1MRK509004-BEN A en Time Over Undervoltage Relays and Protection Assemblies RXEDK 2H RAEDK PDF

The document describes a microprocessor-based time over/undervoltage relay with two independently switchable measuring stages. Stage 1 can be programmed for inverse or definite time characteristics, while Stage 2 has a fixed definite time delay from 30ms to 10s. The relay can be used for applications including neutral point voltage protection, overvoltage protection, flashover protection, undervoltage protection, and stator earth fault protection. Key features include adjustable settings for voltage start values and time delays on each stage.

Uploaded by

Eryanto Setyono
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
601 views18 pages

1MRK509004-BEN A en Time Over Undervoltage Relays and Protection Assemblies RXEDK 2H RAEDK PDF

The document describes a microprocessor-based time over/undervoltage relay with two independently switchable measuring stages. Stage 1 can be programmed for inverse or definite time characteristics, while Stage 2 has a fixed definite time delay from 30ms to 10s. The relay can be used for applications including neutral point voltage protection, overvoltage protection, flashover protection, undervoltage protection, and stator earth fault protection. Key features include adjustable settings for voltage start values and time delays on each stage.

Uploaded by

Eryanto Setyono
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 18

Time over/undervoltage relay RXEDK 2H and

and protection assemblies RAEDK


1MRK 509 004-BEN
Page 1
Issued January 2004
Revision: A
Data subject to change without notice

(SE970120)
(SE970114)

Features Micro-processor based time-over/under- Stage 1 is programmable for two time


voltage relay with continuous settings for characteristics:
start and time functions - Inverse time
Three variants, with wide setting ranges in - Definite time delay settable
two measuring stages: 50 ms-16,1 s
- Stage 1: U1 = (0,5-1,0) x Us
Stage 2 can be delayed up to 10 s
- Stage 2: U2 = (0,25-1,5) x Us Reset ratio typical 96% for overvoltage
- Us = (0,2-1,6) x Ur unction and 104% for undervoltage func-
tion enables a setting close to maximum
The two measuring stages are switchable service values
for over- or undervoltage function indepen-
Available with optional filters for different
dently of each other
frequency characteristics:
- 50-60 Hz, Sharp
- 150-180 Hz, Sharp
- 16 2/3 Hz, Flat
Time over/undervoltage relay and RXEDK 2H and
protection assemblies RAEDK
1MRK 509 004-BEN
Page 2

Application RXEDK 2H is a time-over/undervoltage The time-over/undervoltage relays of type


relay with two measuring stages, which are RXEDK 2H can be used in a number of dif-
switchable for over- or undervoltage func- ferent applications such as:
tions independently of each other. Stage 1 is
programmable for the following two different Neutral point voltage protection
time functions: Time delayed single-phase relay is used to
detect occurrence of an earth fault in a net-
- Definite-time characteristic where the work by detecting neutral point voltage on an
operate time is independent of the volt- open delta winding of phase transformers or
age deviation. The definite-time is set- on a neutral transformer. The start step can be
table from 50 ms to 16,1 s. used to release selective earth fault current
- Inverse time characteristic where the protection.
operate time is dependent of the voltage 1000
deviation from the set value (see Fig. 1).
The relationship between time and volt-
age for this characteristic can be 100
expressed as follows:
Time(s) k=16 k=16

Overvoltage function: 10
k=5 k=5
standard k
t = ----------------- [ s ] k=2 k=2
U
-------- 1 1 k=0,5 k=0,5
U1

16 2/3 Hz 0,1
alternative version 0 1 2
U/U1
k
t = ----------------------------------
- (96000260)
------
U 0, 5
- 1
U 1 Fig. 1 Inverse time characteristic.

Undervoltage function: Overvoltage protection


standard For generator protection an overvoltage relay
k is used to detect failure in voltage regulation.
t = ----------------- [ s ] For transformers and transmission lines,
U
1 -------- overvoltage protection is sometimes used to
U1
detect excessive voltages. For these applica-
tions the high reset ratio is essential.

Flash-over protection
16 2/3 Hz For transformer low voltage windings an
alternative version instantaneous protection will detect the high
k overvoltages occurring at a flash-over from
t = ----------------------------------
- the high to low voltage side of transformers
1 ------ U 0, 5
-
U 1 where the low voltage side is not solidly
earthed.

Undervoltage protection
where An undervoltage protection is used to discon-
k = inverse time constant nect motors at low system voltage to prevent
U1 = over/undervoltage start value problems with inrush at system voltage
U = operate value recovery. Single-phase versions connected
phase-phase are used for asynchronous
Time characteristics is independent to the set- motors, whereas measuring of positive
table value. The delay time is settable sequence voltage is used for synchronous
between 50 ms and 16,1 s. motors.

Stage 2 has a definite-time characteristic, and Stator earth fault protection


is settable from 30 ms to 10 s. With optimal filters for measuring either fun-
damental overvoltage or third harmonic
undervoltage.
Time over/undervoltage relay and RXEDK 2H and
protection assemblies RAEDK
1MRK 509 004-BEN
Page 3

Design The voltage relay assemblies with RXEDK Operate values for both stage 1 and 2, are set
2H can be delivered in several variants for with the potentiometers and programming
single- and three-phase over- or undervoltage switches marked with Us. Both measuring
protection with different output circuits. stages can independently be programmed for
over- or undervoltage functions. Operation
All assemblies are with test switch RTXP 18, occurs for a voltage equal to or larger/lower
for simple secondary testing, and with trip than the product of set scale value and the
indication either with LED or flag relay. selected scale constant.

The RXEDK 2H relay requires a separate dc- The start function output is energized imme-
dc converter for auxiliary supply (24 V). diately after the measured value exceeds or
One RXTUG converter can supply up to nine falls below the set start voltage level.
relays.
Stage 1 can be set for definite-time or
Note: inverse-time delay, while stage 2 only has
When RXEDK 2H relay or the dc-dc con- definite time delay.
verter RXTUG is plugged into or withdrawn
from a terminal base, the auxiliary voltage For definite-time delayed operation the time
supply must be interrupted. Neither is it voltage output operates after the set time
allowed to open wiring on plus or minus sup- delay.
ply with unit in service.
For inverse-time operation, the operate time
RXEDK 2H measuring relay will depend on the time setting (constant k +
The over/undervoltage relay, type RXEDK setting of programming switches), and by
2H, is a static microprocessor based relay how much the measured voltage magnitude
with two delayed stages. The relay consists exceeds or falls below the start voltage level
mainly of an input voltage transformer, filter setting (see Fig. 1 for operation characteris-
circuits, microprocessor, HMI, LEDs for start tic).
and trip indications and three output units
which provide separate change-over contacts The relay can be supplied with optional filters
for start and trip of stage 1, and trip of for sharp measuring of fundamental frequen-
stage 2. The relay has also one binary input cies (50-60 Hz) or third harmonics (150-
for reset LED. 180 Hz). The characteristics of the filters are
shown in Fig. 2.
Time over/undervoltage relay and RXEDK 2H and
protection assemblies RAEDK
1MRK 509 004-BEN
Page 4

Technical data
Table 1: Voltage input
Rated voltage Ur 2/5 V or 20/50 V or 100/200 V, For 16 2/3 Hz: 2/5 V or 20/50 V,
For 16 2/3 Hz: alternative version 20/50 V
Scale constant Us, (0,2-1,6) x Ur (in steps of 0,2)
Setting ranges
Stage U1
2/5 V 0,2-3,2 V/0,5-8 V
20/50 V 2-32 V/5-80 V
100/200 V 10-160 V/20-320 V
Stage U2
2/5 V 0,1-4,8 V/0,25-12V
20/50 V 1-48 V/2,5-120 V
100/200 V 5-240 V/10-480 V
Effective voltage range U (0,25-2,0) x Us
Rated frequency fr 50-60 Hz 16 2/3Hz
Filter opt.:
50-60 Hz, flat std (see Fig. 2) (see Fig. 5)
50-60 Hz, sharp (see Fig. 3)
150-180 Hz, sharp (see Fig. 4)
Frequency range 40-1000 Hz 15-150 Hz
Power consumption
U = lowest Us 2 mVA
U = highest Us 210 mVA
Overload capacity
continuously 3,5 x Ur (Max. 500 V AC for COMBIFLEX)
during 10 s 4,0 x Ur (Max. 500 V AC for COMBIFLEX)

Table 2: Start and trip functions for standard, 50 Hz sharp and 150-180 Hz sharp
Voltage function Stage U1 Stage U2
Scale range (0,5-1,0) x Us (0,25-1,5) x Us
Measuring mode Over/Under voltage
Operate time Start function t = 0,03 s
Over-voltage (typical)
U = 0 => 1,1 x op. value 45 ms 45 ms
U = 0 => 1,5 x op. value 40 ms 40 ms
U = 0,9 => 1,1 x op. value 35 ms 35 ms
U = 0,9 => 1,5 x op. value 30 ms 30 ms
U = 0,9 => 2,0 x op. value 25 ms 25 ms
Under-voltage (typical)
U = 1,1 => 0,9 x op. value 35 ms 35 ms
U = 1,1 => 0,5 x op. value 30 ms 30 ms
U = 1,1 => 0 x op. value 25 ms 25 ms
Reset time, Over-voltage (typical) Start function t = 0,03 s
U = 1,5 => 0,9 x op. value 35 ms 35 ms
U = 1,5 => 0 x op. value 45 ms 45 ms
Consistency of the operate value < 0,5%
Reset ratio over/under > 95% / <105%
Recovery time < 50 ms
Overshoot time < 25 ms
Time over/undervoltage relay and RXEDK 2H and
protection assemblies RAEDK
1MRK 509 004-BEN
Page 5

Table 2: Start and trip functions for standard, 50 Hz sharp and 150-180 Hz sharp
Voltage function Stage U1 Stage U2
Frequency dependence within
frequency range 50 Hz, 5% < 0,5%
frequency range 60 Hz, 5% < 1,0%
Operate value at 150 Hz App. 1,45 x op. value at 50 Hz
Influence of harmonics
100 / 120 Hz, 5% < 2%
150 / 180 Hz, 20% < 6%
250 / 300 Hz, 20% < 3%

Table 3: Time functions for standard, 50 Hz sharp and 150-180 Hz sharp


Time function Stage U1 Stage U2
Time delay Definite time and inverse time Definite time
Setting range
Definite time, Def. time t = 0,05-16,1 s 0,03-10 s
Inverse time, Inv k = 0,05-16,1
Formula for inverse time
Overvoltage function t = k / (a - 1)
Undervoltage function t = k / (1 - a)
k = Inverse time factor
a = Over / under-voltage times
operate value
Accuracy
Definite time 1% and 10 ms 1% and 10 ms
Inverse time 1% of the over/under-voltage
and 10 ms or 3% of the oper-
ate time and 30 ms
Consistency < 0,5% < 0,5%

Table 4: Filter option, deviation from technical data for RXEDK 2H, standard
Filter options
50-60 Hz, sharp 150-180 Hz, sharp
Operate time for start function
over-voltage (typical)
U = 0 => 1,1 x op. value 90 ms 65 ms
U = 0 => 1,5 x op. value 70 ms 50 ms
Reset ratio for over-voltage > 95%
Recovery time < 50 ms < 50 ms
Overshoot time < 35 ms < 30 ms
Frequency dependence within
frequency range 5% < 15% < 15%
Influence of harmonics
50, 60 Hz, 100% < 1%
100, 120 Hz, 100% < 3% < 2%
150, 180 Hz, 100% < 3%
250, 300 Hz, 100% < 1% < 2%
Time over/undervoltage relay and RXEDK 2H and
protection assemblies RAEDK
1MRK 509 004-BEN
Page 6

Technical data (contd)


Table 5: Start and trip functions 16 2/3 Hz
Voltage function Stage U1 Stage U2
Scale range (0,5-1,0) x Us (0,25-1,5) x Us
Measuring mode Over/Under voltage
Operate time Start function t = 0,08 s
Over-voltage (typical)
U = 0,9 => 1,1 x op. value 75 ms 75 ms
U = 0,9 => 1,5 x op. value 55 ms 55 ms
U = 0,9 => 2,0 x op. value 50 ms 50 ms

Under-voltage (typical)
U = 1,1 => 0,9 x op. value 75 ms 75 ms
U = 1,1 => 0,5 x op. value 55 ms 55 ms
U = 1,1 => 0 x op. value 50 ms 50 ms
Reset time, Over-voltage (typical) Start function t = 0,08 s
U = 1,1 => 0,9 x op. value 85 ms 85 ms
U = 1,1 => 0,5 x op. value 60 ms 60 ms
U = 1,1 => 0 x op. value 50 ms 50 ms
Consistency of the op. value < 1,0%
Reset ratio Over/Under > 95% / < 105%
Recovery time over-voltage
U = 1,1 => 0 x op. value < 60 ms
U = 2,0 => 0 x op. value < 90 ms
Overshoot time < 60 ms
Frequency dependence within
frequency range 15,00-18,33 Hz < 2,0%
Influence of harmonics
33 1/3 Hz, 5% < 2%
50 Hz, 20% < 5%
83 1/3 Hz, 20% < 3%

Table 6: Time functions 16 2/3 Hz


Time function Stage U1 Stage U2
Time delay Definite time and inverse time Definite time
Setting range
Definite time, Def. time t = 0,05-16,1 s 0,08-10 s
Inverse time, Inv k = 0,05-16,1
Formula for inverse time
Overvoltage function t = k / (a - 1) *) t = k / (a0,5 - 1)
Undervoltage function t = k / (1 - a) *) t = k / (1 - a0,5)
k = Inverse time factor
a = Over / under-voltage times
operate value
*) 16 2/3 Hz alternative version
Accuracy
Definite time 1% and 30 ms 1% and 30 ms
Inverse time 1% of the over/under-voltage and 30 ms
or 3% of the operate time and 60 ms
Consistency < 0,5% < 0,5%
Time over/undervoltage relay and RXEDK 2H and
protection assemblies RAEDK
1MRK 509 004-BEN
Page 7

Table 7: Auxiliary DC voltage supply


Auxiliary voltage EL for RXTUG 22H 24-250 V DC, 20%
Auxiliary voltage to the relay 24 V (from RXTUG 22H)
Power consumption at RXTUG 22H input Standard Other filters
24-250 V
before operation Max. 4,5 W Max. 5,5 W
after operation Max. 6,0 W Max. 6,5 W
without RXTUG 22H
24 V
before operation Max. 1,3 W Max. 2,0 W
after operation Max. 3,0 W Max. 3,0 W

Table 8: Binary input


Binary input voltage RL 48-60 V and 110-220 V DC, -20% to +10%
Power consumption
48-60 V Max. 0,3 W
110-220 V Max. 1,5 W

Table 9: Output relays


Contacts 3 change-over
Maximum system voltage 250 V AC / DC.
Current carrying capacity
continuous 5A
during 1 s 15 A
Making capacity at inductive load with L/R >10 ms
during 200 ms 30 A
during 1 s 10 A
Breaking capacity
AC, max. 250 V, cos > 0,4 8A
DC, with L/R < 40 ms
48 V 1A
110 V 0,4 A
220 V 0,2 A
250 V 0,15 A

Table 10: Electromagnetic compatibility (EMC), immunity tests


All tests are done together with the DC/DC-converter, RXTUG 22H
Test Severity Standard
Surge 1 and 2 kV, normal service IEC 61000-4-5, class 3
2 and 4 kV, destructive test IEC 61000-4-5, class 4
AC injection 500 V, AC SS 436 15 03, PL 4
Power frequency magnetic field 1000 A/m IEC 61000-4-8
1 MHz burst 2,5 kV IEC 60255-22-1, class 3
Spark 4-8 kV SS 436 15 03, PL 4
Fast transient 4 kV IEC 60255-22-4, class 4
Electrostatic discharge
In normal service with cover on 8 kV (contact) IEC 60255-22-2, class 4
15 kV (air) IEC 60255-22-2, class 4
8 kV, indirect application IEC 61000-4-2, class 4
Radiated electromagnetic field 10 V/m, 26-1000 MHz IEC 61000-4-3, level 3
Conducted electromagnetic 10 V, 0,15-80 MHz IEC 61000-4-6, level 3
Interruptions in auxiliary voltage 2-200 ms IEC 60255-11
110 V DC, no resetting for interruptions < 40 ms
Time over/undervoltage relay and RXEDK 2H and
protection assemblies RAEDK
1MRK 509 004-BEN
Page 8

Technical data (contd)


Table 11: Electromagnetic compatibility (EMC), emission tests
Test Severity Standard
Conducted 0,15-30 MHz, class A EN 50081- 2
Radiated 30-1000 MHz, class A EN 50081- 2

Table 12: Insulation tests


Test Severity Standard
Dielectric
Circuit to circuit and circuit to earth 2,0 kV AC, 1 min IEC 60255-5
Over open contact 1,0 kV AC, 1 min
Impulse voltage 5 kV, 1,2/50 s, 0,5 J IEC 60255-5
Insulation resistance > 100 M at 500 V DC IEC 60255-5

Table 13: Mechanical tests


Test Severity Standard
Vibration Response: 2,0 g, 10-150-10 Hz IEC 60255-21-1, class 2
Endurance: 1,0 g, 10-150-10 Hz, 20 sweeps IEC 60255-21-1, class 1
Shock Response: 5 g, 11 ms, 3 pulses IEC 60255-21-2, class 1
Withstand: 15 g, 11 ms, 3 pulses
Bump Withstand: 10 g, 16 ms, 1000 pulses IEC 60255-21-2, class 1
Seismic X axis: 3,0 g, 1-35-1 Hz IEC 60255-21-3, class 2
Y axis: 3,0 g, 1-35-1 Hz extended (Method A)
Z axis: 2,0 g, 1-35-1 Hz

Table 14: Temperature range


Storage -20 C to +70 C
Permitted ambient temperature -5 C to +55 C

Table 15: Weight and dimensions


Equipment Weight Height Width
RXEDK 2H without RXTUG 22H 0,7 kg 4U 6C
Time over/undervoltage relay and RXEDK 2H and
protection assemblies RAEDK
1MRK 509 004-BEN
Page 9

Operate value/set operate value

10
9
8
7
6
5

1
40 50 60 100 150 180 250 300 400 500 1000
Frequency

Fig. 2 Typical frequency characteristic for RXEDK 50-60 Hz, standard, valid for U 2,0 x Us.

Operate voltage/set operate voltage

10
9
8
7
6
5

1
40 50 60 70 80 90 100
Frequency

Fig. 3 Typical frequency characteristic for RXEDK 50-60 Hz, sharp, valid for U 2,0 x Us.
Time over/undervoltage relay and RXEDK 2H and
protection assemblies RAEDK
1MRK 509 004-BEN
Page 10

Technical data (contd)


Operate voltage/set operate voltage

10
9
8
7
6
5

1
100 150 180 200 250 300
Frequency

Fig. 4 Typical frequency characteristic for RXEDK 150-180 Hz, sharp, valid for U 2,0 x Us.

Operate voltage/set operate voltage

3,5

2,5

1,5

1
15 16,7 20 25 30 40 50 60 70 80 90 100
Frequency

Fig. 5 Typical frequency characteristic for RXEDK 16 2/3Hz, flat, valid for U 2,0 x Us.
Time over/undervoltage relay and RXEDK 2H and
protection assemblies RAEDK
1MRK 509 004-BEN
Page 11

Diagrams

(96000261)
Fig. 6 Terminal diagram RXEDK 2H.

Fig. 7 Terminal diagram 1MRK 001 014-EAA


Time over/undervoltage relay and RXEDK 2H and
protection assemblies RAEDK
1MRK 509 004-BEN
Page 12

Diagrams (contd)

