AC Circuit Power Problems
AC Circuit Power Problems
HOMEWORK PROBLEMS
Section 7.1: Power in AC Circuits b. The average current supplied to a 10- resistor
connected across the voltage source.
7.1 The heating element in a soldering iron has a
resistance of 30 . Find the average power dissipated c. The average power supplied to a 1- resistor
in the soldering iron if it is connected to a voltage connected across the voltage source.
source of 117 V rms.
vS (t), V
7.2 A coffeemaker has a rated power of 1,000 W at 240
V rms. Find the resistance of the heating element. 1
7.3 A current source i(t) is connected to a 50- resistor. 0 1 2 3 4 5 6 t, s
Find the average power delivered to the resistor, given
that i(t) is
a. 5 cos 50t A 3
Figure P7.16
iL(t)
7.17 A load impedance, ZL = 10 + j3 , is connected to
+
a source with line resistance equal to 1 , as shown in
v S(t) ~ ZL Figure P7.17. Calculate the following values:
a. The average power delivered to the load.
b. The average power absorbed by the line.
Figure P7.13
c. The apparent power supplied by the generator.
d. The power factor of the load.
7.14 For the circuit of Figure P7.13, determine the e. The power factor of line plus load.
power factor for the load and state whether it is leading
or lagging for the following conditions:
IS
a. vS (t) = 540 cos (t + 15 ) V Line
iL (t) = 20 cos (t + 47 ) A
R =1
b. vS (t) = 155 cos (t 15 ) V + VS = 2300 V ZL Load
iL (t) = 20 cos (t 22 ) A ~
c. vS (t) = 208 cos (t) V
iL (t) = 1.7 sin (t + 175 ) A Figure P7.17
d. ZL = (48 +j16)
7.15 For the circuit of Figure P7.13, determine whether 7.18 A single-phase motor draws 220 W at a power
the load is capacitive or inductive for the circuit factor of 80 percent (lagging) when connected across a
shown if 200-V, 60-Hz source. A capacitor is connected in
parallel with the load to give a unity power factor, as
a. pf = 0.87 (leading) shown in Figure P7.18. Find the required capacitance.
b. pf = 0.42 (leading)
c. vS (t) = 42 cos (t) V I
iL (t) = 4.2 sin (t) A
d. vS (t) = 10.4 cos (t 12 ) V I1
iL (t) = 0.4 cos (t 12 ) A
R I2
7.16 The circuit shown in Figure P7.16 is to be used on
two different sources, each with the same amplitude
but at different frequencies. V C
a. Find the instantaneous real and reactive power if L
vS (t) = 120 cos 377t V (i.e., the frequency is 60 Hz).
b. Find the instantaneous real and reactive power if
vS (t) = 650 cos 314t V (i.e., the frequency is 50 Hz). Figure P7.18
January 11, 2008 15:33 Chap07 Sheet number 51 Page number 329 magenta black
7.19 If the circuits shown in Figure P7.19 are to be at c. What value of load impedance would permit
unity power factor, find CP and CS . maximum power transfer?
The voltage source is sinusoidal with frequency
60 Hz, and its polarity is such that the current from
CS the voltage source flows into the 10- resistor.
RL RL
+ +
VS ~ CP VS ~ 20 V
?
or +
L L
Figure P7.19 10
20 mH
c. VS = 500 V
IL = 19.20.8 A
d. VS = 740(/4) V
IL = 10.8(1.5) A
Wall Blender iL(t)
socket motor
Figure P7.21
vS (t) +
~
_ ZL
7.22 For the circuit shown in Figure P7.22,
a. Find the Thvenin equivalent circuit for the source.
b. Find the power dissipated by the load resistor. Figure P7.23
January 11, 2008 15:33 Chap07 Sheet number 52 Page number 330 magenta black
7.24 For the circuit of Figure P7.23, determine the a. The source power factor.
power factor for the load and state whether it is leading b. The current IS .
