Eocr
Eocr
EOCR-iFM420
6th floor, Jeil Bldg., 94-46, Youngdeungpo-Dong 7Ka, Youngdeungpo-Ku, Seoul, Korea Wollongong P: +61 2 4285 9978 F: + 61 2 4285 9989
Tel. 82 2 3473 2340 / Fax 82 2 3473 1159
Iksan Plant Gloucester P: +61 2 6558 2986 F: + 61 2 4014 9099
574, Yongie-dong, Iksan-shi, Junbuk, Korea Mackay P: +61 7 4952 3833 F: + 61 2 4014 9099
Tel. 82 63 835 5033 / Fax 82 63 835 4175
www.eocr.com 10/2008
E: [email protected]
website: www.rdtechnology.com.au
EOCR-i Series (with communication)
Basic model : EOCR-i3DM (Z, S, 420) / iFDM (Z, S, 420)
General features
Micro-Controller Unit based
Real time processing / High precision
Protections : Over current, Under current, Phase loss, Phase reversal, Stall, Jam, Current imbalance,
Earth fault (i3MZ/iFMZ), Short circuit (i3MS/iFMS)
Thermal protection / Inverse available up to 32Amps without external CTs.
Auxiliary functions : Fail safe, Accumulated running hour, 3 fault records &
limitation of auto-restart. Analog output
Communication : Modbus / RS-485
Reinforced monitoring function : Monitoring distance up to 400M, 3 phase current display,
& Trip cause indication
Bar graph indication of a load current to the current setting.
Available application on single and 3 phase motor
RoHS Compliance
normal protections are guaranteed even if PDM is disconnected.
9
EOCR-i Series (with communication)
Basic model : EOCR-i3DM (Z, S, 420) / iFDM (Z, S, 420)
Protection functions
Protection item Condition & Setting range Operation time
Condition : Load current (In) exceeds setting current (Is) Definite (Def) : 0.2~30s Adjust.
Over current (oc)
Setting range : 0.5~60A (Def), 0.5~32A (Inv & th) Inverse (Inv) & Thermal (th) : 1~30 class
Condition : Load current (In) less than setting currentIn uc
Under current (uc) oFF, 1~10s Adjustable
uc should be less than oc setting
Condition : max imbalance is more than 85% among 3 phase current,
Phase loss (PL) oFF, 0.5~5s Adjustable
Enable or disable : Selectable
Condition : Reversed phase sequence input on EOCR.
Reverse phase (RP) Within 0.15s
Enable or disable : Selectable
Condition : In Stall current setting (Sc). Active only in motor starting
0.5~30A : 2~8 times of oc setting
Stall (Sc) Right after D-time elapsed
~40A : 2~6 times,
~60A : 2~4 times.
Condition : In Jam current setting (JA). Active only in motor running
Jam (JA) 0.5~50A : 1.5~5 times of oc setting 0.2~5s Adjustable
~60A : 1.5~4 times of oc setting
Condition : Current imbalance Setting imbalance %
Imbalance (IM) 1~10s Adjustable
Setting range : 10~50% of imbalance
Condition : EF current (Ie) exceeds setting current (Ies) 0.05~5s Adjustable
Earth fault (EF)
OFF, 0.03~10A -- i3MZ/iFMZ only --
Condition : SC current (Is) exceeds setting current (Iss)
0.05sec
Short circuit (SH) 0.5~10A : 2~22 times of oc setting,
-- i3MS/iFMS only --
~20A : 2~11 times of oc setting
Auxiliary functions
Password For secured setting parameters
CT ratio For the current setting more than 60A and less than 0.5A
Pre alarm selection Pre alarm signaling by the 07-08 output contact -- i3MS/iFDM only --
Total running hour Total accumulated running hour from the installation which cannot be modified and reset .
Running hour Display or provied a time-out signal to the 07-08 output contact. -- i3MS/iFDM only --
Restart limitation The maximum auto-restart number within 30 minutes in auto-reset mode.
10
EOCR-i Series (with communication)
Basic model : EOCR-i3DM (Z, S, 420) / iFDM (Z, S, 420)
Specifications
Model iFM420
Over current Rated setting range (A) Definite TCC : 0.5~60A. : use external CT higher than 60A
11
EOCR-i Series (with communication)
Basic model : EOCR-i3DM (Z, S, 420) / iFDM (Z, S, 420)
Front face
Set / Store
Bar graph
it shows the load factor to OC setting value by %
7 segment LED Display % value = (running current/setting current) * 100%
Min scale is 65%
if the setting value is the rated motor current,
it shows the load factor of the motor.
Current Display
Shows the highest current among three phases for OC, Stall, Jam trips.
Shows the lowest current among three phases for UC, UB
Reset
Mode selection Shows the lost phase for PL.
switch
Set / Store Shows the phase and the current during running.
Power Communication
AL/UL/TO NO output OL
NC output OL
12
EOCR-i Series (with communication)
Basic model : EOCR-i3DM (Z, S, 420) / iFDM (Z, S, 420)
2sec
L1 current display L2 current display
2sec
Earth leakage current L3 current display
(iXXZ Type only)
Blocking display rotation can be done by pressing the SET button once during running. whenever press the SET
button, the each phase current displays by turns. A fixed phase current display can be done by this.
Pressing the ESC button, it returns to the Auto current display rotation mode.
Memorize the values in the relay by pressing SET button. blinking stops to
show its stored.
Pressing ESC button, it returns to the current display. Without pressing ESC
button, it returns to the load current display in 50sec automatically.
Fault history check : Pressing the ESC button more than 5sec, it displays the latest fault cause and the fault current or
fault phase. Continuing to press DN button, you can see the current of L1(R), L2(S), L3(T), (GR) in turn. press the DN
button again to check the previous fault continually. In the latest fault display, the 100% LED of bar graph lights on and
two LEDs of 95%, 100% lights on for the second fault display, three LEDs of 90%, 95%, 100% lights on for the oldest
fault display. When you press the ECS button in this mode, it returns to the normal current display mode. The oldest
fault record is over written when the number of fault to record exceeds three.
Setting sequence
i3MZ(S) / iFMZ(S)
only
i3MZ /
iFMZ
only
i3MS /
iFMS
only
i3M420 /
iFM420 only
i3DM /
iFDM only i3DM /
iFDM only
13
EOCR-i Series (with communication)
Basic model : EOCR-i3DM (Z, S, 420) / iFDM (Z, S, 420)
Use password other than zero for secured settings. This feature enables
1 Pass word limitation of setting modification by unauthorized person. Zero value is used
for disabling password checking.
Ph:3Ph mode for a 3 phase load, Ph:1Ph mode for a 1 phase load should
Selection of
2 be selected. If you select the Ph:1Ph, RP, PL and Ub functions will be
Phase No.
disabled and not displayed in the menu mode
External CT ratio setting mode. This is applied to definite TCC; higher than 60A
and inverse TCC; higher than 32A. Set the primary value of the external CT.
4 CT ratio For example, 200:5 CT, setting is ct:200. For the low-range current ct: 2t
is for 2 pass through, ct: 5t is for 5 pass through.
Select ct:non in case of no externel CT and no loop.
Selection of fail safe(No volt release) mode for overload trip output, OL.
6 Fail safe
Refer to fail-safe operation
Reversed phase
7 Enable or disable reverse phase detection
detection
Over current Threshold for over current protection . this value cannot be set below the
8
threshold under current threshold (uc).
Motor starting delay, OC, UC, Stall, Jam, Ub are blocked during starting but
9 Start delay time PL, RP are not blocked. For In TCC mode, ,the cold curve is appled before
dt expires and, the hot curve is applied after dt expires.
Over current (tcc:dE) ; the fault(over current) duration of definite overcurrent protection.
duration (tcc:In) ; the trip class for inverse overcurrent protection(refer to TCC curve)
10
(Trip delay time / (tcc:th) ; the thermal overload protection based on the thermal image by
Trip class ) load current (refer to TCC curve).
