door triggering (keep close/open):
0no close/open-keeping
Bit 1door open-keeping (in case
cabin door is pulled by the shaft
door)
Bit 2door close-keeping (in case
tie bolt opens without keep-closemoment)
Bit 3keep close during the
journey (in case tie bolt bangs
against the locking bolt)
Bit 4no door-close-end-switch
Bit 5AT120 door control
Bit 6revolving door
065535
F131
block floor NO.
blockable floors
0: not active
164: number of the floor which
have to be blocked.
064
F132
block floor start time
Time at which the floor <F131>
should be closed: e.g. 730 for
7:30 oclock
065535
F133
block floor end time
Time at which the floor <F131>
should be released. e.g.: 930 for
9:30 o`clock
065535
F134
floor with forced stop (by crossing
Compulsory Stop Floor the lift is stopping mandatory, also
1
without a call)
Bit mask for floors 116
065534
F135
Compulsory Stop Floor
Bit mask for floors 1732
2
065535
F136
Compulsory Stop Floor
Bit mask for floors 3348
3
065535
F137
NS-SW Floor 1
Defines floors, which can be
blocked with a key-switch:
Bit mask 1-16
65535
065535
F138
NS-SW Floor 2
Bit mask 17-32
65535
065535
F139
NS-SW Floor 3
Bit mask 33-48
65535
065535
F129
F130
Unit
Value
Page 53
Manual F5021B - Parameter list
No.
Marking
Description
Stand.
Area
01
Unit
Value
F140
Alone door zone
Second door zone active at door
open:
0X9/X10 configures door
opening.
1X18 configures door opening.
F141
Motor contactor off
delay
Caster time of engine contactore :
approval off=>contactore off.
5100
0.1s
0.5s
F142
door open/close delay
Caster time of the door engine
contactore (after activation of the
end-switch)
010
0.1s
0.1s
F143
Spare
Buffer
F144
Enable off delay
Caster FU-approval after
deactivation of the direction
signals.
0100
0.1s
F145
Spare
Buffer
F146
Spare
Release the scan of SM02
F147
Spare
Buffer
F148
Valid Period password
PIN for run-time-bound
065535
Valid Period mode
0: no run-time-bound
1: approval till date
2: approval for run-time-hours
3:
03
Number of year (F149=1)
e.g. F150=10 => 2010
099
Number of run-time-hours if
<149=2>
065535
Month and day if <F149=1>
e.g. 531 mean 31st may
01231
F149 = multiplier for F150
065535
180
065535
065535
Breaking distance for V4 at 4
floors drive (at fast lifts)
5500
150065535
mm
5.500m
6500
150065535
mm
6.500m
07
F149
F150
F151
Valid Period time 1
Valid Period time 2
F152
Fan & light Delay
Caster time for cabin light/ fan
after the last travel
F153
Spare
Buffer
F154
Short Floor
Definition of the short drive floors
at hydraulic with solenoid switch
F155~
Spare
F156
F157
V4 Dec.distance
V5 Dec.distance
Breaking distance for V5 at 5
floors drivefahrt (fast lifts)
F159
Spare
Buffer
Page 54
Cancel Call model
180s
Bitmask
Buffer
F158
F160
Have to be 0!
call liquidation
Bit 1: Doubble klick on interiorcommands liquids all calls.
Bit 2: Doubble klick on exteriorcommands liquids all calls
Bit 3: Violation detection
Manual F5021B - Parameter list
No.
F161
F162
F163
F164
F165
Marking
Block floor during time
Description
Blocking of floors
(F137,F138,F139)
0: no blocking
1: block with time F131
2: blocking with key-switch
Stand.
Area
01
Spare
Buffer
OEPS Running
Operation with emergency-powersupply
0: no
1: possible
01
Load device type
Type of load-measure-equipment
and load-compensation at FU
start.
0: Load measurement via CANBus, over-load and full-load-switch
via the cabine module, loadcompensation calculated by the
main module.
1: Load measurement and
-compensation via CAN-Bus, over
load and full load calculated by the
main module.
2: Loadmeasurement and
-compensation via CAN-Bus, over
load- and full load switch via the
cabin module.
