Distance Protection for transmission
lines: part 1
s S.A.E
IC - Smart Grid
Siemens AG 2006
SIPROTEC 7SA Distance Protection
Basics of Protection
Page 2
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Why impedance protection?
Situation:
Meshed network and two infeeds
Directional overcurrent time relays
0,6s
0,3s
0,6s
0,3s
0,6s
0,3s
0,6s
0,3s
non-selective trip
Page 3
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Basic principle of impedance protection
Localization of short-circuits by means of an impedance measurement:
- fault on the protected line
Z1
relay A
Selectivity
- fault outside the protected line
margin
Z2
relay A
Objective:
Measure Z with Accuracy and Speed
Master transients and adverse system conditions
Page 4
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Principle of (analog) distance relaying
ZS
ISC
ZL
Usc
Isc
ZSC
U1= k1 USC= k1 ISC ZSC.
Relay design:
operation if
U1< U2
i.e. ZSC< Z Replica
comparator
X
Z Replica (line replica impedance)
(corresponds to the set zone reach)
ZReplica
External fault
U2=k2 ISC Z Replica
Internal fault
R
Page 5
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Distance measurement (principle)
IL1 ZL
6 loops :
ZL = RL + j XL
IL2
3 phase- phase loops and
3 phase- ground loops
IL3
IE
ZE = RE +j XE
ZE
UL1 UL2 UL3
phase- phase -loop: UL1-L2 = ZL ( IL1 - IL2)
Measured current
measured voltage
phase-ground-loop: UL1 =
L1
( RL + j XL )-
L1, E
UL1
The same applies to the remaining loops
Page 6
( RE +j XE)
measured current
measured voltage
The same applies to the remaining loops
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Complex impedance measurement
Normal operation:
Metallic fault:
ZL=RL+jXL
Resistive fault:
ZL
I
Z Load
ZL
Rf
Fault on the next line
X
XL
ZL
Resistive fault
Normal operation
Fault on the line
Fault distance can be estimated from the reactance
Page 7
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Load and short-circuit impedances
Z Load
Distance relay
operating
characteristic
ZLF1
ZLine
ZLF2
RF
F1
X
Fault area
ZL
ZLF2
D
RR
RR
ZLoad
Phase - Phase Fault
ZF2
ZLoad
ZLF1
RF
F2
ZF1
a
Incre
l oa
sing
RR
RF / 2
Phase - Earth Fault
RR
RF /(1 + RE/RL)
SC2
Fault in
reverse
direction
Page 8
SC1
R
Load area
Minimum Load Impedance:
Minimum voltage 0,9 Un
Maximum current 1,1 In
Maximum angle
30
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Typical distance zone-characteristic
MHO-circle
shifted circle
ZR
ZSC'
ZSC'
ZSC
external
fault
ZSC
centre
internal
fault
R
polarised
MHO-circle
quadrilateral
ZS = 0
RF
XA
ZL
R
ZS small
ZS high
Page 9
ZSC-L
settable arc
compensation
Rarc
RA
ZS
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Determination of fault direction
Fault location
Where is the fault ?
Current area for
forward faults
USC
Impedance area for
forward faults
ZSC
SC
SC
SC
R
SC
Current area for
reverse faults
current / voltage diagram
Z'SC
Impedance area for
reverse faults
impedance diagram
The impedance also shows the direction, but ....
Page 10
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Impedance measurement and directional determination
Why impedance measurement and directional determination separately?
A
line characteristic
fault with arc resistance in forward direction
fault in forward direction
close-in fault
R
fault in reverse direction
direction may be determined together with the impedance measurement
but: problems may arise in certain cases (e.g. close-in faults)
separate directional determination required!
Page 11
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Alternatives for the directional measurement
~
Z grid
relay
Distance Measurement
fault L1-E
Z line
Direction Measurement
VL1
Vf
Vf
VL1
If
VL3
Method 1
VL1
Vf
Method 2
If
If
VL2
faulty phase voltage
VL3
VL2-L3
VL2
healthy-phase voltage
(phase to phase voltage)
Page 12
VL3
VL2
voltage memory
(pre-fault voltage)
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Directional measurement
Summery of all 3 methods
uRI = uL2-L3
uf = uL1
if(t)
uL1
Measuring
window
uL1
if
if
uL2-L3
if
Page 13
Distance measurement
Direction measurement
with voltage memory
Direction measurement
with unfaulted voltage
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Fault detection techniques
Over-current fault detection
Voltage dependant
over-current fault detection
Voltage and
angle dependant
over-current
fault detection
Impedance
fault
detection
I>
>
I >>
Not in 7SA522
Page 14
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Why several zones?