Under current Threshold for under current protection. The setting should be higher than
11
threshold no-load current of a motor. The current value cannot be set higher than OC.
Under current duration Fault (under current) duration for the under current Operation. If the setting
12
(Trip delay time) of oFF in the uc mode is selected, this menu is not displayed
Earth fault Threshold for earth fault protection. The capacitance leakage current of the
13
(Ground fault) motor and cable should be taken into account for the setting. The threshold
#1
threshold value corresponds to the primary current of ZCT
14
EOCR-i Series (with communication)
Basic model : EOCR-i3DM (Z, S, 420) / iFDM (Z, S, 420)
Phase loss Fault duration for phase loss operation. The setting range is 0.5~5 sec. if
19
time PL:oFF is selected, this menu is not displayed
Imbalance fault Imbalance fault duration (trip delay time) for current imbalance operation.
21
duration The setting range is 1~10 seconds.
Threshold for locked rotor detection during motor starting. The value is the
multiples of the over current threshold(oc). If the locked rotor condition is
Stall detected, the trip relay operates in 0.5s after the dt expires.
22
threshold If dt=0, this function is disabled and not displayed in the menu.
Setting range : oc=0.4~30A:2~8times, oc < 40A:2~6times, otherwise
(oc<60A) : 2~4times, (with Ext. CT : 2~8times)
Threshold for locked rotor detection during motor running. The value is the
23 Jam threshold multiples of the over current threshold (oc).
Setting : oc=0.4~50A : 1.5~5times, otherwise (oc<60A) : 4times, (with Ext. CT : 15~5times)
Threshold of Alert output, set by % of the over current threshold (oc). If the
load current is higher than this value, alert output(07-08 contact) is energized
according to the setting of ALo : XX.
If the load current is higher than the alert threshold, alert output(07-08
contact) repeats open for 1s and close for 1s (flickering), The flickering starts
26 Alert from the motor starting.
#4 Refer to the alert operation pattern.
If the load current is higher than the alert threshold, alert output(07-08 contact)
is closed (holding) and remains closed until the load current decrease under
the alert threshold. The alert output is blocked during motor starting.
Refer to the alert operation pattern.
If the accumulated running hour is more than the running hour threshold,
the alert output repeats close for 1s and open for 1s.
The alert output is used only for under current protection. If this mode is
selected, a trip by an under current fault is signaled through alert output
(07-08), instead of overload trip output(95-96 or 97-98).
15
EOCR-i Series (with communication)
Basic model : EOCR-i3DM (Z, S, 420) / iFDM (Z, S, 420)
Fault reset (Electrical reset) by a power cycle or by pressing the ESC button.
In this menu, toggle display, -trh- and the accumulated (time) value, is
activated (?)
29 Total running hour read only
The accumulation starts from the installation and the user cannot clear the
accumulated value. This display unit is 1 hour.
In this menu, toggle display, --rh- and the accumulated value, is activated (?)
The user can clear the accumulated value by selecting the running hour
30 Running hour threshold to rh:oFF. This display unit is 0.1 hour (6 minutes). read only
By selecting ALo:to, the user can get the alert signal through alert output
(07-08) when the accumulated value is more than the running hour threshold.
Parity setting
Range : odd, even, non.
When this menu activated, OL trip signal and enabled short or EF trip signal
is generated when (3s+ot) expires.
The display shows End when the test is done. No
33 Test trip By pressing ESC, returns to the load current display mode. parameter
This menu is not displayed when the motor is starting or running.
Before (3s+ot) expires, pressing ESC or motor starting or running blocks the
test trip and return to the load current display. No parameter
34 End No
This shows the end of test trip. Test result is stored in the fault record.
parameter
16
EOCR-i Series (with communication)
Basic model : EOCR-i3DM (Z, S, 420) / iFDM (Z, S, 420)
Fail-safe operation
A1-A2 powered and A1-A2 powered
Fail-Safe A1-A2 not powered
under normal operation and Tripped
ON
OFF
Limitation of In 30minutes, the number of auto-restar For emergency restart, manual reset by pressing ESC clears the restart
auto-restart by auto-reset exceeds the setting counter to zero.