3: Load measurement via CANBus, over load, full load, load
compensation calculated by the
main board
03
Door open selection.
Door open functionality:
Bit 1: no open/close during
inspection.
Bit 2: no opening of the door
during test-operation
Bit 3: door A basic position open
at main stop
Bit 4: door A basic position open
at every stop
Bit 5: door B basic position open
at main stop
Bit 6: door B basic position open
at every stop
065535
F166~
Spare
167
Unit
Value
Buffer
F168
Lift numbering for IC
card service
RFID card reader
0: no RFID card reader
1~255 adress of the lift
0255
F169
Setting landings for
up/down calls by IC
card
RFID card reader generates
0- downwards calls 1- upwards
calls
01
F170
IC card service floor 1
Floors which are only approved
with RFID:
Bit mask Interior calls 1~16
065535
Page 55
Manual F5021B - Parameter list
No.
Marking
Description
Stand.
Area
F171
IC card service floor 2
Floors wich are only approved with
RFID:
Bit mask interior calls 17~32
065535
F172
IC card service floor 3
Floors wich are only approved with
RFID:
Bit mask interior calls 33~48
065535
F173~
Spare
F174
F175
Creeping speed at
start
Unit
Value
0100
mm/s
0.006m/s
0.1%
100.0%
Buffer
Start of creep speed
also see F186
F176~
Spare
F179
Buffer
F180
Speed Gain
Assignment of the nominal speed
of the lift with top values of the
analog outputs.
50.0% - 150.0%, standard 100%
1000
5001500
F181
Group Lift No.
Number of the lift within a group:
smallest number have highest
priority (F32=3)
07
F182
Steps of speed
reduction switches
Number of driving-steps, which are
used for stopping (only at
Multistep-control)
14
F183
Speed at self-learning
for Analog
Speed at reference journey (only
analog-control)
800
100800
mm/s
0.800m/s
10ms
0.50s
%%
0.0%
F184~
Spare
F185
Buffer
F186
Creeping time at start
Time of creeping at start
also see F175
50
01000
F187
Monitor state
Status Monitoring
0Journey counter
1Malfunction of encoder
2CAN-Bus Rx malfunctions
3CAN-Bus Tx malfunctions
4CAN-Bus Error-Resets/sec
5Duplex Rx-Error
6Duplex Tx Error
7Duplex Error Resets/sec
07
F188
Spare
Buffer
F189
Spare
Buffer
F190
Service floor setting 4
Floor approval bit mask 49-64
65535
065535
F191
Front door-open
allowed 4
Door A approval bit mask 49-64
65535
065535
F192
Rear door-open
allowed 4
Door B approval bit mask 49-64
065535
F193
Empty-load
compensation at
lowest landing
Empty load-compensation at
lowest floor
11000
Page 56
Manual F5021B - Parameter list
No.
Marking
F194
Full-load
compensation at
lowest landing
F195
Stand.
Area
Unit
Full-load-compensation at lowest
floor
11000
%%
0.0%
Full-load
compensation at top
landing
Full load-compensation in topmost
floor
11000
%%
0.0%
F196
2nd main landing by
duplex control
2. main stop at Duplex
148
F197
3rd main landing by
duplex control
3. main stop at Duplex
148
F198
Spare
Buffer
F199
NS-SW Floor 4
Blockable floors bit maks 49-64
65535
065535
F200
limited distance in
inspection mode
Virtual inspections-end-switch
(mm before topmost stop)
Inspection move for
limit switch active
Movements of the cabin moreover
the inspection-end-positions (test
end-switch and driving ability)
0no
1relesed
Enabling button Piep and flick of
call buttons:
Bit 1: button-Piep
Bit 2 : flickering ot the interior calls
at arrival at the aimed floor
Bit 3 : flickering of the exterior
calls at arrival
Bit 4 : Piep at crossing floors (e.g.
for blind persons)
`0
Brightness of the indicators for
interior- and exterior calls if not
indicated:
The low-order 4 bits define the
brightness of the external
indicators, the more significant 4
bits the brightness of the internal
indicators.
There are 9 steps of brightness:
e.g. Hex 0x11 = Dez 17 defines as
well inside, as outside indicators a
basic brightness of 12,5% the full
brightness (if indicator active)
function is also common as dualillumination.
