SICAM RTUs AK 1703
SM-25xx/ETA2
Protocol Elements for Ethernet TCP/IP
Protocol element for communication via
LAN/WAN
SM-2546/ETA
1 x optical ethernet
(only for SICAM BC)
SM-25x6 (Symbolfoto)
SM-2556/ETA2
1 x electrical ethernet
SM-2547/ETA2
2 x optical ethernet
(only for SICAM BC)
SM-2557/ETA2
2 x electrical ethernet
The protocol element can be attached to
master control and communication
elements of SICAM RTUs platforms.
SM-25x7 (Symbolfoto)
Copyright Siemens AG 2013
MC0-047-2.02
Table of Contents
Application ........................................................................................................................... 3
Overview............................................................................................................................... 4
Features and Functions ....................................................................................................... 6
Modes of Operation ............................................................................................................. 8
Communication .................................................................................................................... 9
Configuration ..................................................................................................................... 11
Technical Specifications ................................................................................................... 13
Block Diagrams .................................................................................................................. 15
Status and Function display.............................................................................................. 17
Pin Assignment.................................................................................................................. 19
System Components ......................................................................................................... 21
Placement into the Information Landscape ...................................................................... 23
Disclaimer of Liability
Although we have carefully checked the contents of this publication
for conformity with the hardware and software described, we cannot
guarantee complete conformity since errors cannot be excluded.
The information provided in this manual is checked at regular
intervals and any corrections that might become necessary are
included in the next releases. Any suggestions for improvement are
welcome.
Copyright
Copyright Siemens AG 2013
The reproduction, transmission or use of this document or its
contents is not permitted without express written authority.
Offenders will be liable for damages. All rights, including rights
created by patent grant or registration of a utility model or design,
are reserved.
Subject to change without prior notice.
Document Label:
SIC1703-DSSM25XXETA2-ENG_V2.02
Issuing date:
02.09.2013
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
Application
The protocol elements described herein are used in several automation units based on
SICAM RTUs platforms.
SICAM AK
SICAM TM
SICAM BC
Protocol elements process speficic communication protocols when SICAM RTUs automation
units communicate with each other oder with devices of third-party manufacturers, in the field
of telecontrol, automation, and protection.
Due to its features, protocol element technology has a successful tradition for many years at
SIEMENS. A fundamental characteristic is the separation of protocol-bound communication
from application tasks of an automation unit.
Each interface has its own protocol processor
communication has no impact on the application, and vice versa
each processor runs one communication protocol
varioous different protocols run on one and the same hardware
all protocols can be loaded with SICAM TOOLBOX II
You can change the communication protocol, for instance from serial to LAN, without
retroactive effect to the application tasks of an automation unit
Each automation unit can be equipped with various protocols This allows easy
implementation of data nodes and frontends.
Engineering is done using SICAM TOOLBOX II.
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
Overview
SM-2546/ETA2
Protocol element based on a Serial Interface Module (SIM) with one LAN interface:
Standard according to IEC 60870-5-104
Fast Ethernet 100Mbit/s, IEEE 802.3, 100Base-Fx, optical
TCP/IP
time synchronisation via network time protocol (NTP)
The SIM can be expanded for one serial interface via SM-0551/PROTOCOL optionally and
can be attached to the master control element of SICAM BC.
SM-2556/ETA2
Protocol element based on a Serial Interface Module (SIM) with one LAN interface:
Standard according to IEC 60870-5-104
Ethernet / Fast Ethernet 10/100 MBit/s, IEEE 802.3, 10/100Base-TX, electrical
TCP/IP
time synchronisation via network time protocol (NTP)
The SIM can be expanded for one serial interface via SM-0551/PROTOCOL optionally and
can be attached to master control and communication elements of SICAM RTUs platforms
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
SM-2547/ETA2
Protocol element based on a Serial Interface Module (SIM) with dual LAN interface and
integrated switch for ring or star topology:
Standard according to IEC 60870-5-104
Fast Ethernet 100Mbit/s, IEEE 802.3, 100Base-Fx, optical
TCP/IP
Rapid Spanning Tree Protocol (RSTP) according to IEEE 802.1D, Edition 2004
time synchronisation via network time protocol (NTP)
The SIM can be attached to the master control element of SICAM BC.
