Ashe Code Comparison Nfpa 101 LSC & Ibc
Ashe Code Comparison Nfpa 101 LSC & Ibc
Healthcare Engineering
Code Summary Report
CODE SUMMARY HEALTH CARE NEW BUILDINGS
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
1 Occupancy
2 Occupancy Classification I-2 Health care Health care Health care
(308.3) (6.1.5.1) (6.1.5.1) (6.1.5.1)
3 Construction Type
4 Minimum Construction Type Type IB Type II (222) Type II (222) Type II (222)
(Table 503) (Table 18.1.6.2) (Table 18.1.6.1) (Table 18.1.6.1)
5 Height and Area Limits
6 Maximum Height Allowed 180 feet N/A N/A N/A
(Table 503, Section 504.2)
7 Allowable Area UL N/A N/A N/A
(Table 503)
8 Maximum Number of Stories 5 Stories 4 Stories 4 Stories 4 Stories
(Table 503, Section 504.2) (Table 18.1.6.2) (Table 18.1.6.1) Basements shall not be considered a
story
(Table 18.1.6.1)
13 Waiting areas off Corridors Spaces of unlimited area including Waiting areas and similar spaces Waiting areas and similar spaces Waiting areas and similar spaces
waiting areas and similar spaces located off corridors are permitted to located off corridors are permitted to located off corridors are permitted to
constructed as required for corridors be open to the corridor provided the be open to the corridor provided the be open to the corridor provided the
are permitted to be open to the waiting area does not exceed 600 sf waiting area does not exceed 600 sf waiting area does not exceed 600 sf
corridor provided the spaces are not and is protected by an electrically and is protected by an electrically and is protected by an electrically
used for sleeping units, treatment or supevised automatic smoke detection supevised automatic smoke detection supevised automatic smoke detection
hazardous uses, a detection system is system in accordance with 18.3.4. system in accordance with 18.3.4. system in accordance with 18.3.4.
used, and exits are not obstructed. Each area shall be arranged to allow Each area shall be arranged to allow Each area shall be arranged to allow
(407.2.2) direct supervision by facility staff and direct supervision by facility staff and direct supervision by facility staff and
does not obstruct access to exits. does not obstruct access to exits. does not obstruct access to exits.
(18.3.6.1) (18.3.6.1) (18.3.6.1)
Page 1 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
14 Nurses' Stations off Corridors Nurses' Stations and similar spaces Nurse stations do not need to be Nurse stations do not need to be Nurse stations do not need to be
for doctors' and nurses' charting, separated separated separated
communications and related clerical (18.3.6.1(3)) (18.3.6.1(3)) (18.3.6.1(3))
activities are permitted to be open to
the corridor when constructed as
required for corridors.
(407.2.1)
15 Mental Health Treatment Mental health treatment areas are not N/A N/A N/A
(Areas Open to Corridors) required to be separated from
corridors when they meet the
following conditions:
1. Area is no larger than 1500 sq ft.
2. supervision by facility staff
3. No exit access obstruction
4. Area is euipped with fire detection
system
5. One space per smoke compartment
6. Area walls and ceilings constructed
as required for corridors.
(407.2.3)
16 Smoke Compartments: Every story used by patients for Every story used by patients for Every story used by patients for Every story used by patients for
sleeping or treatment and other sleeping or treatment and other sleeping or treatment and other sleeping or treatment and other
stories with an occupant load of 50 or stories with an occupant load of 50 or stories with an occupant load of 50 or stories with an occupant load of 50 or
more must be divided into at least more must be divided into at least more must be divided into at least more must be divided into at least
two smoke compartments constructed two smoke compartments constructed two smoke compartments constructed two smoke compartments constructed
as smoke barriers. as smoke barriers. as smoke barriers. as smoke barriers.
(407.4) (18.3.7.1) (18.3.7.1) (18.3.7.1)
Page 2 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
18 Smoke Compartment Size Compartment sizes may not exceed Compartment sizes may not exceed Compartment sizes may not exceed Compartment sizes may not exceed
22,500 s.f. and the travel distance 22,500 s.f. and the travel distance 22,500 s.f. and the travel distance 22,500 s.f. and the travel distance
from any point in a smoke from any point in a smoke from any point in a smoke from any point in a smoke
compartment to a smoke barrier door compartment to a smoke barrier door compartment to a smoke barrier door compartment to a smoke barrier door
may not exceed 200 feet. Smoke may not exceed 200 feet. Smoke may not exceed 200 feet. Smoke may not exceed 200 feet. Smoke
barriers must comply with Section barriers must comply with Section 8.3 barriers must comply with Section 8.5 barriers must comply with Section 8.5
710. and be no less than 1 hour rated and be no less than 1 hour rated and be no less than 1 hour rated
(407.4) (18.3.7.1 and 18.3.7.3) (18.3.7.1 and 18.3.7.3) (18.3.7.1 and 18.3.7.3)
19 Smoke Compartment Refuge Area Provide at least 30 net sq. feet per Provide at least 30 net sq. feet per Provide at least 30 net sq. feet per Provide at least 30 net sq. feet per
patient within corridors, patient patient within corridors, patient patient within corridors, patient patient within corridors, patient
rooms, lounge or dining , other low rooms, lounge or dining , other low rooms, lounge or dining , other low rooms, lounge or dining , other low
hazard areas on each side of the hazard areas on each side of the hazard areas on each side of the hazard areas on each side of the
smoke barrier. smoke barrier. smoke barrier. smoke barrier.
(18.3.7.4) (18.3.7.5.1) (18.3.7.5.1)
20 For floors not housing bed or litter For floors not housing bed or litter For floors not housing bed or litter For floors not housing bed or litter
patients , provide 6 net square feet patients , provide 6 net square feet patients , provide 6 net square feet patients , provide 6 net square feet
per occupant on each side of smoke per occupant on each side of smoke per occupant on each side of smoke per occupant on each side of smoke
barrier for the total number of barrier for the total number of barrier for the total number of barrier for the total number of
occupants in adjoining smoke occupants in adjoining smoke occupants in adjoining smoke occupants in adjoining smoke
compartments. compartments. compartments. compartments.
(407.4.1) (18.3.7.4) (18.3.7.5.2) (18.3.7.5.2)
21 Smoke Compartment Independent An independent means of egress Not less than two exits of the types Not less than two exits of the types Not less than two exits of the types
Egress must be provided from each smoke described in 18.2.2.2 through described in 18.2.2.2 through described in 18.2.2.2 through
compartment. Reentry into the smoke 18.2.2.10 shall be accessible from each 18.2.2.10 shall be accessible from each 18.2.2.10 shall be accessible from each
compartment for egress is not smoke compartment(s) and shall not smoke compartment(s) and shall not smoke compartment(s) and shall not
permitted. require return through the require return through the require return through the
(407.4.2) compartment of fire origin compartment of fire origin compartment of fire origin
(18.2.4.3) (18.2.4.3) (18.2.4.3)
22 Smoke Compartment Sprinkler Patient sleeping units within smoke Listed quick-response or listed Listed quick-response or listed Listed quick-response or listed
System compartments are required to be residential sprinklers shall be used residential sprinklers shall be used residential sprinklers shall be used
equipped with an NFPA 13 sprinkler throughout smoke compartments throughout smoke compartments throughout smoke compartments
system. Smoke compartments must containing patient sleeping areas containing patient sleeping areas containing patient sleeping areas
use approved quick-response or (18.3.5.2 - See Appendix) (18.3.5.6 - See Appendix) (18.3.5.6 - See Appendix)
residential sprinklers per Section
903.3.2.
(407.6)
25 Smoke Barriers 1-Hour smoke barrier 1-hour smoke barrier 1-hour smoke barrier 1-hour smoke barrier
(710.3) (18.3.7.3) (18.3.7.3) (18.3.7.3)
Page 3 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
26 Must be continuous from outside Smoke barriers must be continuous Smoke barriers must be continuous Smoke barriers must be continuous
wall to outside wall and be from wall to wall, barrier to barrier, from wall to wall, barrier to barrier, from wall to wall, barrier to barrier,
constructed from the floor to the or from floor to floor and through or from floor to floor and through or from floor to floor and through
underside of the floor or roof above concealed spaces. concealed spaces. concealed spaces.
or to the underside of a ceiling and (8.3.2) (8.5.2) (8.5.2)
limit the transfer of smoke.
(710.4)
28 Shaft Enclosures 2-hour fire barrier 2-hour fire barrier 2-hour fire barrier 2-hour fire barrier
(Connecting 4 or More Stories) (708.4) (8.2.5.4(1)) (8.6.5(1)) (8.6.5(1))
Shaft enclosures must be constructed
in accordance with Section 708.
29 Shaft Enclosures 1-hour fire barrier Connecting up to 3 1-hour fire barrier Connecting up to 3 1-hour fire barrier Connecting up to 3 1-hour fire barrier Connecting up to 3
(Connecting 3 Stories or Less) stories stories (8.2.5.4(2)) stories stories
(708.4) (8.6.5(2)) (8.6.5(2))
30 Exit Stair Enclosures 2-hour fire barrier 2-hour fire barrier 2-hour fire barrier 2-hour fire barrier
(Connecting 4 or more Stories) (1022.1) (7.1.3.2.1(b)) (7.1.3.2.1(2)) (7.1.3.2.1(2))
31 Exit Stair Enclosures 1-hour fire barrier 1-hour fire barrier (7.1.3.2.1(a)) 1-hour fire barrier (7.1.3.2.1(1)) 1-hour fire barrier (7.1.3.2.1(1))
(Connecting 3 Stories or Less) (1022.1)
32 Exit Passageways Fire barrier with not less than 1-hour Fire barrier with same rating as that Fire barrier with same rating as that Fire barrier with same rating as that
and/or with same rating as that for for the exit stair enclosure that it for the exit stair enclosure that it for the exit stair enclosure that it
the exit stair enclosure that it serves. serves. serves. serves.
(1023.3) (7.2.6.2) (7.2.6.2) (7.2.6.2)
33 Horizontal Exit wall 2-hour fire barrier and barrier must 2-hour fire barrier and barrier must 2-hour fire barrier and barrier must 2-hour fire barrier and barrier must
extend through all levels of the continue to grade level unless all continue to grade level unless all continue to grade level unless all
building unless floor assemblies have stairs discharge directly to outside stairs discharge directly to outside stairs discharge directly to outside
a fire-resistance rating of not less than and floor with horizontal exit does and floor with horizontal exit does and floor with horizontal exit does
2 hours with no unprotected not have an unprotected vertical not have an unprotected vertical not have an unprotected vertical
openings. opening. opening. opening.
(1025.2) (7.2.4.3.1) (7.2.4.3.1 and 7.2.4.3.3) (7.2.4.3.1 and 7.2.4.3.3)
34 Horizontal Exit Opening Protection 1- 1/2 hours 1- 1/2 hours 1- 1/2 hours 1- 1/2 hours
(doors) (Table 715.4) (8.2.3.2.3) (Table 8.3.4.2) (Table 8.3.4.2)
Page 4 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
35 Permitted Unprotected Floor Permitted provided the following: Communicating space is permitted by Permitted provided the following: Permitted provided the following:
Openings. 1. Connects a mezzanine and the 18.3.1.1 1. Connects no more than two 1. Connects no more than two
floor below Unprotected floor openings permitted adjacent floors adjacent floors
( Unless permitted by the code all 2. Escalator or open stair cannot be a provided: 2. Is separated from floor openings 2. Is separated from floor openings
floor openings to be protected as portion of he means of egress. 1. Conects no more than 2 adjacent serving other floors serving other floors
noted above for a shaft.) (708.2) stories 3. Opening is separated from 3. Opening is separated from
(711) 2. Is separated from floor opening corridors corridors
serving other floors 4. Convenience openings shall be 4. Convenience openings shall be
3. Separated from corridors separated from by a smoke partition. separated from by a smoke partition.
4. Shall not serve as a required means 4. Opening is not part of a required 4. Opening is not part of a required
of egress exit path. exit path.
