1ppac 1B

This document contains design calculations for the electrical panel 1PPAC1B for a new factory building. It determines that the main circuit breaker should be 100AT, 100AF, 3P, 400V, 60Hz MCCB. The main feeder wiring should be 3 cables of 30mm2 THHN + 1 cable of 30mm2 THHN(N) & 1 cable of 8.0mm2 THHN(G) run through a 40mm diameter IMC conduit. The calculations are based on a total maximum connected load of 52,306VA across 14 circuits, with the largest being a 10HP motor load of 10,738VA.

Uploaded by

rjayfran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
51 views1 page

1ppac 1B

This document contains design calculations for the electrical panel 1PPAC1B for a new factory building. It determines that the main circuit breaker should be 100AT, 100AF, 3P, 400V, 60Hz MCCB. The main feeder wiring should be 3 cables of 30mm2 THHN + 1 cable of 30mm2 THHN(N) & 1 cable of 8.0mm2 THHN(G) run through a 40mm diameter IMC conduit. The calculations are based on a total maximum connected load of 52,306VA across 14 circuits, with the largest being a 10HP motor load of 10,738VA.

Uploaded by

rjayfran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

OWNER: ACBEL POLYTECH (PHILIPPINES), INC.

DATE: SEPTEMBER 21, 2016


PROJECT: CONSTRUCTION OF ACBEL TWO-STOREY STANDARD FACTORY BUILDING (PHASE 2)
LOCATION: LOT C3-16, ROAD 1, CARMELRAY INDUSTRIAL PARK II, BRGY. PUNTA, CALAMBA CITY, LAGUNA

SUBJECT: DESIGN CALCULATIONS - ELECTRICAL

Panel ID: 1PPAC1B Voltage: 400 230 Enclosure: NEMA 1


BRANCH FEEDER COMPUTATIONS
Mounting: Surface Phase: 3 Min. KAIC: 10

Circuit Circuit Breaker Connected Connected Load per Phase (VA) Demand Demand
Load Description Ib (A) ICB/WIRE (A) CB Size Feeder Size
No.: AT AF P Load (VA) AN BN CN Factor (%) Load (VA)

1 30 100 3 AHU-1B via FVNR, Nema Size 1 3,464 1,155 1,155 1,155 80% 2,771 / 400 / 1.732 = 4.00 A = Ib x 2 = 8.00 A 30 AT 3 - 3.5mm2 THHN
2 30 100 3 AHU-1B via FVNR, Nema Size 1 3,464 1,155 1,155 1,155 80% 2,771 / 400 / 1.732 = 4.00 A = Ib x 2 = 8.00 A 30 AT 3 - 3.5mm2 THHN
3 30 100 3 AHU-1B via FVNR, Nema Size 1 3,464 1,155 1,155 1,155 80% 2,771 / 400 / 1.732 = 4.00 A = Ib x 2 = 8.00 A 30 AT 3 - 3.5mm2 THHN
4 30 100 3 AHU-1B via FVNR, Nema Size 1 3,464 1,155 1,155 1,155 80% 2,771 / 400 / 1.732 = 4.00 A = Ib x 2 = 8.00 A 30 AT 3 - 3.5mm2 THHN
5 30 100 3 AHU-1B via FVNR, Nema Size 1 3,464 1,155 1,155 1,155 80% 2,771 / 400 / 1.732 = 4.00 A = Ib x 2 = 8.00 A 30 AT 3 - 3.5mm2 THHN
6 30 100 3 AHU-1B via FVNR, Nema Size 1 3,464 1,155 1,155 1,155 80% 2,771 / 400 / 1.732 = 4.00 A = Ib x 2 = 8.00 A 30 AT 3 - 3.5mm2 THHN
7 30 100 3 AHU-1B via FVNR, Nema Size 1 3,464 1,155 1,155 1,155 80% 2,771 / 400 / 1.732 = 4.00 A = Ib x 2 = 8.00 A 30 AT 3 - 3.5mm2 THHN
8 30 100 3 AHU-1B via FVNR, Nema Size 1 3,464 1,155 1,155 1,155 80% 2,771 / 400 / 1.732 = 4.00 A = Ib x 2 = 8.00 A 30 AT 3 - 3.5mm2 THHN
9 30 100 3 AHU-1B via FVNR, Nema Size 1 3,464 1,155 1,155 1,155 80% 2,771 / 400 / 1.732 = 4.00 A = Ib x 2 = 8.00 A 30 AT 3 - 3.5mm2 THHN
10 30 100 3 AHU-1B via FVNR, Nema Size 1 3,464 1,155 1,155 1,155 80% 2,771 / 400 / 1.732 = 4.00 A = Ib x 2 = 8.00 A 30 AT 3 - 3.5mm2 THHN
11 30 100 3 AHU-1B via FVNR, Nema Size 1 3,464 1,155 1,155 1,155 80% 2,771 / 400 / 1.732 = 4.00 A = Ib x 2 = 8.00 A 30 AT 3 - 3.5mm2 THHN
12 30 100 3 AHU-1B via FVNR, Nema Size 1 3,464 1,155 1,155 1,155 80% 2,771 / 400 / 1.732 = 4.00 A = Ib x 2 = 8.00 A 30 AT 3 - 3.5mm2 THHN
13 40 100 3 PEF-2 via FVNR, Nema Size 2, 10HP 10,738 3,579 3,579 3,579 80% 8,591 / 400 / 1.732 = 12.40 A = Ib x 2 = 24.80 A 40 AT 3 - 5.5mm2 THHN
14 100 3 Space

Total Load (VA) 52,306 17,435 17,435 17,435 80% 41,845

COMPUTATIONS:

Ib(DESIGN) = [Max. Connected Load (VA) x 3 x Demand Factor (DF)] / (1.732 x 400V) Unbalanced Load = 0.00%
= 17,435 VA x 3 x DF] / (1.732 x 400V)
= 60.40 A

ICB = Summation of all motor currents + 100% Biggest Motor Current (BMI) + Summation of Other Load Currents
= 72.80 A USE: 100 AT, 100AF, 3P, 400V, 60Hz, MCCB

IWIRE = Summation of all motor currents + 25% Biggest Motor Current (BMI) + Summation of Other Load Currents
= 63.50 A USE: 3 - 30mm2 THHN + 1 - 30mm2 THHN(N) & 1 - 8.0mm2 THHN(G) in 40mm IMC

SUMMARY:

MAIN CIRCUIT BREAKER: 100AT, 100AF, 3P, 400V, 60Hz, MCCB

MAIN FEEDER: 3 - 30mm2 THHN + 1 - 30mm2 THHN(N) & 1 - 8.0mm2 THHN(G) in 40mm IMC