This document provides calculations to design a retaining wall and check its adequacy against overturning and sliding forces. Notations for variables used in the calculations are defined, including wheel load, surcharge load, weights of soil and concrete, wall thickness, footing thickness, and dimensions. Material properties for soil, concrete, and a precast wall are given. Vertical and horizontal load values are then calculated based on the defined variables and material properties. Wind load is also calculated according to building code specifications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
188 views5 pages

Design of Retaining Wall

This document provides calculations to design a retaining wall and check its adequacy against overturning and sliding forces. Notations for variables used in the calculations are defined, including wheel load, surcharge load, weights of soil and concrete, wall thickness, footing thickness, and dimensions. Material properties for soil, concrete, and a precast wall are given. Vertical and horizontal load values are then calculated based on the defined variables and material properties. Wind load is also calculated according to building code specifications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 5

Design by: checked by : Approved by

SAUDI ELECTRICAL COMPANY- EOA

Introduction

The pupose of this Calculation is to design Retaining wall and check the adequecy of this retaining wall

against overturning and sliding forces

Notations :
P= Wheel load
Calculation of pier Foundation

q=Surcharge load
Description

W1: weight of soil above fa part of footing

W2:Weight of Concret pad (footing)

W3: Weight of Retaining wall

Rev.# Date W4: Weight of Soil above ct (part footing)


1 .20/9/07
wt:wall thickness

Ft:Footing thickness

reference : fa:Front part footing width Figure 1

ct: footing part width

A:Footing length

B:Footing width 1m strip wall


Given Data
Soil &Wall Data
s= 19 Density of soil kN/m3
= 25 angle friction of soil deg
ka= 0.47 active earth pressure coefficient
kP= 2.46 passive earht pressure coefficient
A= 2.5 m
wt= 0.3 m
fa= 1.5 m
ct= 0.7 m
Hs= 2.5 m backfilling depth behinde the wall
sd= 0.6 m soil passive pressure depth
Hw= 3 m
P= 7.92 kN concentrat wheel load
q= 0 kN/m2 surcharge load
Ft= 0.35 m

Concrete Material Properties:


fy= 41.188 kN/cm2 yield strength of steel
fc= 3.1 Mpa (kN/cm2) compressive strength of Concrete
s= 24 kN/m3 concrete Density

Job No Project titel: Contractor :

SSEM
plant Number

Designer Office
Design by: checked by : Approved by SAUDI ELECTRICAL COMPANY- EOA

Precast Wall Data

Hp= 3.25 m hight of precast wall


THp= 0.12 m thickness of precast wall
Calculation of pier Foundation

Loads :
Description

Code Vertical Loads


1 W1= 71.25 kN/m` weight of soil at fa width
1 W2= 21 kN/m` weight of footing
1 W3= 21.6 kN/m` weight of retaining wall
1 W4= 7.98 kN/m` weight of soil at ct width
1 W5= 9.36 kN/m` weight of precast wall
0

Rev.# Date 1 q= 11.8 kN/m2 surcharge loads as per AASHTO page 27


1 .20/9/07 1 P= 7.92 kN wheel loads
0 0
0 0
0 0 Horizontal Loads
0 0

Code: Horizontal Pressure of soil and the surcharge


1 Pa1= 22.15 kN/m`
1 Pa2= 3.10 kN/m`
0 PP1= 28.09 kN/m`
0 PP2= 16.39 kN/m`
1 Ps= 5.50 kN/m`
1 Psw= 7.92 kN/m`

Wind Load:AS per UBC97 code

Basic wind speed


Wis= 150 km/h

Pw=wind stagnation pressure

Pw= 22.3 psf


1.07 kPa 108kg/m2
hieght above average level of adjoining Ground

H= 3.25 m

Ppw=Ce*Cq*Iw*Pw

Ce= 1.06 Combined height ,Exposure and gust factor coeff.


Cq= 1.3 Pressure coefficient for retaining wall
Iw= 1.15 Important Factor (occupancy structur)

Ppw= 5.150275 kN/m2 Force Due to wind

Job No Contractor :
SSEM
plant Number
Designer Office
BC= 200 kN/m2 net bearing capacity

Ix= 1.30 m4
Iy= 0.21 m4

1=P/A+( Mx/Ix)y +(My/Iy)x


2=P/A-( Mx/Ix)y -(My/Iy)x
3=P/A+( Mx/Ix)y -(My/Iy)x
4=P/A-( Mx/Ix)y +(My/Iy)x

Job No Project titel: Contractor :


SSEM
plant Number
Designer Office
Design by: checked by : Approved by

SAUDI ELECTRICAL COMPANY- EOA

Lateral pressure due to surcharge Load

P= Nearest Wheel load


Calculation of pier Foundation

P 16 kips

x= 2 ft
Description

H= 8.36 ft

m=x/h 0.24

n=Z/H
0

Rev.# Date
m>0.4


1.77 P m n
2 2
2
H m n
2 23
0.40

0.28 P n
2
m<0.4 0.35

H 0.16 n
3
2 2 0.30
0.25
0.20
n= m= =
0 0.24 0.00 0.15
0.1 0.24 0.13 0.10
0.2 0.24 0.32
0.3 0.24 0.37 0.05
0.4 0.24 0.31 0.00
0.5 0.24 0.23 1.2 1 0.8 0.6 0.4 0.2 0
0.6 0.24 0.16 n=z/H
0.7 0.24 0.11
0.8 0.24 0.08
0.9 0.24 0.06
E93: Hakim:
pressure Due to wheel load

E199: Hakim:

1check aci 318 cluase 14.3.3 & 14.3.4


F81: Hakim:
check this load belong to
which case edge base or above base footing

F112: Hakim:
or 1.15

F168: Hakim:
300-75-dia/2

K42: Engr. Hakim: