03-KERYS - Navigation (Operator Access) ENG

1. The document discusses the menus and functions available on the KERYS ENG module, which is used for generator control and monitoring. 2. It describes the main menus including Operation, Fault Finding, and Archiving and Metering. The Operation menu allows controlling and monitoring generator parameters in real-time. 3. Electrical measurements, mechanical measurements, harmonics measurements, and faults/alarms can all be viewed from the Operation menu. User adjustment functions like set points, output thresholds, and wattmetric control are also covered.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
152 views

03-KERYS - Navigation (Operator Access) ENG

1. The document discusses the menus and functions available on the KERYS ENG module, which is used for generator control and monitoring. 2. It describes the main menus including Operation, Fault Finding, and Archiving and Metering. The Operation menu allows controlling and monitoring generator parameters in real-time. 3. Electrical measurements, mechanical measurements, harmonics measurements, and faults/alarms can all be viewed from the Operation menu. User adjustment functions like set points, output thresholds, and wattmetric control are also covered.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 66

03

Kerys
Navigation
(operator access)

Module KERYS ENG


01/09/2014 Module KERYS ENG
SUMMARY

1- Operation menu
2- Fault finding menu
3- Archiving and metering menu

Service formation AD
01/09/2014 Module KERYS ENG
Menus - Flowchart

01/09/2014 Module KERYS ENG 3


Main page

01/09/2014 Module KERYS ENG 4


System menu 61 and 62

Regional parameters
Language choice
Direct link if you click on the date and
time (top left)
Logo main page choice

Identification application
Display identification numbers
Important when using TELEKERYS

01/09/2014 Module KERYS ENG


5
System Software version menu (63)

Software versions
Important screen to debug version software problems
Be careful with software/hardware compatibilities

01/09/2014 Module KERYS ENG


6
Reminders: IHM fascias

3 KINDS OF Fascias

01/09/2014 Module KERYS ENG 7


Menus - Flowchart

01/09/2014 Module KERYS ENG 8


Overview - menus

01/09/2014 Module KERYS ENG 9


Overview - menus

The 6 menus (on standard basis) are:


1- OPERATION
2- FAULT FINDING
3- ARCHIVING AND METERING
4- MAINTENANCE
5- CONFIGURATION
6- FACTORY
(7- RENTAL SUMMARY) Additional menu for rental application
01/09/2014 Module KERYS ENG 10
01/09/2014 Module KERYS ENG 11
SUMMARY

1- Operation
2- Fault finding
3- Archiving and metering

Service formation AD
01/09/2014 Module KERYS ENG
Operation menu - flowchart

01/09/2014 Module KERYS ENG 13


Operation menu (1)

01/09/2014 Module KERYS ENG 14


Operation menu (11) generator

Digital display

+ SPEED/- SPEED + VOLTAGE/- VOLTAGE

01/09/2014 Module KERYS ENG 15


Operation menu (11) PC
Function keys (menu 12)
Press on GLOBAL OPERATION is like changing the wattmetric
management parameter to WITHOUT .

GLOBAL
OPERATION

01/09/2014 Module KERYS ENG 17


Synchro column (menu 12)

Only
manual mode

With the X179 Reg module, the


PIDs activated are shown in
green (accuracy is 1/10%).

01/09/2014 Module KERYS ENG 18


Synchro column display

01/09/2014 Module KERYS ENG 19


Central unit measure summary (menu 14)

01/09/2014 Module KERYS ENG 20


Central unit measure summary (menu 14)

01/09/2014 Module KERYS ENG 21


Electrical measurements Generator (151)

01/09/2014 Module KERYS ENG 22


Electrical measurements busbar or Mains

Note: another scrolling key is displayed when more than 1 mains are selected
(from firmware 1.05)
01/09/2014 Module KERYS ENG 23
Mechanical measurements menu (153)

01/09/2014 Module KERYS ENG 24


Mechanical measurements (153)

Engine error code


SPN xxxx FMI xxxx

01/09/2014 Module KERYS ENG 25


Exemple of faults

01/09/2014 Module KERYS ENG 26


Harmonics measurement (154)
From the generator and the Mains

FUNDAMENTAL
f = 50hz, amplitude 110V
+
Harmonic RANK 3
f = 50hz, amplitude 10V
+
Harmonic RANK 5
f = 250hz, amplitude 10V
+
Harmonic RANK 7
100 V f = 350hz, amplitude 10V
Amplitude

=
10V 10V 10V OUPUT SIGNAL
Frequency
50Hz 150Hz 250Hz 350Hz
FOURIER representation Temporal representation

01/09/2014 Module KERYS ENG


27
Operation- Electrical measurements (156)

Same Phase sequence

A B C

C B A

Green : phase sensing is clockwise


Red: Phase sensing is anticlockwise
Black: no voltage

01/09/2014 Module KERYS ENG


28
Mesures personnalise Ana (fentre 157)

Si ente Ana personnalis configure


Operation Faults and alarms (menu 16)

01/09/2014 Module KERYS ENG


30
User Adjustment (171)

Set points and production settings

Activation of boxes by KERYS


variables

Green boxes mean variables


used by the KERYS system

U(V) and the Un BUS are very


important and must be set up
properly.

