0 ratings0% found this document useful (0 votes) 294 views2 pagesKEMA Certificate - 7SR11 and 7SR12 IEC 61850
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
UCA
inenafond =» LEC 61850 Certi
icate Level A*
Users Group
No. 10003111-OPE/INC 15-2933
Issued to: For the server product:
‘Siemens Protection Devices Limited Reyrolle 7SR12 Argus
North Farm Road, Hebburn Directional Overcurrent Protection Relay
‘Tyne & Wear, NE31 1LX Firmware Version: 2436H80004R4b
United Kingdom EN100 Communication Module V04.27
S/N: 104483509/001
‘The server product has not been shown to be non-conforming to:
IEC 61850 First Edition Parts 6, 7-1, 7-2, 7-3, 7-4 and 8-1
Communication networks and systems in substations
The conformance test has been performed according to IEC 61850-10, the UCA International Users Group
Server Device Test Procedures version 2.3 with TPCL’ version 1.8, the product's protocol, model and technical
issue implementation conformance statements and extra information for testing: "7SR12 Argus Directional
Overcurrent Protection Relay IEC 61850 Model Implementation Conformance Statement (MICS), 2015/08" and
“7SR11 and 7SR12 Argus Overcurrent Protection Relays IEC 61850 PIXIT, PICS, TICS, 2015/10".
‘The following TEC 61850 conformance blocks have been tested with a positive result (number of relevant and
executed test cases / total number of test cases):
1 Basic Exchange (20/24) 9a GOOSE Publish (10/12)
2 Data Sets (3/6) 9 GOOSE Subscribe (10/11)
2+ Data Set Definition (23/23) 12a Direct Control (5/12)
4 Setting Group Selection (3/3) 412c Enhanced Direct Control (5/13)
5 Unbuffered Reporting (19/19) 412d Enhanced SBO Control (10/19)
6 Buffered Reporting (27/28) 13. Time Synchronization (4/5)
14 File Transfer (4/7)
‘This certificate includes a summary of the test results as carried out at Siemens in The United Kingdom with
UniCA 61850 Client Simulator 4.29.03 with test suite 3.29.00 and UniCA 61850 Analyzer 5.29.02. This
document has been issued for information purposes only, and the original paper copy of the DNV GL report No.
10003111-OPE/INC 15-2935 will prevail
‘The test has been carried out on one single specimen of the product as referred above and submitted to DNV GL
by Siemens. The manufacturer's production process has not been assessed. This certificate does not imply that
DNV GL has approved any product other than the specimen tested.
‘Amhem, Dect 2015
Issued by:
M. Adriaensen
Head of Department
Operational Excellence DNV'GL
2 Level A - Independent test lab with certified 150 9001 Quality System
*TPCL - Test procedures change list
!. Schimmel
Verification Manager
Copyright © KEMA Nederland 8.V. Amhem, the Netherlands. All rights reserved. It is prohibited to update or change
this certificate in any manner whatsoever, including but not limited to dividing it into parts.
ENA Nederand 8 V Utechisewen 310, 6812 AR Arnhem, PO. Box 9035, 6800 ET Amer, the Netherands
‘T3128 3562025 F +31 26351 3685 salesdeskebdrl com wna drvglcom Page 12UCA
Intemational
Users Group
IEC 61850 Certificate Level A
No. 10003111-OPE/INC 15-2933
Applicable Test Procedures from the UCA International Users Group Server Device Test Procedures
version 2.3 with TPCL 1.8
Conformance Block | Mandatory Conditional
1: Basic Exchange | ASS1, ASS2, ASS3, ASsN2, ASSN, ASSNS ‘ASSN3, S1v6, S1v7, S18, STVNIe,
Srvi, Srv2, S1v3, Srv4, S1v5, SrvNiabod, | STVNAf, SrvN3
Srv
2: _ Data Sets Det, Dseti0a, DsetWiae
2#: Data Set Definition | Dset2, Dset3, Dset4, DsetS, Dsetb, Dset7,
Dset8, Dset9
DsetNicd, DsetN2, DsetN3, DsetN4, DsetN5,
DsetN6, DsetN7, DsetN8, DsetN9, DsetNi0,
DsetN11, DsetNi2, DsetNi3, DsetNi4,
DsetNi5
4: Setting Group S91, SoNia, 593
Selection
5: Unbuffered Rpt, Rp2, Rp3, Rp4, ROS, R15, RPNI, RPN2, | RDS, Rp6, RBZ, ReB, R10, Rit, R12,
Reporting RpN3, RPI, RONE DNS
6: Buffered Reporting | Bri, Br2, Br3, Br4, Br9, Bris, Br20, Br2i, | Br5, Br6, Br7, Br8, Bri0, Bri, Bri2,
Br22, Br25, 6+26, Br27, Br28, BrN1, BrNv2, | Br24
BrN3, BrN4, BrNS, Brn
9a:_GOOSE Publish ‘Gop2, Gop3, Gop4, Gop8, Gopi0a Gopi, Gop6, Gop7, Gopi05, GopNit
9b: GOOSE Subscribe | Gosia, Gos2, Gos3, GosN1, GosN2, Gosn3, | Gosib
GosN4, Goss, Gosné
‘12a: Direct Control ‘GtIN3, CHING, DOnst (CuINA, DOns3
112c: Enhanced Direct | CUINS, CUINS, DOes2, DOesé cunt
Control
12d: Enhanced S80 (CHB, CLINE, CUN2, CUNS, CUNA, CNS, cunt
Control ‘$BOes1, S80¢52, SB0es3
Time Syne Tint, Tm2 m3, TN
File Transfer Ful, Fab, Fea, FtNLab
Al configuration file and data model tests have been successfully performed for the product variants using
the same communication hardware and software version:
Reyrolle 7SR11 Argus Overcurrent protection relay
KEMA Nederland 8 V.Uvechtseweg 310, 6512 AR Amer, PO. 8ox 9035, 6900 ET Arnhem, the Nethetands
"7 +51 28 3562025 F #3126351 3683 saleedeek@@inwglcom wow drial com
Pepe 22