Generator Neutral Grounding Resistor Calculations Equipment Data

This document contains calculations for selecting a neutral grounding resistor for a generator. It provides equipment data like phase capacitance values and cable properties. It then calculates the capacitance to ground, capacitive reactance, and resistive component of the neutral grounding resistor. The final calculations determine the maximum secondary current, required primary current, and power rating for the neutral grounding resistor.

Uploaded by

William Cheung
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
228 views

Generator Neutral Grounding Resistor Calculations Equipment Data

This document contains calculations for selecting a neutral grounding resistor for a generator. It provides equipment data like phase capacitance values and cable properties. It then calculates the capacitance to ground, capacitive reactance, and resistive component of the neutral grounding resistor. The final calculations determine the maximum secondary current, required primary current, and power rating for the neutral grounding resistor.

Uploaded by

William Cheung
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

Generator Neutral Grounding Resistor Calculations

Equipment Data TBC


unsat
Equipment Phase Cap to Ground (Co) X"d 0.203
Surge Cap 125000 pF 0.125uF base 34.97
Generator 140000 pF 0.14uF baseV 13.8
Cables 25904 pF
Main Trans 4000 pF 100 f
Aux Trans 1000 pF 0.0189394 mi

Co 295904.0487 pF Westinghouse T&D Reference Book


Cable Calc
Xco 8964.332852 Ohms k 2.3
d 18.77 mm
Xcg Xco/3 2988.110951 Ohms T 10.36 mm
T/d 0.551945 mm
Xcg/Rn (design param) 1 G 0.75
Co 0.273547 uF per phase per mile
Rn Xcg 2988.110951 Ohms # of Cables per phase 5

N (gnd transformer) 66.39528096

Rsec Rn/N^2 0.677832352


% Field Forcing 30%
Isec max 177.0349256 A
Ipri 3.46629158 A

Resistor Rating 21.24419108 kW

Trans Rating 21.24419108 kVA