Auto-Transformer Impedance Worksheet
For: Example Transformer
INPUT DATA HV 400 kV Test Impedances on common base
XV 230 kV
TV 33 kV MVA base = 100
Transformer Positive Sequence Nameplate Impedances Converted to per unit
Measured Shorted Open Transformer Per Unit %Z
Impedance From Winding Winding %Z MVA base
ZHX H X T 15.00 520 +j 0.02885 +j 2.885
ZHT H T X 20.00 70 +j 0.28571 +j 28.571
ZXT X T H 15.00 70 +j 0.21429 +j 21.429
Transformer Zero Sequence Test Impedances
Measured Shorted Open Transformer pu %Z
Impedance From Winding Winding %Z MVA base
ZHX0 H X T 13.00 520 +j 0.02500 +j 2.500
ZHT0 H T X 17.00 70 +j 0.24286 +j 24.286
ZXT0 X T H 13.00 70 +j 0.18571 +j 18.571
CALCULATIONS
Equivalent Positive Sequence Star Leakage Impedances pu %Z
ZH1 = 1/2(ZHX + ZHT - ZXT) 0.05014 +j 5.014
ZX1 = 1/2(ZHX + ZXT - ZHT) -0.02129 +j -2.129
ZT1 = 1/2(ZHT + ZXT - ZHX) 0.23558 +j 23.558
Equivalent Zero Sequence Star Leakage Impedances pu %Z
ZH0 = 1/2(ZHX0 + ZHT0 - ZXT0) 0.04107 +j 4.107
ZX0 = 1/2(ZHX0 + ZXT0 - ZHT0) -0.01607 +j -1.607
ZT0 = 1/2(ZHT0 + ZXT0 - ZHX0) 0.20179 +j 20.179
System Parameter
Base = 100 MVA
System 400 kV
Connected to H
Z1sys = Z2sys = +j 5.0 %
Z0sys = +j 17.0 %
Z1sys = Z2sys = +j 0.050 pu
Z0sys = +j 0.170 pu
Transformer Positive Sequence Impedances from Impedance Worksheet
ZH1 0.0501 pu
ZX1 -0.0213 pu
ZT1 0.2356 pu
Transformer Zero Sequence Impedances from Impedance Worksheet
ZH0 0.0411 pu
ZX0 -0.0161 pu
ZT0 0.2018 pu
Positve Sequence Network of System & Transformer
For 3 Phase Fault on "H":
Z1 = Zsys, H side ll (ZH1 +ZX1+Zsys, X side)
Z1 = 0.0316 pu
If = 31.6487 pu
I fault 3 phase = 3165 MVA 4.568 kA
For 3 Phase Fault on "X":
Z1 = Zsys, X side ll (ZX1 +ZH1+Zsys, H side)
Z1 = 0.0331 pu
If = 30.2268 pu
I fault 3 phase = 3023 MVA 7.588 kA
Zero Sequence Network of System & Transformer
For Line to Ground Fault on "H" side
Z1 = Z2 = +j Z1sys, H side ll Z1sys, X side + ZX1+ZH1
Z1 = Z2 = +j 0.05 ll 0.09 =
Z0 = + j Z0sys, H side ll [(Z0sys, X side + ZX0) ll ZT0 + ZH0]
+ j 0.170 ll ( 0.1839 ll 0.202
+ j 0.170 ll ( 0.0962 + 0.041
+ j 0.170 ll 0.1373 =
I1 = I2 = I0 = 1/(Z1+Z2+Z0) = 1/(2*Z1+Z0)
I1=I2=I0 = 7.187 pu 1.03734
3I0 = 21.56 pu 3.1120
Ifault L-G = 3.11 kA
For Line to Ground Fault on "X" side:
Z1 = Z2 = Z1sys, X side ll Z1sys, H side + ZH1 + ZX1
Z1 = Z2 = 0.057 ll 0.0788 =
Z0 = + j Z0sys, X side ll [(Z0sys, H side+ZH0) ll ZT0 + ZX0]
+ j 0.200 ll 0.2111 ll 0.202
+ j 0.200 ll 0.1032 + -0.016
+ j 0.200 ll 0.0871 =
I1 = I2 = I0 = 1/(Z1+Z2+Z0) = 1/(2*Z1+Z0)
I1=I2=I0 = 7.884 pu 1.97914
3I0 = 23.652 pu 5.93741
Ifault L-G = 5.94 kA
230 kV
X
+j 5.7 %
+j 20.0 %
0.057 pu
0.200 pu
ZH1
+ j 0.0316
ll ZT0 + ZH0]
+ 0.041 )
)
+ j 0.0760
kA
kA
+j 0.0331
ll ZT0 + ZX0]
+ ZX0
+j 0.0607
kA
kA
Winding Currents for L-G Fault on "H" side:
I = common winding current = IH - IX
IN = current in grounded neutral = IfH - IfX
Assume fault is a phase "a" to ground fault:
then IaF = 3*I0 = 3.11 kA
H side system contribution:
I1 = I2 = 1.0373 X 0.63194
I0 = 1.0373 X 0.44678
Ia fault = 1.77 kA
H side Transformer contribution:
I1 = I2 = 1.0373 X 0.36806
I0 = 1.0373 X 0.55322
Ia fault = 1.34 kA
X side Transformer contribution:
HV/XV
I1X = I2X = 1.739 X 0.368063 X
I0X = 1.739 X 0.28941 X
Ia fault = 1.85 kA
Tertiary Current
I1 = I2 = I0 = 0.26380 X 1.0373 X
Tertiary Current direction is: OK
Neutral Current
Neutral Current -0.51 kA
Neutral Current direction is: Down
Winding Currents for L-G Fault on "X" side:
I = common winding current = IX - IH
IN = current in grounded neutral = IfX - IfH
Assume fault is a phase "a" to ground fault:
then IaF = 3*I0 = 5.94 kA
X side system contribution:
I1 = I2 = 1.9791 X 0.58041
I0 = 1.9791 X 0.30336
Ia fault = 2.90 kA
X side Transformer contribution:
I1 = I2 = 1.9791 X 0.41959
I0 = 1.9791 X 0.69664
Ia fault = 3.04 kA
H side Transformer contribution:
XV/HV
I1H = I2H = 0.575 X 0.419592 X
I0H = 0.575 X 0.34049 X
Ia fault = 1.34 kA
Tertiary Current
I1 = I2 = I0 = 0.35616 X 1.9791 X
I1 = I2 = I0 = 2.84
Tertiary Current direction is: OK
Neutral Current
Neutral Current 1.7 kA
Neutral Current direction is: Up
= 0.66 kA
= 0.46 kA
= 0.38 kA
= 0.57 kA
I1
1.0373 = 0.66 kA
1.0373 = 0.52 kA
(HV/1.732)/TV
7.0 = 1.92 kA
= 1.15 kA
= 0.60 kA
= 0.83 kA
= 1.38 kA
1.9791 = 0.48 kA
1.9791 = 0.39 kA
(LV/1.732)/TV
4.0 = 2.84 kA