ANC-100e and ANC-120e
Ethernet and USB to DH+
Converter
Ignition SCADA to SLC5/04 or PLC5
on Data Highway Plus network
This document provides information to configure Ignition HMI software running in a
computer connected via Ethernet Network with an ANC-100e or USB using a ANC-120e
to communicate with a SLC5/04 or PLC5 on a Data Highway Plus network.
Ignition software from Inductive Automation is a powerful industrial software platform
built for SCADA, MES and IIoT applications.
Visit https://inductiveautomation.com for more information about Ignition software
Ignition by Inductive Automation is a trademark of Inductive Automation, LLC.
Note: Before proceeding, make sure
ANC-120e Driver is installed (Only if using ANC-120e)
Network Adapter is correctly configured to access ANC-120e or ANC-100e
ANC-120e is connected to the computer and DH+ network or ANC-100e is
connected to the same Ethernet network or directly to your computer, and to the
DH+ network.
For this example:
ANC-100e IP address = 192.168.0.230
SLC5/04 DH+ node = 03
Ignition Version 7.9.3
ANC-120e and ANC-100e
USB and Ethernet to DH+ Converter
2
1. Open the Ignition Gateway Control Utility and click on Go to webpage
2. Login to the configuration setting and go to the OPC-UA SERVER section on the
left area of the screen and click on Devices
ANC-120e and ANC-100e
USB and Ethernet to DH+ Converter
3
3. Click on the blue arrow on Create New Device
4. On the Add Device Step 1: Choose Type screen, select Allen-Bradley SLC or
Allen-Bradley PLC5, depending on your case, and click Next.
In our case, we are selecting Allen-Bradley SLC
ANC-120e and ANC-100e
USB and Ethernet to DH+ Converter
4
5. On the New Device page, leave all the default values and type in the following
fields:
Name: SLC (or the name you would like the device to have)
Hostname: type the IP address of the ANC-100e (default is 192.168.0.230)
Connection Path: 1,1,2,NN
Where NN is the node address of the target DH+ device
(03 for our example, so the resulting connection path is: 1,1,2,3
6. Click Create New Device
ANC-120e and ANC-100e
USB and Ethernet to DH+ Converter
5
7. The Devices page is displayed showing the SLC device is added to Ignition.
The Status will show as Disconnected for a brief period of time and then
Connected
8. To test the connection, go to OPC Connections -> Quick Client
ANC-120e and ANC-100e
USB and Ethernet to DH+ Converter
6
9. In the OPC Quick Client screen, browse the Devices folder to find your device.
You can expand it to see all the filenames and tags
10. To read a tag, use the [r] option to its left
11. If you can read the tags in your DH+ device, then you have successfully configured
your ANC-100e or ANC-120e and Ignition software to communicate with a
SLC5/04 or PLC5 on Data Highway Plus.