Trip in first-zone time
7SA
Trip only if there is no fast fault
clearance by other relays
7SA
etc.
t
t3
X3
X2
t2
X1
Diagrams:
t1
R
Impedance plain
Page 15
X1
X2
Time-grading diagram
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Determination of grading times
2nd Zone: It must initially allow the 1st zone on the neighbouring feeder(s) to clear the fault.
The grading time therefore results from the addition of the following times:
operating time of the neighbouring feeder mechanical 25 - 80 ms
static:
15 - 40
digital:
15 - 30
circuit breaker operating time
HV / EHV:
MV
40 ms (2 cycles) / 20 ms (1 cycles)
up to about 80 ms (4 cycles)
distance relay reset time
mechanical: approx. 60-100 ms
static:
approx. 30 ms
digital:
approx. 20 ms.
errors of the distance relay internal timers mechanical: 5% of the set time, minimum 60-100 ms
static:
3% of the set time, minimum 10 ms
digital:
1% of the set time, minimum 10 ms
distance protection starting time *)
mechanical: O/C starter: 10 ms, impedance starter: 25 ms
static:
O/C starter: 5 ms, impedance starter: 25 ms
digital:
generally 15 ms
safety margin
grading;
mechanical-mechanical:
static/digital-mechanical or vice versa:
digital-digital or static-static
100 ms
75 ms
50 ms
*) only relevant if the set relay times relate to the instant of fault detection / zone pick-up. This is the case with all Siemens relays. There are
other relays where the time is adapted by software to relate to the instant of fault inception. In the latter case the starting time has to be
dropped.
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Page 16
Reach and time co-ordination
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
-50%
Page 17
0%
85%
100%
120%
150%
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Impedance zones of digital relays (7SA6 and 7SA52)
for
rds
wa
Line
Distance zones
Z6
Inclined with line angle
Angle prevents overreach of Z1
on faults with fault resistance that
are fed from both line ends
Z5
Z4
Z2
Z1B
Z1
re v
e rs
e
Load
Load
fo rw
a rd
s
Z3
e
ers
re v
Page 18
Fault detection
no fault detection polygon: the
largest zone determines the fault
detection characteristic
simple setting of load encroachment
area with Rmin and Load
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Graded distance zones
Z3
t = grading time
Z2
time
Z1
t3
t2
t1
B
D1
C
D2
Grading rules:
Z1 = 0,85 ZAB
Z2 = 0,85 (ZAB + 0,85 ZBC)
Z3 = 0,85 (ZAB + 0,85 (ZBC + 0,85 ZCD))
Page 19
D
D3
distance
Safety margin is 15 %:
- line error
- CT, VT error
- measuring error
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
SIPROTEC 7SA Distance Protection
Teleprotection
Page 20
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
20
Selectivity in distance protection,
Teleprotection is the solution
Normal setting: X1 = 0.85 XL
2
1
15%
Faults in this area are
tripped from side 2 in
t2
70%
Faults in this area are tripped
from both sides in first-zone
time
15%
Faults in this area are
tripped from side 2 in
t2
Faults on approximately 70% of the line length are cleared
without delay at both line ends
Faults in the remaining 30% of the line length
are cleared with a time delay.
Remedy:
Exchange of information between the two line ends
Required:
Communication channel (PLC, microwave radio, fibre optic, etc.)
Teleprotection logic (dedicated device or internal
function in numerical protection devices)
Page 21
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Teleprotection schemes
Z1B
Z1
2
Z1
Z1B
7SA
7SA
I see the fault forward,
but outside zone 1
tio
rma
o
f
In
on
issi
m
s
an
n tr
I clearly see the
fault on my line
Prerequisite for the use of teleprotection schemes
After receiving the information
from the opposite end I recognize
that the fault is on my line
Page 22
Teleprotection logic in the devices
Transmission channel (Signal cables, PLC,
Radio link system, Optical fibers, Communication
network)
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
7SA522 - Permissive underreach transfer trip (PUTT)
Z1(A)
Z1B(B)
Z1B(A)
Z1(B)
Substation A
7SA522
Substation B
Dis. T. Send 2103
Tele-comm.
Tele-comm.
