Ignition HMI To SLC Through ANC-100e or ANC-120e

This document provides information to configure Ignition HMI software running in a computer connected via Ethernet Network with an ANC-100e or USB using a ANC-120e to communicate with a SLC5/04 or PLC5 on a Data Highway Plus network.

Uploaded by

Jonathan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
223 views6 pages

Ignition HMI To SLC Through ANC-100e or ANC-120e

This document provides information to configure Ignition HMI software running in a computer connected via Ethernet Network with an ANC-100e or USB using a ANC-120e to communicate with a SLC5/04 or PLC5 on a Data Highway Plus network.

Uploaded by

Jonathan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

ANC-100e and ANC-120e

Ethernet and USB to DH+


Converter

Ignition SCADA to SLC5/04 or PLC5


on Data Highway Plus network
This document provides information to configure Ignition HMI software running in a
computer connected via Ethernet Network with an ANC-100e or USB using a ANC-120e
to communicate with a SLC5/04 or PLC5 on a Data Highway Plus network.

Ignition software from Inductive Automation is a powerful industrial software platform


built for SCADA, MES and IIoT applications.

Visit https://inductiveautomation.com for more information about Ignition software

Ignition by Inductive Automation is a trademark of Inductive Automation, LLC.

Note: Before proceeding, make sure

ANC-120e Driver is installed (Only if using ANC-120e)

Network Adapter is correctly configured to access ANC-120e or ANC-100e

ANC-120e is connected to the computer and DH+ network or ANC-100e is


connected to the same Ethernet network or directly to your computer, and to the
DH+ network.

For this example:


ANC-100e IP address = 192.168.0.230
SLC5/04 DH+ node = 03
Ignition Version 7.9.3
ANC-120e and ANC-100e
USB and Ethernet to DH+ Converter
2

1. Open the Ignition Gateway Control Utility and click on Go to webpage

2. Login to the configuration setting and go to the OPC-UA SERVER section on the
left area of the screen and click on Devices
ANC-120e and ANC-100e
USB and Ethernet to DH+ Converter
3

3. Click on the blue arrow on Create New Device

4. On the Add Device Step 1: Choose Type screen, select Allen-Bradley SLC or
Allen-Bradley PLC5, depending on your case, and click Next.
In our case, we are selecting Allen-Bradley SLC
ANC-120e and ANC-100e
USB and Ethernet to DH+ Converter
4

5. On the New Device page, leave all the default values and type in the following
fields:
Name: SLC (or the name you would like the device to have)
Hostname: type the IP address of the ANC-100e (default is 192.168.0.230)
Connection Path: 1,1,2,NN
Where NN is the node address of the target DH+ device
(03 for our example, so the resulting connection path is: 1,1,2,3

6. Click Create New Device


ANC-120e and ANC-100e
USB and Ethernet to DH+ Converter
5

7. The Devices page is displayed showing the SLC device is added to Ignition.
The Status will show as Disconnected for a brief period of time and then
Connected

8. To test the connection, go to OPC Connections -> Quick Client


ANC-120e and ANC-100e
USB and Ethernet to DH+ Converter
6

9. In the OPC Quick Client screen, browse the Devices folder to find your device.
You can expand it to see all the filenames and tags

10. To read a tag, use the [r] option to its left

11. If you can read the tags in your DH+ device, then you have successfully configured
your ANC-100e or ANC-120e and Ignition software to communicate with a
SLC5/04 or PLC5 on Data Highway Plus.