(8.2.5.5) (8.6.8.2) (8.6.8.2)
36 Horizontal Assemblies Floor and roof assemblies required to Required by NFPA 220 Required by NFPA 221 Required by NFPA 222
have a fire-resistive rating must
comply with this section. Otherwise,
713.4.2
(712)
38 Exterior Walls Fire resistive rating per Table 601 & N/A N/A N/A
602
(705.5)
Buildings on the same lot must have
and imaginary line assumed between
them for opening protection, fire
rating & roof covering requirements.
(705.3)
Structural stability
(705.6)
Parapets
(705.11)
Joints
(714.1)
Voids at intersection of exterior
curtain wall and floor/ceiling
assembly must be properly sealed
(714.4)
39 Elevator Lobbies Elevator lobbies required in Required if used for occupant Required if used for occupant Required if used for occupant
accordance with Section 708 unless evacuation. Shall meet the following: evacuation. Shall meet the following: evacuation. Shall meet the following:
the elevator hoistway is pressurized. very floor served by the elevator shall very floor served by the elevator shall very floor served by the elevator shall
Construct as smoke partitions . have an elevator lobby and form a 1- have an elevator lobby and form a 1- have an elevator lobby and form a 1-
(708.14.1) hour barrier in accordance with 8.5 hour barrier in accordance with 8.5 hour barrier in accordance with 8.5
(7.2.13.3) (7.2.13.3) (7.2.13.3)
Page 5 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
40 Fire-Resistance Ratings of Structural Structural elements to comply with Structural members supporting the 2 Structural members supporting the 2 Structural members supporting the 2
Members Section 704. hour floor assembly shall have the hour floor assembly shall have the hour floor assembly shall have the
(704) resistance rating required of the resistance rating required of the resistance rating required of the
building building building
(18.1.6.2(b)) (18.1.6.2(3)) (18.1.6.2(3))
41 Ducts and Air Transfer Openings Includes provisions for fire dampers, Smoke dampers shall not be required Smoke dampers shall not be required Smoke dampers shall not be required
smoke dampers and combination in duct penetrations of smoke barriers in duct penetrations of smoke barriers in duct penetrations of smoke barriers
fire/smoke dampers. in fully ducted heating, ventilating, in fully ducted heating, ventilating, in fully ducted heating, ventilating,
(716) and air conditioning systems. and air conditioning systems. and air conditioning systems.
Provide approved alternative (18.3.7.3(2)) (18.3.7.3(2)) (18.3.7.3(2))
protection where the installation of a
fire damper will interfere with the
operation of a required smoke control
system.
(716.2.1)
42 Opening Protectives
43 Corridor Doors- Group I-2 Group I-2 - Must limit the passage of New Health Care - Doors protecting New Health Care - Doors protecting New Health Care - Doors protecting
smoke and be provided with positive corridor openings shall be corridor openings shall be corridor openings shall be
latching. Roller latches are not constructed to resist the passage of constructed to resist the passage of constructed to resist the passage of
permitted. smoke. Bottom clearence shall not smoke. Bottom clearence shall not smoke. Bottom clearence shall not
(407.3.1) exceede 1 inch. Doors shall have exceede 1 inch. Doors shall have exceede 1 inch. Doors shall have
positive latching hardware and no positive latching hardware and no positive latching hardware and no
roller latches. roller latches. roller latches.
(18.3.6.3.1 and 18.3.6.3.2) (18.3.6.3.1 and 18.3.6.3.5) (18.3.6.3.1 and 18.3.6.3.5)
44 2- hour Elevator Hoistways 1-1/2 hour 1-1/2 hour 1-1/2 hour 1-1/2 hour
(Table 715.4) (8.2.3.2.3.1) (Table 8.3.4.2) (Table 8.3.4.2)
45 1- hour Elevator Hoistways 1-hour 1-hour 1-hour 1-hour
(Table 715.4) (8.2.3.2.3.1) (Table 8.3.4.2) (Table 8.3.4.2)
46 2-hour Vertical Shafts (including 1-1/2 hour 1-1/2 hour 1-1/2 hour 1-1/2 hour
stairways, exits, and chutes) (Table 715.4) (8.2.3.2.3.1) (Table 8.3.4.2) (Table 8.3.4.2)
47 1-hour Vertical Shafts (including 1-hour 1-hour 1-hour 1-hour
stairways, exits, and chutes) (Table 715.4) (8.2.3.2.3.1) (Table 8.3.4.2) (Table 8.3.4.2)
48 2- hour Fire Barriers 1-1/2 hour 1-1/2 hour 1-1/2 hour 1-1/2 hour
(Table 715.4) (8.2.3.2.3.1) (Table 8.3.4.2) (Table 8.3.4.2)
49 1- hour Fire Barriers 3/4 hour 3/4 hour 3/4 hour 3/4 hour
(Table 715.4) (8.2.3.2.3.1) (Table 8.3.4.2) (Table 8.3.4.2)
50 2- hour Horizontal Exits 1-1/2 hour 1-1/2 hour 1-1/2 hour 1-1/2 hour
(T.715.4) (7.2.4.3.2 and 8.2.3.2.3) (Table 8.3.4.2) (Table 8.3.4.2)
51 Smoke Barriers 1/3 hour 20 minutes 20 minutes 21 minutes
(Table 715.4) (8.2.3.2.3.1) (Table 8.3.4.2) (Table 8.3.4.2)
52 Fire Window Assembly (Table 715.5) 8.2.3.2.2 8.3.3.1 8.3.3.2
53 Occupancy Separations
Page 6 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
54 Non-separated Uses Occupancy separation is not required Occupancy separation is not required Occupancy separation is not required Occupancy separation is not required
when the entire building meets the when the entire building meets the when the entire building meets the when the entire building meets the
most restrictive requirements of most restrictive requirements of each most restrictive requirements of each most restrictive requirements of each
Section 403 and Chapter 9. individual occupancy. (A3.3.134.10 individual occupancy. individual occupancy.
(508.3.1) and 6.1.14.2) (6.1.14.3.2) (6.1.14.3.2)
55 Boiler and fuel-fired heater rooms 1-hour or provide automatic fire 1 hour 1-Hour 1-Hour
sprinkler system (Table 18.3.2.1) (18.3.2.1) (18.3.2.1)
(Table 508.2.5)
56 Central/bulk laundries more than 1 hour or provide automatic fire 1 hour 1 hour 2 hour
100 sf extinguishing system (Table 18.3.2.1) (Table 18.3.2.1) (Table 18.3.2.1)
(Table 508.2.5)
57 Laboratories employing flammable or 1 hour or provide automatic fire Smoke tight and self-closing Smoke tight and self-closing Smoke tight and self-closing
combustible materials in quantities sprinkler system (18.3.2.1) (18.3.2.1) (18.3.2.1)
less than that which would be (Table 508.2.5)
considered severe.
58 Laboratories that use hazardous Applicable to any laboratory located See 18.3.6.3.11 See 18.3.6.3.11 See 18.3.6.3.11
materials that would cause in Group I-2 occupancies (Table 18.3.2.1) (Table 18.3.2.1) (Table 18.3.2.1)
classification as a severe hazard in 1 hour or provide automatic sprinkler
accordance with NFPA 99 "Standard system.
for Health Care Facilities" (Table 508.2.5)
59 Paint Shops not classified as an H 2 hours or 1 hour and provide 1 hour 1 hour 1 hour
occupancy automatic fire-extinguishing system (Table 18.3.2.1) (Table 18.3.2.1) (Table 18.3.2.1)
(Table 508.2.5)
Page 7 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
64 Termination rooms must be into a Any trash chute chute shall discharge Any trash chute chute shall discharge Any trash chute chute shall discharge
room separated form the remainder into a trash collection room used for into a trash collection room used for into a trash collection room used for
of the building by a 1 hour fire no ther purpose and protected in no ther purpose and protected in no ther purpose and protected in
barrier. accordance with section 8.4 accordance with section 8.7 accordance with section 8.7
Openings in to access rooms must be (18.5.4.3) (18.5.4.4) (18.5.4.4)
protected by a 3/4 hour self-or
automatic opening door.
Provide automatic sprinkler system
per Section 903.2.11.2.
(708.13)
65 Storage rooms between 50-100 sf of N/A Smoke tight and self-closing. Smoke tight and self-closing. Smoke tight and self-closing.
combustible materials (18.3.2.1) (18.3.2.1) (18.3.2.1)
66 Storage rooms greater than 100 sf of N/A 1 hour 1 hour 2 hour
combustible materials (Table 18.3.2.1) (Table 18.3.2.1) (Table 18.3.2.1)
67 Gift shops less than 500 sf and not Not required to be separated from No separation required. (18.3.2.5) No separation required. No separation required.
considered hazardous corridors when fully sprinklered and (18.3.6.1(4)) (18.3.6.1(4))
storage areas are protected in
accordance with Section 508.2.5.
(407.2)
68 Gift shops more than 500 sf and not Separated from corridors with smoke Separated from the corridor by non Separated from the corridor by non Separated from the corridor by non
considered hazardous partitions fire rated walls. fire rated walls. fire rated walls.
(407.2) (18.3.2.5) (18.3.6.1) (18.3.6.1)
69 Gift shops with combustible loading N/A 1 hour 1 hour 2 hour
considered hazardous (8.4.1.1) (8.7.1) (8.7.1)
70 Non-flammable gas storage including Oxidizers and oxidizer gases may not 1 hour 1 hour 2 hour
oxidizers exceed the exempt quantities per (NFPA 99:4-3.1..1.2(a)2) (NFPA 99:4-5.1.3.3.2(4)) (NFPA 99:4-5.1.3.3.2(4))
control area. See also mechanical
code & plumbing code.
