Cable Reference Installation Methods - Open Electrical

The document defines 7 methods (A-G) for installing electrical cables based on the IEC 60364 standard. Method A covers cables in thermally insulated walls or conduits. Method B includes cables in conduits on or near walls. Method C applies to cables on wooden walls, attached directly to walls/ceilings, or in masonry walls. Method D covers underground cables. Method E is for cables in free air spaced from walls. Method F is for cables in free air touching. Method G has separately spaced flat cables in free air.

Uploaded by

Doly Damanik
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
144 views3 pages

Cable Reference Installation Methods - Open Electrical

The document defines 7 methods (A-G) for installing electrical cables based on the IEC 60364 standard. Method A covers cables in thermally insulated walls or conduits. Method B includes cables in conduits on or near walls. Method C applies to cables on wooden walls, attached directly to walls/ceilings, or in masonry walls. Method D covers underground cables. Method E is for cables in free air spaced from walls. Method F is for cables in free air touching. Method G has separately spaced flat cables in free air.

Uploaded by

Doly Damanik
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

1/14/2017

CableReferenceInstallationMethodsOpenElectrical

CableReferenceInstallationMethods
FromOpenElectrical

Contents
1Introduction
2MethodA
3MethodB
4MethodC
5MethodD
6MethodE
7MethodF
8MethodG
9Relatedtopics:

Introduction
TheIEC60364standarddefinesanumberofinstallationmethodswhichrepresentthevariousinstallation
conditions.Bythefollowingicons,theyaredividedintogroupsanddefinedbythelettersAtoGwhichdetermine
howtoreadthetableofthecurrentcarryingcapacitiesinconductors.

MethodA
A1Insulatedsinglecoreconductorsinconduitinathermallyinsulatedwall
A2Multicorecableinconduitinathermallyinsulatedwall
Thismethodalsoappliestosinglecoreormulticorecablesinstalleddirectlyina
thermallyinsulatedwall(usemethodsA1andA2respectively),conductorsinstalledin
mouldings,architravesandwindowframes.

MethodB
B1Insulatedsinglecoreconductorsinconduitonawall
B2Multicorecableinconduitonawall
Thismethodapplieswhenaconduitisinstalledinsideawall,againstawallorspaced
lessthan0.3xD(overalldiameterofthecable)fromthewall.MethodBalsoapplies
forcablesinstalledintrunking/cableductagainstawallorsuspendedfromawalland
cablesinstalledinbuildingcavities.

http://www.openelectrical.org/wiki/index.php?title=Cable_Reference_Installation_Methods

1/3

1/14/2017

CableReferenceInstallationMethodsOpenElectrical

MethodC
CSinglecoreormulticorecableonawoodenwall
Thismethodalsoappliestocablesfixeddirectlytowallsorceilings,suspendedfrom
ceilings,installedonunperforatedcabletrays(runhorizontallyorvertically)andinstalled
directlyinamasonrywall(withthermalresistivitylessthan2K.m/W).

MethodD
D1Multicoreorsinglecorecablesinstalledinconduitburiedintheground
D2Multicoreorsinglecorecablesburieddirectlyintheground

MethodE
EMulticorecableinfreeair
Thismethodappliestocablesinstalledoncableladder,perforatedcabletrayorcleatsprovided
thatthecableisspacedmorethan0.3xD(overalldiameterofthecable)fromthewall.Note
thatcablesinstalledonunperforatedcabletraysareclassifiedunderMethodC.

MethodF
FSinglecorecablestouchinginfreeair
Thismethodappliestocablesinstalledoncableladder,perforatedcabletrayorcleatsprovidedthatthecableis
spacedmorethan0.3xD(overalldiameterofthecable)fromthewall.Notethatcablesinstalledonunperforated
cabletraysareclassifiedunderMethodC.
http://www.openelectrical.org/wiki/index.php?title=Cable_Reference_Installation_Methods

2/3

1/14/2017

CableReferenceInstallationMethodsOpenElectrical

MethodG
GSinglecorecableslaidflatandspacedinfreeair
Thismethodappliestocablesinstalledoncableladder,perforatedcabletrayorcleats
providedthatthecableisspacedmorethan0.3xD(overalldiameterofthecable)from
thewallandwithatleast1xDspacingsbetweencables.Notethatcablesinstalledon
unperforatedcabletraysareclassifiedunderMethodC.Thismethodalsoappliesto
cablesinstalledinairsupportedbyinsulators.