Fig. 8 Terminal diagram 1MRK 001 014-ZAA

Protection RAEDK normally available with output logic with


assemblies Protection assemblies are built up based upon heavy duty relay RXME 18 (RK 221 825-
time voltage relay RXEDK 2H. Test device XX) with indicating flag and can upon
RXTP 18 and dc/dc-converter RXTUG 22H request be completed with an output logic of
can also be included for specific application free choice. Output relays are connected to
requirements. Test device RTXP 18 is a tool separate auxiliary voltage.
for relay testing.
The extremely flexible mounting system
DC/DC-converter RXTUG 22H can be used COMBIFLEX together with a modern CAD-
either separately for a single protection or to system enables us to present a unique flexi-
feed also other protections with up to 9 units bility for designing assemblies upon the cus-
of the same relay family. With RXTUG 22H tomers requests.
all requirements concerning disturbance
emission and immunity with this protection The interface voltage for enable or block
assembly will be met. impulses can be connected to either 48-
60 V dc or 110-220 V dc by connecting the
The assemblies have output contacts as speci- voltage circuit to separate terminals. At deliv-
fied for the relay RXEDK 2H, which in most ery all relays are connected for 110-220 V dc.
cases are fully sufficient. Protections are
Time over/undervoltage relay and RXEDK 2H and
protection assemblies RAEDK
1MRK 509 004-BEN
Page 13

RAEDK 1 Single-phase voltage protection

27,59 101 107 101 107 101 107 113 101 107 113 119
U><
2
319

1=> 0

101 RTXP 18 101 RXTUG 22H 101 RTXP 18 101 RTXP 18


107 RXEDK 2H 107 RXEDK 2H 107 RXTUG 22H 107 RXTUG 22H
113 RXEDK 2H 113 RXEDK 2H
119 RXME 18
319 RXME 18

Order No. Circuit Order No. Circuit Order No. Circuit Order No. Circuit
diagram diagram diagram diagram
Standard 1MRK 1MRK 1MRK 1MRK 1MRK 1MRK 1MRK 1MRK
001 013-BS 001 014-BA 001 013-CS 001 014-CA 001 013-DS 001 014-DA 001 013-ET 001 014-EA
Filter 1MRK 1MRK 1MRK 1MRK 1MRK 1MRK 1MRK 1MRK
001 013-BA 001 014-BA 001 013-CA 001 014-CA 001 013-DA 001 014-DA 001 013-EA 001 014-EA

RAEDK 2 Two-phase voltage protection

27,59 101 107 113 101 107 113 119 101 107 113 119 125
2U >
101 107 113
<
2
325

1=> 0

101 RTXP 18 101 RXTUG 22H 101 RTXP 18 101 RTXP 18


107 RXEDK 2H 107 RXEDK 2H 107 RXTUG 22H 107 RXTUG 22H
113 RXEDK 2H 113 RXEDK 2H 113 RXEDK 2H 113 RXEDK 2H
119 RXEDK 2H 119 RXEDK 2H
125 RXME 18
325 RXME 18

Order No. Circuit Order No. Circuit Order No. Circuit Order No. Circuit
diagram diagram diagram diagram
Standard 1MRK 1MRK 1MRK 1MRK 1MRK 1MRK 1MRK 1MRK
001 013-GS 001 014-GA 001 013-HS 001 014-HA 001 013-KS 001 014-KA 001 013-LS 001 014-LA
Filter 1MRK 1MRK 1MRK 1MRK 1MRK 1MRK 1MRK 1MRK
001 013-GA 001 014-GA 001 013-HA 001 014-HA 001 013-KA 001 014-KA 001 013-LA 001 014-LA
Time over/undervoltage relay and RXEDK 2H and
protection assemblies RAEDK
1MRK 509 004-BEN
Page 14

Protection
assemblies (contd)

RAEDK 3 Three-phase voltage protection

27,59 101 107 113 119 101 107 113 119 101 107 113 119 125 101 107 113 119 125 131
3U >
<
2
331

1=> 0

101 RTXP 18 101 RXTUG 22H 101 RTXP 18 101 RTXP 18


107 RXEDK 2H 107 RXEDK 2H 107 RXTUG 22H 107 RXTUG 22H
113 RXEDK 2H 113 RXEDK 2H 113 RXEDK 2H 113 RXEDK 2H
119 RXEDK 2H 119 RXEDK 2H 119 RXEDK 2H 119 RXEDK 2H
125 RXEDK 2H 125 RXEDK 2H
131 RXME 18
331 RXME 18