or lagging for the following conditions:
c. The apparent power delivered to the load.
a. vS (t) = 780 cos(t + 1.2) V
d. The apparent power supplied by the source.
iL (t) = 90 cos(t + /2) A
e. The power factor of the load.
b. vS (t) = 39 cos(t + /6) V
iL (t) = 12 cos(t 0.185) A
~
c. vS (t) = 104 cos(t) V IS
Line
iL (t) = 48.7 sin(t + 2.74) A
R=1
d. ZL = (12 + j8)
+ ~
_ VS = 2300
~ ZL Load
7.25 For the circuit of Figure P7.23, determine whether
the load is capacitive or inductive for the circuit
shown if
a. pf = 0.48 (leading) Figure P7.28
b. pf = 0.17 (leading)
7.29 The load ZL in the circuit of Figure P7.28 consists
c. vS (t) = 18 cos(t) V of a 25- resistor in series with a 0.1-H inductor.
iL (t) = 1.8 sin(t) A Assuming f = 60 Hz, calculate the following.
d. vS (t) = 8.3 cos(t /6) V a. The apparent power supplied by the source.
iL (t) = 0.6 cos(t /6) A b. The apparent power delivered to the load.
7.26 Find the real and reactive power supplied by the c. The power factor of the load.
source in the circuit shown in Figure P7.26. Repeat if
7.30 The load ZL in the circuit of Figure P7.28 consists
the frequency is increased by a factor of 3.
of a 25- resistor in series with a 0.1-mF capacitor and
a 70.35-mH inductor. Assuming f = 60 Hz, calculate
1
2H 18 F the following.
a. The apparent power delivered to the load.
vS(t) = 10 cos 3t V +
~ 4 b. The real power supplied by the source.
c. The power factor of the load.
Figure P7.26
7.31 Calculate the apparent power, real power, and
reactive power for the circuit shown in Figure P7.31.
7.27 In the circuit shown in Figure P7.27, the sources Draw the power triangle. Assume f = 60 Hz.
are VS1 = 36(/3) V and VS2 = 240.644 V. Find
a. The real and imaginary current supplied by each ~
IS
source.
b. The total real power supplied.
R = 20
+ ~
~
_ VS = 50 V
8 6 j12
C = 100 F
~ ~
VS 1 +
~ j6
+
~ V
S2 Figure P7.31
7.39 Determine the time-averaged total power, the 7.42 A center-tapped transformer has the schematic
real power dissipated, and the reactive power stored in representation shown in Figure P7.41. The
each of the impedances in the circuit shown in primary-side voltage is stepped down to a
Figure P7.39 if secondary-side voltage Vsec by a ratio of n:1. On the
secondary side, Vsec1 = Vsec2 = 12 Vsec .
VS1 = 170/ 20 V
a. If Vprim = 2200 V and n = 11, find Vsec , Vsec1 ,
VS2 = 170/ 2 V
2 and Vsec2 .
= 377 rad/s b. What must n be if Vprim = 1100 V and we desire
|Vsec2 | to be 5 V rms?
Z1 = 0.7
6
Z2 = 1.50.105 7.43 For the circuit shown in Figure P7.43, assume that
vg = 120 V rms. Find
Z3 = 0.3 + j0.4
a. The total resistance seen by the voltage source.
b. The primary current.
+ Z1
_ Vs1
c. The primary power.
