100% found this document useful (1 vote)
2K views

Tank Mat Foundation Design

This document provides design specifications for a foundation supporting a tank. It includes: 1) Dimensions and load data for the equipment, structural components, soil properties, and design load combinations. 2) Calculations of the seismic forces, wind loads, foundation weight, buoyant force, and maximum soil bearing pressures. 3) Checks that the foundation design meets requirements for allowable soil bearing capacity, sliding resistance, and overturning stability.

Uploaded by

dantevarias
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
2K views

Tank Mat Foundation Design

This document provides design specifications for a foundation supporting a tank. It includes: 1) Dimensions and load data for the equipment, structural components, soil properties, and design load combinations. 2) Calculations of the seismic forces, wind loads, foundation weight, buoyant force, and maximum soil bearing pressures. 3) Checks that the foundation design meets requirements for allowable soil bearing capacity, sliding resistance, and overturning stability.

Uploaded by

dantevarias
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

TOSHIBA PLANT SYSTEMS & SERVICES CORPORATION CAL-NC-XCSV2-0115 Rev.

2.3 STABILITY AND STRENGTH DESIGN


1 DIMENSION DATA

le
B = 5.310 m , footing width
L = 5.310 m , footing length
he = 5.745 m , height of equipment
x
B be = 4.512 m , width of equipment
le = 4.512 m , length of equipment
he d1 = 0.35 m
d2 = 2.00 m
z
d3 = 0.00 m
Q M h
L h = 3.00 m
H
d1
d2
d3

Rubble/LeanConcrete

1. DESIGN LOAD 4) SEISMIC CALCULATION


1) EQUIPMENT LOADING DATA Tank Seismic Force :
Empty Weight (Qe) = 6,691 kg = 65.57 KN Total Design Base Shear, He = 30.24 kN
Operation Weight (Qo) = 66,855 kg = 655.18 KN Ring Wall Overturning Moment, Mrw = 67.25 kN.m
Test Weight (Qt) = 73,580 kg = 721.08 KN Slab Overturning Moment, Ms = 85.92 kN.m
Total Design Moment about shell to
= Mrw + Ms
2) WEIGHT OF STRUCTURAL PROPER bottom of tank, Mt
3
Soil (s) = 18.0 KN/m = 153.17 kN.m
3
Reinforced concrete (rc) = 24.0 KN/m
Ground water (w) = 10.0 KN/m 3 Maximum Seismic Coefficient = 0.084
*) assumed ground water level GL-0.0m shall be considered on design
Foundation Seismic Force, Hef = 0.084 x (Wf+Wrc)
3) LOAD COMBINATION = 133.64 kN
For soil bearing capacity & stability check
Components A B C D E F 5) WIND CALCULATION
FDN Weight 1.0 1.0 0.9 1.0 0.9 1.0 Velocity Pressure (qz) = 1.28 kN/m 2
Empty 0.9 0.9 Total Wind Moment, Mwt = 77.34 kN.m
Operation 1.0 1.0 1.0 Wind Shear Force on Tank, Hw = 29.79 kN
Test 1.0 Hw < 0.7He, L/C B is neglective
Wind 1.0 1.0
Earthquake 0.70 0.70 6) FOUNDATION WEIGHT
Footing Weight (Wf) = 1591 kN
Rubble Concrete (Wrc) = 0 kN
2. SOIL BEARING CHECK
3.1 ALLOWABLE BEARING CAPACITY 7) BOUYANT FORCE
For fixed load Bouyant Force (Bf) = 564 kN
Qaf = 250.0 kN/m 2
For combined load
Qac = 250.0 kN/m 2 3. SLIDING CHECK

3.2 ACTUAL BEARING PRESSURE : Friction coefficient = 0.35


qmax : P/Af + Mx/Sfx + Mz/Sfz, Maximum soil reaction, kN/m 2 F : Actual safety ratio
qmin : P/Af - Mx/Sfx - Mz/Sfz, Minimum soil reaction, kN/m 2 N : Wf + Q - Bf
P : Q + Wf + Wrc, Total Vertical Load, kN Due to Load Case C:
Total Moment about X-Axis, kN-m : N 0.35 x 927
F = = = 10.89 > 1.5 OK
Case B & C Hw 29.8
Mx : M + H * ( d1 + d2) Due to Load Case E:
Case D & E N 0.35 x 927
F = = = 2.83 > 1.5 OK
Mx : M + (H*(d1 + d2))+ (Hef * (d1 + d2)/2)) 0.7*He 114.7

Af : 28.2 m 2 , B * L, Area of Footing 4. OVERTURNING CHECK


Sfx : 24.95 m 3 , (L * B2 ) / 6, Section Modulus of Footing about X-Axis MR : Resisting moment
MO : Overturning moment
N : Wf + Qo - Bf
CASE P (kN) Mx (kN) qmax qmin Ratio Judge Due to Load Case C:
A 2246 0 80 80 0.32 OK! B 5.310
MR = N = 927 x = 2461.0 kNm
B 2246 147 86 74 0.34 OK! 2 2
C 1491 147 59 47 0.24 OK!
Mo = 147 kNm
D 2246 267 90 69 0.36 OK!
E 1491 267 64 42 0.25 OK! MR 2461.0
F = = = 16.70 > 1.5 OK
F 2312 0 82 82 0.33 OK! Moe 147.3
5 RE-BAR ARRANGEMENT Due to Load Case E:
This foundation is a block foundation so re-bar requirement is only shrinkage B 5.310
MR = N = 927 x = 2461.0 kNm
requirement based on 300mm concrete layer at each face with 0.3% 2 2
reinforcement
Mo = 267 kNm

Closer Bar D16 @ 200 MR 2461.0


F = = = 9.22 > 1.5 OK
Bottom Bar D16 @ 200 Moe 267

Asc = 1005.3 mm 2 0.003Ac OK 5. UPLIFT CHECK


Asb = 1005.3 mm 2 0.003Ac OK P : Q + Wf + Wrc, Total Vertical Load, kN
BF : Bouyant Force
Due to Load Case Empty Condition:
P 1491
F = = = 2.64 > 1.1 OK
BF 564
Due to Load Case Operation Condition:
P 2246
F = = = 3.98 > 1.5 OK
BF 564