The document discusses wire sizing for the electrical system of a small family dwelling. It determines that a 38 mm2 copper wire should be used for the main feeder based on the total computed load exceeding 10,000 watts. A 100A main breaker is also specified to match the wire sizing.

Uploaded by

jungatbunton
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
59 views1 page

Electrical Design 101 45

The document discusses wire sizing for the electrical system of a small family dwelling. It determines that a 38 mm2 copper wire should be used for the main feeder based on the total computed load exceeding 10,000 watts. A 100A main breaker is also specified to match the wire sizing.

Uploaded by

jungatbunton
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

70% of the ungrounded(live wire) conductor or TWO TRADE SIZE SMALLER SIZE THAN THE

UNGROUNDED CONDUCTOR. (PEC specs) Therefore use1- 22 mm2 Tw copper wire for the Neutral
line.
4. Determine the Size of the Conduit pipe. Refer to Table , use 32 mm diameter pipe.
5. For main Breaker, refer to Table . Use 2 - 100 A 2 - wires 250 V, 2 pole molded air circuity breaker.
COMMENT:
The total computed load is 63.37 A. The 30 mm2 copper wire could be used considering its 90 A capacity.
However, The NEC provides that:
" If the computed load exceeds 10000 watts, the conductor and overcurrent protection shall be rated not
less than 100 A.
THEREFORE USE 2 - 38 mm2 TW WIRE FOR THE MAIN FEEDER AND 2 - 100 A FOR THE MAIN
BREAKER.

Small Family Dwelling


Type of Service - 230 volts; two wire
Line to Ground system

A single family dwelling with a floor area of 80 square meters has the following receptacles and outlets
load.
LIGHTING:
7 pcs. - 40 watts fluorescent lamps
2 pcs. - 20 watts Incandescent lamps
CONVENIENCE OUTLET:
1 - Electric Iron .............................................. 1000 watts
1 - Electric stove.............................................. 1100 watts
2 - Electric fan ................................................ 500 watts
1 - 7 cu. ft Refrigerator .................................... 175 watts
1 - Portable stereo ........................................... 100 watts
1 - 20" TV set ................................................... 300 watts

SOLUTION:
A. Circuit 1 - Lighting Load by the Area method
1. Determine the wattage required per square meter area. From, the wattage required per square meter for
dwelling units is 24 watts. Multiply:
80 sq.m x 24 watts = 1920 watts