Z3
+ Z2
_ Vs2
Figure P7.39 1
1:4 +
7.40 If the voltage and current supplied to a circuit or
+ 16
load by a source are vg
_ v2
VS = 170(0.157) V IS = 130.28 A _
3 1:n
Z
Customers
load
vg +
_ 8
Figure P7.45
Figure P7.48
7.46 For the ideal transformer shown in Figure P7.46,
consider that vS (t) = 294 cos(377t) V. Find
7.49 If we knew that the transformer shown in Figure
a. Primary current. P7.49 were to deliver 50 A at 110 V rms with a certain
b. vo (t). resistive load, what would the power transfer
c. Secondary power. efficiency between source and load be?
vS(t) +
_ 25 vo(t)
_
_
Figure P7.49
Figure P7.46
7.50 A method for determining the equivalent circuit of
a transformer consists of two tests: the open-circuit test
7.47 If the transformer shown in Figure P7.47 is ideal, and the short-circuit test. The open-circuit test, shown
find the turns ratio N = 1/n that will provide in Figure P7.50(a), is usually done by applying rated
maximum power transfer to the load. voltage to the primary side of the transformer while
leaving the secondary side open. The current into the
primary side is measured, as is the power dissipated.
The short-circuit test, shown in Figure P7.50(b),
RS n:1 is performed by increasing the primary voltage until
+ rated current is going into the transformer while the
secondary side is short-circuited. The current into the
vS(t) +
_ RL vo(t)
transformer, the applied voltage, and the power
_ dissipated are measured.
The equivalent circuit of a transformer is shown
RS = 1,800 RL = 8
in Figure P7.50(c), where rw and Lw represent the
Figure P7.47 winding resistance and inductance, respectively, and rc
and Lc represent the losses in the core of the
transformer and the inductance of the core. The ideal
transformer is also included in the model.
7.48 Assume the 8- resistor is the load in the circuit With the open-circuit test, we may assume that
shown in Figure P7.48. Assume vg = 110 V rms and a IP = IS = 0. Then all the current that is measured is
variable turns ratio of 1 : n. Find directed through the parallel combination of rc and Lc .
a. The maximum power dissipated by the load. We also assume that |rc || jLc | is much greater than
rw + jLw . Using these assumptions and the
b. The maximum power absorbed from the source. open-circuit test data, we can find the resistance rc and
c. The power transfer efficiency. the inductance Lc .
January 11, 2008 15:33 Chap07 Sheet number 56 Page number 334 magenta black
In the short-circuit test, we assume that Vsecondary is The transformer is a 460-kVA transformer, and the
zero, so that the voltage on the primary side of the ideal tests are performed at 60 Hz.
transformer is also zero, causing no current flow through the 7.52 A method of thermal treatment for a steel pipe is to
rc Lc parallel combination. Using this assumption with heat the pipe by the Joule effect, flowing a current
the short-circuit test data, we are able to find the resistance directly in the pipe. In most cases, a low-voltage
rw and inductance Lw . high-current transformer is used to deliver the current
Using the following test data, find the equivalent through the pipe. In this problem, we consider a
circuit of the transformer: single-phase transformer at 220 V rms, which delivers
Open-circuit test: V = 241 V 1 V. Due to the pipes resistance variation with
I = 0.95 A temperature, a secondary voltage regulation is needed
in the range of 10 percent, as shown in Figure P7.52.
P = 32 W
The voltage regulation is obtained with five different
Short-circuit test: V = 5 V slots in the primary winding (high-voltage regulation).
I = 5.25 A Assuming that the secondary coil has two turns, find
P = 26 W the number of turns for each slot.
+ 220 V
A W
~
Vs +
_ V 5 1
2
(a) 4 3
A W
+
~
Vs V Pipe
_ 1.2 V
(b)
rw Lw Sliding contact
+
~ ~ Figure P7.52
Ip IS
rc Lc Vsecondary
7.53 With reference to Problem 7.52, assume that the
pipes resistance is 0.0002 , the secondary resistance
_ (connections + slide contacts) is 0.00005 , and the
primary current is 28.8 A with pf = 0.91 Find
(c)
a. The plot number.
Figure P7.50
b. The secondary reactance.
7.51 Using the methods of Problem 7.50 and the c. The power transfer efficiency.
following data, find the equivalent circuit of the
7.54 A single-phase transformer used for street lighting
transformer tested:
(high-pressure sodium discharge lamps) converts 6 kV
Open-circuit test: VP = 4,600 V to 230 V (to load) with an efficiency of 0.95. Assuming
IOC = 0.7 A pf = 0.8 and the primary apparent power is 30 kVA,
P = 200 W find
Short-circuit test: P = 50 W a. The secondary current.
