Pressure Reducing Valve: Model
Pressure Reducing Valve: Model
Optional Features
Item Description
A X46A Flow Clean Strainer SUD
B CK2 (Isolation Valve)
C CV Flow Control (Closing)*
D Check Valves with Isolation Valve
M X144 e-FlowMeter
P X141 Pressure Gauge
S CV Flow Control (Opening)
see page 3 for
V X101 Valve Position Indicator
approvals
Y X43 "Y" Strainer
H X43H Style Strainer
Typical Applications
Typical applications include pressure reducing valve station Cla-Val Model 90-01KO Pressure Reducing Valve with Anti-
using Model 90-01BY and Model 90-01AS in parallel to handle Cavitation Trim provides for optimum downstream pressure
wide range of flow rates. Larger Model 90-01BY valve meets control while reducing noise and eliminating damage
requirements of peak loads and smaller Model 90-01AS handles associated with cavitation. See Cavitation Guide to determine if
the valve is a candidate for the KO Anti-Cavitation Trim.
low flows.
High Pressure Upper Zone
X43H Strainer
X43H Strainer
CLA-VAL 90-01BY/690-01BY Isolation Valve
Pressure Reducing Valve
Isolation Valve CLA-VAL Model
90-01KO
X43H Strainer Anti-Cavitation Trim
Gauge for Excess Pressure Drop
Consult Cavitation Chart
Constant
CLA-VAL 90-01AS/690-01AS Downstream
Pressure Reducing Valve
Pressure
Area Of Heavy Demand
Model 90-01 (Uses Basic Valve Model 100-01)
B (Diameter)
J
Pressure Ratings (Recommended Maximum Pressure - psi) 100-01
Threaded &
Flanged K
Pressure Class X
Valve Body & Cover H
Flanged Grooved Threaded C
(MAX)
Pattern G, A G, A G, A G, A G, A G, A G, A G, A G, A G, A G, A G, A G, A G G G, A G G
Basic Valve
100-01
T, F, T, F, T, F, T, F, F, F, F,
End Detail T T F F F F F F F F F
Gr* Gr Gr* Gr Gr Gr* Gr*
Maximum 55 93 125 210 300 460 800 1800 3100 4900 7000 8400 11000 14000 17000 25000 42000 50000
Suggested
Maximum
Flow Intermittent
68 120 160 260 370 580 990 2250 3900 6150 8720 10540 13700 17500 21700 31300 48000 62500
(gpm)
100-01 Series is the full internal port Hytrol. For Lower Flows Consult Factory *Globe Grooved Only
Notes:
For sizes 18 through 36-inches, use 90-66 E-Sheet
Many factors should be considered in sizing pressure reducing valves including inlet pressure, outlet pressure and flow rates.
For sizing questions or cavitation analysis, consult Cla-Val with system details.
Main Valve Body All necessary repairs and/or modifications other than replacement
No separate chambers shall be allowed between the main valve of the main valve body shall be possible without removing the
cover and body. Valve body and cover shall be of cast material. valve from the pipeline. Packing glands and/or stuffing boxes
Ductile Iron is standard and other materials shall be available. No shall not be permitted.
fabrication or welding shall be used in the manufacturing process.
Total shipping weight shall be equal or greater in all respects to The valve manufacturer shall warrant the valve to be free of
the Hytrol 100-01 body. defects in material and workmanship for a period of three years
from date of shipment, provided the valve is installed and used in
The valve shall contain a resilient, synthetic rubber disc, with a accordance with all applicable instructions. Electrical components
rectangular cross-section contained on three and one-half sides shall have a one year warranty.
by a disc retainer and forming a tight seal against a single
removable seat insert. No O-ring type discs (circular, square, or The valve manufacturer shall be able to supply a complete line of
quad type) shall be permitted as the seating surface. The disc equipment from 1 1/4" through 36" sizes and a complete selection
guide shall be of the contoured type to permit smooth transition of of complementary equipment. The valve manufacturer shall also
flow and shall hold the disc firmly in place. provide a computerized cavitation chart which show flow rate,
differential pressure, percentage of valve opening, Cv factor,
The disc retainer shall be of a sturdy one-piece design capable of system velocity, and if there will be cavitation damage.
withstanding opening and closing shocks. It must have straight
edge sides and a radius at the top edge to prevent excessive Pilot Control System
diaphragm wear as the diaphragm flexes across this surface. No The pressure reducing pilot control shall be a direct-acting,
hourglass-shaped disc retainers shall be permitted and no V-type adjustable, spring-loaded, normally open, diaphragm valve
or slotted type disc guides shall be used. designed to permit flow when controlled pressure is less than the
spring setting. The pilot control is held open by the force of the
The diaphragm assembly containing a non-magnetic 303 compression on the spring above the diaphragm, and it closes
stainless steel stem with sufficient diameter to withstand high when the delivery pressure acting on the underside of the
hydraulic pressures shall be fully guided at both ends by a diaphragm exceeds the spring setting. The pilot control system
bearing in the valve cover and an integral bearing in the valve shall include a fixed orifice. No variable orifices shall be permitted.
seat. No center guides shall be permitted. The stem shall be The pilot system shall include an opening speed control on all
drilled and tapped in the cover end to receive and affix such valves 3" and smaller for the model 90-01 as standard equipment.
accessories as may be deemed necessary. The diaphragm
assembly shall be the only moving part and shall form a sealed The pilot control shall have a second downstream sensing port
chamber in the upper portion of the valve, separating operating which can be utilized to install a pressure gauge. A full range of
pressure from line pressure. spring settings shall be available in ranges of 0 to 450 psi.
The flexible, non-wicking, FDA approved diaphragm shall consist A direct factory representative shall be made available for start-up
of nylon fabric bonded with synthetic rubber compatible with the service, inspection and necessary adjustments.
operating fluid. The center hole for the main valve stem must be
sealed by the vulcanized process or a rubber grommet sealing
the center stem hole from the operating pressure. The diaphragm This valve shall be a Cla-Val Co. Model No. 90-01 Pressure
must withstand a Mullins Burst Test of a minimum of 600 psi per Reducing Valve. As manufactured by Cla-Val Co. Costa Mesa,
layer of nylon fabric and shall be cycle tested 100,000 times to CA 92627.
ensure longevity.
CLA-VAL 1701 Placentia Ave Costa Mesa CA 92627 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: [email protected] www.cla-val.com
Cla-Val 2016 Printed in USA Specifications subject to change without notice.