UNIFLAIR Modbus InstructionManual
UNIFLAIR Modbus InstructionManual
Instruction Manual
Version: 1.1
Date: May 2009
Language: English
Modbus Variables List For UECH420DF
EN
2
Modbus Variables List For UECH420DF
SUMMARY
page
Modbus Functions and Resources 4
Data Format (RTU) 4
Network 5
Available Modbus Functions and data areas 5
Address Configuration 6
Description of Parameters 6
Table of Parameters 8
3
Modbus Variables List For UECH420DF
Modbus is a protocol of client/server communication for communication between devices connected by means of a
network. Modbus communicates using a master-slave technique in which only one device (master) can send messages.
The other devices on the network (slaves) respond by returning the data requested by the master or following the actions
indicated in the message sent. The definition of a slave is a device connected to a network which elaborates information
and sends the results to the master using the Modbus protocol. The master instrument can send messages to a single
slave or to the whole network (broadcast), while the slave instruments respond individually to the master device. The
Modbus standard used by Eliwell provides for the use of RTU encoding for the transmission of data.
The model of encoding used defines the structure of the messages transmitted via the network and the method in which
this information is decoded. The type of encoding used is usually chosen on the basis of specific parameters (baud rate,
parity, etc.) also, certain devices only support determined models of encoding, which must be the same for all
instruments connected to a Modbus network.
The protocol uses the binary RTU method with the byte composed as follows:
8 bits for the data, bits of even parity (non configurable), 1 bit of stop.
4
Modbus Variables List For UECH420DF
NETWORK
ATTENTION! It is necessary to request the reading of 2 registers (WORD) to obtain 1 in response. Requesting the
reading of only one register gives the highest byte reading.
ATTENTION! To write values in WORD it is necessary to send requests for writing with 2 registers, to obtain a response
of size 2.
5
Modbus Variables List For UECH420DF
ADDRESS CONFIGURATION
The address of a device inside a Modbus message is composed of a byte and is formed from the family code and the
instrument code composed of the respective parameters H65 and H66.
The address (Device Address) is therefore formed from two nibbles:
H66: low nibble
H65: high nibble
To calculate the address starting with the parameters H65 and H66:
address = H65 x 16 + H66
The address 0 is used for broadcast messages which all slaves recognise. The slaves do not respond to broadcast type
requests.
ADDRESS TABLES
Description of Parameters
The tables of addresses contain the necessary information: reading, writing and decoding for every single resource
accessible to the instrument.
Two tables are present:
- the parameters table contains all the configuration parameters of the device memorized in the non volatile
memory of the instrument.
- the client table includes all the resources of the I/O state and of the alarms available in the volatile memory of
the instrument.
INDEX: For the parameter table this value represents the order of visualisation of the parameter in the instrument menu.
For the client table this value is not significant.
FOLDER: Indicates the label of the folder inside which the parameter in question is contained.
LABEL: Indicates the label with which the parameters are visualised in the instrument menu.
ADDRESS: As a whole it represents the address of the MODBUS register containing the resource value to read or write
in the instrument. The value after the comma indicates the position of the most significant bit of the data inside the
register, if not indicated it is assumed equal to zero. This information is always supplied when the register contains more
than one piece of information and it is necessary to distinguish which bits effectively represent the data (the useful
dimension of the data is also considered and indicated in the column DATA SIZE). Considering that the Modbus registers
have the dimension of a WORD (16 bit), the integer after the comma can vary from 0 (least significant bit LSb-) to 15
(most significant bit MSb-).
Example (in the binary representation the least significant bit is the first on the right):
Important: when the register contains more than one data, the writing operation proceeds in the following way:
- read the current value of the register
- modify the bits which represent the resources of interest
- write the register
6
Modbus Variables List For UECH420DF
CPL: When the field indicates Y, the value read from the register necessitates a conversion because the value
represents a positive or negative number. In other cases the value is always positive or null.
To carry out the conversion proceed in the following way:
- if the value of the register is between 0 and 32.767, the result is the value itself (zero and positive values).
- if the value of the register is between 32.768 and 65.535 the result is the value of the register - 65.536 (negative
value)
RANGE: Describes the interval of values which the parameter can assume. It can be correlated to other parameters of
the instrument (indicated by the label of the parameter).
DEFAULT: Indicates the value set in the factory for the standard model of the instrument.
EXP: Is the multiplier integer to apply to convert the read value from the register, to the values indicated in the RANGE
and DEFAULT column to convert them into the final value according to the unit of measure indicated in the column M.U.
The multiplier is calculated by the exponential function with base 10 and exponent equal to that indicated in the column
EXP. When not indicated the value is 0. The valid values are as follows:
Value Corresponding
Multiplier
-2 = 10-2 (0,01)
-1 = 10-1 (0,1)
0 = 100 (1)
1 = 101 (10)
2 = 102 (100)
M.U.: Unit of measure of the converted values on the basis of the rules indicated in the column CPL and EXP.
7
Modbus Variables List For UECH420DF
TABLE OF ADDRESSES
DATA
INDEX FOLDER LABEL ADDRESS RAN DESCRIPTION SIZE CPL RANGE DEFAULT EXP M.U.