17
EOCR-i Series (with communication)
Basic model : EOCR-i3DM (Z, S, 420) / iFDM (Z, S, 420)
Current
[Multiples of current setting]
Current Current
[Multiples of current setting] [Multiples of current setting]
18
EOCR-i Series (with communication)
Basic model : EOCR-i3DM (Z, S, 420) / iFDM (Z, S, 420)
0.25 ~ 3A 2 No CT combination
Off
Elec. Elec.
Off
440,380/220 Reset 440,380/220 Reset
MC MC
On On
Trip
MC Y Trip Y MC
A1 08 96 98 A1 08 96 98
AL/uc OL AL/uc OL
to to
A2 07 95 97 A2 07 95 97
Single phase motor (window type) Single phase motor (window type)
L1 L3(L2;N) L1 L3(L2;N)
MCCB MCCB
MC MC
On On
Trip
MC Y Trip Y MC
A1 08 96 98 A1 08 96 98
AL/uc OL AL/uc OL
to to
A2 07 95 97 A2 07 95 97
RS485 RS485
Communication
Bottomhole type
Communication
19
EOCR-i Series (with communication)
Basic model : EOCR-i3DM (Z, S, 420) / iFDM (Z, S, 420)
Elec.
Off Elec.
440,380/220V Reset
440,380/220V Reset Off
MC
MCCB
MC
On
MCCB-a On
MC
MCCB
MC SC Trip
shunt trip coil
A1 96 58 Z2 SC MC Y
OL GR A1 48 96 98
To: Z1 , Z2
ZCT OL
SH
200:1.5 A2 95 57 Z1
A2 47 95 97
RS485
Communication
RS485
Communication
L1 L2 L3
MCCB
Tr. Fuse
Elec.
Off
440,380/220V Reset
MC
On
Trip
Y MC
4~20mA
A1 96 98
OL
A2 95 97
RS485
Communication
Cabling for a three phase motor Cabling for a single phase motor
20
EOCR-i Series (with communication)
Basic Model : EOCR-i3DM (Z, S, 420) / iFDM (Z, S, 420)
Control terminals
EOCR-i3DM/iFDM
AL / UL / TO OL OL COMM
A1 A2 07 08 95 96 97 98 V- D1 D0 S
Modbus
Communication
Control power
OL NO output
AL/UL/TO NO output OL NC output
EOCR-i3MZ/iFMZ (A type)
OL
OL GR
GR ZCT
ZCT COMM
COMM
OL GR ZCT COMM
A1 A2 97
A1 97 98 57
57 58 Z1
Z1 Z2 V-
V- D1 D0
D0 S
A1 A2
A2 97 98
98 57 58
58 Z1 Z2
Z2 V- D1
D1 D0 S
S Modbus
Communication
Control power
ZCT input
OL NO output EF NO output
EOCR-i3MZ/iFMZ (C type) OL // GR
OL GR ZCT
ZCT COMM
OL / GR ZCT COMM
COMM
A1 A2 95
A1 95 96 97
97 98 Z1
Z1 Z2 V-
V- D1 D0
D0 S
A1 A2
A2 95 96
96 97 98
98 Z1 Z2
Z2 V- D1
D1 D0 S
S
Modbus
Control power
Communication
OL/EF NO/NC common output ZCT input
EOCR-i3MZ/iFMZ (D type)
OL
OL GR
GR ZCT
ZCT COMM
COMM
OL GR ZCT COMM
A1 A2 95
A1 95 96 57
57 58 Z1
Z1 Z2 V-
V- D1 D0
D0 S
A1 A2
A2 95 96
96 57 58
58 Z1 Z2
Z2 V- D1
D1 D0 S
S Modbus
Communication
Control power
ZCT input
OL NC output EF NO output
EOCR-iFM420
OL OL
4~20mA
A1 A2 95 96 97 98 + V- D1 D0 S Modbus
Communication
Control power
4~20mA output
OL NC output OL NO output
EOCR-i3MS/iFMS
SH OL OL COMM
A1 A2 47 48 95 96 97 98 V- D1 D0 S Modbus
Communication
Control power
OL NO output
SH NO output OL NC output
21
EOCR-i Series (with communication)
Basic model : EOCR-i3DM (Z, S, 420) / iFDM (Z, S, 420)
Dimension of iFXX
Window type
EOCR-iFDM EOCR-iFM420 22.5 22.5 3-12
EOCR-iFMZ EOCR-iFMS
74.5
56.3
4.5
83.8 82
70 102.4 95
21.4
56.3
70
4.5
21.4
82
108.1 95
126.7
Terminal type
EOCR-iFDM EOCR-iFM420
EOCR-iFMZ EOCR-iFMS
53.3
91.3
4.5
6-M4 45.3
21.4 21.4 108.1 82
70 126.7 95
Display
EOCR-PDM
65
64
72
13.4
72
28.1 MOUNTING HOLE SIZE
23
EOCR-i Series (with communication)
Basic model : EOCR-i3DM (Z, S, 420) / iFDM (Z, S, 420)
Ordering
Display EOCR-PDMQ
25
Technical information
