6/2 Introduction
6/14 Configuration
Siemens LV 10 2016/2017
Siemens AG 2016
Introduction
Overview
Devices Page Application Standards
5SD7 lightning arresters, type 1 6/3 With plug-in protective modules for TN-C, TN-S and EN 61643-11
TT systems.
Rated voltage 350 V AC for lightning currents
from 25 kA to 100 kA.
All versions with remote signaling contact.
For installation in main distribution boards, upstream or
downstream of the counter.
5SD7 combination surge arresters, 6/5 With plug-in protective modules for TN-C, TN-S and EN 61643-11
type 1 + type 2 TT systems.
Rated voltage 350 V AC for lightning currents from
25 kA to 100 kA.
6 All versions with remote signaling contact.
For installation in main distribution boards downstream
of the counter.
5SD7 combination surge arresters, 6/7 With plug-in protective modules for TN-C, TN-S and EN 61643-11
type 1 / type 2 TT systems.
Rated voltage 335 V AC for lightning currents or
discharge surge currents up to 50 kA.
Versions with or without remote signaling.
5SD7 surge arresters, 6/9 With plug-in protective modules for TN-C, TN-S and EN 61643-11
type 2 TT systems.
Rated voltage 350 V AC, rated discharge surge current
20 kA and discharge surge current 40 kA.
For installation in sub-distribution boards.
5SD7 surge arresters, 6/13 With plug-in protective modules for single-phase and EN 61643-11
type 3 three-phase systems. Rated voltage, single-phase 24 V,
120 V, 230 V AC and three-phase 230/400 V AC.
For installation as close as possible upstream from the
terminal equipment.
I201_13815
5SD7 surge arresters for 6/17 With plug-in protective modules for measuring and EN 61643-21
measuring and control technology control technology for installation in signal circuits.
Overview
Type 1 lightning arresters are the most powerful overvoltage pro- The lightning conductors can therefore also be used in the
tection. They protect low-voltage systems against any overvolt- precounter area.
age or high impulse currents that may be triggered by a direct
or indirect lightning strike. The protective modules are available as connectors.
The majority of lightning arresters have a remote signaling
All lightning arresters are fitted with a mechanical fault indica- contact, which signals if the device fails.
tion, which does not require an extra power supply.
Technical specifications
5SD7411-2 5SD7412-1 5SD7413-1 5SD7414-1
Standards IEC 61643-11 (DIN VDE 06754-6)
Approvals KEMA, UL/cUL UL/cUL UL/cUL
Rated voltage UN V AC 690 240 240/415
Rated arrester voltage UC
L-N, N-PE, L-(PE)N V AC 800 350 350 350
Lightning impulse current Iimp
(10/350 Ps)
6
L-N or L-(PE)N, 1P/3P kA 35 25 25/75 25/75
N-PE kA -- 100 -- 100
Rated discharge surge current In
(8/20 Ps)
L-N or L-(PE)N, 1P/3P kA 35 25 25/75 25/75
N-PE kA -- 100 -- 100
Protection level Up
L-(PE)N kV d 4.50 d 1.50 d 1.50 d 1.50
L-PE kV -- d 2.50 -- d 2.50
N-PE kV -- d 1.50 -- d 1.50
Follow current discharge capacity Ifi
(AC)
L-N or L-(PE)N for 264 V/350 V kA -- 50/25 50/25 50/25
N-PE A -- 100 -- 100
Response time tA
L-N or L-(PE)N ns d 100 d 100 d 100 d 100
L-(N)-PE ns -- d 100 -- d 100
Max. back-up fuse
acc. to IEC 61643-1
For stub wiring A 400 gL/gG 315 gL/gG 315 gL/gG 315 gL/gG
For V-wiring A 125 gL/gG 125 gL/gG 125 gL/gG 125 gL/gG
Short-circuit withstand current kArms 50 50 50 50
With max. back-up fuse
Temperature range C -40 ... +80
Degree of protection IP20, with connected conductors
Conductor cross-section
Finely stranded mm2 16 ... 50 2.5 ... 25 2.5 ... 25 2.5 ... 25
Solid mm2 16 ... 50 2.5 ... 35 2.5 ... 35 2.5 ... 35
Replacement plugs
N-PE: 5SD7418-0 1 1 unit 1BK 0.230
5SD7412-1
5SD7414-1
1)
No modular installation device.
