11kV Checklist
11kV Checklist
html
Once all the test results are produced and verified by the Consulting Engineer/Designer and
all tests have been verified by the Service Engineer, then only the 11-kV electricity supply be
switched on the incoming Circuit Breaker/LBS.
There are other basic and important requirement such as Danger and No-Entry signages, 11-
Kv and 415-V Switch Boards labelling, Rubber Mat, CPR Intruction Manual, As-built
Diagram, etc. must be installed before or once the switchboards are energised.
B. Distribution Transformer
1. 11-kV Primary cable termination is a bit doubtful (saddled with wood)
2. Cable trenches are not properly constructed and covered
3. Secondary cables (415V) are not properly saddled/bracketed to the side walls of trench;
instead the cables are 'pulling-down' the bus-bar attached to cable termination flags
4. PVC/PVC green cable used as star-point neutral is not properly terminated/linked/welded
to the earth electrode at the earth pit;
5. To verify whether the Alarm and TRip contacts are linked to the Ring Main Unit (RMU)