Transmit
Transmit
4056
Z1
(A)
4056
Ts
TS Send signal
Send signal
T1B
Further
Zones
Z1
(A)
Ts
TS
T1
T1
Z1B
(A)
7SA522
2103 Dis. T. Send
&
>1
>Dis Tel Rec. Ch1
4006
Trip
Trip
receive
receive
>1
T1B
&
Z1B
(A)
Further
Zones
>Dis Tel Rec. Ch1
4006
TS
Page 23
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
7SA522 - Permissive overreach transfer trip (POTT)
Z1(A)
Z1B(B)
Z1B(A)
Z1(B)
Substation B
Substation A
7SA522
Tele-comm.
Dis. T. Send 2103
Z1B
(A)
Tele-comm.
Dis. T. Send 2103
4056
&
T1B
Z1 or
Further
Zones
Ts
&
>1
4006
>Dis Tel Rec. Ch1
Z1B
(A)
4056
Transmit
Send signal
>1
7SA522
Transmit
Trip
Send signal
Trip
>1
>1
Ts
&
4006
receive
receive
>Dis Tel Rec. Ch1
&
T1B
Z1 or
Further
Zones
TS
Page 24
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
7SA522 - Blocking
7SA522
FD
(B)
Substation A
d (u,i)
dt
(A)
Z1(A)
FD
(A)
Z1B(A)
Z1B(B)
FD
(A)
FD
(B)
Z1(B)
Substation B
&
&
40 ms
2103 Dis. T. Send
&
Forw.
(A)
4060
4060
Dis. Jump Bl.
Dis. Jump Bl.
>1
&
FD
(A)
0
Ts
4056
Transmit
T1B
Z1 or
Further
Zones
&
Forw.
(A)
>1
4056
Ts
Send signal
Send signal
&
&
>1
Trip
Trip
T1B
1
1
0
0
receive
&
>1
0
4006
>Dis Tel Rec. Ch1
FD
(A)
Tv
TV
Page 25
Transmit
Tv
Z1B
(A)
Dis. T. Send 2103
Tele-comm.
Tele-comm.
d (u,i)
dt
40 ms
(A)
receive
4006
>Dis Tel Rec. Ch1
Z1B
(A)
Z1 or
Further
Zones
TS
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
7SA522 - Unblocking
Z1(A)
Z1B(B)
Z1(B)
Substation A
7SA522
4056
&
T1B
Z1 or
Further
Zones
Ts
&
Substation B
Tele-comm.
Dis. T. Send 2103
Z1B
(A)
>1
Tele-comm.
fu
fu
fo
fo
Transmit
Send signal
Transmit
Send signal
Trip
4031
receive
7SA522
Dis. T. Send 2103
Z1B
(A)
4056
Trip
>1
Unblock
Logic
Z1B(A)
4030
>1
4031
4030
receive
>1
Ts
&
Unblock
Logic
Fo : Off frequency (monitoring frequency)
U : Unblocking signal
Fu : Unblock frequency (send frequency)
B : blocking signal
&
T1B
Z1 or
Further
Zones
TS
Page 26
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
SIPROTEC 7SA Distance Protection
Power Swing
Page 27
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
27
Power swing detection by trajectory monitoring
x
Fault Impedance
dR(k-n)
dX(k-n)
Jump from load to
fault impedance
swing trajectory
dR(k)
dX(k)
Load
impedance
Trajectory monitoring for
Continuous movement
No sign change
Page 28
Detection of power swing 30ms after
start!
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Principle of power swing detection
Continuous
calculation and
monitoring of
Impedances
Zone
First impedance in
power swing area:
algorithm starts to
analyze the
impedance trajectory
automatically sized
power swing area
Page 29
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Main criteria for power swing detection
Page 30
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
monotony criterion
X
X1
X2
X2
X11
R2
R2
R2
X2
R1
R1
power swing if
R1 and R2 or and
X1 and X22
have same direction
directions
no power swing if
R1 and R2 and
X1 and X2 have
different directions
Page 31
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
continuity criterion
power swing
if R or X
exceed a threshold
X
X
no power swing
if R and X are
below the threshold
R
R
Page 32
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
smoothness criterion
X
X1
X1
R2
R2
R1
R1 X 2
power swing if
R1 nearly R2
and X1 nearly X2
X2 no power swing if
R1 strong vary from R2
or
X1 strong vary from X2
Page 33
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
SIPROTEC 7SA Distance Protection
Practical Application Example
Page 34
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
34
Practical Application Example for 7SA6
220 kV
100 km OHL
Z1 = 0,25 Ohm/km 85
Z0 = 0,8 Ohm/km 75
7SA6
IF Min = 2 kA (phase)
IF Min = 0,5 kA (earth)
7SA6
1&3 Pole trip
21 with Quadrilateral
Teleprotection - POTT
Page 35
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Plant Data
220 kV
L1
L2
L3
1200 / 1
220 kV / 0.1 kV
Make a diagram
of how the plant
is connected to
the relay
220 kV / 0.1 kV
L1 L2 L3
Page 36
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Binary I/O
Refer to
System Description
Chapter 5
Relay PICKUP
Allocate the required
functions to the
available binary
inputs and outputs
Distance teleprotection send
Trip L1
Trip L2
Trip L3
The number of
available binary
inputs and outputs
depends on the
hardware version
AR Close
General supervision alarm
Relay alarm/live contact
Page 37
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Configuration
First step is configuration - Functions that are disabled here will not appear later.