75 Interior Wall Finish Based on Group I- Exit enclosure & exit passageway - B Permitted throughout if Class A or B Permitted throughout if Class A or B Permitted throughout if Class A or B
2 Corridors - B and compliant with 10.2 and compliant with 10.2 and compliant with 10.2
Rooms & enclosed spaces - B (18.3.3.2) (18.3.3.2) (18.3.3.2)
(Table 803.9)
Page 8 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
77 Maximum flame spread for vertical Class A: 0-25 Class A: 0-25 Class A: 0-25 Class A: 0-25
exitways, access corridors, other exits, Class B: 26-75 Class B: 26-75 Class B: 26-75 Class B: 26-75
rooms and enclosed spaces, textile Class C: 76-200 Class C: 76-200 Class C: 76-200 Class C: 76-200
wall coverings (803.1.1) (Table A.10.2.2) (Table A.10.2.2) (Table A.10.2.2)
78 Textiles Class A flame spread index in See 10.2.4.1 See 10.2.4.1 See 10.2.4.2
(Wall & Ceiling Finish) accordance with ASTM E 84
(803.6.1)
79 Suspended Acoustical Ceiling ASTM C 635 & ASTM C 636 N/A N/A N/A
Systems (803.9)
80 Interior Floor Finish Class II in exit enclosures, corridors No Requirement See 10.2.7.1 or 10.2.7.2 See 10.2.7.1 or 10.2.7.2
and rooms not separated from (18.3.3.3) (18.3.3.3) (18.3.3.3)
corridors by full height partitions
DOC FF-1 "pill test" (CPC 16 CFR,
Part 1630)
(804.4.1)
81 Helistops
82 Size < 3,500 pounds - 20' x 20' min. with N/A N/A N/A
average open space of 15 feet at roof
level and no less than 5 feet
(412.7.1)
84 Means of egress Must comply with Chapter 10. < 60' N/A N/A N/A
in length or 2,000 sf may have fire
escape or ladder leading to the floor
below for second means of egress
(412.7.3)
Page 9 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
94 Storage & Mechanical Spaces 300 sf / occupant. 300 sf/occupant Anticipated Occupancy 42.1.7 Anticipated Occupancy 42.1.8
(Table 1004.1.1) (Table 7.3.1.2)
95 Sleeping Areas 120 sf / occupant. 120 sf / occupant 120 sf / occupant 120 sf / occupant
(Table 1004.1.1) (Table 7.3.1.3) (Table 7.3.1.3) (Table 7.3.1.3)
96 Locker Rooms 50 sf / occupant. 50 sf / occupant 50 sf / occupant 50 sf / occupant
(Table 1004.1.1) (Table 7.3.1.4) (Table 7.3.1.4) (Table 7.3.1.4)
97 Kitchen 200 sf / occupant. 100 sf / occupant 100 sf / occupant 100 sf / occupant
(Table 1004.1.1) (Table 7.3.1.5) (Table 7.3.1.2) (Table 7.3.1.2)
98 Minimum Number of Exits
99 1-500 occupants 2 exits 2 exits 2 exits 2 exits
(Table 1021.1) (7.4.1.1) (7.4.1.1) (7.4.1.1)
100 501-1,000 occupants 3 exits 3 exits 3 exits 3 exits
(Table 1021.1) (7.4.1.2(1)) (7.4.1.2(1)) (7.4.1.2(1))
101 Greater than 1,000 occupants 4 exits 4 exits 4 exits 4 exits
(Table 1021.1) (7.4.1.2(2)) (7.4.1.2(2)) (7.4.1.2(2))
102 Patient sleeping rooms or suites that 2 exits 2 exits 2 exits 2 exits
include patient sleeping rooms more (1014.2.3.2) (18.2.5.2) (18.2.5.5.1) (18.2.5.5.1)
than 1,000 sf in area
103 Any room or suite of rooms, other 2 exits 2 exits 2 exits 2 exits
than patient sleeping rooms, more (1014.2.4.2) (18.2.5.3) (18.2.5.5.2) (18.2.5.5.2)
than 2,500 sf in area
104 Each smoke compartment Based on O.L. and travel distance. Access to 2 exits Access to 2 exits Access to 2 exits
Travel distance not to exceed 200 feet (18.2.4.3) (18.2.4.3) (18.2.4.3)
from smoke barrier to barrier door
(407.4)
Independent egress required without
reentry into smoke compartment per
407.4.2.
105 Every habitable room or suite must (1014.2.2) (18.2.5.1) (18.2.5.6.1) (18.2.5.6.1)
have an exit access door leading
directly to an exit corridor,unless
permitted by exceptions
106 Exit Access from a patient sleeping (1014.2.3) (18.2.5.1(2)) (18.2.5.6.2) (18.2.5.6.2)
room with not more than 8 beds shall
be permitted to pass through one
intervening room to reach an exit
access corridor, provided there is
constant supervision by nursing
personnel.
Page 10 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
108 Two or more exits or exit access doors At least two exits or access doors At least two exits or access doors At least two exits or access doors N/A
required from an area must be placed a distance apart equal must be placed a distance apart equal must be placed a distance apart equal
to not less than 1/3 the length of the to not less than 1/3 the length of the to not less than 1/3 the length of the
maximum overall diagonal maximum overall diagonal maximum overall diagonal
dimension of the building or area dimension of the building or area dimension of the building or area
served, measured in a straight line served, measured in a straight line served, measured in a straight line
between exits, for sprinklered between exits, for sprinklered between exits, for sprinklered
buildings. buildings. (See Exception 2) buildings.
(1015.2.1) (7.5.1.4) (7.5.1.3.3)
Suites greater than 7,500 sf and not Suites greater than 7,500 sf and not
exceeding 10,000 sf is allowed when exceeding 10,000 sf is allowed when
direct visual supervision and direct visual supervision and
automactic smoke detection in automactic smoke detection in
common areas is provided. common areas is provided.
112 Suites of rooms other than patient Shall not exceed 10,000 sf Shall not exceed 10,000 sf Shall not exceed 10,000 sf Shall not exceed 10,000 sf
sleeping rooms (1014.2.4.1) (18.2.5.7) (18.2.5.7.3.3) (18.2.5.7.3.3)
113 Hazardous areas within suites Not addressed N/A See 18.2.5.7.1.3 See 18.2.5.7.1.4
options
114 Intervening rooms other than patient One intervening room is allowed if One intervening room is allowed if One intervening room is allowed if One intervening room is allowed if
sleeping rooms. the travel distance within the suite to the travel distance within the suite to the travel distance within the suite to the travel distance within the suite to
the exit access door does not exceed the exit access door does not exceed the exit access door does not exceed the exit access door does not exceed
100 feet and two intervening rooms 100 feet and two intervening rooms 100 feet and two intervening rooms 100 feet and two intervening rooms
are permitted where the travel are permitted where the travel are permitted where the travel are permitted where the travel
distance to the exit access door does distance to the exit access door does distance to the exit access door does distance to the exit access door does
not exceed 50 feet. not exceed 50 feet. not exceed 50 feet. not exceed 50 feet.
(1014.2.4.3 and 1014.2.4.4) (18.2.5.8) (18.2.5.7.3.4(A)) (18.2.5.7.3.4(A))
115 Intervening rooms for patient Patient sleeping rooms are permitted Exit access from a patient sleeping Exit access from a patient sleeping Exit access from a patient sleeping
sleeping rooms. to have one intervening room when room with not more than eight room with not more than eight room with not more than eight
the intervening room is not used as patient beds shall be permitted to patient beds shall be permitted to patient beds shall be permitted to
an exit access for more than eight pass through one intervening room. pass through one intervening room. pass through one intervening room.
patient beds. (18.2.5.1(2)) (18.2.5.6.2) (18.2.5.6.2)
(1014.2.3)
116 Special Nursing Suites May have one intervening room May have one intervening room May have one intervening room May have one intervening room
where the arrangement allows for where the arrangement allows for where the arrangement allows for where the arrangement allows for
direct and constant visual supervision direct and constant visual supervision direct and constant visual supervision direct and constant visual supervision
by nursing personnel. by nursing personnel. by nursing personnel. by nursing personnel.
(1014.2.3) (18.2.5.1(3)) (18.2.5.7.2.1) (18.2.5.7.2.1)
Page 11 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
117 Egress into another suite See intervening rooms. Not addressed A suite that requires two means of A suite that requires two means of
Exit acces from all other portions of a egress is premitted have one means of egress is premitted have one means of
building not classified as a suite in a egress to be into another suite, egress to be into another suite,
Group I-2 occupancy shall not pass provided that the separation between provided that the separation between
through a suite the suite complies with 18.3.6.2 the suite complies with 18.3.6.2
(1014.2.5) through 18.3.6.5 through 18.3.6.5
(18.2.5.7.2.2(C)) (18.2.5.7.2.2(C))
118 Exit Access from a Corridor Corridors in occupancies in Group I-2 Every corridor shall provide access to Every corridor shall provide access to Every corridor shall provide access to
shall be continuous from to the exits at least two exits without passing at least two exits without passing at least two exits without passing
and separated from other areas in through any intervening rooms or through any intervening rooms or through any intervening rooms or
accordance with 407.3 except spaces spaces other than corridors or lobbies. spaces other than corridors or lobbies. spaces other than corridors or lobbies.
conforming with 407.2.1 through (18.2.5.9) (18.2.5.4) (18.2.5.4)
407.2.4
(407.2)
125 Between any point in a sleeping suite Maximum 200 feet N/A Maximum 200 feet Maximum 200 feet
and an exit (Table 1016.1) (18.2.5.7.2.4(B)) (18.2.5.7.2.4(B))
126 Common Path of Travel Group I-2 - 75 feet N/A Maximum 100 feet Maximum 100 feet
(1014.3) (18.2.5.3) (18.2.5.3)
127 Doors
128 Minimum clear width serving 41.5 inches 41.5 inches 41.5 inches 41.5 inches
sleeping rooms, diagnostic and (1008.1.1) (18.2.3.5(1)) (18.2.3.6(1)) (18.2.3.6(1))
treatment rooms
129 Minimum clear width all other areas 32 inches net clear width 32 inches clear width 32 inches clear width 32 inches clear width
(1008.1.1) (18.2.3.5 and 7.2.1.2.3) (18.2.3.7 and 7.2.1.2.3.2) (18.2.3.7 and 7.2.1.2.3.2)
130 Minimum Height 80 inches 90 inches 90 inches 90 inches
(1008.1.1) (7.1.5) (7.1.5.1) (7.1.5.1)
Page 12 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
131 Door Swing Doors are required to be of the side Doors in the direction of egress Doors in the direction of egress Doors in the direction of egress
Doors should be of the side hinged hinged swinging type. Exceptions: 7.2.1.4.1 7.2.1.4.1 7.2.1.4.1
swinging type. 1. Critical or intensive care patient
rooms within suites
2. Horizontal sliding doors
complying with 1008.1.4.3
3. Manually operated horizontal
sliding doors are permitted in a
means of egress from spaces with an
occupant load less than 10
(1008.1.2)
132 Swing in direction of exit travel when (1008.1.2) (7.2.1.4.2 and 7.2.1.4.3) (7.2.1.4.2) (7.2.1.4.2)
serving high hazardous area or
serving an occupant load greater than
50.
133 Exit door shall be openable from the (1008.1.9) (7.2.1.5.1 / 18.2.2.2.4) (7.2.1.5.1 / 7.2.1.5.2 / 18.2.2.2.4) (7.2.1.5.1 / 7.2.1.5.2 / 18.2.2.2.4)
egress side without the use of key
locking device
134 Bolt locks are generally prohibited (1008.1.9.4) N/A N/A N/A
except for storage or equipment and
rooms or where doors serve patient
care rooms.