Overview
Combination surge arresters, type 1 + type 2 are compact de- A thermal isolating arrester for the varistors offers a high degree
signs comprising lightning arresters (type 1) and surge arresters of protection against overload. The protective modules are avail-
(type 2). They protect low-voltage systems against overvoltages able as connectors. All combination surge arresters have a
triggered by lightning strikes or by switching operations in the remote signaling contact, which signals if the device fails.
network.
Technical specifications
5SD7442-1 5SD7443-1 5SD7444-1
Standards IEC 61643-11; EN 61643-11
Approvals KEMA, UL/cUL
Rated voltage UN V AC 240 240/415
Rated arrester voltage UC
L-N, N-PE, L-(PE)N V AC 350
Lightning impulse current Iimp
(10/350 Ps)
L-N or L-(PE)N, 1P/3P kA 25 25/75 25/75 6
N-PE kA 100 -- 100
Rated discharge surge current In
(8/20 Ps)
L-N or L-(PE)N, 1P/3P kA 25 25/75 25/75
N-PE kA 100 -- 100
Protection level Up
L-(PE)N kV d 1.50 d 1.50 d 1.50
L-PE kV d 2.20 -- d 2.20
N-PE kV d 1.50 -- d 1.50
Follow current discharge capacity Ifi
(AC)
L-N or L-(PE)N kA 25 25 25
N-PE kA 100 -- 100
Response time tA
L-N or L-(PE)N ns d 100 d 100 d 100
L-(N)-PE ns d 100 -- d 100
Max. back-up fuse Acc. to IEC 61643-1
For stub wiring A 315 gL/gG
For V-wiring A 125 gL/gG
Short-circuit withstand current with max. back-up fuse kArms 25
Temperature range C -40 ... +80
Degree of protection IP20, with connected conductors
Conductor cross-section
Finely stranded mm2 2.5 ... 25
Solid mm2 2.5 ... 35
Mounting width Acc. to DIN 43880 MW 4 6 8
Visual function/fault indication Yes
Replacement plugs
N-PE: 5SD7418-0 1 1 unit 1BK 0.230
5SD7442-1
5SD7444-1
Overview
Combination surge arresters type 1 / type 2 are compact A thermal isolating arrester for the varistors offers a high degree
designs which can be used as both lightning arresters type 1 of protection against overload. The protective modules are avail-
and surge arresters type 2. able as connectors. The combination surge arresters can be fit-
ted either with or without a remote signaling contact, which sig-
They protect low-voltage systems against overvoltages trig- nals if the device fails.
gered by lightning strikes or by switching operations in the
network.
Technical specifications
5SD7411-2 5SD7412-2 5SD7413-2 5SD7414-2 5SD7483-6
5SD7412-3 5SD7413-3 5SD7414-3 5SD7483-7
Standards IEC 61643-11 EN 50539
Approvals KEMA, UL/cUL KEMA
Rated voltage UN V AC 690 240 240/415 --
Rated arrester voltage UC
L-L-N, N-PE, L-(PE)N
Lightning impulse current Iimp
V 800 AC 335 AC 1000 DC
6
(10/350 Ps)
L-N or L-(PE)N, 1P/3P kA 35 12.5 12.5/37.5 12.5 d5
N-PE kA -- 50 -- 50 --
Rated discharge surge current In
(8/20 Ps)
L-N or L-(PE)N, 1P/3P kA 35 12.5 12.5/37.5 12.5/50 15
N-PE kA -- 50 -- --
Max. discharge surge current Imax
(8/20Ps)
L-N kA 100 12.5 50/150 50 40
N-PE kA -- 50 -- 50 --
Protection level Up
L-(PE)N kV d 4.50 d 1.20 d 1.20 d 1.20 d 3.50
L-PE kV -- -- -- -- --
N-PE kV -- d 1.70 -- d 1.70 --
Response time tA
L-N or L-(PE)N ns d 100 d 25
L-(N)-PE ns -- d 100 -- d 100 d 25
Max. back-up fuse acc. to IEC 61643-1
For stub wiring A 400 gL/gG 160 gL/gG --
For V-wiring A 125 gL/gG 80 gL/gG --
Short-circuit withstand current kArms 50 25
With max. back-up fuse
Temperature range C -40 ... +80
Degree of protection IP20, with connected conductors
Conductor cross-section
Finely stranded mm2 16 ... 50 1.5 ... 25
Solid mm2 16 ... 50 1.5 ... 35
2-pole
3-pole
For TN-C systems
Without remote signaling 3 5SD7413-2 1 1 unit 1BK 0.556
With remote signaling 3 5SD7413-3 1 1 unit 1BK 0.538
4-pole
For TN-S and TT systems
Without remote signaling 4 5SD7414-2 1 1 unit 1BK 0.678
With remote signaling 4 5SD7414-3 1 1 unit 1BK 0.682
Replacement plugs
N-PE: 5SD7418-2 1 1 unit 1BK 0.099
5SD7412-2, 5SD7412-3
5SD7414-2, 5SD7414-3
1)
No modular installation device.