SM-2557/ETA2
Protocol element based on a Serial Interface Module (SIM) with dual LAN interface and
integrated switch for ring or star topology:
Standard according to IEC 60870-5-104
Ethernet / Fast Ethernet 10/100 MBit/s, IEEE 802.3, 10/100Base-TX, electrical
TCP/IP
Rapid Spanning Tree Protocol (RSTP) according to IEEE 802.1D, Edition 2004
time synchronisation via network time protocol (NTP)
The SIM can be attached to master control and communication elements of SICAM RTUs
platforms
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
Features and Functions
LAN/WAN Communication over Ethernet TCP/IP - General
10/100MBit (half duplex / full duplex)
parameters for TCP/IP optimization
LAN/WAN Communication over Ethernet TCP/IP according to IEC 60870-5-104
controlled station
controlling Station
max. connections: 100
SICAM RTUs Interoperability IEC 60870-5-101/104 (DC0-013-2)
Ax 1703 Interoperability IEC 60870-5-101/104 (DA0-046-2)
Acquisition of events (transmission of data ready to be sent)
General interrogation, outstation interrogation
Clock synchronization according to NTP (Network Time Protocol) - RFC 1305
NTP server
NTP client
Command transmission
Supervision of maximum transport delay in control direction
Command Transfer Monitoring (Dwell Time Monitoring)
Transmission of integrated totals
Functions for the support of redundant communication routes
PSI redundancy (synchronous connections)
104 redundancy according IEC 60870 5 104 Edition 2.0)
104 redundancy controlling station
104 redundancy controlled station with 1 Ethernet interface
104 redundancy controlled station with 2 Ethernet interfaces
1703 redundancy
Deactivation of interface (with PRE control message)
Dual LAN interface with integrated switch for ring or star configurations (DNIP)
RSTP mode
Line Mode
switch mode
single mode
single + service mode
Protocol Element Control and Return Information
Protocol Element Control
Interface Enable/Disable
Send (general) interrogation command
Send (general) interrogation command to GI-group
Send (general) interrogation command
Protocol Element return information
Station failure
protocol-specific return information 0 Status DATA TRANSFER (BSE)
protocol-specific return information 1 Status DATA TRANSFER (104)
TOOLBOX II connection over LAN/WAN ("remote connection")
Remote connection based on integrated terminal server
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
Web Server
Integrated web server to display connection- statistic- and developer information
Access to the web server with standard web browser via HTTP
(Hyper Text Transfer Protocol)
Password for Web Server
Web Server (Enable/Disable) option
Special functions
Summer time bit (SU)=0 for all messages in transmit direction (time tag)
Day of week (DOW)=0 for all messages in transmit direction (time tag)
Originator address=0 for all messages in transmit direction
Special functions for project DBAG / PSI
Breaker delay in transmit direction (<TI=150>)
Send originator address with settable value
Special functions for project RWE
Bit by bit marking of the field
Cyclic measured values
Address of the return information for selection command 2
NT-Bit, IV-Bit according to RWE requirements
Hint
The above mentioned functions are described in detail in the document SICAM RTUs Ax 1703 Common
Functions Protocol Elements, section "LAN Communication (104)"..
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
Modes of Operation
Operating mode
Optical LAN interface
(multimode fibre optic)
SIM
Patch
Plug/Modul
SM-2546
CM-5861 b)
Fast Ethernet IEEE 802.3 100Base-FX
100Mbps
1300nm signals
50/125 and 62.5/125 fibres
MT-RJ connector
SM-2556/7
CM-2860 a)
plus media converter or switch according to
SICAM RTUs Platforms Configuration
Automation Units and Automation Networks
(DC0-021-2)
SM-2556/7
CM-2860 a)
SM-2547
Ethernet IEC 60870-5-104
Optical LAN interface
(fibre optic)
Ethernet IEC 60870-5-104
Electrical LAN interface
(twisted pair)
Ethernet IEC 60870-5-104
CM-5860 b)
Note
Ethernet / Fast Ethernet IEEE 802.3
10/100Base-TX
10Mbps / 100Mbps
RJ45 connector 8-pin according to
IEC 603.7
a)
Patch Plug for SICAM AK, SICAM TM; AK 1703, AMC 1703, AM 1703, BC 1703
b)
Patch Module for SICAM BC
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
Communication
Communication 100Base-FX (optical)
For the stations to communicate with each other, suitable transmission facilities and/or
network components may be needed in addition.