135 Horizontal Sliding doors are 1. Power operated and capable of Horizontal doors that are not 1. Area served is not high hazard; 2. (7.2.1.14 / 18.2.2.2.10.1 /
permitted to be a component of a being operated manually in the event automatic closing are limited to a Door is readily operable from both 18.2.2.2.10.2)
means of egress when meeting the of power failure. 2. Operable by a single leafe and must be latching or sides without special knowledge; 3.
following: simple method form both sides be provided with means to not Force to set door in motion in
without special knowledge or effort. rebound when pushed closed in an direction of travel is < 30 lbf and < 15
3. Force required to operate is a emergency (7.2.1.14 / 18.2.2.2.9) lbf to open to minimum width or to
maximum of 30 lbs to set door in close; 4. Doors to be fire rated are
motion and 15 lbs to close or open to self- or auto-closing based on smoke
the required width. 4. Operable with detection per NFPA 80; and 5. Doors
a force not to exceed 15 lbs when a requried to latch are provided with a
136 force of 250 lbs is applied mechanism that will latch or
perpendicular to the door adjacent to eliminate potential for rebound.
the operating device. 5. If the door is (7.2.1.14 / 18.2.2.2.10.1 /
required to be rated, it must be self or 18.2.2.2.10.2)
automatic closing operated by smoke
detection. 6. The door assembly must
have an integrated standby power
supply. 7. The door assembly power
supply must be electronically
supervised. 8. The door must open to
the minimum required width within
10 seconds after activation of the
operating device. (1008.1.4.3)
Page 13 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
137 Horizontal sliding doors serving a (1008.1.2(9)) N/A 7.2.1.4.1.6, 18.2.2.2.10.2 7.2.1.4.1.6, 18.2.2.2.10.3
room or area with an occupant load
of fewer than 10 in health care
occupancies shall be exempt from the
requirements of 7.2.1.4.1
138 Vision panels of approved assemblies 18.3.7.9 Vision panels shall not be wired
of fire-rated glazing or wired glass be glass panels
provided at each cross corridor door
and each cross-corridor horizontal-
sliding door in a smoke barrier.
139 Corridors
140 Minimum width where inpatients are 96 inches 8 feet (96 inches) 8 feet (96 inches) 8 feet (96 inches)
moved on beds (1018.2) (18.2.3.3) (18.2.3.4) (18.2.3.4)
(Exception 6)
141 Projections in corridor with minimum The required width of corridors shall Tentative Interim Amendment (2006 6 inches from the corridor wall, Not addressed
width 6 feet be unobstructed LSC) above the handrail height, shall be
(1018.3) 6 inches from the corridor wall, permitted for hand-rub dispensing
above the handrail height, shall be units. Projections in the corridors on
permitted for hand-rub dispensing both sides are permitted if the
units. Projections in the corridors on projection does not exceed a depth of
both sides are permitted if the 6 inches, the length is less than 36
projection does not exceed a depth of inches, positioned not less than 40
6 inches, the length is less than 36 inches above the floor, and has not
inches, positioned not less than 40 less than 48 inches of horizontal
inches above the floor, and has not separation from other projections.
less than 48 inches of horizontal (18.2.3.4)
separation from other projections.
Page 14 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
142 Permitted projections when corridor Non-continuous projections that are
width is 8 feet maximum 6 inches when located > 38
inches AFF; and wheeled equipment
in use for patient movement and
medical emergencies that do not
reduce clear width < 5 ft when staff
are trained and provisions are
included in facility emergency plans
for dealing with the equipment.
Furniture fixed to wall is permitted in
groups not exceeding 50 sq ft, set
minimum 10 ft apart, does not reduce
minimul clear width < 6 ft, is located
on one side, not blocking building
service equipment, and the smoke
compartment is sprinklered
throughout, and corridors are
protected with smoke detectors when
the furniture is not under direct
visual supervision from a nurses
station. (18.2.3.4 #2, 4 and 5).
143 Minimum Width for limited care No similar requirement 6 feet 6 feet 6 feet
facility or hospital for psychiatric care (18.2.3.4) (18.2.3.5) (18.2.3.5)
147 Stairways
148 Risers Minimum 4 inches; Maximum 7 Minimum 4 inches; Maximum 7 Minimum 4 inches; Maximum 7 Minimum 4 inches; Maximum 7
inches inches inches inches
(1009.4.2) (Table 7.2.2.2.1(a)) (Table 7.2.2.2.1.1(a)) (Table 7.2.2.2.1.1(a))
149 Treads Minimum 11 inches Minimum 11 inches Minimum 11 inches Minimum 11 inches
(1009.4.2) (Table 7.2.2.2.1(a)) (Table 7.2.2.2.1.1(a)) (Table 7.2.2.2.1.1(a))
Page 15 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
150 Width O.L. < 50 - 36" Minimum 44 inches <2000 persons = Minimum 44 inches <2000 persons = Minimum 44 inches
O.L. 50 - 44" (Table 7.2.2.2.1(a)) >2000 persons = minimum 56 inches >2000 persons = minimum 56 inches
See occupant egress width Section (Table 7.2.2.2.1.2(B)) (Table 7.2.2.2.1.2(B))
1005.1 for further requirements of
width
(1009.1)
151 Landings Width - Not less than the width of the Width - Not less than the width of the Width - Not less than the width of the Width - Not less than the width of the
stair but need not exceed 48 inches stair but need not exceed 48 inches stair but need not exceed 48 inches stair but need not exceed 48 inches
when the stair has a straight run. when the stair has a straight run. when the stair has a straight run. when the stair has a straight run.
(1009.5) (7.2.2.3.2) (7.2.2.3.2.4) (7.2.2.3.2.4)
152 Vertical Rise Vertical Distance between floor levels Vertical Distance between floor levels Vertical Distance between floor levels Vertical Distance between floor levels
and landings - 12 feet. and landings - 12 feet. and landings - 12 feet. and landings - 12 feet.
(1009.7) (Table 7.2.2.2.1(a)) (Table 7.2.2.2.1.1(a)) (Table 7.2.2.2.1.1(a))
153 Headroom 80 inches 80 inches 80 inches 80 inches
(1009.2) (Table 7.2.2.2.1(a)) (Table 7.2.2.2.1(a)) (Table 7.2.2.2.1(a))
154 Handrails Circular Diameter minimum 1-1/4 Circular Diameter minimum 1-1/4 Circular Diameter minimum 1-1/4 Circular Diameter minimum 1-1/4
(Note: Shall also coordinate with inches max 2 inches inches max 2 inches inches max 2 inches inches max 2 inches
TAS requirements: minimum 1-1/4 (1012.3.1) (7.2.2.4.5) (7.2.2.4.4.6) (7.2.2.4.4.6)
inches max 1-1/2 inches, 4.26.2)
155 Height - minimum 34 inches Height - minimum 34 inches Height - minimum 34 inches Height - minimum 34 inches
maximum 38 inches maximum 38 inches maximum 38 inches maximum 38 inches
(1012.2) (7.2.2.4.5) (7.2.2.4.4.1) (7.2.2.4.4.1)
156 Clear space to wall - 1-1/2 inches Clear space to wall - 1-1/2 inches Clear space to wall - 2-1/4 inches Clear space to wall - 2-1/4 inches
(1012.7) (7.2.2.4.5) (7.2.2.4.4.5) (7.2.2.4.4.5)
157 Intermediate handrails are required Intermediate handrails are required Intermediate handrails are required Intermediate handrails are required
so that all portions of the stairway are so that all portions of the stairway are so that all portions of the stairway are so that all portions of the stairway are
within 30 inches of the handrail. within 30 inches of the handrail. within 30 inches of the handrail. within 30 inches of the handrail.
(1012.9) (7.2.2.4.1) (7.2.2.4.1.2) (7.2.2.4.1.2)
158 Guardrails Height - 42 inches Height - 42 inches Height - 42 inches (7.2.2.4.5.2) Height - 42 inches (7.2.2.4.5.2)
required along open-sided walking (1013.2) (7.2.2.4.6(2))
surfaces, mezzanines, stairways,
ramps and landings
159 Open guardrails shall have Open guardrails shall have Open guardrails shall have Open guardrails shall have
intermediate rails or an ornamental intermediate rails or an ornamental intermediate rails or an ornamental intermediate rails or an ornamental
pattern such that a sphere 4 inches in pattern such that a sphere 4 inches in pattern such that a sphere 4 inches in pattern such that a sphere 4 inches in
diameter cannot pass through up to diameter cannot pass through up to diameter cannot pass through up to diameter cannot pass through up to
34 inches in height and a sphere 4- 34 inches in height. 34 inches in height 34 inches in height
3/8 inches in diameter cannot pass (7.2.2.4.6) (7.2.2.4.5.3) (7.2.2.4.5.3)
through at any point 36-42 inches in
height.
(1013.3)
Page 16 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
160 Stairway Signage Signs must be located at each floor N/A Signs must be located at each floor Signs must be located at each floor
level in all enclosed stairways serving level in all enclosed stairways serving level in all enclosed stairways serving
3 or more stories. The signs must 3 or more stories. The signs must 3 or more stories. The signs must
identify the story of and direction to identify the stairway access, floor identify the stairway access, floor
exit discharge, floor level, and the level, and the upper and lower level, and the upper and lower
upper and lower terminus of the terminus of the stairway. terminus of the stairway.
stairway. Sign shall be located 5 feet (7.2.2.5.4.1 A-M) (7.2.2.5.4.1 A-M)
above the floor landing in a position
readily visible when the door is in the
open and closed positions. See
Section 1022.8.1 for specific signage
requirements.
(1022.8)
Page 17 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
172 Horizontal exits in a corridor 6 feet or N/A (18.2.2.5.5) (18.2.2.5.5) (18.2.2.5.5)
more and serving as an exit from both
sides must have a pair of opposite
swinging doors with a clear width of
no less than 32 inches.
180 Smoke barriers must be provided on Other stories with an occupant load (18.3.7.2) N/A N/A
stories that are useable, even if of 50 or more must be divided into at See 18.3.7.2 See 18.3.7.2
unoccupied. least two smoke compartments.
(407.4)
182 Minimum clear width for individual N/A 41.5 inches 41.5 inches 41.5 inches
smoke barrier doors (18.3.7.5) (18.3.7.6) (18.3.7.6)
183 Doors must be self-closing or N/A (18.3.7.6) (18.3.7.8) (18.3.7.8)
automatic
184 Vision panels with fire-rated glazing N/A (18.3.7.7) (18.3.7.9) (18.3.7.9)
or wired glass at each cross corridor
door
Page 18 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
187 Duct penetrations of smoke (716.5.5) (8.3.5.1) (8.5.5.2) (8.5.5.2)
compartment walls must be protected
by smoke dampers.
188 Smoke dampers are not required in (716.5.5) (8.3.5.1 (8.5.5.3) (8.5.5.3)
smoke barriers where steel duct Exception 3)
openings are limited to one
compartment
189 Smoke dampers are not required in N/A (18.3.7.3 (18.3.7.3(2)) (18.3.7.3(2))
smoke barriers with fully ducted Exception 3)
HVAC systems.
199 Illumination Minimum of 5 foot-candles. Externally illuminated by not less Externally illuminated by not less Externally illuminated by not less
(1011.5.2) than 5 foot-candles than 5 foot-candles or internally than 5 foot-candles or internally
(7.10.6.3) illuminated in accordance with UL illuminated in accordance with UL
924 Standard for Emergency Lighting 924 Standard for Emergency Lighting
and Power Equipment and Power Equipment
(7.10.6.3) (7.10.6.3)
200 Listing Shall be installed in accordance with The face of a photoluminescent sign The face of a photoluminescent sign The face of a photoluminescent sign
its listing. shall be continually illuminated while shall be continually illuminated while shall be continually illuminated while
(1011.4) the building is occupied. Illumination the building is occupied. Illumination the building is occupied. Illumination
level shall be in accordance with its level shall be in accordance with its level shall be in accordance with its
listing. listing. listing.
