Technical Documentation Sheet SH2

The document describes spring hanger units types SH.1 and SH.2 that are designed to support and stabilize pipelines and equipment. They can be placed at right angles to stabilize equipment in one plane. The spring hangers have various applications including generator sets, air conditioning machines, pumps, and more. The document provides specifications for different types of spring hangers including their stiffness, maximum force, preferential force, and dimensions. It describes how to select the appropriate spring hanger type by determining the load and following the provided recommendations.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
99 views2 pages

Technical Documentation Sheet SH2

The document describes spring hanger units types SH.1 and SH.2 that are designed to support and stabilize pipelines and equipment. They can be placed at right angles to stabilize equipment in one plane. The spring hangers have various applications including generator sets, air conditioning machines, pumps, and more. The document provides specifications for different types of spring hangers including their stiffness, maximum force, preferential force, and dimensions. It describes how to select the appropriate spring hanger type by determining the load and following the provided recommendations.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

DOCUMENTATION SHEET General

Spring hanger units type SH.1 and SH.2 are designed to support pipelines and will stabilise
Steel Spring Isolator installations. Placed at the right angle the spring hangers will stabilise the equipment in one
Type SH2 plane.

Applications

Generator sets Air-conditioning machines


Emergency power supplies Compressor packages
DC-AC converters Electrical equipment
Industrial fans Refrigerators
Air-handling units Cooler units
Pumps

DIMENSIONS

1 SSM / SH2 / NOV 2012


Type Cz [N/mm] Cx, y [N/mm] Fz max [N] Fz preferential [N]
SH2-253 43,8 Depending on rod length 1112 963
SH2-352 61,3 Depending on rod length 1557 1348
SH2-440 65,7 Depending on rod length 1669 1445
SH2-550 96,3 Depending on rod length 2447 2119
SH2-638 114,6 Depending on rod length 2911 2521
SH2-715 131,4 Depending on rod length 3336 2890

CHARACTERISTICS

Isolator selection

This described isolator selection is based on the vertical load of the isolators, if required seis-
mic and 6 DOF calculations can be performed by our specialists.

1. Determine the total weight of the machine to be isolated, including work load
2. Determine the position of the combined centre of gravity in horizontal and vertical planes
3. Decide the number of isolators and the positions where the isolators are to be placed
relative to the combined centre of gravity
4. Calculate the load per isolator
5. Select with the help of the preferential load in the table the suitable type of mounting

We recommend selection of the isolators be made with the load per isolator within + or - 10%
of the preferential load. The static deflection of the isolator is calculated by dividing the load
per isolator by the stiffness Cz given in the table for the selected isolator.

Rubber Design B.V.


Industrieweg 21
2995BE Heerjansdam
The Netherlands
Phone: +31 ( 0 ) 78 677 87 78
Fax: +31 ( 0 ) 78 677 10 38
Email: [email protected]
Web: www.rubberdesign.nl

2 SSM / SH2 / NOV 2012