Design by: checked by : Approved by
SAUDI ELECTRICAL COMPANY- EOA
Introduction
The pupose of this Calculation is to design Retaining wall and check the adequecy of this retaining wall
against overturning and sliding forces
Notations :
P= Wheel load
Calculation of pier Foundation
q=Surcharge load
Description
W1: weight of soil above fa part of footing
W2:Weight of Concret pad (footing)
W3: Weight of Retaining wall
Rev.# Date W4: Weight of Soil above ct (part footing)
1 .20/9/07
wt:wall thickness
Ft:Footing thickness
reference : fa:Front part footing width Figure 1
ct: footing part width
A:Footing length
B:Footing width 1m strip wall
Given Data
Soil &Wall Data
s= 19 Density of soil kN/m3
= 25 angle friction of soil deg
ka= 0.47 active earth pressure coefficient
kP= 2.46 passive earht pressure coefficient
A= 2.5 m
wt= 0.3 m
fa= 1.5 m
ct= 0.7 m
Hs= 2.5 m backfilling depth behinde the wall
sd= 0.6 m soil passive pressure depth
Hw= 3 m
P= 7.92 kN concentrat wheel load
q= 0 kN/m2 surcharge load
Ft= 0.35 m
Concrete Material Properties:
fy= 41.188 kN/cm2 yield strength of steel
fc= 3.1 Mpa (kN/cm2) compressive strength of Concrete
s= 24 kN/m3 concrete Density
Job No Project titel: Contractor :
SSEM
plant Number
Designer Office
Design by: checked by : Approved by SAUDI ELECTRICAL COMPANY- EOA
Precast Wall Data
Hp= 3.25 m hight of precast wall
THp= 0.12 m thickness of precast wall
Calculation of pier Foundation
Loads :
Description
Code Vertical Loads
1 W1= 71.25 kN/m` weight of soil at fa width
1 W2= 21 kN/m` weight of footing
1 W3= 21.6 kN/m` weight of retaining wall
1 W4= 7.98 kN/m` weight of soil at ct width
1 W5= 9.36 kN/m` weight of precast wall
0
Rev.# Date 1 q= 11.8 kN/m2 surcharge loads as per AASHTO page 27
1 .20/9/07 1 P= 7.92 kN wheel loads
0 0
0 0
0 0 Horizontal Loads
0 0
Code: Horizontal Pressure of soil and the surcharge
1 Pa1= 22.15 kN/m`
1 Pa2= 3.10 kN/m`
0 PP1= 28.09 kN/m`
0 PP2= 16.39 kN/m`
1 Ps= 5.50 kN/m`
1 Psw= 7.92 kN/m`
Wind Load:AS per UBC97 code
Basic wind speed
Wis= 150 km/h
Pw=wind stagnation pressure
Pw= 22.3 psf
1.07 kPa 108kg/m2
hieght above average level of adjoining Ground
H= 3.25 m
Ppw=Ce*Cq*Iw*Pw
Ce= 1.06 Combined height ,Exposure and gust factor coeff.
Cq= 1.3 Pressure coefficient for retaining wall
Iw= 1.15 Important Factor (occupancy structur)
Ppw= 5.150275 kN/m2 Force Due to wind
Job No Contractor :
SSEM
plant Number
Designer Office
BC= 200 kN/m2 net bearing capacity
Ix= 1.30 m4
Iy= 0.21 m4
1=P/A+( Mx/Ix)y +(My/Iy)x
2=P/A-( Mx/Ix)y -(My/Iy)x
3=P/A+( Mx/Ix)y -(My/Iy)x
4=P/A-( Mx/Ix)y +(My/Iy)x
Job No Project titel: Contractor :
SSEM
plant Number
Designer Office
Design by: checked by : Approved by
SAUDI ELECTRICAL COMPANY- EOA
Lateral pressure due to surcharge Load
P= Nearest Wheel load
Calculation of pier Foundation
P 16 kips
x= 2 ft
Description
H= 8.36 ft
m=x/h 0.24
n=Z/H
0
Rev.# Date
m>0.4
1.77 P m n
2 2
2
H m n
2 23
0.40
0.28 P n
2
m<0.4 0.35
H 0.16 n
3
2 2 0.30
0.25
0.20
n= m= =
0 0.24 0.00 0.15
0.1 0.24 0.13 0.10
0.2 0.24 0.32
0.3 0.24 0.37 0.05
0.4 0.24 0.31 0.00
0.5 0.24 0.23 1.2 1 0.8 0.6 0.4 0.2 0
0.6 0.24 0.16 n=z/H
0.7 0.24 0.11
0.8 0.24 0.08
0.9 0.24 0.06
E93: Hakim:
pressure Due to wheel load
E199: Hakim:
1check aci 318 cluase 14.3.3 & 14.3.4
F81: Hakim:
check this load belong to
which case edge base or above base footing
F112: Hakim:
or 1.15
F168: Hakim:
300-75-dia/2
K42: Engr. Hakim:
angle are in radian so check