Own Station 100Base-FX (optical)
System
System Element
Protocol Element
SICAM AK
CP-2010/CPC25
CP-2014/CPCX25
CP-2017/PCCX25
SM-2556/ETA2
SM-2557/ETA2
SICAM BC
CP-5014/CPCX55
SM-2546/ETA2
SM-2547/ETA2
SICAM TM
CP-6014/CPCX65
SM-2556/ETA2
SM-2557/ETA2
Note
Media converter or switch
required
Media converter or switch
required
Remote Station 10/100Base-TX (optical)
System
System Element
Protocol Element
Note
SICAM AK
CP-2010/CPC25
CP-2014/CPCX25
CP-2017/PCCX25
SM-2556/ET02
SM-2556/ETA2
SM-2557/ETA2
SM-2557/ET02
SM-2558/ETA4
SICAM BC
CP-5014/CPCX55
SM-2546/ET02
SM-2546/ETA2
SM-2547/ETA2
SM-2547/ET02
SM-2558/ETA4
SICAM TM
CP-6014/CPCX65
SM-2556/ET02
SM-2556/ETA2
SM-2558/ETA4
Media converter or switch
required
SICAM EMIC
CP-6010/CPC30
ETT0
Media Converter oder
Switch erforderlich
SICAM CMIC
CP-8000/CPC80
ET84
Media Converter oder
Switch erforderlich
SICAM MIC
CP-6040/CPC60
Third-party system
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
---
Media converter or switch
required
10Base-TX
---
IEC 60870-5-104 according
SICAM RTUs
Interoperabilitt IEC 608705-101/104 (DC0-012-2) or
Ax 1703 Interoperabilitt
IEC 60870-5-101/104
(DA0-040-2)
Communication 10/100Base-TX (electrical)
For the stations to communicate with each other, suitable transmission facilities and/or
network components may be needed in addition.
Own Station 100Base-FX (electrical)
System
System Element
Protocol Element
SICAM AK
CP-2010/CPC25
CP-2014/CPCX25
CP-2017/PCCX25
SM-2556/ETA2
SM-2557/ETA2
SICAM BC
CP-5014/CPCX55
SM-2556/ETA2
SM-2557/ETA2
SICAM TM
CP-6014/CPCX65
SM-2556/ETA2
SM-2557/ETA2
Note
Remote Station 10/100Base-TX (electrical)
System
Protocol Element
Note
SICAM AK
CP-2010/CPC25
CP-2017/PCCX25
SM-2556/ET02
SM-2556/ETA2
SM-2557/ET02
SM-2557/ETA2
SM-2558/ETA4
SICAM BC
CP-5014/CPCX55
SM-2556/ET02
SM-2556/ETA2
SM-2557/ET02
SM-2557/ETA2
SM-2558/ETA4
SICAM TM
CP-6014/CPCX65
SM-2556/ET02
SM-2556/ETA2
SM-2557/ET02
SM-2557/ETA2
SM-2558/ETA4
SICAM EMIC
CP-6010/CPC30
ETT0
SICAM CMIC
CP-8000/CPC80
ET84
SICAM MIC
CP-6040/CPC60
AK 1703
CP-2000/CPC00
CP-2002/PCCE00
CP-2002/CE00
CP-2012/CE20
SM-2556/ET02
only IEC 60870-5-104 via
Ethernet 10Base-TX
AMC 1703
CP-4000/CPC4x
SM-2556/ET02
only IEC 60870-5-104 via
Ethernet 10Base-TX
Third-party system
10
System Element
---
only IEC 60870-5-104 via
Ethernet 10Base-TX
10Base-TX
---
IEC 60870-5-104 according
SICAM RTUs
Interoperabilitt IEC 608705-101/104 (DC0-012-2) or
Ax 1703 Interoperabilitt
IEC 60870-5-101/104
(DA0-040-2)
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
Configuration
SM-2546
The following table lists supported configurations. In addition to one SM-2546 (SI0/SI1) all
parts (carrier module, patch plug, etc.) listed for the choosen configuration are needed:
Configuration
Carrier Module
CP-5000, CP-5014
Patch Module
Interfaces
1)
SI0
one integrated patch module per SIx
1)
SI1
SI2
SI3
2)
1)
each variant of the SICAM BC (Bay Controller) which can be ordered comes with a determined
patch module for each interface
2)
serial interface (V.28) can be added optionally (SM-0551)
SM-2556
The following table lists supported configurations. In addition to one (SI0/SI1 or SI2/SI3) or
two (SI0/SI1 and SI2/SI3) SM-2556, all parts (carrier module, connection board, patch plug,
etc.) listed for the choosen configuration are needed:
Configuration
Interfaces
Carrier Module
Connection Board 1)
Patch Plug 1)
CP-2010, CP-2014
CM-2837
2)
4)
CP-2012, CP-2017
CM-2838
2)
4)
CP-5000, CP-5014
CP-6003,CP-6014
one integrated patch module per SIx
3)
2)
---
SI0
SI1
SI2
SI3
4)
4)
4)
1)
one connection board for each carrier module, one patch plug for each
interface
2)
For patch plugs for standard protocols in standard configurations as
supported see modes of operation of the respective protocol element; for
patch plugs in other than standard configurations see SICAM RTUs