F201
Button beep and
flicker enable
F202
Brightness of button
normally
F203
F204~
Spare
F230
Description
Value
65535
mm
015
Buffer
F231
Enable function building fillup/clear
Heavy up demand and 0: no function
heavy down traffic
1: building fill-up
2: clean building
3: both functions
F232
Heavy up demand
start time
Start time for buliding fill-up:
e.g. 730 means 7:30 oclock
730
02359
Page 57
Manual F5021B - Parameter list
No.
Marking
Description
Stand.
Area
F233
Heavy up demand end End time for building fill-up:
time
e.g. 930 means 9:30 oclock
930
02359
F234
Heavy down traffic
start time
Start time for clean builiding:
e.g. 1700 means 17:00 oclock
1700
02359
F235
Heavy down traffic
end time
End time for clean builiding:
e.g. 1830 means 18:30 oclock
1830
02359
F236~
Spare
F239
Buffer
F240
User-defined break
open speed code
0255
F241
User-defined
inspection low speed
code
0255
F242
User-defined
releveling speed code
0255
F243
User-defined creeping
speed code
0255
F244
User-defined
inspection high speed
code
0255
F245
User-defined single
floor speed code
0255
F246
User-defined double
floor floor speed code
0255
F247
User-defined triple
floor speed code
0255
F248
User-defined
quadruple floor speed
code
0255
F249
User-defined pentaple
floor speed code
0255
Page 58
User-defined Multistep control of
the frequency inverters:
F24 = 0F32 = 7
Unit
Value
Manual F5021B - Error codes
15.Error codes
Code
Error display
Error
Comment
The period of validity of
Definded attendence interval
No inspection travel possible if the attendence
maintenance is over.
expired
interval is expired.
02
Safety Circuit Breaks off
Security cicle open
03
Up limit switch breaks off
upper end-switch reached
01
04
Down limit switch breaks
off
lower end-switch reached
05
Door cant be opened.
Door can not be opened.
8 failure tryies of open (std. operation mode)
06
Door cant be closed.
Door can not be closed
8 failure tryies of close (std. operation mode)
07
08
09
10
11
13
15
Landing door lock is
short.
18
No connection to the cabin module, or the
communication err.
module is jammed
closing-off resistor is not active.
Inverter Failure
Errof encoder
input X9 show errrof of the encoder
Up deceleration switch
Correction switch above out of
has errors.
order
Down deceleration switch Correction switch below out of
has errors.
Up/down force slow switch acts the same time
as up/down limit switch more than 3 seconds,
errors.
when the lift stops at door zone.
When the lift stops at leveling zone and
Terminal floor is split-
terminal switch active, but the 01 board shows
level.
that it is not at terminal position.
The distance of the above
installation distance is not correction switch to the terminal
Choose the distance respective to the nominal
speed.
end stop is not far enough
Down deceleration switch The distance of the below
Choose the distance respective to the nominal
installation distance is not correction switch to the terminal
speed.
enough
end stop is not far enough
Attached door lock
Anti surf input in the floor active.
X24 is active, but SM04 Antisurf door
detection input has error.
(door monitoring)
monitoring reports error (SM-04 /JP10.7)
closed limit acts at the
same time
20
order
Terminal switch has
Door open limit and
19
closed.
CAN-bus connection to cabin
enough
17
Door blocks 3s after door opening its still
Car Board
Up deceleration switch
16
Shaft door locking blot block
Ground floor and service
floor setting are wrong.
Both door endswitch are active at
the same time
TX0 and TX1 respectively TX11 and TX12 are
active at the same time.
Buliding ground floor and service
floor=1Ground floor blocked respectivly door
floor can not be reached, because
side blocked.
floors are blocked.
floor=2Fire stop is a blocked floor.
Page 59
Manual F5021B - Error codes
Code
Error display
Error
Comment
floor=3Fire stop door A is blocked.
floor=4Less than 2 floors are enabled
21
Motor overheat protection Motor overheated
22
The lift runs in reverse
PTC input more than 2 sec active.
Current direction is not according to Encoder signal in wrong direction in standard
the triggered direction.
mode at more than 0,15m/s.