(7.10.7.2) (7.10.7.2) (7.10.7.2)
201 Emergency Power Shall be connected to an emergency Must be connected to an emergency Must be connected to an emergency Must be connected to an emergency
power system electrical system in accordance with electrical system in accordance with electrical system in accordance with
(1011.5.3) the Electric Code. the Electric Code. the Electric Code.
(7.10.4 ) (7.10.4 ) (7.10.4 )
Page 19 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
202 Emergency Power Duration 90 minutes in case of primary power 90 minutes in case of primary power 90 minutes in case of primary power 90 minutes in case of primary power
loss. loss. loss. loss.
(1011.5.3) (7.9.2.1) (7.9.2.1) (7.9.2.1)
203 Tactile Exit Signs Required at each door to an egress Shall be provided at each exit door Shall be provided at each exit door Shall be provided at each exit door
stairway, exit passageway & exit requiring an exit sign and comply requiring an exit sign and comply requiring an exit sign and comply
discharge. with ICC/ANSI A117.1 with ICC/ANSI A117.1 with ICC/ANSI A117.1
(1011.3) (7.10.1.3) (7.10.1.3) (7.10.1.3)
206 Smoke compartments containing (903.3.2) (18.3.5.2) (18.3.5.6) Stated in Appendix 18.3.5.6 that
sleeping rooms must used listed quick residential sprinklers are
response sprinklers. considered acceptable in patient
sleeping rooms even though not
specifically listed for this purpose.
Page 20 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
217 Outside Window or Door N/A Every patient sleeping room shall Outside window is not required. Outside window is not required.
have an outside window or door.
The allowable sill height shall not
exceed 36 inches above the floor.
(18.3.8)
218 Emergency Power System An on-site power generator system is An on-site power generator system is An on-site power generator system is
Requirements required. required. required.
(18.5.1.2 (18.5.1.2 (18.5.1.2
NFPA 99) NFPA 99) NFPA 99)
219 The emergency system is limited to The emergency system is limited to The emergency system is limited to
circuits essential to life safety and circuits essential to life safety and circuits essential to life safety and
critical patient care and are critical patient care and are critical patient care and are
designated the life safety branch and designated the life safety branch and designated the life safety branch and
critical branch critical branch critical branch
(NFPA 99 3-4.2.2.2) (NFPA 99 3-4.4.2.2.2.1) (NFPA 99 3-4.4.2.2.2.1)
220 Laboratories in Health care Must be below exempt amount per Total volume of Class I, II and IIIA Total volume of Class I, II and IIIA Total volume of Class I, II and IIIA
Occupancies Table 307.1(1) & (2) liquids outside of approved storage liquids outside of approved storage liquids outside of approved storage
(307.1, Exception 1) cabinets and safety cans shall not cabinets and safety cans shall not cabinets and safety cans shall not
exceed 1 gal per 100 sf. exceed 1 gal per 100 sf. exceed 1 gal per 100 sf.
(NFPA 99: 10-7.2.2) (NFPA 99:11-7.2.3.1) (NFPA 99:11-7.2.3.1)
221 N/A At least one approved flammable or At least one approved flammable or At least one approved flammable or
combustible liquid storage room shall combustible liquid storage room shall combustible liquid storage room shall
be available within any health care be available within any health care be available within any health care
facility regularly maintaining a facility regularly maintaining a facility regularly maintaining a
reserve storage capacity of in excess reserve storage capacity of in excess reserve storage capacity of in excess
of 300 gal of 300 gal of 300 gal
(NFPA 99: 10-7.2.2) (NFPA 99: 11-7.2.3.4) (NFPA 99: 11-7.2.3.4)
222 N/A Flammable gas cylinder storage for a Flammable gas cylinder storage for a Flammable gas cylinder storage for a
laboratory shall be separated from laboratory shall be separated from laboratory shall be separated from
the health care facility. the health care facility. the health care facility.
2 hours 2 hours 2 hours
(NFPA 99: 10-10.2.2) (NFPA 99: 11-10.2.2) (NFPA 99: 11-10.2.2)
223 N/A Rooms or enclosures for storage of Rooms or enclosures for storage of Rooms or enclosures for storage of
gas cylinders shall be well ventilated gas cylinders shall be well ventilated gas cylinders shall be well ventilated
(NFPA 99:10-10.2.3) (NFPA 99: 11-10.3.2) (NFPA 99: 11-10.3.2)
224 Total quantity and size of cylinders Total quantity and size of cylinders Total quantity and size of cylinders
shall comply with Table 8-1 of NFPA shall comply with Table 8-1 of NFPA shall comply with Table 8-1 of NFPA
45. 45. 45.
(NFPA 99: 10-10.3) (NFPA 99: 11-10.3) (NFPA 99: 11-10.3)
Page 21 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
227 N/A Oxidizing gases shall be separated Oxidizing gases shall be separated Oxidizing gases shall be separated
from combustible or incompatible from combustible or incompatible from combustible or incompatible
materials by a minimum of 20 feet or materials by a minimum of 20 feet or materials by a minimum of 20 feet or
5 feet if the storage area is provided 5 feet if the storage area is provided 5 feet if the storage area is provided
with automatic sprinklers. with automatic sprinklers. with automatic sprinklers.
(NFPA 99: 8-3.1.11.2) (NFPA 99: 9.4.1) (NFPA 99: 9.4.1)
228 Alcohol Based Hand Rub (ABHR) N/A The corridor width is 6 feet or greater The corridor width is 6 feet or greater The corridor width is 6 feet or greater
Dispensers and dispensers are at least 4 feet apart and dispensers are at least 4 feet apart (18.3.2.6(1))
(Joint Commission) (18.3.2.6(1))
229 N/A The dispensers shall not be installed The dispensers shall not be installed The dispensers shall not be installed
over or directly adjacent to electrical over or directly adjacent to electrical over or directly adjacent to electrical
outlets and switches. Adjacent is outlets and switches. Adjacent is outlets and switches. Adjacent is
defined as being no closer than 6 defined as being no closer than 1 defined as being no closer than 1
inches from the center of the inches from each side of the inches from each side of the
dispenser to either side. dispenser. dispenser.
(Joint Commission) (18.3.2.6(7)) (18.3.2.6(8))
230 N/A In locations with carpeted floor In locations with carpeted floor In locations with carpeted floor
coverings, dispensers installed coverings, dispensers installed coverings, dispensers installed
directly over carpeted surfaces are directly over carpeted surfaces are directly over carpeted surfaces are
permitted only in sprinklered smoke permitted only in sprinklered smoke permitted only in sprinklered smoke
compartments. compartments. compartments.
(Joint Commission) (18.3.2.6(8)) (18.3.2.6(9))
231 N/A Each smoke compartment may Each smoke compartment may Each smoke compartment may
contain a maximum aggregate of 10 contain a maximum aggregate of 10 contain a maximum aggregate of 10
gallons (37.8 liters) of ABHR product gallons (37.8 liters) of ABHR product gallons (37.8 liters) of ABHR product
in dispensers and a maximum of 5 in dispensers and a maximum of 5 in dispensers and a maximum of 5
gallons (18.9 liters) in storage. gallons (18.9 liters) in storage. gallons (18.9 liters) in storage.
(Joint Commission) (18.3.2.6(5&6)) (18.3.2.6(6&7))
232 N/A The maximum individual dispenser The maximum individual dispenser The maximum individual dispenser
fluid capacity is 1.2 liters for fluid capacity is 1.2 liters for fluid capacity is 1.2 liters for
dispensers in rooms, corridors, and dispensers in rooms, corridors, and dispensers in rooms, corridors, and
areas open to corridors. areas open to corridors. areas open to corridors.
(Joint Commission) (18.3.2.6(2a)) (18.3.2.6(2a))
233 N/A The maximum individual dispensers The maximum individual dispensers The maximum individual dispensers
in suites of rooms is 2.0 liters in suites of rooms is 2.0 liters in suites of rooms is 2.0 liters
(Joint Commission) (18.3.2.6(2b)) (18.3.2.6(2b))
Page 22 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
234 Cooking Facilities Residential cooking equipment
used for food warming or limited
cooking not required to be protected
as a hazardous area.
(18.3.2.5.2)
Where protected in accordance with
9.2.3 cooking equipment area shall
not be considered hazardous.
Should be separated from corridor.
(18.3.2.5.5)
Page 23 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
235 1) portion of healthcare facility
served by cooking facility is limited
to 30 beds and separated from other
portions of the facility by a smoke
barrier.
2) cooktop or range is equipped
with a range hood with a minimum
width equal to width of cooking
surface with grease baffles or other
grease collecting and clean out
capability.
3) Hood systems provided with a
minimum airflow of 500 cfm
4) hood systems that are no ducted
to the exterior additionaly have a
charcoal filter to remove smoke and
odor.
5) cooktop or range is protected with
a fire suppression system listed in
accordance with UL 300 and meets
all requirements of UL 300A.
Should be provided with a manual
release
Page 24 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
236 extinguishing system in accordance
with NFPA 96 and an interlock to
turn off all fuel sources and
electrical power when suppression
system is activated.
6) Solid fuel for the use of cooking
is not permitted
7) Deep fat frying is not permitted
8) Portable fire extinguishers shall
be provided in all kitchen areas
9) A locked switch, or located within
a restricted location, shall be
provided that can deactivate the
cooking equipment whenever
kitchen is not under staff
supervision, can be set on a timer
that deactivates cooking equipment
regardless of staff action. Timer
shall not exceed 120 minutes.
10) Procedures for the use,
inspection, testing, and maintenance
of cooking equipment shall be in
accordance with NFPA 96 and
manufacturer's instructions.
Page 25 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
238 FirePlaces Vent gas fireplaces are permitted in
smoke compartments containing
sleeping areas provided that:
1) all devices are installed,
maintained, and used in accordance
with 9.2.2
2) No direct device is located within
a patient sleeping room
3) Smoke compartment where
fireplace is located is protected by
an approved supervised automatic
sprinkler system with listed quick-
response or residential sprinklers.
4) Direct vent fireplace includes a
sealed glass fron with a wire mesh
panel or screen.
5) controls for direct vent fireplace
are locked or located within
restricted area.
6) electrically supervised carbon
monoxide detection in accordance
with Section 9.8 provided in room
fireplace is present.
(18.5.2.3)
Page 26 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
245 NOTE: There are 4 exceptions which N/A N/A N/A
may exempt a walkway from
requiring 2-hour fire barriers.
(3104.5)
246 Public Way The exit discharge shall provide a Every smokeproof enclosure shall Every smokeproof enclosure shall Every smokeproof enclosure shall
direct and unobstructed access to a discharge into a public way discharge into a public way discharge into a public way
public way (7.2.3.5) (7.2.3.5) (7.2.3.5)
(1027.6)
247 Egress Access must be available at all times N/A N/A N/A
for pedestrian walkways used as
egress.
(3104.7)
249 Exit Access Travel Distance 200 feet N/A N/A N/A
Exceptions:
1. With NFPA 13 sprinkler - 250 feet
2. Open both sides at least 50% - 300
feet
3. Open on both sides 50% & NFPA
13 sprinkler system - 400 feet
(3104.9)
252 Elevators
253 Hoistway enclosure Enclosure protection per Section 708 N/A N/A N/A
(3002.1)
Page 27 of 28
4/22/2011 NEW BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Code Category Component/Requirement 2009 IBC 2000 Edition NFPA 101 LSC 2009 Edition NFPA 101 LSC 2012 Edition NFPA 101 LSC
260 Machine Rooms (3306)
261 Machine Room Access (3006.1) N/A N/A N/A
262 Machine Room Venting Independent venting required for N/A N/A N/A
solid-state equipment.