1 Set G01 2049 RW Set point Cooling WORD Y H04H03 120 -1 C/F
2 Set G02 2050 RW Set point Heating WORD Y H02H01 400 -1 C/F
3 Cnf H01 2051 RW Max set point Heating WORD Y G02 ... 990 600 -1 C/F
4 Cnf H02 2052 RW Min set point Heating WORD Y -400 ... 300 -1 C/F
5 Cnf H03 2053 RW Max set point Cooling WORD Y G02 ... 990
G01 300 -1 C/F
6 Cnf H04 2054 RW Min set point Cooling WORD Y -400 ...G01 0 -1 C/F
7 Cnf H05 2055 RW Number of circuits in the unit 4 bit 0 ... 2 1 Num
8 Cnf H06 2056 RW Number of compressors for circuit 4 bit 0 ... 4 2 Num
9 Cnf H07 2057 RW Number of partialisations for compressor 4 bit 0 ... 3 0 Num
10 Cnf H08 2058 RW Ignition sequence of the compressors BYTE 0 ... 2 0 Num
11 Cnf H09 2059 RW Balancing of the circuits 1 bit 0 ... 1 1 Flag
12 Cnf H10 2060 RW Heat-pump presence 1 bit 0 ... 1 1 Flag
13 Cnf H11 2061 RW Configuration A11 4 bit 0 ... 4 1 Num
14 Cnf H12 2062 RW Configuration A12 4 bit 0 ... 2 1 Num
15 Cnf H13 2063 RW Configuration A13 4 bit 0 ... 5 2 Num
16 Cnf H14 2064 RW Configuration A14 4 bit 0 ... 3 0 Num
17 Cnf H15 2065 RW Configuration A15 4 bit 0 ... 1 0 Num
18 Cnf H16 2066 RW Configuration A16 4 bit 0 ... 4 0 Num
19 Cnf H17 2067 RW Pressure scale end WORD 0 ... 999 300 Kpa*10
20 Cnf H18 2068 RW Polarity 1D1 1D2 1D3 1D4 4 bit 0 ... 15 15 Num
21 Cnf H19 2069 RW Polarity 1D5 1D6 1D7 1D8 4 bit 0 ... 15 15 Num
22 Cnf H20 2070 RW Polarity 1D9 1D10 1D11 A14 4 bit 0 ... 15 12 Num
23 Cnf H21 2071 RW Polarity A11 1 bit 0 ... 1 0 Flag
24 Cnf H22 2072 RW Polarity A12 1 bit 0 ... 1 0 Flag
25 Cnf H23 2073 RW Configuration digital input 1D1 BYTE 0 ... 29 1 Num
26 Cnf H24 2074 RW Configuration digital input 1D2 BYTE 0 ... 29 2 Num
27 Cnf H25 2075 RW Configuration digital input 1D3 BYTE 0 ... 29 3 Num
28 Cnf H26 2076 RW Configuration digital input 1D4 BYTE 0 ... 29 4 Num
29 Cnf H27 2077 RW Configuration digital input 1D5 BYTE 0 ... 29 5 Num
30 Cnf H28 2078 RW Configuration digital input 1D6 BYTE 0 ... 29 12 Num
31 Cnf H29 2079 RW Configuration digital input 1D7 BYTE 0 ... 29 0 Num
32 Cnf H30 2080 RW Configuration digital input 1D8 BYTE 0 ... 29 0 Num
33 Cnf H31 2081 RW Configuration digital input 1D9 BYTE 0 ... 29 0 Num
34 Cnf H32 2082 RW Configuration digital input 1D10 BYTE 0 ... 29 10 Num
35 Cnf H33 2083 RW Configuration digital input 1D11 BYTE 0 ... 29 0 Num
8
Modbus Variables List For UECH420DF
DATA
INDEX FOLDER LABEL ADDRESS RAN DESCRIPTION SIZE CPL RANGE DEFAULT EXP M.U.