Option-1. Looping (Protect smaller current by looping option) Option-2. External current transformer option
Some motor size may require one-third or one-fourth of particular EOCR current (Ext. CT option protect bigger current)
range. These installations can be accommodated by looping the motor wire 2 or Ordering option - 05 type of each model fitted to an external current transformer
3 times through the integral current transformers of the EOCR. This reduces the can achieve higher ampere ranges.
number and type of relays inventoried for spare purposes. Each additional loop (EOCR-3DM/3MZ/3M420/FDM/FMZ/FM420)
will increase the current measured as indicated by the following chart.
Current setting No. of passing No. of loops DIP SW Current setting Current ratio
range (A) (#) (#) setting range (A) of Ext. CT
05 Type 0.5 ~ 6 1 0 05 type 05 0.5 ~ 10 NIL
0.25 ~ 3 2 1 60 type 60 5.0 ~ 60 NIL
0.17 ~ 2 3 2 05 10 ~ 120 100 : 5
Looping Option 0.12 ~ 1.5 4 3 Ext. CT option 05 15 ~ 180 150 : 5
0.10 ~ 1.2 5 4 05 20 ~ 240 200 : 5
05 30 ~ 360 300 : 5
setting exceed
Preset current
setting exceed
Preset current
45
Technical information
1. Over current threshold (OC) : Set the OC at the rating current of a motor. To protect
machine together, it is recommended to set at
110~120% of the actual normal operating current.
2. Starting delay time (D-time) : Set an expected start-up time to reach the normal speed
of load. If you do not know it, set to 15sec at first and
start-up the motor to measure the time to reach the
normal operation speed by monitoring the displayed
current and then change the time into 2 sec longer than
the time measured. For a Y-D start, its better to set time
longer than the preset time of the timer by 2sec
minimum normally.
3. Operation time (O-time) : Set the trip delay time which activates and counts down
under a fault condition.
2. Starting delay time (D-time) : Usually, set D-time to zero. With zero D-time, the cold
curve is applied before the load current cross down the
OC, and then the hot curve is applied.
If the start-up time is long and fast trip is required during
motor running, set D-time to start-up time or longer. In
this case, over current protection is blocked during the
start-up, and the hot curve is applied when D-time
expires.
Since thermal inverse has no relation with D-time, set D-
time to zero when the thermal inverse is selected.
46
EOCR Setting Guide
Basic model (3DM / FDM) It means under current (Dry Run) protection, If a level
Password input is necessary to chage the setting value of switch has a problem in a submersible pump, It backs up
EOCR, if a password is memorized except 000. the level switch function from no water running of pump
If the password is set to 000, no password input is necessary and protect the motor from overheating. For the
in 000 to enter the setting change mode. Please take machinery running with a belt (including conveyer), It
caution not to forget the password.No password function is candetect a broken belt. The current setting should be
provided in 3DM2/FDM2, 3MZ2/FMZ2. higher than rating no load current of motor for this function.
