Test Procedure 7sj61

1. The document provides instructions for testing the protection functions of a Siemens 7SJ61 relay. It describes connecting the relay to a laptop using an RS232 cable and using Digsi software to communicate with the relay and access its settings. 2. It explains how to enable only the protection function being tested, such as overcurrent, and set the relevant pickup and trip times for testing in setting group A. 3. It also describes how to configure output masking and LEDs to indicate pickup of each phase for overcurrent testing.

Uploaded by

Anoss Olier
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
242 views7 pages

Test Procedure 7sj61

1. The document provides instructions for testing the protection functions of a Siemens 7SJ61 relay. It describes connecting the relay to a laptop using an RS232 cable and using Digsi software to communicate with the relay and access its settings. 2. It explains how to enable only the protection function being tested, such as overcurrent, and set the relevant pickup and trip times for testing in setting group A. 3. It also describes how to configure output masking and LEDs to indicate pickup of each phase for overcurrent testing.

Uploaded by

Anoss Olier
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

TEST PROCEDURE OF SIEMENS 7SJ61 RELAY

1. Connect the relay to the laptop by cross RS232 communication cable.


2. Open Digsi software by double click on the software icon, following page will appear on screen

3. Go to file open new, write the project name e.g. XYZ and click ok.
4. Go to folder and right click, in options click on Device>Digsi (Plug and play)
5. On this select direct and select your pc interface then click ok. After this it will communicate to
the relay. After successful communication following page will appear, in this page device setting
is come to your software.
6. To open device setting double click on the file
7. Now we can make changes in setting online or offline. For online select direct
8. To open setting click on setting

9. Now click on device configuaration


10. Here in device configuration we can enable or disable each protection function as per our
requirement. For testing purpose only that element should be enable which element we have to
test. Suppose O/C element has to test then keep this function enable rest all function should be
disable.
11. In power system data 1 set the system power system data for which the relay is installed e.g.
Power frequency, CT ratio, phase sequence etc.
12. In setting group A we can set the setting value for all enabled protection functions. Here we
select only for O/C protection so we will set O/C pickup and trip time as per our test format.
13. For tripping we can configure any output in masking I/O (configuration matrix). For example we
have taken Binary Output 1 for over current tripping. Also we can configure the LEDs here in
following pic LED 2,3and 4 is used for pickup of A, B and C phase respectively.