Refer to Manual - Chapter 2.1 General
Page 38
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Routing in DIGSI Matrix
Route the selected functions to the binary inputs and outputs in the matrix
Page 39
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Set Power system data1 - Transformers
Make sure the entered settings match the plant data
Refer to Manual - Chapter 2.1 General
Page 40
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Power system data1 - Power system
Select the mode for zero sequence compensation: RE/RL and XE/XL or
K0 and angle K0
Refer to Manual - Chapter 2.1
Page 41
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Setting Group A
Setting blocks for the functions enabled during configuration
are available in Setting Group A
(if setting group changeover is selected, also Group B, C and D)
Refer to Manual - Chapter 2.1
Page 42
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Setting Group A: Power System Data 2
Select entry of impedance in primary or secondary values.
CT and VT ratio may not change after entry with primary values
Separate setting
for Z1 and
remaining zones
Refer to Manual
Chapter 2.1
Page 43
Incorrect entries may lead to incorrect
measured value or fault location data
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Calculation of residual compensation factors
Use the RE/RL and XE/XL or K0 and angle K0 setting (selected during configuration)
RE
1
=
RL
XE
R0
-
X0
R1
XL
X1
As only ratios are used either primary or secondary impedance may be used. The
values may apply to the whole line or be per unit length
R1 = 0,25 cos 85 = 0,022
X1 = 0,25 sin 85 = 0,249
R0 = 0,8 cos 75 = 0,207
X0 = 0,8 sin 75 = 0,773
RE/RL = 1/3 (0,207/0,022 - 1) XE/XL = 1/3 (0,773/0,249 - 1)
RE/RL = 2,80*
XE/XL = 0,70
* Note that RE/RL setting increases earth fault reach in R direction. Recommend set < 2
In this example the same setting is used for Zone 1 and the other Zones
Page 44
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Setting Group A: Line Status
The line status (open/closed) is required by several functions
(e.g. E/F protection blocking during single pole open).
Current, voltage and
auxiliary contacts
may be used to
check the line status.
After line closure
special protection
functions may be
activated for a set
Time (SOTF)
Refer to Manual
Chapter 2.1
Page 45
Release of manual close command may be subject to sync check
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Setting Group A: Distance protection, general settings
This is similar
to ON/OFF with
binary input
Used to set
load area in
polygon
Single pole trip
in Zone 2 can be
selected
The overreach zone Z1b may be controlled by the Auto Reclosure
Page 46
Refer to Manual
Chapter 2.2
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Calculate the Load Area setting
Max Load Angle
Maximum load current = 2200 A
Minimum operating voltage = 90%
Min Power factor cos = 0,85
Z2
Z1B
Z1
RLOAD (min) = Umin / 3 ILmax
Load
RLOAD (min) = 0,9
= 95
220 kV / 3
(prim.)
2200 A
Max Load Angle = 1,2 * arccos (cos
)
RLOAD (min)
Max Load Angle
Page 47
= 1,2* arccos ( 0,85)
= 38
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Setting Group A: Distance protection, Earth faults
Set the threshold
for earth fault
pickup
Additional
settings have the
supplement A
Refer to Manual
Chapter 2.2
Page 48
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Setting Group A: Distance protection, Time Delays
Set the zone
timers:
Separate
setting for
1 and multi
phase faults
in Z1, Z2 and
Z1b
The same parameters are
also shown with the
individual zone settings.
Page 49
Setting infinity ( ) may be
applied for clarity to unused
zones.