(3006.2)
263 Machine Room Pressurization Required if hoistway is pressurized N/A N/A N/A
via activation of a heat or smoke
detector in the machine
(3006.3)
264 Shunt trip Required where protected by fire N/A N/A N/A
sprinkler system per NFPA 72 Section
6.16.4
(3006.5)
Page 28 of 28
4/22/2011 NEW BUILDINGS
CODE SUMMARY HEALTH CARE EXISTING BUILDINGS
13 Unlimited Areas Spaces off N/A Spaces shall be permitted to be Spaces shall be permitted to be Spaces shall be permitted to be
Corridors unlimtied in area and open to unlimtied in area and open to unlimtied in area and open to the
the corridor, provided that the corridor, provided that corridor, provided that
sections 19.3.6.1(1)(a) through compartments are sprinklered compartments are sprinklered and
19.3.6.1(1)(d) are met and comply with Sections comply with Sections 19.3.6.1(1)(a)
(19.3.6.1(1)) 19.3.6.1(1)(a) through through 19.3.6.1(1)(d) are met
19.3.6.1(1)(d) are met (19.3.6.1(1))
(19.3.6.1(1))
14 Nurses' Stations off Corridors N/A Nurse stations do not need to be Nurse stations do not need to be Nurse stations do not need to be
separated separated separated
(19.3.6.1(3)) (19.3.6.1(3)) (19.3.6.1(3))
Page 1 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
17 Smoke Compartment Size N/A Compartment sizes may not Compartment sizes may not Compartment sizes may not exceed
exceed 22,500 s.f. and the travel exceed 22,500 s.f. and the travel 22,500 s.f. and the travel distance
distance from any point in a distance from any point in a from any point in a smoke
smoke compartment to a smoke smoke compartment to a smoke compartment to a smoke barrier
barrier door may not exceed 200 barrier door may not exceed 200 door may not exceed 200 feet. If the
feet. Smoke barriers must feet. If the length and width of length and width of the corridor is
comply with Section 8.3 and be the corridor is less than 150 feet, less than 150 feet, the travel distance
no less than 1 hour rated the travel distance is unlimited. is unlimited. Smoke barriers must
(19.3.7.1 and 19.3.7.3) Smoke barriers must comply comply with Section 8.5 and be no
with Section 8.5 and be no less less than 1/2 hour rated
than 1/2 hour rated (19.3.7.1 through 19.3.7.3)
(19.3.7.1 through 19.3.7.3)
18 Smoke Compartment Refuge N/A Provide at least 30 net sq. feet Provide at least 30 net sq. feet Provide at least 30 net sq. feet per
Area per patient within corridors, per patient within corridors, patient within corridors, patient
patient rooms, lounge or dining , patient rooms, lounge or dining , rooms, lounge or dining , other low
other low hazard areas on each other low hazard areas on each hazard areas on each side of the
side of the smoke barrier. side of the smoke barrier. smoke barrier.
(19.3.7.4) (19.3.7.5.1) (19.3.7.5.1)
19 N/A For floors not housing bed or For floors not housing bed or For floors not housing bed or litter
litter patients , provide 6 net litter patients , provide 6 net patients , provide 6 net square feet
square feet per occupant on each square feet per occupant on each per occupant on each side of smoke
side of smoke barrier for the side of smoke barrier for the barrier for the total number of
total number of occupants in total number of occupants in occupants in adjoining smoke
adjoining smoke compartments. adjoining smoke compartments. compartments.
(19.3.7.4) (19.3.7.5.2) (19.3.7.5.2)
Page 2 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
21 Smoke Compartment Sprinkler N/A Listed quick-response or listed Listed quick-response or listed Listed quick-response or listed
System residential sprinklers shall be residential sprinklers shall be residential sprinklers shall be used
used throughout smoke used throughout smoke throughout smoke compartments
compartments containing compartments containing containing patient sleeping areas
patient sleeping areas patient sleeping areas (19.3.5.8(5) - See Appendix)
(19.3.5.3(4) - See Appendix) (19.3.5.8(5) - See Appendix)
Page 3 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
24 Smoke Barriers N/A 1/2-hour smoke barrier 1/2-hour smoke barrier 1/2-hour smoke barrier
(19.3.7.3) (19.3.7.3) (19.3.7.3)
25 Smoke Barriers N/A Smoke barriers must be Smoke barriers must be Smoke barriers must be continuous
continuous from wall to wall, continuous from wall to wall, from wall to wall, barrier to barrier,
barrier to barrier, or from floor barrier to barrier, or from floor or from floor to floor and through
to floor and through concealed to floor and through concealed concealed spaces.
spaces. spaces. (8.5.2)
(8.3.2) (8.5.2)
26 Shaft Enclosures Vertical Openings protecting 2 2-hour fire barrier 2-hour fire barrier 2-hour fire barrier
(Connecting 4 or More Stories) or more stories must be (8.2.5.4(1)) (8.6.5(3)) (8.6.5(3))
protected with 1-hour rated
construction
(4603 3 1)
27 Shaft Enclosures Vertical Openings protecting 2 1/2-hour fire barrier Connecting 1/2-hour fire barrier Connecting 1/2-hour fire barrier Connecting up
(Connecting 3 Stories or Less) or more stories must be up to 3 stories (8.2.5.4(2)) up to 3 stories to 3 stories
protected with 1-hour rated (8.6.5(3)) (8.6.5(3))
construction
(4603 3 1)
28 Exit Stair Enclosures Vertical Openings protecting 2 2-hour fire barrier 1-hour fire barrier 1-hour fire barrier
(Connecting 4 or more Stories) or more stories must be (7.1.3.2.1(b)) (7.1.3.2.1(2a/b)) (7.1.3.2.1(2a/b))
protected with 1-hour rated
construction
(4603 3 1)
29 Exit Stair Enclosures Vertical Openings protecting 2 1-hour fire barrier (7.1.3.2.1(a)) 1-hour fire barrier (7.1.3.2.1(1)) 1-hour fire barrier (7.1.3.2.1(1))
(Connecting 3 Stories or Less) or more stories must be
protected with 1-hour rated
construction
(4603 3 1)
Page 4 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
31 Horizontal Exit wall N/A 2-hour fire barrier and barrier 2-hour fire barrier must 2-hour fire barrier must continue to
must continue to grade level continue to grade level unless grade level unless all stairs
unless all stairs discharge all stairs discharge directly to discharge directly to outside and
directly to outside and floor outside and floor with floor with horizontal exit does not
with horizontal exit does not horizontal exit does not have an have an unprotected vertical
have an unprotected vertical unprotected vertical opening. opening.
opening. (7.2.4.3.1 and 7.2.4.3.3) (7.2.4.3.1 and 7.2.4.3.3)
(7.2.4.3.1)
32 Horizontal Exit Opening N/A 1- 1/2 hours 1- 1/2 hours 1- 1/2 hours
Protection (doors) (8.2.3.2.3) (Table 8.3.4.2) (Table 8.3.4.2)
33 Permitted Unprotected Floor N/A Communicating space is Permitted provided the Permitted provided the following:
Openings. permitted by 18.3.1.1 following: 1. Connects no more than two
Unprotected floor openings 1. Connects no more than two adjacent floors
( Unless permitted by the code permitted provided: adjacent floors 2. Is separated from floor openings
all floor openings to be 1. Conects no more than 2 2. Is separated from floor serving other floors
protected as noted above for a adjacent stories openings serving other floors 3. Opening is separated from
shaft.) 2. Is separated from floor 3. Opening is separated from corridors
(711) opening serving other floors corridors 4. Convenience openings shall be
3. Separated from corridors 4. Convenience openings shall separated from by a smoke partition.
4. Shall not serve as a required be separated from by a smoke 4. Opening is not part of a required
means of egress partition. exit path.
(8.2.5.5) 4. Opening is not part of a (8.6.8.2)
required exit path.
(8.6.8.2)
34 Horizontal Assemblies N/A N/A N/A N/A
37 Elevator Lobbies N/A Every floor served by the Every floor served by the Every floor served by the elevator
elevator shall have an elevator elevator shall have an elevator shall have an elevator lobby and
lobby and form a 1-hour barrier lobby and form a 1-hour barrier form a 1-hour barrier in accordance
in accordance with 8.3 in accordance with 8.5 with 8.5
(7.2.13.3) (7.2.13.3) (7.2.13.3)
Page 5 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Page 6 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
43 2- hour Elevator Hoistways Vertical Openings protecting 2 1-1/2 hour 1-1/2 hour 1-1/2 hour
or more stories must be (8.2.3.2.3.1) (Table 8.3.4.2) (Table 8.3.4.2)
protected with 1-hour rated
construction
(4603 3 1)
44 1- hour Elevator Hoistways Vertical Openings protecting 2 1-hour 1-hour 1-hour
or more stories must be (8.2.3.2.3.1) (Table 8.3.4.2) (Table 8.3.4.2)
protected with 1-hour rated
construction
(4603 3 1)
45 2-hour Vertical Shafts (including Vertical Openings protecting 2 1-1/2 hour 1-1/2 hour 1-1/2 hour
stairways, exits, and chutes) or more stories must be (8.2.3.2.3.1) (Table 8.3.4.2) (Table 8.3.4.2)
protected with 1-hour rated
construction
(4603 3 1)
46 1-hour Vertical Shafts (including Vertical Openings protecting 2 1-hour 1-hour 1-hour
stairways, exits, and chutes) or more stories must be (8.2.3.2.3.1) (Table 8.3.4.2) (Table 8.3.4.2)
protected with 1-hour rated
construction
(4603 3 1)
47 1/2-hour vertical shafts Vertical Openings protecting 2 No Requirement 1/3-hour 1/3-hour
(including stairways, exits, and or more stories must be (Table 8.3.4.2) (Table 8.3.4.2)
chutes) protected with 1-hour rated
construction
(4603 3 1)
48 2- hour Fire Barriers N/A 1-1/2 hour 1-1/2 hour 1-1/2 hour
(8.2.3.2.3.1) (Table 8.3.4.2) (Table 8.3.4.2)
49 1- hour Fire Barriers N/A 45 minutes 45 minutes 45 minutes
(8.2.3.2.3.1) (Table 8.3.4.2) (Table 8.3.4.2)
50 1/2-hour Fire Barriers N/A ? 1/3-hour 1/3-hour
(Table 8.3.4.2) (Table 8.3.4.2)
Page 7 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Page 8 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
56 Non-separated Uses N/A Occupancy separation is not Occupancy separation is not Occupancy separation is not
required when the entire required when the entire required when the entire building
building meets the most building meets the most meets the most restrictive
restrictive requirements of each restrictive requirements of each requirements of each individual
individual occupancy. individual occupancy. occupancy.