VP = 5.2 V b. The transformers ratio.
January 11, 2008 15:33 Chap07 Sheet number 57 Page number 335 magenta black
d. : N = 1/18
7.57 The wire that connects an antenna on your roof to
If Vprim = 120 V, find and draw the connections that will the TV set in your den is a 300- wire, as shown in
allow you to construct the following voltage sources: Figure P7.57(a). This means that the impedance seen
a. 24.670 V by the connections on your set is 300 . Your TV,
however, has a 75- impedance connection, as shown
b. 36.670 V in Figure P7.57(b). To achieve maximum power
c. 180 V transfer from the antenna to the television set, you
d. 54.67180 V place an ideal transformer between the antenna and the
TV as shown in Figure P7.57(c). What is the turns
ratio, N = 1/n, needed to obtain maximum power
transfer?
a
+
300
a'
b
(a)
75
Vprim b'
c
Antenna
c' connections
d Rear view of
television
(b)
_ 300
n:1
d'
+
Figure P7.55 Vantenna 75 Vsignal
(c)
7.56 The circuit in Figure P7.56 shows the use of ideal
Figure P7.57
transformers for impedance matching. You have a
limited choice of turns ratios among available
transformers. Suppose you can find transformers with Section 7.4: Three-Phase Power
turns ratios of 2:1, 7:2, 120:1, 3:2, and 6:1. If ZL is
475 25 and Zab must be 267 25 , find the 7.58 The magnitude of the phase voltage of a balanced
combination of transformers that will provide this three-phase wye system is 220 V rms. Express each
impedance. (You may assume that polarities are easily phase and line voltage in both polar and rectangular
reversed on these transformers.) coordinates.
January 11, 2008 15:33 Chap07 Sheet number 58 Page number 336 magenta black
7.59 The phase currents in a four-wire wye-connected 7.62 For the circuit shown in Figure P7.62, find the
load are as follows: current in the neutral wire and the real power.
5
Ian = 100 A, Ibn = 12 A Icn = 82.88 A
6 ~
IR
~
Determine the current in the neutral wire. VR = 220 0
~ 10
7.60 For the circuit shown in Figure P7.60, we see that IW
~ 10
VW = 220 2 3
each voltage source has a phase difference of 2/3 in
relation to the others.
~ 10
a. Find VRW , VWB , and VBR , where IB
~
VB = 220 4 3
VRW = VR VW , VWB = VW VB , ~
IN
and VBR = VB VR .
b. Repeat part a, using the calculations
VRW = VR 3(/6) Figure P7.62
VWB = VW 3(/6)
VBR = VB 3(/6) 7.63 A three-phase steel-treatment electric oven has a
phase resistance of 10 and is connected at
c. Compare the results of part a with the results of three-phase 380-V AC. Compute
part b.
a. The current flowing through the resistors in wye
and delta connections.
~ ~ b. The power of the oven in wye and delta
VW VR
connections.
+ + 7.64 A naval in-board synchronous generator has an
_
_
120 2 3 120 0
apparent power of 50 kVA and supplies a three-phase
network of 380 V. Compute the phase currents, the
active powers, and the reactive powers if
a. The power factor is 0.85.
120 4 3
_
+
b. The power factor is 1.
7.65 In the circuit of Figure P7.65:
~
VB vs1 = 170 cos(t) V
Figure P7.60 vs2 = 170 cos(t + 2/3) V
vs3 = 170 cos(t 2/3) V
7.61 For the three-phase circuit shown in Figure P7.61, f = 60 Hz Z1 = 0.520
find the current in the neutral wire and the real power. Z2 = 0.350 Z3 = 1.7(90 )
Determine the current through Z1 , using
~ a. Loop/mesh analysis.
