N41 - R2 - CL - Im30-Dr - Eng

This three-phase relay provides overcurrent protection, directional earth fault protection, and autoreclosing capabilities. It has settings for two stages of three-phase overcurrent, two stages of directional earth fault, negative sequence overcurrent, and a four-shot programmable autoreclosing function. Additional features include breaker failure protection, time synchronization, and communication capabilities.

Uploaded by

jjcanoolivares
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
107 views2 pages

N41 - R2 - CL - Im30-Dr - Eng

This three-phase relay provides overcurrent protection, directional earth fault protection, and autoreclosing capabilities. It has settings for two stages of three-phase overcurrent, two stages of directional earth fault, negative sequence overcurrent, and a four-shot programmable autoreclosing function. Additional features include breaker failure protection, time synchronization, and communication capabilities.

Uploaded by

jjcanoolivares
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

THREE-PHASE OVERCURRENT with DIRECTIONAL

EARTH FAULT + AUTORECLOSING

46,50/51,50N/51N,51BF,67N,68,79
IM30-DR m Two Phase-Fault levels.
m Two Directional Earth-Fault levels.
I>

PROG/
I.R.F.
I>>

I2>
O> O>>

BR.FAIL. RECLOSE
BL.ACT. TIME/L.O.

m Zero Sequence Overvoltage level. IA 500A


m One Negative Sequence current level.

N41 -R2
m Four-shot programmable Autoreclosing.
m Reclosure sequence coordination.
M-LINE MODE SELECT +

m Selectable double setting program. MULTIFUNCTION


3Ph O/C + NEG.SEQ.+ _
m Blocking Outputs and Blocking Inputs for pilot wire DIRECTIONAL E/F +
4-SHOT AUTORECLOSE PROG.
selectivity coordination. RELAY TYPE
IM30-DR
m Breaker Failure protection.

M
ENTER/RESET

LINE m IRIG-B Time Synchronization.


m Modbus Communication Protocol.
m UL / CSA listed.

Three-phase overcurrent + directional earth fault + autoreclose relay with programmable Time-Current
Curves suitable for protection of HV & MV, Transmission and Distribution systems.

The neutral current and the zero sequence voltage input circuits include a 3rd harmonic active filter.

Two complete setting programs selectable via serial port or by the front face keyboard.

Real Time Measurements = IA - IB - IC - Io - I2 - Uo - jo


Maximum Demand and Inrush Recording = IA - IB - IC - Io - I2 - Uo

Programmable Input Quantities


Fn = System frequency : (50-60) Hz

In = Rated primary current of phase CTs : (0-9999)A, step 1A

On = Rated primary current of earth fault detection CTs : (0-9999)A, step 1A


Connection Diagram

IM30-DR

AUXILIARY
}
SUPPLY

C US LISTED
19CN MS-SCE1573-R1 MS-SCE1574-R1
RINA IND.CONT.EQ. Standard Output Double Output

24
IM30-DR M N41-R2

1F - 50/51 (I>) : First Overcurrent Level


Current setting range : I> = (0.5 - 4)In, step 0.01In
Instantaneous output : 0.03s
Definite trip time delay in the mode (D)
(10x[I>] in inverse time operation modes) : tI> = (0.05 - 30)s, step 0.01s
Time current curves F(I>) : Indepedent Definite Time (D), IEC (A / B / C), IEEE (MI / VI / I / EI / SI)

2F - 50/51 (I>>): Second Overcurrent Level


Current setting range : I>> = (0.5 - 40)In, step 0.01 In
Instantaneous element : 0.03s
Independent time delay : tI>> = (0.05 - 3)s, step 0.01s
Automatic doubling of level I>> on inrush : I>>x2 = ON/OFF

F67 : Directional Earth Fault


Max sensitivity displacement of zero sequence current on zero sequence voltage : ao = (0 - 359), step1.
Minimum zero sequence voltage level for enabling the operation of function F1,2 67N : Uo = (2 - 25)V at input, step 1V.
Selection of the operation mode : Non Directional - Directional Supervision - Full Directional

1F - 67N (O>) : First Directional Earth Fault


Current setting range : O> = (0.02 - 0.4)On, step 0.01On
Instantaneous element : 0.04s
Definite trip time delay in the mode (D)
(10x[O>] in inverse time operation modes) : tO> = (0.05 - 30)s, step 0.01s
Time current curves F(O>) : Indepedent Definite Time (D), IEC (A / B / C), IEEE (MI / VI / I / EI / SI)

2F - 67N (O>>): Second Directional Earth Fault level


Current setting range : O>> = (0.02 - 1)On, step 0.01On
Independent time delay : tO>> = (0.05 - 3)s, step 0.01s
Instantaneous element : 0.04s

F46 (I2) : Negative Sequence Element


Current setting range : I2 = (0.5 - 4)In, step 0.01In
Instantaneous element : 0.04s
Definite trip time delay in the mode (D)
(10x[I2>] in inverse time operation modes) : tO> = (0.05 - 30)s, step 0.01s
Time current curves F(I2>) : Indepedent Definite Time (D), IEC (A / B / C), IEEE (MI / VI / I / EI / SI)

F79 : Autoreclose
Selection of function initiating the autoreclose shot (tI>, tI>>, tO>, tO>>, tI2):

First shot 1C:(tI> - tI>> - tO> - tO>> - tI2); any combination


Second shot 2C:(tI> - tI>> - tO> - tO>> - tI2); any combination
Third shot 3C:(tI> - tI>> - tO> - tO>> - tI2); any combination
Fourth shot 4C:(tI> - tI>> - tO> - tO>> - tI2); any combination

Reclosing time delay for each shot:

First shot t1C: (0.1 - 1800)s, step 0.1s


Second shot t2C: (0.1 - 1800)s, step 0.1s
Third shot t3C: (0.1 - 1800)s, step 0.1s
Fourth shot t4C: (0.1 - 1800)s, step 0.1s

Reset (Reclaim) time : tr = (1 - 200)s, step 1s

Breaker Failure Element


Trip time delay : tBF = (0.05 - 0.25)s, step 0.01s