36 CnF H34 2084 RW Configuration analogue input 4 as for digital BYTE 0 ... 29 0 Num
37 CnF H35 2085 RW Configuration relay RL2 BYTE 0 ... 20 9 Num
38 CnF H36 2086 RW Configuration relay RL3 BYTE 0 ... 20 1 Num
39 CnF H37 2087 RW Configuration relay RL4 BYTE 0 ... 20 0 Num
40 CnF H38 2088 RW Configuration relay RL5 BYTE 0 ... 20 5 Num
41 CnF H39 2089 RW Configuration relay RL6 BYTE 0 ... 20 3 Num
42 CnF H40 2090 RW Configuration relay RL7 BYTE 0 ... 20 7 Num
43 CnF H41 2091 RW Polarity RL2 1 bit 0 ... 1 0 Flag
44 CnF H42 2092 RW Polarity RL3 1 bit 0 ... 1 1 Flag
45 CnF H43 2093 RW Polarity RL4 1 bit 0 ... 1 0 Flag
46 CnF H44 2094 RW Polarity RL5 1 bit 0 ... 1 0 Flag
47 CnF H45 2095 RW Polarity relay alarm 1 bit 0 ... 1 0 Flag
48 CnF H46 2096 RW Configuration ventilator output 1 1 bit 0 ... 1 0 Flag
49 CnF H47 2097 RW Configuration ventilator output 2 1 bit 0 ... 1 0 Flag
50 CnF H48 2098 RW Qualification / Enable regulation with probe 2 1 bit 0 ... 1 0 Flag
51 CnF H49 2099 RW Configuration method of function selection 1 bit 0 ... 1 0 Flag
52 CnF H50 2100 RW Qualification / Enable dynamic set point 1 bit 0 ... 1 0 Flag
53 CnF H51 2101 RW Offset dynamic set point in Cooling WORD Y -500 ... 800 0 -1 C/f
54 CnF H52 2102 RW Offset dynamic set point in Heating WORD Y -500 ... 800 0 -1 C/f
55 CnF H53 2103 RW Set point dynamic set point in Cooling BYTE Y -127 ... 127 0 C/f
56 CnF H54 2104 RW Set point dynamic set point in Heating BYTE Y -127 ... 127 0 C/f
57 CnF H55 2105 RW Proportional band dynamic set point in Cooling WORD Y -500 ... 800 0 -1 C/f
58 CnF H56 2106 RW Proportional band dynamic set point in Heating WORD Y -500 ... 800 0 -1 C/f
59 CnF H57 2107 RW A11 offset BYTE Y -127 ... 127 0 -1 C/f
60 CnF H58 2108 RW A12 offset BYTE Y -127 ... 127 0 -1 C/f
61 CnF H59 2109 RW A13 offset BYTE Y -127 ... 127 0 C/10-kpa*10
62 CnF H60 2110 RW A14 offset BYTE Y -127 ... 127 0 -1 C/f
63 CnF H61 2111 RW A15 offset BYTE Y -127 ... 127 0 -1 C/f
64 CnF H62 2112 RW A16 offset BYTE Y -127 ... 127 0 C/10-kpa*10
65 CnF H63 2113 RW Frequency of power supply 1 bit 0 ... 1 0 Flag
66 CnF H64 2114 RW Temperature unit of measure 1 bit 0 ... 1 0 Flag
67 CnF H65 2115 RW Serial family address 4 bit 0 ... 14 0 Num
68 CnF H66 2116 RW Serial device address 4 bit 0 ... 14 1 Num
69 CnF H67 2117 RW User password BYTE 0 ... 255 0 Num
70 CnF H68 2118 RW Copy card password BYTE 0 ... 255 1 Num
71 CnF H69 2119 RW Keyboard presence 1 bit 0 ... 1 0 Flag
9
Modbus Variables List For UECH420DF
DATA
INDEX FOLDER LABEL ADDRESS RAN DESCRIPTION SIZE CPL RANGE DEFAULT EXP M.U.
72 Cnf H70 2120 RW Start of scale AI3 (H13=3) BYTE Y -127 ... 127 -50 -1 C/10-Kpa*10
73 Cnf H71 2121 RW End of scale AI3 (H13=3) WORD Y -500 ... 800 700 -1 C/10-Kpa*10
74 Cnf H72 2122 RW Qualification / Enable relay alarm in Off 1 bit 0 ... 1 0 Flag
75 ALL A01 2123 RW Low pressure alarm bypass time BYTE 0 ... 255 120 Sec
76 ALL A02 2124 RW Event/time low pressure alarm BYTE 0 ... 255 0 Num
77 ALL A03 2125 RW Water flow meter bypass time on pump activation BYTE 0 ... 255 10 Sec
78 ALL A04 2126 RW attivazione pompa
Input duration water flow meter active BYTE 0 ... 255 15 Sec
79 ALL A05 2127 RW Input duration water flow meter non active BYTE 0 ... 255 15 Sec
80 ALL A06 2128 RW Event/time water flow meter alarm BYTE 0 ... 255 0 Num
81 ALL A07 2129 RW Thermal compressor alarm bypass time BYTE 0 ... 255 5 Sec
82 ALL A08 2130 RW Event/time thermal compressor alarm BYTE 0 ... 255 0 Num
83 ALL A09 2131 RW Event/time thermal ventilator alarm BYTE 0 ... 255 0 Num
84 ALL A10 2132 RW Antifreeze alarm bypass time BYTE 0 ... 255 4 Min
85 ALL A11 2133 RW Antifreeze alarm set point BYTE Y -127 ... 127 3 C/F
86 ALL A12 2134 RW Hysteresis antifreeze alarm BYTE 0 ... 255 20 -1 C/F
87 ALL A13 2135 RW Event/time antifreeze alarm BYTE 0 ... 255 0 Num
88 ALL A14 2136 RW Differential oil pressure switch alarm bypass time BYTE 0 ... 255 0 Sec
89 ALL A15 2137 RW Above temperature set point of analogical input BYTE Y -127 ... 127 55 C/F
90 ALL A16 2138 RW Duration of above temperature conditions BYTE 0 ... 255 255 Sec*10
91 ALL A17 2139 RW State of compressors for above temperature alarm 1 bit 0 ... 1 0 Flag
92 ALL A18 2140 RW Event/time high pressure alarm BYTE 0 ... 255 0 Num
93 CP C01 2141 RW Minimum time On-Off compressor BYTE 0 ... 255 18 Sec*10
94 CP C02 2142 RW Minimum time On-On compressor BYTE 0 ... 255 36 Sec*10
95 CP C03 2143 RW Hysteresis thermoregulator Cooling BYTE 0 ... 255 10 -1 C/F
96 CP C04 2144 RW Hysteresis thermoregulator Heating BYTE 0 ... 255 10 -1 C/F
97 CP C05 2145 RW Differential insertion steps /compressors BYTE 0 ... 255 10 -1 C/F
98 CP C06 2146 RW Delay start up compressors BYTE 0 ... 255 10 Sec
99 CP C07 2147 RW Delay shut down compressors BYTE 0 ... 255 1 Sec
100 CP C08 2148 RW Delay insertion or disconnection steps BYTE 0 ... 255 0 Sec
101 CP C09 2149 RW Delay star-line WORD 0 ... 900 0 Sec/10
102 CP C10 2150 RW Function time of star WORD 0 ... 900 0 Sec/10
103 CP C11 2151 RW Delay delta-star WORD 0 ... 900 0 Sec/10
104 CP C12 2152 RW Integral time screw compressor WORD 0 ... 900 0 Sec
105 CP C13 2153 RW Opening time screw compressor WORD 0 ... 900 0 Sec
106 CP C14 2154 RW Closing time screw compressor WORD 0 ... 900 0 Sec
107 CP C15 2155 RW Hysteresis time screw compressor BYTE 0 ... 255 0 Sec
10
Modbus Variables List For UECH420DF
DATA
INDEX FOLDER LABEL ADDRESS RAN DESCRIPTION SIZE CPL RANGE DEFAULT EXP M.U.