Multistep mode: After 1,5sec delay the speed
is still at 0,2m/s.
Analog mode: As is-speed is 25% above the
23
The lift is over speed.
Lift is driving to fast.
desired speed.
Excess speed
As is-speed is more than 8% higher as the
nominal speed.
Speed at drive-in into the door zone is above
the drive-in speed limit warning.
Multistep: after 3s still below 50mm/s.
24
The lift is under-speed.
Under speed
Analog-mode: Lift is 50% slower than the
desired speed.
25
27
28
Running time restriction
failure
Up-leveling switch failure
re-levelling up sensor out of order
Down-leveling switch
re-levelling down sensor out of
failure
order
Machine room
29
Run-time-control activated!
temperature sensor
failure.
Temerature monitoring machine
Lift is longer in operation than in F62 defined
time; without change of the door/flush signals.
X21 active
room active
30
Car illumination failure
Cabine light dropped out
input TX16 active.
31
The lift is slippage failure
Engine is suddenly rotating
Encoder reports movement despite of stop
32
33
34
Safety circuit switch is
fauilure in running.
Security cycle opens during journey
Door lock is short.
Door-locking bolt is by-passed!
Motor contactor 1 is
contactor monitoring engine
failure
contactor K1 reports error
35
Brake Contact is failure
36
Motor Contact 2 is failure
contactor monitoring break
e.g. due to door locking bolt
door open end-switch reports door open, but
locking bolt is closed.
output Y2 do not communicate with input X15.
output Y0 do not communicate with input X17.
contactor K8 reports error
contactor monitoring engine
output Y3 do not communicate with input X16.
contactor K2 reports error
Door lock relay detection input is no signal, but
37
Door lock relay detection
both landing and car door lock are closed.
is failure.
Door lock relay detection input has signal, but
either landing or car door lock is opened.
Page 60
Manual F5021B - Error codes
Code
38
39
40
45
Error display
Brake switch failure
Error
Break switch monitoring reports
error
Comment
Break contactor active, but break do not get
active, respectively breaks do not work
synchron(X22,X23).
Safety Circuit relay
Safety circuit input signal differ from safety
contact is failure
circuit relay detection signal.
Inverter running signal
Inverter enable control recognize
Bremslftsignal vorhanden, aber keine
detection has errors.
malfunction
Umrichter Run (Enable) Signal.
Door open with re-
The detection with door open with re-leveling
leveling relay contact
ouput and relay contact is different.
failure
54
Landing and car door
The landing and car door lock have different
lock is different
for 3seconds.
Down direction single
58
decerlation switch is
installed falsely.
Down direction double
59
decerlation switch is
installed falsely.
Correction downwards is installed
switch liefert falsche Signale.
incorrectly. Sequence is wrong.
Correction downwards 2 is installed
incorrectly. Sequence is wrong.
Down direction triple
60
decerlation
Correction downwards 3 is installed
switchAufwrts is
incorrectly. Sequence is wrong.
installed falsely.
Down direction fourfold
61
decerlation switch is
installed falsely.
Up direction single
62
decerlation switch is
installed falsely.
Up direction double
63
decerlation switch is
installed falsely.
Up direction triple
64
decerlation switch is
installed falsely.
Up direction fourfold
65
decerlation switch is
installed falsely.
66
The steps of deceleration
switch have errors.
Correction downwards 4 is installed
incorrectly. Sequence is wrong.
Correction upwards is installed
incorrectly. Sequence is wrong.
Correction upwards 2 is installed
incorrectly. Sequence is wrong
Correction upwards 3 is installed
incorrectly. Sequence is wrong
Correction upwards 4 is installed
incorrectly. Sequence is wrong.
Number of installed correction
switches is not according to the
definded parameters
Page 61
Manual F5021B - Error codes
Code
Error display
Leveling switches have
67
been connected in
reverse
68
Error
Comment
re-levelling switches are
interchanged installed.
Leveling zone or leveling
Length of the flush/door zone is
plate failure
shorter as the distance to the stop
Number of the flush/door zones is
69
Floor err in self-learning.
not according to the number of
floors
70
The lift cant do selflearning
Page 62
Correction below, reference journey end
Reference journey not possible
-switch, or flush signal not correct at reference
journey start position