(A3.3.134.10 and 6.1.14.2) (6.1.14.3.2) (6.1.14.3.2)
57 Boiler and fuel-fired heater N/A 1 hour 1-Hour Fire Barrier or 1-Hour Fire Barrier or automatic
rooms (Table 19.3.2.1) automatic extinguishing system extinguishing system
(19.3.2.1) (19.3.2.1)
58 Central/bulk laundries more N/A 1 hour Fire Barrier or automatic 1-Hour Fire Barrier or 1-Hour Fire Barrier or automatic
than 100 sf extinguishing system automatic extinguishing system extinguishing system
(Table 19.3.2.1) (19.3.2.1) (19.3.2.1)
59 Laboratories employing N/A Smoke tight and self-closing 1-Hour Fire Barrier or 1-Hour Fire Barrier or automatic
flammable or combustible (19.3.2.1) automatic extinguishing system extinguishing system and smoke
materials in quantities less than and smoke partitions partitions
that which would be considered (19.3.2.1 and 19.3.2.1.2) (19.3.2.1 and 19.3.2.1.2)
severe.
61 Paint Shops 1-Hour Fire Barrier or 1-Hour Fire Barrier or 1-Hour Fire Barrier or automatic
automatic extinguishing system automatic extinguishing system extinguishing system and smoke
and smoke partitions and smoke partitions partitions
(19.3.2.1) (19.3.2.1 and 19.3.2.1.2) (19.3.2.1 and 19.3.2.1.2)
Page 9 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
65 Refuse(waste) & Laundry N/A See Section 9.5 Existing chutes that open Existing chutes that open directly to
Chutes Chute charging or discharging directly to a corridor shall be a corridor shall be permanently
room require max 1-hour fire permanently sealed to prevent sealed to prevent further use by fire
rating. further use by fire resistive resistive construction or a 1-hour
Enclosed by walls or partitions construction or a 1-hour fire fire door shall be installed. Chute
in accordance with 8.2. Inlet door shall be installed. Chute must be protected by sprinkler
openings in accordance with 8.2. must be protected by sprinkler system. Any flue-fed incinerators
Installed and maintained in system. Any flue-fed shall be sealed by fire resistive
accordance with NFPA 82: incinerators shall be sealed by construction to prevent further use.
Standard on Incinerators and fire resistive construction to Shall comply with NFPA 82.
Waste Linen Handling Systems prevent further use. Shall (19.5.4)
and Equipment. comply with NFPA 82
(9.5 and 19.5.4) (19.5.4)
66 N/A Any trash chute chute shall Any trash chute chute shall Existing laundry chutes may
discharge into a trash collection discharge into a trash collection discharge into same room as
room used for no ther purpose room used for no ther purpose rubbish discharge chutes provided
and protected in accordance and protected in accordance discharge room is protected by
with section 8.4 with section 8.4 automatic sprinklers.
(19.5.4.3) (19.5.4.4)
67 Storage rooms greater than 50 sf N/A 1-Hour Fire Barrier or 1-Hour Fire Barrier or 1-Hour Fire Barrier or automatic
of combustible materials automatic extinguishing system automatic extinguishing system extinguishing system and smoke
and smoke partitions and smoke partitions partitions
(19.3.2.1) (19.3.2.1 and 19.3.2.1.2) (19.3.2.1 and 19.3.2.1.2)
68 Gift shops less than 500 sf and N/A No separation required. No separation required from No separation required from
not considered hazardous (19.3.2.5) corridor required. corridor required.
(19.3.6.1(4)) (19.3.6.1(4))
69 Gift shops more than 500 sf and N/A Separated from the corridor by Separated from the corridor by Separated from the corridor by non
not considered hazardous non fire rated walls. Must be non fire rated walls. fire rated walls.
protected by sprinkler system (19.3.6.1) (19.3.6.1)
(19.3.2.5)
70 Gift shops with combustible N/A 1 hour 1 hour barrier or automatic 1 hour barrier or automatic
loading considered hazardous (8.4.1.1) extinguishing system extinguishing system
(8.7.1) (8.7.1)
Page 10 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
75 Interior Wall & Finish Systems N/A May comply with NFPA 355 or In accordance with ASTEM E84 In accordance with ASTEM E84 or
286 or ANSI/UL 723 ANSI/UL 723
(10.2.3) (10.2.3) (10.2.3)
76 Interior Wall Finish Based on N/A Permitted throughout if Class A Permitted throughout if Class A Permitted throughout if Class A or B
Group I-2 or B and compliant with 10.2.3 or B and compliant with 10.2 in and compliant with 10.2 in corridor
in corridor separated rooms corridor separated rooms separated rooms
(19.3.3.2) (19.3.3.2) (19.3.3.2)
77 Maximum smoke developed N/A 0-450 0-450 0-450
(Table A.10.2.2) (Table A.10.2.2) (Table A.10.2.2)
78 Maximum flame spread for N/A Class A: 0-25 Class A: 0-25 Class A: 0-25
vertical exitways, access Class B: 26-75 Class B: 26-75 Class B: 26-75
corridors, other exits, rooms and Class C: 76-200 Class C: 76-200 Class C: 76-200
enclosed spaces, textile wall (Table A.10.2.2) (Table A.10.2.2) (Table A.10.2.2)
coverings
79 Textiles N/A See 10.2.4.1 See 10.2.4.1 See 10.2.4.1
(Wall & Ceiling Finish)
80 Interior Floor Finish N/A No Requirement No Requirement No Requirement
(19.3.3.3) (19.3.3.3) (19.3.3.3)
81 Helistops N/A
82 Size N/A N/A N/A N/A
83 Design N/A N/A N/A N/A
84 Means of egress N/A N/A N/A N/A
85 Rooftop N/A N/A N/A N/A
86 Exit Capacity
87 Stairways 0.3 inches per occupant 0.3 inches per occupant 0.3 inches per occupant 0.3 inches per occupant
(Table 4604.7) (Table 7.3.3.1) (Table 7.3.3.1) (Table 7.3.3.1)
88 Other egress components 0.3 inches per occupant 0.2 inches per occupant (Table 0.2 inches per occupant (Table 0.2 inches per occupant (Table
(Table 4604.7) 7.3.3.1) 7.3.3.1) 7.3.3.1)
89 Occupant Load Factors
Page 11 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Page 12 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
109 Dead ends No Requirement Maximum of 30 feet. Existing Maximum of 30 feet. Existing Maximum of 30 feet. Existing
(Table 4604.18.2) corridors can extend further corridors can extend further corridors can extend further than 30
than 30 feet if it is unfeasible to than 30 feet if it is unfeasible to feet if it is unfeasible to alter them.
alter them. alter them. (19.2.5.2)
(19.2.5.10) (19.2.5.2)
Page 13 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
112 Suites of sleeping rooms N/A Shall not exceed 7,500 sf if in Shall not exceed 7,500 sf if in direct
direct visual supervision, have visual supervision, have total smoke
total smoke coverage, and total coverage, and total sprinkler
sprinkler coverage. coverage.
(19.2.5.7.2.3(B)) (19.2.5.7.2.3(B))
113 Suites of rooms other than N/A Shall not exceed 10,000 sf Shall not exceed 10,000 sf Shall not exceed 10,000 sf
patient sleeping rooms (19.2.5.7) (19.2.5.7.3.3) (19.2.5.7.3.3)
114 Hazardous areas within suites N/A N/A See 19.2.5.7.1.3 See 19.2.5.7.1.3
options
115 Intervening rooms other than N/A One intervening room is One intervening room is One intervening room is allowed if
patient sleeping rooms. allowed if the travel distance allowed if the travel distance the travel distance within the suite
within the suite to the exit within the suite to the exit to the exit access door does not
access door does not exceed 100 access door does not exceed 100 exceed 100 feet and two intervening
feet and two intervening rooms feet and two intervening rooms rooms are permitted where the
are permitted where the travel are permitted where the travel travel distance to the exit access
distance to the exit access door distance to the exit access door door does not exceed 50 feet.
does not exceed 50 feet. does not exceed 50 feet. (19.2.5.7.3.4(A))
(19.2.5.8) (19.2.5.7.3.4(A))
Page 14 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
117 Special Nursing Suites N/A May have one intervening room N/A
where the arrangement allows
for direct and constant visual
supervision by nursing
personnel.
(19.2.5.1(3))
118 Egress into another suite N/A N/A A suite that requires two means A suite that requires two means of
of egress is premitted have one egress is premitted have one means
means of egress to be into of egress to be into another suite,
another suite, provided that the provided that the separation
separation between the suite between the suite complies with
complies with 19.3.6.2 through 19.3.6.2 through 19.3.6.5
19.3.6.5 (19.2.5.7.2.2(C))
(19.2.5.7.2.2(C))
119 Exit Access from a Corridor N/A Every corridor shall provide Every corridor shall provide Every corridor shall provide access
access to at least two exits access to at least two exits to at least two exits without passing
without passing through any without passing through any through any intervening rooms or
intervening rooms or spaces intervening rooms or spaces spaces other than corridors or
other than corridors or lobbies. other than corridors or lobbies. lobbies.
(19.2.5.9) (19.2.5.4) (19.2.5.4)
Page 15 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
128 Doors
129 Minimum clear width serving 41.5 inches 34 inches 34 inches 34 inches
sleeping rooms, diagnostic and (4604.8) (19.2.3.5(1)) (19.2.3.7) (19.2.3.7)
treatment rooms
130 Minimum clear width all other 28 inches clear width 28 inches clear width 28 inches clear width for doors 28 inches clear width for doors not
areas (4604.8) (19.2.3.5(2)) not requiring evacuation of requiring evacuation of beds,
beds, gurneys, or wheelchairs. gurneys, or wheelchairs.
(19.2.3.7) (19.2.3.7)
131 Minimum Height 80 inches 84 inches 84 inches 84 inches
(4604.8) (7.1.5(1)) (7.1.5.1) (7.1.5.1)
132 Door Swing N/A Doors in the direction of egress Doors in the direction of egress Doors in the direction of egress
Doors should be of the side 7.2.1.4.1 7.2.1.4.1 7.2.1.4.1
hinged swinging type.
133 Swing in direction of exit travel N/A (7.2.1.4.2 and 7.2.1.4.3) (7.2.1.4.2) (7.2.1.4.2)
when serving high hazardous
area or serving an occupant load
greater than 50.
134 Exit door shall be openable from N/A (7.2.1.5.1 / 19.2.2.2.4) (7.2.1.5.1 / 7.2.1.5.2 / 19.2.2.2.4) (7.2.1.5.1 / 7.2.1.5.2 / 19.2.2.2.4)
the inside without the use of key
locking device
135 Bolt locks are generally N/A N/A N/A N/A
prohibited except for storage or
equipment rooms.
Page 16 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Page 17 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Page 18 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
145 Stairways
146 Risers Maximum 8-1/4 inches Maximum 8 inches; Maximum 8 inches Maximum 8 inches
(4604.11) (Table 7.2.2.2.1(b)) (Table 7.2.2.2.1.1(b)) (Table 7.2.2.2.1.1(b))
147 Treads Maximum 9 inches Minimum 10 or 9 inches Minimum 9 inches Minimum 9 inches
(4604.11) (Table 7.2.2.2.1(b)) (Table 7.2.2.2.1.1(b)) (Table 7.2.2.2.1.1(b))
148 Width N/A Minimum 44 inches or 36 inches 36 inches minimum width clear 36 inches minimum width clear of
if serving fewer than 50 people of all obstructions, except all obstructions, except projections
(Table 7.2.2.2.1(b)) projections not more than 4-1/2 not more than 4-1/2 inches at or
inches at or below handrail below handrail height on each side
height on each side (Table 7.2.2.2.1.2(b))
(Table 7.2.2.2.1.2(b))
149 Landings N/A Width - Not less than the width Width - Not less than the width Width - Not less than the width of
of the stair but need not exceed of the stair but need not exceed the stair but need not exceed 48
48 inches when the stair has a 48 inches when the stair has a inches when the stair has a straight
straight run. straight run. run.