108 CP C16 2156 RW Qualification/Enable accumulation compensation 1 bit 0 ... 1 0 Flag
109 CP C17 2157 RW Set accumulation compensation block in Cooling BYTE 0 ... 255 0 C
110 CP C18 2158 RW Set accumulation compensation block in Heating BYTE 0 ... 255 0 C
111 CP C19 2159 RW Delta increase set accumulation compensation BYTE 0 ... 255 0 -1 C
112 CP C20 2160 RW Reset time of the accumulation compensation increase BYTE 0 ... 255 0 Sec*10
113 CP C21 2161 RW Constant accumulation compensation BYTE 0 ... 255 0 -1 C/(10*sec)
114 Fan F01 2162 RW Configuration ventilator output 4 bit 0 ... 2 0 Num
115 Fan F02 2163 RW Ventilator cue time BYTE 0 ... 255 30 Sec/10
116 Fan F03 2164 RW Ventilator phase displacement BYTE 0 ... 100 8 Num
117 Fan F04 2165 RW Triac comand impulse duration BYTE 0 ... 255 30 Usec*100
118 Fan F05 2166 RW Ventilator switched on with compressor 1 bit 0 ... 1 0 Flag
119 Fan F06 2167 RW Minimum velocity in Cooling BYTE 0 ... 100 30 Num
120 Fan F07 2168 RW Silent velocity in Cooling BYTE 0 ... 100 100 Num
121 Fan F08 2169 RW Set point T/P minimum velocity in Cooling WORD Y -500 ... 800 130 C/10-Kpa*10
122 Fan F09 2170 RW Ventilator proportional band in Cooling BYTE 0 ... 255 40 C/10-Kpa*10
123 Fan F10 2171 RW Differential T/P cut-off ventilator BYTE 0 ... 255 20 C/10-Kpa*10
124 Fan F11 2172 RW Hysteresis cut-off ventilator BYTE 0 ... 255 5 C/10-Kpa*10
125 Fan F12 2173 RW Bypass time cut-off ventilator BYTE 0 ... 255 10 Sec
126 Fan F13 2174 RW Maximum velocity in Cooling BYTE 0 ... 100 100 Num
127 Fan F14 2175 RW Set point T/P maximum velocity in Cooling WORD Y -500 ... 800 170 C/10-Kpa*10
128 Fan F15 2176 RW Minimum velocity in Heating BYTE 0 ... 100 30 Num
129 Fan F16 2177 RW Silent velocity in Heating BYTE 0 ... 100 100 Num
130 Fan F17 2178 RW Set point T/P minimum velocity in Heating WORD Y -500 ... 800 70 C/10-Kpa*10
131 Fan F18 2179 RW Ventilator proportional band in Heating BYTE 0 ... 255 20 C/10-Kpa*10
132 Fan F19 2180 RW Maximum velocity in Heating BYTE 0 ... 100 100 Num
133 Fan F20 2181 RW Set point T/P maximum velocity in Heating WORD Y -500 ... 800 50 C/10-Kpa*10
134 Fan F21 2182 RW Pre-ventilation in Cooling BYTE 0 ... 255 0 Sec
135 Fan F22 2183 RW Configuration together or separate 1 bit 0 ... 1 1 Flag
136 Fan F23 2184 RW Set point T/P ventilator in defrosting WORD Y -500 ... 800 800 C/10-Kpa*10
137 Fan F24 2185 RW Hysteresis ventilator in defrosting BYTE 0 ... 255 0 C/10-Kpa*10
138 Fan F25 2186 RW Qualification/Enable condensation compensation cooling 1 bit 0 ... 1 0 Flag
139 Fan F26 2187 RW Offset condensation compensation WORD Y -500 ... 800 -40 C-Kpa*100
140 Fan F27 2188 RW Set point condensation compensation BYTE Y -127 ... 127 20 C/F
141 Fan F28 2189 RW Proportional band condensation compensation WORD Y -500 ... 800 -50 C-Kpa*100
142 PUP P01 2190 RW Configuration water pump 1 bit 0 ... 1 0 Flag
143 PUP P02 2191 RW Delay On pump-compressor BYTE 0 ... 255 15 Sec
11
Modbus Variables List For UECH420DF
DATA
INDEX FOLDER LABEL ADDRESS RAN DESCRIPTION SIZE CPL RANGE DEFAULT EXP M.U.