Platforms Configuration Automation Units and Automation Networks (DC0021-2)
3)
each variant of the SICAM BC (Bay Controller) which can be ordered
comes with a determined patch module for each interface
4)
serial interface (V.28) can be added optionally (SM-0551)
SM-2547
The following table lists supported configurations. In addition to one SM-2546 (SI0/SI1) all
parts (carrier module, patch plug, etc.) listed for the choosen configuration are needed:
Configuration
Carrier Module
CP-5000, CP-5014
1)
Patch Module
Interfaces
1)
one integrated patch module per SIx
SI0
1)
SI1
SI2
SI3
2)
each variant of the SICAM BC (Bay Controller) which can be ordered comes with a determined
patch module for each interface
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
11
SM-2557
The following table lists supported configurations. In addition to one (SI0/SI1 or SI2/SI3) or
two (SI0/SI1 and SI2/SI3) SM-2556, all parts (carrier module, connection board, patch plug,
etc.) listed for the choosen configuration are needed:
Configuration
Carrier Module
Patch Plug
CP-2010, CP-2014
CM-2837
2)
CP-2012, CP-2017
CM-2838
2)
CP-5000, CP-5014
CP-6003, CP-6014
12
Connection Board
Interfaces
1)
one integrated patch module per SIx
---
1)
SI0
SI1
SI2
SI3
3)
2)
1)
one connection board for each carrier module, one patch plug for each
interface
2)
For patch plugs for standard protocols in standard configurations as
supported see modes of operation of the respective protocol element; for
patch plugs in other than standard configurations see SICAM RTUs
Platforms Configuration Automation Units and Automation Networks (DC0021-1)
3)
each variant of the SICAM BC (Bay Controller) which can be ordered
comes with a determined patch module for each interface
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
Technical Specifications
SM-2546
Communication Circuits
Optical LAN interface
(multimode fibre optic)
Fast Ethernet acc. to IEEE 802.3, 100Base-FX
Data rate
100 Mbps
Line lengths
50/125 m
up to 1000 m
62.5/125 m
up to 1000 m
SM-2546 provides a PECL signal at this interface. The
conversion to an optical signal is done by the patch module
which is installed for the interface.
1 serial interface
(SM-0551 can be added optionally)
For Technical Specifications, see data sheet
SM-x551/PROTOCOL (MC0-003-2)
Power Supply
Operating voltage
4.75 .. 5.25 VDC,
typ. 400 mA,
max. 500 mA @5 V
(without SM-0551)
4.75 .. 5.25 VDC,
typ. 525 mA,
4.75 .. 5.25 VDC,
typ. 90 mA,
max. 770 mA @5 V
(with SM-0551)
max. 120 mA @5 V
(CM-5861)
The voltage is supplied by the carrier module.
Mechanics
Dimensions
227.3 x 63.5 mm
Weight
Approx. 90 g
SM-2556
Communication Circuits
Electrical LAN interface
(twisted pair)
1 serial interface
(SM-0551 can be added optionally)
Ethernet / Fast Ethernet acc. to IEEE 802.3, 10/100Base-TX
Data rate:
10 Mbps / 100 Mbps
Line lengths
up to 100 m
For Technical Specifications, see SM-x551/PROTOCOL
(MC0-003-2)
Power Supply
Operating voltage
4.75 .. 5.25 VDC,
typ. 400 mA,
max. 500 mA @5 V
(without SM-0551)
4.75 .. 5.25 VDC,
typ. 525 mA,
max. 770 mA @5 V
(with SM-0551)
The voltage is supplied by the carrier module.
Mechanics
Dimensions
227.3 x 63.5 mm
Weight
Approx. 90 g
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
13
SM-2547
Communication Circuits
Optical LAN interface
(multimode fibre optic)
Fast Ethernet acc. to IEEE 802.3, 100Base-FX
Data rate
100 Mbps
Line lengths
50/125 m
62.5/125 m
up to 1000 m
up to 1000 m
SM-2547 provides a TTL signal at this interface. The conversion
to an optical signal is done by the patch module which is installed
for the interface.
Power Supply
Operating voltage
4.75 .. 5.25 VDC,
typ. 400 mA,
max. 500 mA @5 V
4.75 .. 5.25 VDC,
typ. 90 mA,
max. 120 mA @5 V
(CM-5861)
The voltage is supplied by the carrier module.