IR
~
VR = 110 0 V b. Node analysis.
~ 50
IW
~ j 45 c. Superposition.
VW = 110 2 3 V
_ j20
~
IB
~ ~
VB = 110 4 3 V VS1
_+
~ Z1
IN
+
_
~ ~ Z2 Z3
VS3
+_
VS2
(a)
~ ~ ~ ~
V1 ~ V1 V2 V3
V3
_+
R
+
_
L R1 R2 R3
~ C
+_
V2
L1 L2 L3
Figure P7.66
(b)
7.67 The three sources in the circuit of Figure P7.67 are
connected in wye configuration and the loads in a delta
~ ~
configuration. Determine the current through each VR, IR
impedance. + R1
vs1 = 170 cos(t) V 416 _30 ~ ~
VW, IW R2
_ L1 L2
vs2 = 170 cos(t + 2/3) V 416 210 +
(c)
~ Z1
_+
V1 Figure P7.68
Z2
+
_
~
V3 ~
+_
V2 Z3
7.71 A residential four-wire system supplies power at d. Does the company risk facing a power factor
220 V rms to the following single-phase appliances: penalty on its next bill if all the motors in the
On the first phase, there are ten 75-W bulbs. On the factory are similar to this one?
second phase, there is a 750-W vacuum cleaner with a
power factor of 0.87. On the third phase, there are ten
40-W fluorescent lamps with power factor of 0.64. W
Find R 5
+ + j6
_
_ j6
a. The current in the netural wire. 120 2 3
120 0 5
b. The real, reactive, and apparent power for each 5
phase. 120 _2 3
_
+
j6
7.72 The electric power company is concerned with the B
loading of its transformers. Since it is responsible for a
large number of customers, it must be certain that it Figure P7.72
can supply the demands of all customers. The power
companys transformers will deliver rated kVA to the
secondary load. However, if the demand increased to a
7.73 To correct the power factor problems of the motor
in Problem 7.72, the company has decided to install
point where greater than rated current were required,
capacitors as shown in Figure P7.73. Assume rms
the secondary voltage would have to drop below rated
values.
value. Also, the current would increase, and with it the
I 2R losses (due to winding resistance), possibly a. What capacitance must be installed to achieve a
causing the transformer to overheat. Unreasonable unity power factor if the line frequency is 60 Hz?
current demand could be caused, for example, by b. Repeat part a if the power factor is to be 0.85
excessively low power factors at the load. (lagging).
The customer, on the other hand, is not greatly
concerned with an inefficient power factor, provided
that sufficient power reaches the load. To make the
customer more aware of power factor considerations,
the power company may install a penalty on the
customers bill. A typical penaltypower factor chart is
shown in Table 7.3. Power factors below 0.7 are not 5 j6
permitted. A 25 percent penalty will be applied to any
billing after two consecutive months in which the
5
customers power factor has remained j6
below 0.7. C
C
Table 7.3
W IR
R
R 1200 V
+ + IW
~
~
j60 40 Fuse
1200
120120 W 40
N 40 120120 V 40
j60
+
~ 120240 40 j60
t =t1 j30
B j30
Figure P7.74
j30
7.75 The circuit shown in Figure P7.75 is a Y--Y
connected three-phase circuit. The primaries of the
transformers are wye-connected, the secondaries are 40
delta-connected, and the load is wye-connected. Find B IB
the currents IRP , IWP , IBP , IA , IB , and IC . 120120 V
Figure P7.76
IRP IA
4600 V 4: 1
10
10 7.77 For the circuit shown in Figure P7.77, find the
currents IA , IB , IC and IN , and the real power dissipated
IWP j7 j7 by the load.
460120 V 4: 1
j7
IA
2200 V
IBP
460120 V 4: 1 10 40 20
IB
IC j10
j5
Ideal
transformer
Figure P7.75 j5
b. t t1 Figure P7.77