144 PUP P03 2192 RW Delay Off compressor-pump BYTE 0 ... 255 15 Sec
145 PUP P04 2193 RW Qualification/Enable second water pump 1 bit 0 ... 1 0 Flag
146 PUP P05 2194 RW Rotation pump hours of function BYTE 0 ... 255 100 Ore*100
147 PUP P06 2195 RW Set point T external pump activation BYTE -127 ... 127 0 C
148 PUP P07 2196 RW Hysteresis external temperature pump activation BYTE 0 ... 255 0 -1 C
149 Fro R01 2197 RW Resistance configuration in defrosting 1 bit 0 ... 1 0 Flag
150 Fro R02 2198 RW Qualification/Enable resistence in Cooling 1 bit 0 ... 1 0 Flag
151 Fro R03 2199 RW Qualification/Enable resistance in Heating 1 bit 0 ... 1 0 Flag
152 Fro R04 2200 RW Probe resistance regulation 1 4 bit 0 ... 3 2 Num
153 Fro R05 2201 RW Probe resistance regulation 2 4 bit 0 ... 3 2 Num
154 Fro R06 2202 RW Resistance configuration in Off or stand-by 1 bit 0 ... 1 1 Flag
155 Fro R07 2203 RW Set point resistance 1 in Heating BYTE Y R10 ... R09 4 CIF
156 Fro R08 2204 RW Set point resistance 1 in Cooling BYTE Y R10 ... R09 4 CIF
157 Fro R09 2205 RW Electrical resistance max set point BYTE Y R10 . ... 127 10 CIF
158 Fro R10 2206 RW Electrical resistance min set point BYTE Y -127 ... R09 -10 CIF
159 Fro R11 2207 RW Hysteresis electrical resistance BYTE 0 ... 255 10 -1 CIF
160 Fro R12 2208 RW Qualification/Enable resistance in parallel 1 bit 0 ... 1 0 Flag
161 Fro R13 2209 RW Set point resistance 2 in Heating BYTE Y R10 ... R09 4 CIF
162 Fro R14 2210 RW Set point resistance 2 in Cooling BYTE Y R10 ... R09 4 CIF
163 Fro R15 2211 RW Qualification/Enable resistance in integration in Heating 1 bit 0 ... 1 0 Flag
164 Fro R16 2212 RW Differential resistance 1 in integration BYTE 0 ... 255 0 -1 CIF
165 Fro R17 2213 RW Differential resistance 2 in integration BYTE 0 ... 255 0 -1 CIF
166 Dfr D01 2214 RW Qualification/Enable defrosting 1 bit 0 ... 1 0 Flag
167 Dfr D02 2215 RW Set point TIP start of defrosting WORD Y -500 ... 800 -20 CI10-Kpa*10
168 Dfr D03 2216 RW Cumulative time for start of defrosting BYTE 0 ... 255 2 Min
169 Dfr D04 2217 RW Set point TIP end of defrosting WORD Y -500 ... 800 100 CI10-Kpa*10
170 Dfr D05 2218 RW Maximum duration defrosting BYTE 0 ... 255 10 Min
171 Dfr D06 2219 RW Delay start of defrosting valve BYTE 0 ... 255 5 Sec
172 Dfr D07 2220 RW Dripping time BYTE 0 ... 255 5 Sec
173 Dfr D08 2221 RW Delay between defrosting of circuits BYTE 0 ... 255 30 Min
174 Dfr D09 2222 RW Probe configuration at end of defrosting circuit 1 4 bit 0 ... 5 0 Num
175 Dfr D10 2223 RW Probe configuration at end of defrosting circuit 2 4 bit 0 ... 5 0 Num
176 Dfr D11 2224 RW Start up delay compressors in defrosting BYTE 0 ... 255 0 Sec
177 Dfr D12 2225 RW Qualification/Enable defrosting compensation 1 bit 0 ... 1 1 Flag
178 Dfr D13 2226 RW Offset defrosting compensation WORD Y -500 ... 800 -130 CI10-Kpa*10
179 Dfr D14 2227 RW Set defrosting compensation BYTE Y -127 ... 127 100 CIF
12
Modbus Variables List For UECH420DF
DATA
INDEX FOLDER LABEL ADDRESS RAN DESCRIPTION SIZE CPL RANGE DEFAULT EXP M.U.