The default setting is oFF .
The default setting is a 3phase motor. The setting change
to is necessary for 1 phase motor. It is uc trip delay time setting . If you don t set the uc
function (uc:oFF), ut setting doesnt appear at the menu.
Time current characteristic (TCC). the defaut setting is
tcc : dE (definite TCC). This memu is to determine enable/disable of PL (Phase
loss) funnction. If you set Ph:1Ph at the power phase
The default setting is non, setting value is the primary selection menu for a single phase power supply line, this
current with an external CT combination in this mode. menu doesnt appear automatically.
( Ex: in case of 200; 5, the setting is 200 )
It is trip delay time setting for PL. The default setting is 2
If the control power or EOCR itself has a problem, the sec. For single phase power line setting, it doesn t appear
motor stops with the output relay trip in the FS: on mode. at the munu.
The default setting is.
EOCR calculates the unbalance rate among three
For the application which motor rotation direction is phase currents. It trips after Ubt setting time under a
important , rP: on should be set . unbalanced condition. The default setting is oFF.
rP:oFF setting doesnt make a problem after completion
of the installation for the permanent stable application. Locked Rotor protection during starting up a motor (Stall).
The default setting is rP:oFF. If a rotor of motor is locked during starting and keep the
current at higher than the Sc setting during D-time,
It is recommended for oc to set at the rating current of EOCR trips in 0.5sec after D-time. The default setting is
motor. Default setting is oc:5.0A . Sc: 4.
The setting value is a multiple of oc setting value. This
It means a starting delay time setting for a motor start up function operates under the Definite TCC condition.
duration from the start of motor to the normal running It is disabled under the Inverse TCC setting generally. But
current. The start up duration depends on the inertia of if you set D-time greater than zero in Inverse setting, Stall
load. Therefore, it is recommended to set the time after operates when d-time expires.
47
EOCR Setting Guide
Electrical Reset . EOCR resets by power cycle Short Circuit trip delay time during motor starting to
of control power or ESC button. It can be used prevent a trip caused by starting current. OFF setting is
for a remote reset which enables EOCR to reset possible .
from a remote site.
Additional Menu (i3MZ/iFMZ, 3MZ2/FMZ2)
Hand Reset (Manual Reset). EOCR can be
Earth leakage protection current setting. The default
reset by ESC button only.
setting is 0.5A. Minimum setting value is recommeded, if
there is no leakage current in the motor by the current
Auto Reset . The time setting range is up to 20
display. If the display shows a leakage current more than
minutes (20n). The auto reset number. of times
50mA, user must check the insulation of motor and line. In
is connected to the restart limitation setting
the case of installing EOCR at the secondary side of
menu. If the number of restrat over the restart
Inverter, its better to take care of EOCR opreration error
limitation number. in the rn setting menu
due to harmonics of Inverter.
during 30 minutes, EOCR doesn t reset
anymore.
Earth leakage trip time. The default setting is 0.05sec.
It is recommended to set the faster time and lower current
Restart limitation number. It prevent a motor from a
than the earth fault protection relay in the upper power
burning fail caused by many restarts during 30 minutes.
system.
In case an emergency restart is necessary, put the setting
at OFF This function activates in Auto-Reset mode only.
Earth leakage trip delay time during motor starting to
prevent a trip caused by a stray current and harmonics of
Modbus slave (ID) address. It can be set at No. 1 ~ 247.
the starting current in motor.
48
Troubleshooting Guide
Troubleshooting Guide
1. Reversed phase :
It trips instantly within 0.15sec from the motor starting. Check the 7. Current unbalance :
phase sequence and cable direction of the power Ideally, the motor currents of three phases are balanced. If a current
line going to the motor first. The sequence of EOCR internal CT is unbalance is high, the motor need to be checked.
