(RE-wrenches) SB 240 - No Neutral Sense Conductor: Previous Message: Next Message

The document is an email discussion about grid-tied inverters not requiring a neutral conductor. It summarizes that while most single-phase inverters have a neutral, it is not strictly necessary as the phases can be compared to ground instead. Utility-interactive inverters only inject current when voltage is in the proper range, so they do not independently produce a voltage. The only issues could be a slightly raised voltage from current flow or temporary overvoltage if the utility voltage drops to zero during an outage.

Uploaded by

NOELGREGORIO
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
64 views

(RE-wrenches) SB 240 - No Neutral Sense Conductor: Previous Message: Next Message

The document is an email discussion about grid-tied inverters not requiring a neutral conductor. It summarizes that while most single-phase inverters have a neutral, it is not strictly necessary as the phases can be compared to ground instead. Utility-interactive inverters only inject current when voltage is in the proper range, so they do not independently produce a voltage. The only issues could be a slightly raised voltage from current flow or temporary overvoltage if the utility voltage drops to zero during an outage.

Uploaded by

NOELGREGORIO
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

[RE-wrenches] SB 240 - No Neutral Sense Conductor http://lists.re-wrenches.org/pipermail/re-wrenches-re-wrenches.or...

[RE-wrenches] SB 240 - No Neutral Sense


Conductor
Bill Brooks billbrooks7 at yahoo.com
Thu Dec 19 08:44:19 PST 2013

Previous message: [RE-wrenches] SB 240 - No Neutral Sense Conductor


Next message: [RE-wrenches] Any familiarity with Dynapro batteries?
Messages sorted by: [ date ] [ thread ] [ subject ] [ author ]

Mark,

There are many inverters that do not have a neutral-just not many
single-phase inverters. Since all inverters must have at least an equipment
ground, the phases can be compared with ground. The testing standard covers
what is required. If neutral-ground bond is lost, it will show up in a bad
voltage phase-to-ground.

Since utility-interactive (U-I) inverters just inject current when the


utility voltage is in proper range, our inverters do not produce a separate
voltage. The only problems that our inverters can cause is a slightly raised
voltage due to current flow at the point of connection. Also, a much less
likely but current concern in Hawaii is temporary overvoltage. As the
utility voltage goes to zero in an outage, a U-I inverter must quickly clamp
its current or the voltage at the inverter terminals (and potentially the
house service) could momentarily go above nominal voltage. Generally, this
is not a problem since an inverter that does not act quickly enough will
damage itself.

Bill.

Bill Brooks, PE

Principal

Brooks Engineering

3949 Joslin Lane

Vacaville, CA 95688

707-332-0761 (office and mobile)

bill at brooksolar.com (email)

www.brooksolar.com (web)

1 of 2 2015-11-07 7:16 AM
[RE-wrenches] SB 240 - No Neutral Sense Conductor http://lists.re-wrenches.org/pipermail/re-wrenches-re-wrenches.or...

From: re-wrenches-bounces at lists.re-wrenches.org


[mailto:re-wrenches-bounces at lists.re-wrenches.org] On Behalf Of Mark Frye
Sent: Thursday, December 19, 2013 8:10 AM
To: RE-wrenches
Subject: [RE-wrenches] SB 240 - No Neutral Sense Conductor

Folks,

I was looking at the SMA micro inverter and notice only connections for L1,
L2 and earth. I thought all grid tied inverters needed a neutral sense
conductor to monitor for phase loss.

Any ideas?

Mark Frye

---
This email is free from viruses and malware because avast! Antivirus protection is active.
http://www.avast.com
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.re-wrenches.org/pipermail/re-wrenches-re-wrenches.org/attachments
/20131219/f6c3dffc/attachment-0002.htm>

Previous message: [RE-wrenches] SB 240 - No Neutral Sense Conductor


Next message: [RE-wrenches] Any familiarity with Dynapro batteries?
Messages sorted by: [ date ] [ thread ] [ subject ] [ author ]

More information about the RE-wrenches mailing list

2 of 2 2015-11-07 7:16 AM

You might also like