(7.2.2.3.2) (7.2.2.3.2.4) (7.2.2.3.2.4)
150 Vertical Rise N/A Vertical Distance between floor Vertical Distance between floor Vertical Distance between floor
levels and landings - 12 feet. levels and landings - 12 feet. levels and landings - 12 feet.
(Table 7.2.2.2.1(b)) (Table 7.2.2.2.1.1(b)) (Table 7.2.2.2.1.1(b))
151 Headroom N/A 80 inches 80 inches 80 inches
(Table 7.2.2.2.1(b)) (Table 7.2.2.2.1(b)) (Table 7.2.2.2.1(b))
152 Handrails N/A Circular Diameter minimum 1- Circular Diameter minimum 1- Circular Diameter minimum 1-1/4
(Note: Shall also coordinate 1/4 inches max 2 inches 1/4 inches max 2 inches inches max 2 inches
with TAS requirements: (7.2.2.4.5) (7.2.2.4.4.6) (7.2.2.4.4.6)
minimum 1-1/4 inches max 1-
1/2 inches, 4.26.2)
Page 19 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
155 Guardrails Height - 30 inches Height - 30 inches Height - 30 inches (7.2.2.4.5.2(3)) Height - 30 inches (7.2.2.4.5.2(3))
required along open-sided (4604.6) (7.2.2.4.6(2(3)))
walking surfaces, mezzanines,
stairways, ramps and landings
156 Open guardrails shall have Open guardrails shall have Open guardrails shall have Open guardrails shall have
intermediate rails or an intermediate rails or an intermediate rails or an intermediate rails or an ornamental
ornamental pattern such that a ornamental pattern such that a ornamental pattern such that a pattern such that a sphere 4 inches
sphere 6 inches in diameter sphere 4 inches in diameter sphere 4 inches in diameter in diameter cannot pass through up
cannot pass through up to 34 cannot pass through up to 34 cannot pass through up to 34 to 34 inches in height
inches in height inches in height. inches in height (7.2.2.4.5.3)
(4604.6.2) (7.2.2.4.6) (7.2.2.4.5.3)
158 Stairway to Roof Not less than required by the N/A N/A N/A
(DA1015.2.1.1) code which it was constructed
under
(4604.7)
159 Exit Ramps
160 Width Not less than required by the serving patient sleeping rooms = serving patient sleeping rooms = serving patient sleeping rooms = 48
code which it was constructed 48 inches 48 inches inches
under Other = 44 inches Other = 44 inches Other = 44 inches
(4604.7) (19.2.3.3) (19.2.3.4) (19.2.3.4)
161 Maximum slope in direction of N/A Class A: 1:10 1:8 1:8
travel Class B: 1:8 (Table 7.2.5.2 (b)) (Table 7.2.5.2 (b))
(Table 7.2.5.2 (b))
Page 20 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Page 21 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Page 22 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Page 23 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
196 Illumination Unless signs are approved Unless signs are approved Unless signs are approved Unless signs are approved exsting
exsting signs, they must be exsting signs, they must be exsting signs, they must be signs, they must be externally
externally illuminated by not externally illuminated by not externally illuminated by not illuminated by not less than 5 foot-
less than 5 foot-candles or less than 5 foot-candles or less than 5 foot-candles or candles or internally illuminated in
internally illuminated in internally illuminated in internally illuminated in accordance with UL 924 Standard for
accordance per their listing accordance with UL 924 accordance with UL 924 Emergency Lighting and Power
(4604.3) Standard for Emergency Lighting Standard for Emergency Lighting Equipment
and Power Equipment and Power Equipment (7.10.6.3)
(7.10.6.3) (7.10.6.3)
Page 24 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
198 Emergency Power Must be connected to an Must be connected to an Must be connected to an Must be connected to an emergency
emergency electrical system. emergency electrical system in emergency electrical system in electrical system in accordance with
(4604.4) accordance with the Electric accordance with the Electric the Electric Code.
Code. Code. (7.10.4 )
(7.10.4 ) (7.10.4 )
199 Emergency Power Duration 90 minutes in case of primary 90 minutes in case of primary 90 minutes in case of primary 90 minutes in case of primary power
power loss. power loss. power loss. loss.
(7.9.2.1) (7.9.2.1) (7.9.2.1) (7.9.2.1)
200 Tactile Exit Signs N/A Not Required Not Required Not Required
Page 25 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
204 Supervision No specific requirement. In accordance with NFPA 72 In accordance with NFPA 72 In accordance with NFPA 72
9.7.2.1 9.7.2.1 9.7.2.1
205 Sprinklers in clothes closets of Not required in closets where the
patient sleeping rooms in area of the closet < 6 sf, if the
hospitals distance from the sprinkler in the
patient sleeping room to the back
wall of the closet does not exceed
the maximum distance permitted by
NFPA 13. (19.3.5.10)
Page 26 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
218 Outside Window or Door N/A Every patient sleeping room Outside window not required. Outside window not required.
shall have an outside window or
door. The allowable sill height
shall not exceed 36 inches above
the floor.
(19.3.8)
219 Emergency Power System The emergency power system An on-site power generator An on-site power generator An on-site power generator system
Requirements shall provide power and consist system is required. system is required. is required.
of storage batteries, unit (18.5.1.2 (18.5.1.2 (18.5.1.2
equipment or on site generator. NFPA 99) NFPA 99) NFPA 99)
(4604.5.1)
Page 27 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
224 N/A Total volume of Class I, II and Total volume of Class I, II and Total volume of Class I, II and IIIA
IIIA liquids outside of approved IIIA liquids outside of approved liquids outside of approved storage
storage cabinets and safety cans storage cabinets and safety cans cabinets and safety cans shall not
shall not exceed 1 gal per 100 sf. shall not exceed 1 gal per 100 sf. exceed 1 gal per 100 sf.
(NFPA 99: 10-7.2.2) (NFPA 99:11-7.2.3.1) (NFPA 99:11-7.2.3.1)
225 N/A At least one approved At least one approved At least one approved flammable or
flammable or combustible liquid flammable or combustible liquid combustible liquid storage room
storage room shall be available storage room shall be available shall be available within any health
within any health care facility within any health care facility care facility regularly maintaining a
regularly maintaining a reserve regularly maintaining a reserve reserve storage capacity of in excess
storage capacity of in excess of storage capacity of in excess of of 300 gal
300 gal 300 gal (NFPA 99: 11-7.2.3.4)
(NFPA 99: 10-7.2.2) (NFPA 99: 11-7.2.3.4)
Page 28 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
227 N/A Rooms or enclosures for storage Rooms or enclosures for storage Rooms or enclosures for storage of
of gas cylinders shall be well of gas cylinders shall be well gas cylinders shall be well ventilated
ventilated ventilated (NFPA 99: 11-10.3.2)
(NFPA 99:10-10.2.3) (NFPA 99: 11-10.3.2)
228 N/A Total quantity and size of Total quantity and size of Total quantity and size of cylinders
cylinders shall comply with cylinders shall comply with shall comply with Table 8-1 of
Table 8-1 of NFPA 45. Table 8-1 of NFPA 45. NFPA 45.
(NFPA 99: 10-10.3) (NFPA 99: 11-10.3) (NFPA 99: 11-10.3)
229 Medical Gas Storage
230 Medical gas storage and
administration shall be in
accordance with Section 8.7 and
NFPA 99
19.3.2.4
231 N/A Oxidizing gases such as oxygen Oxidizing gases such as oxygen Oxidizing gases such as oxygen and
and nitrous oxide shall not be and nitrous oxide shall not be nitrous oxide shall not be stored
stored with any flammable gas, stored with any flammable gas, with any flammable gas, liquid or
liquid or vapor, liquid or vapor, vapor,
(NFPA 99: 8-3.1.11.2) (NFPA 99: 9.4.1) (NFPA 99: 9.4.1)
232 N/A Oxidizing gases shall be Oxidizing gases shall be Oxidizing gases shall be separated
separated from combustible or separated from combustible or from combustible or incompatible
incompatible materials by a incompatible materials by a materials by a minimum of 20 feet or
minimum of 20 feet or 5 feet if minimum of 20 feet or 5 feet if 5 feet if the storage area is provided
the storage area is provided the storage area is provided with automatic sprinklers.
with automatic sprinklers. with automatic sprinklers. (NFPA 99: 9.4.1)
(NFPA 99: 8-3.1.11.2) (NFPA 99: 9.4.1)
233 Alcohol Based Hand Rub N/A The corridor width is 6 feet or The corridor width is 6 feet or The corridor width is 6 feet or
(ABHR) Dispensers greater and dispensers are at greater and dispensers are at greater
least 4 feet apart least 4 feet apart (19.3.2.6(1))
(Joint Commission) (19.3.2.6(1))
Page 29 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
235 N/A In locations with carpeted floor In locations with carpeted floor In locations with carpeted floor
coverings, dispensers installed coverings, dispensers installed coverings, dispensers installed
directly over carpeted surfaces directly over carpeted surfaces directly over carpeted surfaces are
are permitted only in are permitted only in permitted only in sprinklered smoke
sprinklered smoke sprinklered smoke compartments.
compartments. compartments. (19.3.2.6(9))
(Joint Commission) (19.3.2.6(8))
236 N/A Each smoke compartment may Each smoke compartment may Each smoke compartment may
contain a maximum aggregate contain a maximum aggregate contain a maximum aggregate of 10
of 10 gallons (37.8 liters) of of 10 gallons (37.8 liters) of gallons (37.8 liters) of ABHR
ABHR product in dispensers ABHR product in dispensers product in dispensers and a
and a maximum of 5 gallons and a maximum of 5 gallons maximum of 5 gallons (18.9 liters) in
(18.9 liters) in storage. (18.9 liters) in storage. storage.
(Joint Commission) (19.3.2.6(5&6)) (19.3.2.6(6&7))
237 N/A The maximum individual The maximum individual The maximum individual dispenser
dispenser fluid capacity is 1.2 dispenser fluid capacity is 1.2 fluid capacity is 1.2 liters for
liters for dispensers in rooms, liters for dispensers in rooms, dispensers in rooms, corridors, and
corridors, and areas open to corridors, and areas open to areas open to corridors.
corridors. corridors. (19.3.2.6(2a))
(Joint Commission) (19.3.2.6(2a))
238 N/A The maximum individual The maximum individual The maximum individual dispensers
dispensers in suites of rooms is dispensers in suites of rooms is in suites of rooms is 2.0 liters
2.0 liters 2.0 liters (19.3.2.6(2b))
(Joint Commission) (19.3.2.6(2b))
Page 30 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Page 31 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Page 32 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Page 33 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Page 34 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Page 35 of 36
4/22/2011 EXISTING BUILDINGS
AMERICAN SOCIETY FOR HEALTHCARE ENGINEERING
CODE SUMMARY REPORT
Page 36 of 36
4/22/2011 EXISTING BUILDINGS