Overview
Surge arresters type 2 are used downstream of lightning arrest- A thermal isolating arrester for the varistors offers a high degree
ers type 1 in main distribution boards or sub-distribution boards. of protection against overload. The protective modules are avail-
They protect low-voltage systems against transient overvolt- able as connectors. The surge arresters have an optional remote
ages, such as those triggered by switching operations. signaling contact, which signals if the device fails.
Technical specifications
Standard design
N-PE
5SD7481-0 5SD7461-0 5SD7481-1 5SD7463-0 5SD7464-0 5SD7473-1 5SD7483-5
5SD7461-1 5SD7463-1 5SD7464-1
Standards IEC 61643-11; EN 61643-11
Approvals KEMA -- KEMA,
UL/cUL
Rated voltage UN V AC 240 240 690 240/415 240/415 500 554/960
Rated arrester voltage UC
L-N
L-N or L-(PE)N
V AC
V AC
--
--
350
--
800
--
--
350
--
350
--
580
760
--
6
N-PE V AC 260 -- -- -- 260 -- --
Rated discharge surge current In
(8/20 Ps)
L-N kA -- 20 15 -- -- -- 15
L-N or L-(PE)N, 1P kA -- -- -- 20 20 15 --
N-PE kA 20 -- -- -- 20 -- --
Max. discharge surge current Imax
(8/20Ps)
L-N kA -- 40 30 -- -- -- 30
L-N or L-(PE)N, 1P kA -- -- -- 40 40 -- --
L-N or L-(PE)N, 1P/multi-pole kA -- -- -- -- -- 30 --
N-PE kA 40 -- -- -- 40 -- --
Lightning impulse current Iimp (10/350 Ps) kA 12 --
Protection level Up
L-(PE)N kV -- d 1.50 d5 d 1.50 d 1.60 d 2.50 d 2.90
L-PE kV -- -- d5 -- d 1.90 d 2.50 --
N-PE kV d 1.50 -- -- -- d 1.50 -- --
Response time tA
L-N or L-(PE)N ns -- d 25 d 100 d 25 d 25 d 25 d 25
N-PE ns d 100 -- -- -- d 100 -- --
Max. back-up fuse acc. to IEC 61643-1
For stub wiring A -- 125 gL/gG 100 gL/gG 125 gL/gG 100 gL/gG
For V-wiring A -- -- 80 gL/gG 80 gL/gG 80 gL/gG
Short-circuit withstand current kArms 25
With max. back-up fuse
Temperature range C -40 ... +80
Degree of protection IP20, with connected conductors
Conductor cross-section
Finely stranded mm2 1.5 ... 25
Solid mm2 1.5 ... 35
Mounting width according to DIN 43880 MW 1 1 2 3 4 3 3
Visual function/fault indication Yes
Narrow design
5SD7422-0 5SD7424-0
5SD7422-1 5SD7424-1
Standards IEC 61643-11 (DIN VDE 06754-6)
Approvals KEMA/UL/cUL
Rated voltage UN V AC 240 240/415
Rated arrester voltage UC
L-N or L-(PE)N V AC 350 350
N-PE V AC 264 264
Rated discharge surge current In (8/20 Ps)
L-N or L-(PE)N, 1P/3P kA 20 20
N-PE kA 20 20
Max. discharge surge current Imax (8/20Ps)
L-N or L-(PE)N, 1P/3P kA 40 40
N-PE kA 40 40
Protection level Up
L-(PE)N kV d 1.50 d 1.50
6 L-PE kV -- --
N-PE kV d 1.50 d 1.50
Response time tA
L-N ns d 25 d 25
N-PE ns d 100 d 100
Max. back-up fuse Acc. to IEC 61643-1
For stub wiring A 315 gL/gG
For V-wiring A 63 gL/gG
Short-circuit withstand current with max. back-up fuse kArms 25 25
Temperature range C -40 ... +80
Degree of protection IP20, with connected conductors
Conductor cross-section
Finely stranded mm2 1.5 ... 16
Solid mm2 1.5 ... 25
Mounting width Acc. to DIN 43880 mm 26 50
Visual function/fault indication Yes
1-pole
Without remote signaling 1 5SD7461-0 1 1 unit 1BK 0.139
With remote signaling 1 5SD7461-1 1 1 unit 1BK 0.143
Replacement plugs
N-PE: 5SD7488-0 1 1 unit 1BK 0.056
5SD7481-0
5SD7464-0, 5SD7464-1
4-pole
For TN-S and TT systems
Replacement plugs
N-PE: 5SD7428-0 1 1 unit 1BK 0.088
5SD7422-0, 5SD7422-1
5SD7424-0, 5SD7424-1
Overview
Type 3 surge arresters are installed downstream of type 2 surge
arresters in sub-distribution boards as close as possible to the
load. The protective modules are available as connectors. In the
event of a power failure, a remote signaling is output over an
optocoupler with open collector output.