Order No. Circuit Order No. Circuit Order No. Circuit Order No. Circuit
diagram diagram diagram diagram
Standard 1MRK 1MRK 1MRK 1MRK 1MRK 1MRK 1MRK 1MRK
001 013-NS 001 014-NA 001 013-YS 001 014-YA 001 013-PS 001 014-PA 001 013-ZS 001 014-ZA
Filter 1MRK 1MRK 1MRK 1MRK 1MRK 1MRK 1MRK 1MRK
001 013-NA 001 014-NA 001 013-YA 001 014-YA 001 013-PA 001 014-PA 001 013-ZA 001 014-ZA

Mounting All assemblies can be delivered in the


alternatives following mounting alternatives:

- on apparatus bars
- in equipment frame 60C
- in RHGX
- in RHGS
Time over/undervoltage relay and RXEDK 2H and
protection assemblies RAEDK
1MRK 509 004-BEN
Page 15

Ordering Specify RAEDK (Protection): Specify RXEDK (Loose Relay):


Quantity Quantity
Ordering number Ordering number
Code U, H, M
Desired wording on the lower half of the
test switch face plate max. 13 lines with 14
characters per line.

Over/undervoltage relay, standard 50-60 Hz


Type Voltage Filter Article No. Code
RXEDK 2H 2/5 V 50-60 Hz (standard) 1MRK 000 841-AA U1
RXEDK 2H 20/50 V 50-60 Hz (standard) 1MRK 000 841-HA U5
RXEDK 2H 100/200 V 50-60 Hz (standard) 1MRK 000 841-RA U9

Over/undervoltage relay; with optional filters


Type Voltage Filter Article No. Code
RXEDK 2H 2/5 V 50-60 Hz (sharp) 1MRK 000 841-BA U2
RXEDK 2H 2/5 V 150-180 Hz (sharp) 1MRK 000 841-CA U3
RXEDK 2H 2/5 V 16 2/3 Hz (flat) 1MRK 000 841-EA U4
RXEDK 2H 20/50 V 50-60 Hz (sharp) 1MRK 000 841-KA U6
RXEDK 2H 20/50 V 150-180 Hz (sharp) 1MRK 000 841-LA U7
2
RXEDK 2H 20/50 V 16 /3 Hz (flat) 1MRK 000 841-NA U8
RXEDK 2H 100/200 V 50-60 Hz (sharp) 1MRK 000 841-SA U10
RXEDK 2H 100/200 V 150-180 Hz (sharp) 1MRK 000 841-TA U11
RXEDK 2H 20/50 V 16 2/3 Hz (alternative version) 1MRK 000 841-PA U12

Auxiliary voltage
For included auxiliary relays
Code
24 V dc H5
48-55 V dc H6
110-125 V dc H7
220-250 V dc H8
Time over/undervoltage relay and RXEDK 2H and
protection assemblies RAEDK
1MRK 509 004-BEN
Page 16

Mounting
Mounting alternatives Size Article No. Code
Apparatus bars M10
Equipment frame without door 4U 19 1MRK 000 137-GA M11
Equipment frame with door 4U 19 1MRK 000 137-KA M12
RHGX 4 4U 12C RK 927 001-AB M71
RHGX 8 4U 24C RK 927 002-AB M72
RHGX 12 4U 36C RK 927 003-AB M73
RHGX 20 4U 60C RK 927 004-AB M74
RHGS 30 6U x 1/1 19 rack 1MRK 000 315-A M81
RHGS 12 6U x 1/2 19 rack 1MRK 000 315-B M82
RHGS 6 6U x 1/4 19 rack 1MRK 000 315-C M83
Time over/undervoltage relay and RXEDK 2H and
protection assemblies RAEDK
1MRK 509 004-BEN
Page 17

References Connection and installation components in


COMBIFLEX 1MRK 513 003-BEN

Relay accessories COMBIFLEX 1MRK 513 004-BEN

Users Guide RXEDK 1MRK 508 008-UEN

Manufacturer ABB Automation Technology Products AB


Substation Automation
SE-721 59 Vsters
Sweden
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
www.abb.com/substationautomation
Time over/undervoltage relay and RXEDK 2H and
protection assemblies RAEDK
1MRK 509 004-BEN
Page 18