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Setting Group A: Distance zones, Zone 1
Set mode for Zone1
- Forward
- Reverse
- Non-directional
- Inactive
Set reach for
Zone1 Primary
or secondary
Set time delay
for Zone1
(Same as under
general settings
The zone reduction angle is only available for Zone1
(Used to prevent overreach resulting from load current
in the presence of resistive faults)
Settings for further Zones is similar
Page 50
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Short-circuit with fault resistance and infeed from both
sides - equivalent circuit
EA
A
UA
ZL
D
U A = I A ZL + I A + I B RF
U A = I A ZL + RF + I B RF
UA
IB
ZA =
= ZL + RF +
RF
IA
IA
RF
EB
X
RF
ZL
RF
The fault resistor RF is seen larger
Page 51
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Influence of load flow on the distance
measurement for faults with fault resistance
U2
U1
load
ZL2
ZL1
U1
RF
L
SC2
SC1
U2
RF = fault resistance
1
RF
2
1
RF
RF
RF
ZL1
ZL2
ZSC2
ZSC1
ZSC1 sin
ZSC2 sin
SC1
SC2
SC1
ZK1 = ZL1 + RF +
2
1
Page 52
RF
ZK2 = ZL1 + RF +
SC2
An Over-reach
(left) or
an Under -reach
(right) is possible.
The grading
characteristic must
be adapted.
RF
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Settings for zone Z1
X(Z1)
Line
R(Z1)
RE(Z1)
R
Page 53
Recommendation for zone 1 settings:
X1
80...90% of the line reactance
R1
120% of the arc (1/2) resistance
R1E
120% of the arc resistance
T1(1-phase.)
0 ms
T1(multi-phase) 0 ms
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Impedance zones of digital relays (7SA6 and 7SA52)
for
rds
wa
Line
Distance zones
Z6
Inclined with line angle
Angle prevents overreach of Z1
on faults with fault resistance that
are fed from both line ends
Z5
Z4
Z2
Z1B
Z1
re v
e rs
e
Load
Load
fo rw
a rd
s
Z3
e
ers
re v
Page 54
Fault detection
no fault detection polygon: the
largest zone determines the fault
detection characteristic
simple setting of load encroachment
area with Rmin and Load
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Setting Group A: High Current Switch on to Fault
Following energisation of the line (recognition of CB close) the
high speed SOTF clears bolted faults.
Function must be switched ON
2404
I>>>
L1
I>>>
L2
>1
4282
SOTF-OC Pick up L1
&
4283
L3
SOTF-OC Pick up L1
2. 2 .I>>>
4284
SOTF-OC Rel. L1
SOTF-OC Pick up L1
>1
SOTF-OC Rel. L1
Pick-up setting must be
above maximum expected
charging current
4281
SOTF-OC Rel. L1
>1
SOTF-OC Rel. L123
L1
L2
SOTF-OC Trip L123
L3
Page 55
SOTF-OC Pick up
4295
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
SIPROTEC 4 Distance Protection
Buck up over current
Address 2601 is set according to the desired mode of operation of the overcurrent protection: Operating
Mode = ON: always active means that the overcurrent protection works independently of other protection
functions, i.e. as a backup overcurrent protection. If it is to work only as an emergency function in case of
loss of VT supply, ON: with VT loss must be set
Page 56
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
SIPROTEC 4 Distance Protection
Buck up over current
If not all stages are required, each individual stage can be deactivated by setting the pickup threshold to .
But if you set only an associated time delay to this does not suppress the pickup signals but prevents the
timers from running
Page 57
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
SIPROTEC 4 Distance Protection
STUB protection for 11/2-circuit breaker arrangement
IA
CB
(A)
IK= I A+ I B
Line isolator 1
Feeder 1
Busbar A
stub fault
CB
(C)
IB
Feeder 2
Line isolator 2
CB
(B)
Release of STUB-stage with open line isolator:
Busbar B
The stub protection is an over current prot. which is only in service when the state of the
isolator indicates the open conditions via a binary input >I-STUB ENABLE
Page 58
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
SIPROTEC 4 Distance Protection:
High Resistance Earth Fault Protection
Definite-time characteristic
T
T3I0>
T3I0>>
T3I0>>>
3I0>
Page 59
3I0>>
3I0>>>
3I0
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device
Polarizing Options for Directional Earth Fault Relays
Settings for direction:
Directional Characteristic (U0 and IY)
*)
I0P
U0P U2P
*)
not needed for numerical relays,
U0P may also be internally calculated
Page 60
I0L, I2L
Siemens
AG Grid
2006
s
S.A.E - Smart
Distance Protection Device