Technical specifications
2-pole 4-pole
5SD7432-1 5SD7432-2 5SD7432-4 5SD7434-1
Standards IEC 61643-11; EN 61643-11
Approvals KEMA/UL/cUL KEMA
Rated voltage UN V AC 230 120 24 230/400
Rated load current IL (at 30 C) A 26 26 26 3 26
Rated arrester voltage UC V AC 264 150 34 335
Rated discharge surge current In
(8/20 Ps)
kA 3 3 1 1.5
6
Combined surge Uoc kV 6 6 2 4
Protection level Up L-N / L-PE, N-PE V d 1350/d 1500 d 850/d 950 d 250/d 650 d 1200/d 1500
Response time tA ns d 100 d 100 d 100 d 100
Required back-up fuse, max. A (gG/B/C) 25 25 25 25
Temperature range C -40 ... +80
Degree of protection IP20, with connected conductors
Conductor cross-section
Finely stranded mm2 0.2 ... 2.5
Solid mm2 0.2 ... 4
Mounting width Acc. to DIN 43880 MW 1 1 1 2
Visual function/fault indication Yes
4-pole
With remote signaling 230/400 2 5SD7434-1 1 1 unit 1BK 0.138
Replacement plugs1)
5SD7432-1 5SD7437-1 1 1 unit 1BK 0.046
5SD7432-2 5SD7437-2 1 1 unit 1BK 0.041
5SD7432-3 5SD7437-3 1 1 unit 1BK 0.048
5SD7432-4 5SD7437-4 1 1 unit 1BK 0.047
5SD7434-1 5SD7438-1 1 1 unit 1BK 0.060
1) Products and replacement plugs have a new shape.
Configuration
More information
Selection of overvoltage protection devices
Situation Systems Basic protection
Which type of building For installation upstream of counters in main distribution boards
do you want to protect? or in combined main/sub-distribution boards
Generally speaking, all our
devices are suitable for resi-
dential buildings, office build-
ings, industrial and commercial
Low risk buildings TN-S and TT systems Surge arresters, type 2
5SD7424-0, 5SD7424-1, 5SD7464-0, 5SD7464-1
Combination surge arresters, type 1 / type 2
5SD7414-2, 5SD7414-3
6 - No outer lightning
protection TN-C systems Surge arresters, type 2
- Power supply over
ground conductor 5SD7423-0, 5SD7423-1, 5SD7463-0, 5SD7463-1
Combination surge arresters, type 1 / type 2
5SD7413-2, 5SD7413-3
- Power supply over TN-S and TT systems Combination surge arresters, type 1 + type 2
overhead lines 5SD7444-1
- Grounded aerial
structures
TN-C systems Combination surge arresters, type 1 + type 2
5SD7443-1, 5SD7441-1
Configuration
Configuration
Dimensioning of conductor cross-sections
The different conductor cross-sections (Lq 1 to Lq 3) must be
dimensioned according to the rated current of the miniature
circuit breaker or of the fuse.