180 Der D15 2228 RW Proportional band defrosting compensation WORD Y -500 ... 800 -200 CI10-Kpa*10
181 ESP N01 2229 RW Polarity ID12 ID13 ID14 ID15 4 bit 0 ... 15 0 Num
182 ESP N02 2230 RW Configuration digital input ID12 BYTE 0 ... 29 0 Num
183 ESP N03 2231 RW Configuration digital input ID13 BYTE 0 ... 29 19 Num
184 ESP N04 2232 RW Configuration digital input ID14 BYTE 0 ... 29 6 Num
185 ESP N05 2233 RW Configuration digital input ID15 BYTE 0 ... 29 7 Num
186 ESP N06 2234 RW Configuration relay RL9 BYTE 0 ... 20 10 Num
187 ESP N07 2235 RW Configuration relay RL10 BYTE 0 ... 20 11 Num
188 ESP N08 2236 RW Configuration relay RL11 BYTE 0 ... 20 11 Num
189 ESP N09 2237 RW Configuration relay RL12 BYTE 0 ... 20 11 Num
190 ESP N10 2238 RW Configuration relay RL13 BYTE 0 ... 20 11 Num
191 ESP N11 2239 RW Configuration AI7 4 bit 0 ... 1 0 Num
192 ESP N12 2240 RW Configuration AI8 4 bit 0 ... 1 0 Num
193 SPL L01 2241 RW Enable Water Free Cooling 4 bit 0 ... 3 0 Num
194 SPL L02 2242 RW Delta input Free Cooling BYTE Y -100 ... 100 -0,2 -1 *C
195 SPL L03 2243 RW Hysteresis output Free Cooling BYTE 0 ... 100 0,2 -1 *C
196 SPL L04 2244 RW Antifreeze pre-alarm threshold BYTE Y -100 ... 100 0,2 -1 *C
197 SPL L05 2245 RW Proportional band Free Cooling BYTE 0 ... 100 0,1 -1 *C
198 SPL L06 2246 RW Delta temperature minimum Free Cooling BYTE Y -100 ... 100 -0,1 -1 *C
199 SPL L07 2247 RW Delta temperature cut-off Free Cooling BYTE Y -100 ... 100 -0,1 -1 *C
200 SPL L08 2248 RW Scanning time antifreeze pre-alarm WORD 0 ... 999 180 Sec
201 SPL L09 2249 RW Delay start up compressors WORD 0 ... 999 0 Sec
13
Modbus Variables List For UECH420DF
CLIENT TABLE
INDEX FOLDER LABEL ADDRESS R/W DESCRIPTION DATA SIZE CPL RANGE DEFAULT EXP M.U.
1 AI1 4097 R Analog input 1 WORD Y -670 ... 3020 0 -1 C/F
2 AI2 4098 R Analog input 2 WORD Y -670 ... 3020 0 -1 C/F
3 AI3 4099 R Analog input 3 WORD Y -670 ... 3020 0 -1 C/F
4 AI4 4100 R Analog input 4 WORD Y -670 ... 3020 0 -1 C/F
5 AI5 4101 R Analog input 5 WORD Y -670 ... 3020 0 -1 C/F
6 AI6 4102 R Analog input 6 WORD Y -670 ... 3020 0 -1 C/F
7 AI7 4103 R Analog input 7 WORD Y -670 ... 3020 0 -1 C/F
8 AI8 4104 R Analog input 8 WORD Y -670 ... 3020 0 -1 C/F
9 DI1 16485,13 R Digital input 1 1 bit 0 ... 1 0 num
10 DI2 16485,12 R Digital input 2 1 bit 0 ... 1 0 num
11 DI3 16485,11 R Digital input 3 1 bit 0 ... 1 0 num
12 DI4 16485,1 R Digital input 4 1 bit 0 ... 1 0 num
13 DI5 16485,2 R Digital input 5 1 bit 0 ... 1 0 num
14 DI6 16485,0 R Digital input 6 1 bit 0 ... 1 0 num
15 DI7 16485,3 R Digital input 7 1 bit 0 ... 1 0 num
16 DI8 16485,6 R Digital input 8 1 bit 0 ... 1 0 num
17 DI9 16485,7 R Digital input 9 1 bit 0 ... 1 0 num
18 DI10 16485,5 R Digital input 10 1 bit 0 ... 1 0 num
19 DI11 16485,8 R Digital input 11 WORD 0 ... 1 0 num
20 DI12 16485,4 R Digital input 12 WORD 0 ... 1 0 num
21 DI13 16485,9 R Digital input 13 1 bit 0 ... 1 0 num
22 DI14 16485,14 R Digital input 14 1 bit 0 ... 1 0 num
23 DI15 16485,15 R Digital input 15 1 bit 0 ... 1 0 num
24 DIG AI4 16485,10 R Digital input 16 1 bit 0 ... 1 0 num
25 DIG AI1 16505,8 R Digital input 17 1 bit 0 ... 1 0 num
26 DIG AI2 16505,9 R Digital input 18 1 bit 0 ... 1 0 num
27 DIG AI5 16505,13 R Digital input 19 1 bit 0 ... 1 0 num
28 AN1 14337 R Analog output 1 WORD 0 ... 255 0 num
29 AN2 14338 R Analog output 2 WORD 0 ... 255 0 num
30 RL1 16795,1 R Control output 1 1 bit 0 ... 1 0 num
31 RL2 16795,2 R Control output 2 1 bit 0 ... 1 0 num
14
Modbus Variables List For UECH420DF
INDEX FOLDER LABEL ADDRESS R/W DESCRIPTION DATA SIZE CPL RANGE DEFAULT EXP M.U.
