Data sheet 6EP1331-5BA10

SITOP PSU100C 24 V/1.3 A


SITOP PSU100C 24 V/1.3 A stabilized power supply input: 120/230
V AC (DC 110-300 V) output: 24 V DC/1.3 A

Input
Input 1-phase AC or DC
Rated voltage value Vin rated 100...230V
Voltage range AC 85...264V
Input voltage
at DC 110...300V
Wide-range input Yes
Overvoltage resistance 2.3 Vin rated, 1.3 ms
Mains buffering at Iout rated, min. 20ms; at Vin = 230 V
Rated line frequency 1 50Hz
Rated line frequency 2 60Hz
Rated line range 47...63Hz
Input current
at rated input voltage 100 V 0.63A
at rated input voltage 230 V 0.31A
Switch-on current limiting (+25 C), max. 34A
It, max. 1.2As
Built-in incoming fuse internal

6EP1331-5BA10 Subject to change without notice


Page 1/4 09/14/2017 Copyright Siemens
Protection in the mains power input (IEC 898) Recommended miniature circuit breaker: from 6 A characteristic B
or from 3 A characteristic C

Output
Output Controlled, isolated DC voltage
Rated voltage Vout DC 24V
Total tolerance, static 3%
Static mains compensation, approx. 0.1%
Static load balancing, approx. 0.2%
Residual ripple peak-peak, max. 200mV
Residual ripple peak-peak, typ. 25mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 300mV
Spikes peak-peak, typ. (bandwidth: 20 MHz) 20mV
Adjustment range 22.2...26.4V
Product function Output voltage adjustable Yes
Output voltage setting via potentiometer
Status display Green LED for output voltage OK
On/off behavior Overshoot of Vout approx. 5 %
Startup delay, max. 0.6s
Voltage rise, typ. 90ms
Rated current value Iout rated 1.3A
Current range 0...1.3A
Note +60 ... +70 C: Derating 0.8%/K; at +70 C Iout rated 1.2 A
Supplied active power typical 30W
Short-term overload current
at short-circuit during operation typical 3.1A
Parallel switching for enhanced performance Yes; Start-up with single nominal load only
Numbers of parallel switchable units for enhanced 2
performance

Efficiency
Efficiency at Vout rated, Iout rated, approx. 86%
Power loss at Vout rated, Iout rated, approx. 4.5W
Power loss [W] during no-load operation maximum 0.75W

Closed-loop control
Dynamic mains compensation (Vin rated 15 %), 0.1%
max.
Dynamic load smoothing (Iout: 10/90/10 %), Uout 3%
typ.
Load step setting time 10 to 90%, typ. 5ms
Load step setting time 90 to 10%, typ. 5ms

Protection and monitoring


Output overvoltage protection Yes, according to EN 60950-1
Current limitation, typ. 1.4A

6EP1331-5BA10 Subject to change without notice


Page 2/4 09/14/2017 Copyright Siemens
Property of the output Short-circuit proof Yes
Short-circuit protection Electronic shutdown, automatic restart
Overload/short-circuit indicator -

Safety
Primary/secondary isolation Yes
Galvanic isolation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN
50178
Protection class Class I
Leakage current
maximum 3.5mA
typical 0.4mA
CE mark Yes
UL/cUL (CSA) approval cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259;
cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File
E151273, NEC class 2 (acc. to UL 1310)
Explosion protection ATEX (EX) II 3G Ex nA IIC T4; cCSAus (CSA C22.2 No. 213-
M1987, ANSI/ISA-12.12.01-2007) Class I, Div. 2, Group ABCD,
T4
FM approval -
CB approval Yes
Marine approval GL, ABS
Degree of protection (EN 60529) IP20

EMC
Emitted interference EN 55022 Class B
Supply harmonics limitation not applicable
Noise immunity EN 61000-6-2

Operating data
Ambient temperature
during operation -20...+70C
Note with natural convection
during transport -40...+85C
during storage -40...+85C
Humidity class according to EN 60721 Climate class 3K3, no condensation

Mechanics
Connection technology screw-type terminals
Connections
Supply input L, N, PE: Removable screw terminal, each for 1 x 0.5 ... 2.5 mm
Output +: 1 screw terminal for 0.5 ... 2.5 mm; -: 2 screw terminals for 0.5
... 2.5 mm
Auxiliary -
Width of the enclosure 30mm
Height of the enclosure 80mm

6EP1331-5BA10 Subject to change without notice


Page 3/4 09/14/2017 Copyright Siemens
Depth of the enclosure 100mm
Required spacing
top 50mm
bottom 50mm
left 0mm
right 0mm
Weight, approx. 0.17kg
Product feature of the enclosure housing for side-by- Yes
side mounting
Installation Snaps onto DIN rail EN 60715 35x7.5/15
Electrical accessories Removable spring-type terminal 6EP1971-5BA00
MTBF at 40 C 3838624h
Other information Specifications at rated input voltage and ambient temperature +25
C (unless otherwise specified)

6EP1331-5BA10 Subject to change without notice


Page 4/4 09/14/2017 Copyright Siemens