V-wiring Stub wiring
MCB L1 MCB
L1 Lq1 Lq2
Lq1 Lq2
S
P
F2
D
S
Lq3 P
I201_10791a
I201_10790a
PE Lq3
PAS PAS
a) Protection of the SPD using miniature circuit breakers a) Protection of the SPD using miniature circuit breakers
F1 F1
L1
6 L1
Lq1
S
Lq2 Lq1
F2
Lq2
P
D
Lq3
I201_10794a
I201_10793a
PE Lq3
PAS
PAS
b) Protection of the SPD using fuses b) Protection of the SPD using fuses
PAS = Equipotential bonding strip
Conductor cross-sections for lightning arresters (type 1) and Conductor cross-sections for lightning arresters (type 1) and
combination surge arresters (type 1 + type 2) for V-wiring combination surge arresters (type 1 + type 2) for stub wiring
MCB/fuse (F1) Lq 2 Lq 3 MCB/fuse (F1) upstream Lq 2 Lq 3 F2 fuse
upstream [A gL/gG] [mm2] [mm2] [A gL/gG]
2 2
[A gL/gG] [mm ] [mm ] 25 6 16 /
25 10 16 35 10 16 /
35 10 16 40 10 16 /
40 10 16 50 10 16 /
50 10 16 63 10 16 /
63 10 16 80 10 16 /
80 16 16 100 16 16 /
100 25 16 125 16 16 /
125 35 16 160 25 25 /
200 35 35 1601)
250 35 35 1601)
Conductor cross-sections for surge arresters (type 2) 315 50 50 1601)
for V-wiring > 315 50 50 1601)
MCB/fuse (F1) Lq 2 Lq 3 1)
Recommended fuse.
upstream
[A gL/gG] [mm2] [mm2]
25 6 6 Conductor cross-sections for surge arresters (type 2)
for stub wiring
35 6 6
MCB/fuse (F1) Lq 2 Lq 3 F2 fuse
40 6 6 upstream
50 10 10 [A gL/gG] [mm2] [mm2] [A gL/gG]
63 10 10 25 6 6 /
32 6 6 /
40 6 6 /
50 6 6 /
63 10 10 /
80 10 10 /
100 16 16 /
125 16 16 /
> 125 16 16 125
Overview
The surge arresters for measuring and control technology are Through the number of integrated paths, it is possible to protect
overvoltage protection modules that comprise two parts, a basic up to four signal cores or two double cores against overvoltages.
element and a plug-in part. Their application area is the protec-
tion of signal circuits. The arresters are made up of two parts (plug-in part and base
element).
The cable shields of basic elements can be either directly or
indirectly grounded. A mechanical encoding ensures protection against reverse
polarity.
The mounting width of the surge arresters is 1 MW.
Technical specifications
5SD7502-0KB 5SD7522-7KA 5SD7530-4KA 5SD7540-6KB 5SD7541-7KB 5SD7550-4KA
5SD7522-7KB 5SD7530-4KB 5SD7550-4KB
IEC category/EN type C1/C2/C3/D1 C1/C2/C3/D1 C1/C2/C3/D1 C1/C2/C3/D1 C1/C2/C3/D1 C1/C2/C3/D1
Max. continuous voltage UC
Direct voltage
AC voltage
V DC
V AC
68
48
40
28
14
8.3
27
18.6
40
28
14
9.8 6
Rated current IN mA 2000 450 450 2000 300 450
Lightning test current Iimp Per path kA 5 2.5 2.5 2.5 2.5 2.5
10/350Ps
Rated discharge current In 8/20Ps
Core Core kA -- 10 10 0.365 -- 10
Core Ground kA 20 10 10 0.365 10 10
Total surge current IN 8/20Ps kA 40 20 20 20 20 20
Output voltage limit at 1 kV/Ps
Core Core V -- d 55 25 25 -- d 25
Core Ground V d 600 d 450 40 40 d 55 d 25
Residual voltage at In
Core Core V -- d 55 -- -- -- d 25
Core Ground V -- -- -- -- d 55 d 40
Response time tA
Core Core ns -- d1 d 500 d1 -- d 500
Core Ground ns d 100 d 100 d 500 d 100 d1 d 500
Insertion loss aE
Symmetrical in the 50 : system dB -- Typ. 0.5 -- 0.1 dB -- --
(1.5 MHz) to 1 MHz
Asymmetrical in the 50 : system dB 0.1 (1 MHz) -- -- -- 0.5 (1.5 MHz) --
Symmetrical in the 100 : system dB -- -- 0.2 (5 MHz) -- -- 0.2 (5 MHz)
Limit frequency fG (3 dB)
Symmetrical in the 50 : system MHz -- Typ. 8 -- 6 MHz (typ.) -- --
Asymmetrical in the 50 : system MHz -- -- -- -- Typ. 8 --
Symmetrical in the 100 : system MHz -- -- Typ. 70 -- -- Typ. 70
Resistance per path : -- 2.2 -- -- 4.7 2.2
Temperature range C -40 ... +85
Degree of protection according to IP20
IEC 60529/EN 60529
Flammability class acc. to UL 94 V0
Test standards EN 61643-21 EN 61643-21 IEC 61643-21/ IEC 61643-21/ EN 61643-21 IEC 61643-21
EN 61643-21 EN 61643-21