32 RL3 16795,3 R Control output 3 1 bit 0 ... 1 0 num
33 RL4 16795,4 R Control output 4 1 bit 0 ... 1 0 num
34 RL5 16795,5 R Control output 5 1 bit 0 ... 1 0 num
35 RL6 16795,6 R Control output 6 1 bit 0 ... 1 0 num
36 RL7 16795,7 R Control output 7 1 bit 0 ... 1 0 num
37 RL ALL 16795,0 R Alarm output 1 bit 0 ... 1 0 num
38 RL9 16795,15 R Control output 9 1 bit 0 ... 1 0 num
39 RL10 16795,14 R Control output 10 1 bit 0 ... 1 0 num
40 RL11 16795,12 R Control output 11 1 bit 0 ... 1 0 num
41 RL12 16795,13 R Control output 12 1 bit 0 ... 1 0 num
42 RL13 16795,11 R Control output 13 1 bit 0 ... 1 0 num
43 16509,8 RW Selecting cooling mode 1 bit 0 ... 1 0 num
44 16509,9 RW Selecting heating mode 1 bit 0 ... 1 0 num
45 16509,15 RW State regulator 1 bit 0 ... 1 0 num
46 REG_DIG 17301,11 R Thermoregulator digital adjusting 1 bit 0 ... 1 0 num
47 AUTOTEST 17301,13 R Enable self-testing 1 bit 0 ... 1 0 num
48 ABI_MODOKB 17301,15 R Selecting change of keyboard mode WORD 0 ... 1 0 num
D
49 ORE COMP1 16511 R Compressor operating hours 1 WORD 0 ... 65535 0 num
50 ORE COMP2 16513 R Compressor operating hours 2 WORD 0 ... 65535 0 num
51 ORE COMP3 16515 R Compressor operating hours 3 WORD 0 ... 65535 0 num
52 ORE COMP4 16517 R Compressor operating hours 4 WORD 0 ... 65535 0 num
53 ORE POMPA1 16519 R Pump operating hours 1 WORD 0 ... 65535 0 num
54 ORE POMPA2 16521 R Pump operating hours 2 1 bit 0 ... 65535 0 num
55 M_AONOFF 16989,8 R Remote Off input 1 bit 0 ... 1 0 num
56 M_HIPCIR1 16989,9 R High pressure pressostat circuit 1 1 bit 0 ... 1 0 num
57 M_LOPCIR1 16989,10 R Low pressure pressostat circuit 1 1 bit 0 ... 1 0 num
58 M_TERMC1 16989,11 R Thermal compressor alarm 1 1 bit 0 ... 1 0 num
59 M_TERMF1 16989,12 R Thermal fun 1 1 bit 0 ... 1 0 num
60 M_GELO1 16989,13 R Threshold exceeded of circuit 1 antifreeze alarm 1 bit 0 ... 1 0 num
61 M_ERRST2 16989,14 R Analog input fault 2 1 bit 0 ... 1 0 num
62 M_ERRST3 16989,15 R Analog input fault 3 1 bit 0 ... 1 0 num
63 M_OLIO1 16989,0 R High pressure compressor 1 1 bit 0 ... 1 0 num
64 M_POMPA1 16989,1 R Thermal pump 1 1 bit 0 ... 1 0 num
65 M_POMPA2 2189 R Thermal pump 2 1 bit 0 ... 1 0 num
66 M_TERMC2 2190 R Thermal compressor alarm 2 1 bit 0 ... 1 0 num
67 M_OLIO2 2191 R High pressure compressor 2 1 bit 0 ... 1 0 num
15
Modbus Variables List For UECH420DF
DATA
INDEX FOLDER LABEL ADDRESS R/W DESCRIPTION SIZE CPL RANGE DEFAULT EXP M.U.
68 M_HIPCIR2 16989,5 R High pressure pressostat circuit 2 1 bit 0 ... 1 0 num
69 M_LOPCIR2 16989,6 R Low pressure pressostat circuit 2 1 bit 0 ... 1 0 num
70 M_TERMC3 16989,7 R Thermal compressor alarm 3 1 bit 0 ... 1 0 num
71 M_TERMF2 16991,8 R Thermal fun 2 1 bit 0 ... 1 0 num
72 M_GELO2 16991,9 R Threshold exceeded of circuit 2 antifreeze alarm 1 bit 0 ... 1 0 num
73 M_ERRST5 16991,10 R Analog input fault 5 1 bit 0 ... 1 0 num
74 M_ERRST6 16991,11 R Analog input fault 6 1 bit 0 ... 1 0 num
75 M_OLIO3 16991,12 R High pressure compressor 3 1 bit 0 ... 1 0 num
76 M_GELO12 16991,13 R Threshold exceeded of external circuit antifreeze alarm 1 bit 0 ... 1 0 num
77 M_ERRST7 16991,14 R Analogue input fault 7 1 bit 0 ... 1 0 num
78 M_TERMC4 16991,15 R Thermal compressor alarm 4 1 bit 0 ... 1 0 num
79 M_OLIO4 16991,0 R High pressure compressor 4 1 bit 0 ... 1 0 num
80 M_ERRST1 16991,1 R Analog input fault 1 1 bit 0 ... 1 0 num
81 M_FLUSS 16991,2 R water flow meter 1 bit 0 ... 1 0 num
82 M_ERRST4 16991,3 R Analog input fault 4 1 bit 0 ... 1 0 num