A(L1), B(L2), C(L3) from the left side. If the passing order of motor The formula is as follows.
line to the EOCR doesnt coincide with the order of EOCR CT or not Unbalance factor (%) = (Imax phase - Imin_phase) / Imax_phase 100%
same all the direction of cables, It trips by RP. In this case, change
the order of the two cables among three. When the sequence of 8. Jam :
cables to the motor changes in the downstrenm side of EOCR , Rapid overload protection during motor running, Check the load
EOCR isnt able to check the RP. The sequence of cables should be which cause impacts it. If you find no problem in the load and motor,
coincided from the power mains to the motor. If the RP is not an try to chage the setting value higher of the time and current to be
indispensable function or only necessary for the first installation and appropriate for the application.
fixed in the site, The setting is recommended for normal
operation. 9. Unable to reset :
If you cannot reset EOCR by control power interruption, Check the
2. Overcurrent : reset type setting first. In the setting of
Overcurrent trip displays the biggest current among three phases User can reset EOCR by ECS button only. If you want to reset
and the small LED in the left side shows the phase. EOCR by both control power cycle and ECS button, Put the setting
If the trip current is lower than the rating current of motor, check the at
oc setting if it is too low. The recommended oc setting is
110%~120% of actual running current in the definite TCC.
3. Stall :
When the starting current doesn t go down below the Sc setting
during D-time. EOCR trips by Stall within 0.5se when D-time expires.
Check the status of load and D-time, whether the D-time is too short
or not. The recommended D-time is longer by 1sec than a time that
the motor come to the normal running current .
4. Phase loss :
The small LED in the left side lights up and designates which phase
is lost in the display like as PL - r, PL - S, PL - t,
To check the PL status, put the PL trip time at the maximum and
measure the lost phase current by a clamp meter after a test start,
whether there is a current in the motor line or not. The minimum
operating current (min setting current) of motor sensed by EOCR
can make trip due to hunting current. Need to check load operation
condition of the application in this case. If the clamp meter shows a
normal current in the lost phase line, Check the EOCR status.
5. Unable to starting :
Even though the sequence wiring is O.K. If the motor is not able to
be started with no magnetic contactor energized, Check the Fail
Safe menu of with the output contact status
(NO, NC) of EOCR .
6. Undercurrent :
Undercurrent trip displays the lowest current among three phases
and the small LED in the left side shows the phase.
The example shows the sensing current of 1.6A in L2(S) phase. For
the heater line broken detection in a heater application. EOCR trips
by undercurrent according to the setting in delta connection, and
trips by phase loss in Star connection.
49
Communication Guide
Slave address
The EOCR has slave addresses from 1 to 247.
The factory default setting is 1.
Baud rate
The Communication speed provided is like below.
1.2kbps
2.4kbps
4.8kbps
9.6kbps
19.2kbps
38.4kbps
The factory default setting is 19.2kbps
Parity setting
Even
Odd
None
The factory default setting is even. Please refer to the table for the stop bit setting.
Parity setting Stop bit
Even or Odd 1
None 2
50
Communication Guide
Standard connection
The standard connection conforms to the Modbus specifications, sepecially 2 wire
multidrop serial bus diagram, presented at the website of Modbus.org in 2002
(Modbus_over_serial_line_V1.pdf, Nov.2002). Simple wiring diagram is like below.
Items Contents
single, shielded, twisted pair cable.
Type of trunk cable
Min 3rd cable
Maximum number of
32 stations (31 slaves)
stations without repeater
20m (66ft, at 1 tapoff)
Maximum length of tapoffs 40m (131ft, divided by tapoff no.
in Multi-Junction Box)
450 - 650 Pullup resistor, 5V basis
450 - 650 Pulldown resistor,
Bus polarization Recommend the polarization to Master at
Common. There is no polarization at
RS485 of EOCR .
Line terminator 120 Resistor, + /- 5%
YES (connect 1 protection ground minimum
Common polarity
to the bus)
51
Communication Guide
Please use a cable with 2pair shieded twisted conductors for Interface protection.
It is adviced to isolate the Modbus cable 30cm(11.8in) at least from a power cable.
If necessary, intersect the Modbus cable to a power cable perpendicularly.
Refer to the diagram in the left side for the line terminator wiring.
52