Mechanics
Dimensions
227.3 x 63.5 mm
Weight
Approx. 90 g
SM-2557
Communication Circuits
Electrical LAN interface
(twisted pair)
Ethernet / Fast Ethernet acc. to IEEE 802.3, 10/100Base-TX
Data rate:
10 Mbps / 100 Mbps
Line lengths
up to 100 m
4.75 .. 5.25 VDC,
typ. 400 mA,
Power Supply
Operating voltage
max. 500 mA @5 V
The voltage is supplied by the carrier module.
Mechanics
14
Dimensions
227.3 x 63.5 mm
Weight
Approx. 90 g
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
Block Diagrams
SM-25x6
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
15
SM-25x7
16
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
Status and Function display
The protocol elements SM-2546/ETA2, SM-2547/ETA2, SM-2556/ETA2 and SM-2557/ETA2
itself have neither a front panel nor LED displays.
They use the LEDs of the master control unit or communication elements. The meaning of
these LED displays is described in the manual of the concerning system element.
Protocol elements Mounting place and LED display SICAM AK/SICAM TM
SIM0
Master control element CP-2014
(symbolic illustration)
LEDs for SIM0
SM-0551
SIM0
SIM1
Communication element CP-2017
(symbolic illustration)
LEDs for
SIM0
LEDs for
SIM1
LEDs for SIM0 and SIM1
RY
RES
X1
X16
P USH TO
RELEAS E
4
ER
5
PWR
24-60VDC
X14
X15
X5
WD
X12
PUSH TO UNLOCK
X11
X9
X10
M-PRE/3
SI3
FB X4
X8
M-PRE/2
SI2 (FB)
X13
SI3
SI1
SI2
SI0
COM
CPY
/ LK
ER
/PK
/ LK
/PK
ERx RX TX
TM 1703 ACP CP-6014
SIM0
X7
M-PRE/0
SI0
M-PRE/1
SI1 (ETO)
X6
NC
X2
PUS H TO
RELEA SE
TB
X3
SICAM
SIM1
LOC
SIM0
Master Control Module CP-6014
(symbolic illustration)
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
17
Protocol elements Mounting place SICAM BC
SIM0
SM-0551
Master control element CP-5014
(symbolic illustration)
Hint
SICAM BC has no LED's for status and function display of protocol elements.
18
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
Pin Assignment
SM-2556, SM-2546
The abbreviations have the following meaning:
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
19
SM-2557, SM-2547
The abbreviations have the following meaning:
20
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
System Components
Hardware
Designation
Item-Number/MLFB
SM-2546 Ethernet 100FX + 1 SS
(optional)
BC2-546
6MF10130CF460AA0
SM-2556 Ethernet 10/100TX + 1 SS
(optional)
BC2-556
6MF10130CF560AA0
SM-2547 Network-Interf.Ethernet
2x100FX
BC2-547
6MF10130CF470AA0
SM-2557 Network-Interf.Ethernet
2x100TX
BC2-557
6MF10130CF570AA0
Can be equipped optional on SM-2546 and SM-2556
Designation
SM-0551 Serieller Interface
Prozessor 1 SS
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
Item-Number/MLFB
BC0-551
6MF10130AF510AA0
21
Firmware
Designation
Item-Number/MLFB
ETA2 Ethernet Interface
IEC60870-5-104
SC0-555-1
TU ETA2 TB II-Update
SC0-555-1.XX/53
Accessories
Designation
22
Item-Number/MLFB
CM-2860 Patch Plug Standard
V28,ET,TR
CA2-860
6MF12110CJ600AA0
CM-5860 Patch Modul el. V.28/ET
CC5-860
6MF12130FJ600AA0
CM-5861 Patch Modul optisch ET
100FX mit MTRJ-Stecker
(SM-2546)
CC5-861
6MF12130FJ610AA0
CM-5863 Patch Modul optisch ET
100FX LC-Stecker
(SM-2547)
CC5-863
6MF12130FJ630AA0
CM-5864 Patch Modul optisch ET
100FX LC-Stecker
(SM-2546)
CC5-864
6MF12130FJ640AA0
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
Placement into the Information Landscape
Document name
Item number
ACP 1703 Ax 1703 Common Functions Protocol Elements
DC0-023-2
SICAM RTUs Platforms Configuration Automation Units and Automation Networks
DC0-021-2
SICAM RTUs Interoperability IEC 60870-5-101/104
DC0-013-2
Ax 1703 Interoperability IEC 60870-5-101 bzw. -104
DA0-046-2
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013
23
24
SICAM RTUs AK 1703, SM-25xx/ETA2
MC0-047-2.02, Edition 09.2013