83 M_ERRST8 16991,4 R Analog input fault 8 1 bit 0 ... 1 0 num
84 M_CONFIG 16991,5 R Error on digital inputs change mode 1 bit 0 ... 1 0 num
85 M_OVERH 16991,6 R High temperature input water 1 bit 0 ... 1 0 num
86 M_FLUREC 16991,7 R Recovery Flussostat 1 bit 0 ... 1 0 num
87 M_AONOFF 16993,8 R Off remote input 1 bit 0 ... 1 0 num
88 M_HIPCIR1 16993,9 R High pressure pressostat circuit 1 (manual reset) 1 bit 0 ... 1 0 num
89 M_LOPCIR1 16993,10 R Low pressure pressostat circuit 1 (manual reset) 1 bit 0 ... 1 0 num
90 M_TERMC1 16993,11 R Thermal compressor alarm 1 (manual reset) 1 bit 0 ... 1 0 num
91 M_TERMF1 16993,12 R Thermal fun 1 (manual reset) 1 bit 0 ... 1 0 num
92 M_GELO1 16993,13 R Threshold exceeded of circuit 1 antifreeze alarm (m. r.) 1 bit 0 ... 1 0 num
93 M_ERRST2 16993,14 R Analog input fault 2 (manual reset) 1 bit 0 ... 1 0 num
94 M_ERRST3 16993,15 R Analog input fault 3 (manual reset) 1 bit 0 ... 1 0 num
95 M_OLIO1 16993,0 R High pressure compressor 1 1 bit 0 ... 1 0 num
96 M_POMPA1 16993,1 R Thermal pump 1 (manual reset) 1 bit 0 ... 1 0 num
97 M_POMPA2 16993,2 R Thermal pump 2 (manual reset) 1 bit 0 ... 1 0 num
98 M_TERMC2 16993,3 R Thermal compressor Alarm 2 (manual reset) 1 bit 0 ... 1 0 num
99 M_OLIO2 16993,4 R High pressure compressor 2 1 bit 0 ... 1 0 num
100 M_HIPCIR2 16993,5 R High pressure pressostat circuit 2 (manual reset) 1 bit 0 ... 1 0 num
101 M_LOPCIR2 16993,6 R Low pressure pressostat circuit 2 (manual reset) 1 bit 0 ... 1 0 num
102 M_TERMC3 16993,7 R Thermal compressor alarm 3 (manual reset) 1 bit 0 ... 1 0 num
103 M_TERMF2 16995,8 R Thermal fun 2 (manual reset) 1 bit 0 ... 1 0 num
16
Modbus Variables List For UECH420DF
DATA
INDEX FOLDER LABEL ADDRESS R/W DESCRIPTION SIZE CPL RANGE DEFAULT EXP M.U.
104 M_GELO2 16995,9 R Threshold exceeded of circuit 2 antifreeze alarm ( m. r.) 1 bit 0 ... 1 0 num
105 M_ERRST5 16995,10 R Analog input fault 5 (manual reset) 1 bit 0 ... 1 0 num
106 M_ERRST6 16995,11 R Analog input fault 6 (manual reset) 1 bit 0 ... 1 0 num
107 M_OLIO3 16995,12 R High pressure compressor 3 1 bit 0 ... 1 0 num
108 M_GELO12 16995,13 R Threshold exceeded of external circuit antifreeze alarm(m.r.) 1 bit 0 ... 1 0 num
109 M_ERRST7 16995,14 R Analog input fault 7 (manual reset) 1 bit 0 ... 1 0 num
110 M_TERMC4 16995,15 R Thermal compressor alarm 4 (manual reset) 1 bit 0 ... 1 0 num
111 M_OLIO4 16995,0 R High pressure compressor 4 1 bit 0 ... 1 0 num
112 M_ERRST1 16995,1 R Analog input fault 1 (manual reset) 1 bit 0 ... 1 0 num
113 M_FLUSS 16995,2 R water flow meter (manual reset) 1 bit 0 ... 1 0 num
114 M_ERRST4 16995,3 R Analog input fault 4 (manual reset) 1 bit 0 ... 1 0 num
115 M_ERRST8 16995,4 R Analog input fault 8 (manual reset) 1 bit 0 ... 1 0 num
116 M_CONFIG 16995,5 R Error on digital inputs change mode (manual reset) 1 bit 0 ... 1 0 num
117 M_OVERH 16995,6 R High temperature input water (manual reset) 1 bit 0 ... 1 0 num
118 M_TE_FC 16995,7 R Thermal freecooling pump alarm 1 bit 0 ... 1 0 num
NOTA:
line 56.86: automatic reset
line 118: automatic reset
line 88.117: manual reset
17
Modbus Variables List For UECH420DF
18
Modbus Variables List For UECH420DF
19
UNIFLAIR S.p.A.
Legal and Aministrative Headquarters: Viale della Tecnica
2, 35026
Conselve (PD) Italy
Tel +39 049 5388211 Fax +39 049 5388212 - uniflair.com
[email protected]
P.IVA 02160760282 C.C.I.A.A. di PD R.E.A. 212586 del
21/04/1988 - R.I.N. 02160760282 M. PD004505
06MA002@00B0110