01/09/2014 Module KERYS ENG


31
Ex Consigne
U GE and Busbar= 400v
KW mains= 0
Cos Phi GE = 0.80 L

Only withX179

Activate the box by


variables

01/09/2014 32
Module KERYS ENG
User adjustment - Output Threshold (172)

When the KW in % is
reached, the relevant
boxes become green

CPU: power plant


Total KW of the multiple
generators

%Kw reached based on the nominal KW generator and/or nominal KW power plant

01/09/2014 Module KERYS ENG


33
User adjustment Wattmetric control (173)

Activation of the Wattmetric control


Setting of running timers

Selection of priorities of generators in


the powerplant ( You only need to
change the priority sequence on one
KERYS the sequence will be
autamatically transferred to the other
KERYS which are in communication)

The Number seven is the first one to shutdown


The priorities for all the generators is done from
one kerys.
Priorities of the generators to shutdown
based on the load

01/09/2014 Module KERYS ENG


34
Only for the
configurations A632, 633,
and 635

This sub menu is displayed


only if 2 fuel pompes or 2
starter motors or selection
permanent/temporary sync
with mains activated

Module KERYS ENG


01/09/2014 35
Wattmetric management activated

WITH
The wattmetric management starts after 10 mins when
600 the 5 generators are in parallel together.

60 60
Generator Ramp up time Generator Ramp down time

This parameter limits the numbers of generators to start when


mains failure or remote start order detected if 5 is the number of
Number of generator to start in addition of generators you can put less than 5.
the minimun number of generator

Module KERYS ENG


Exemple of priorities

Change the priority on one generator


the other generators will have their
priorities changed accordingly while they
are running.
Since the X179, there is no need to press
on backup to perform .
Module KERYS ENG
Module KERYS ENG
User adjustment Wattmetric control (173)

Threshold 8GS => 7GS

01/09/2014 Module KERYS ENG


39
User parameters (174)

Off Load Test: 10 mins


Time before start up when mains failure

Time before stop the generator when mains healthy


If mains fails to syn the generator
without : the generator supplies the load
With changeover: for the mains to supply the load
If generator fails to syn with the mains
without : the mains supplies the load
With : changeover for the generator to supply the load

Exemple with 2 mains (power means mains)

01/09/2014 Module KERYS ENG 40


User parameters (175)
CRF= Shor t term sync (10 secs) with Mains
CRP: permanent sync with Mains. A641

60 60
Ramp up Ramp down

Related to starter motors

Ramps:
Consider 60 secs/ 1MW when synchronize with the UTILITY
01/09/2014 Module KERYS ENG 41
SUMMARY

1- Operation
2- Fault finding
3- Archiving and metering

Service formation AD
01/09/2014 Module KERYS ENG
Fault Finding Menu (2)

01/09/2014 Module KERYS ENG


43
Mapping Variables KERYS

01/09/2014 Module KERYS ENG 44


Address 1 0 x x
BUS CAN1 OUTPUT @module Chanel N

Address 1 1 x x
BUS CAN1 INPUT @module Chanel N

01/09/2014 Module KERYS ENG 45


Mapping Variables KERYS
Address 3 0 x x
BASE OUTPUT @module Chanel N

Address 3 1 x x
BASE INPUT @module Chanel N

01/09/2014 Module KERYS ENG 47


Mapping Variables KERYS
Mapping Variables KERYS
Fault Finding O/I variables (menus 21,22, 23)

Menu 21 Menu 22 Menu 23

Digital I/O Analog I/O REG & PRO I/O


Display digital values Display analog values Display regulation and
40XX to 42XX Input variables 50XX to 52XX Input variables of the protection values
(Auto mode, LED test, + speed, close ANA module
Mains breaker) (temperature, number of generator in Display measurements, statuses,
43XX to 44XX Input operator the powerplant, priority) thresholds
45XX to 49XX Internal variables 53XX to 55XX Input operator Utilization of variable tables of
(Run order, Top synchro, synchro ) 56XX to 58XX Internal inputs
each module.
(temperature, voltage, frequency)
4AXX and ADXX to AFXX Available
59XX to 5FXX Available

01/09/2014 Module KERYS ENG


50
Fault Finding Curves (menu 24)

Graphics

from 4 variables

evolution of these 4
variables

Only with IHM Tactile

01/09/2014 Module KERYS ENG


51
Fault Finding Electrical faults (menu 25)

Electrical Faults function

To visualize value of a
data in a short scale of
time

Dont reset fault and alarm


to visualize the screen

01/09/2014 Module KERYS ENG


52
Help Menu (menu 26)

Help function

To have a short definition


of anomalies (alarms,
faults )

Possibility to key words to find out the fault number 6xxx

01/09/2014 Module KERYS ENG


53
Regulation module display (menu 27)

Reg module display function


(from Version 1.05b)

To know the % of regulation


output (speed and voltage)

To know if the AVR and ASR have


good setting (if too much
correction, might be an error in
AVR and ASR set points)

To know the status of the system


(syncro)

Only if the regulation module is selected

01/09/2014 Module KERYS ENG


54
Visualisation TOR (menu 28)
SUMMARY

1- Operation
2- Fault finding
3- Archiving and metering

Service formation AD
01/09/2014 Module KERYS ENG
Architecture

01/09/2014 Module KERYS ENG 57


Event archive (menu 31)

Kind of event logs ( FIFO) where faults, alarms and statuses are
listed par date and hour to understand the history of events during
failures.
512 messages
01/09/2014 Module KERYS ENG 58
Electrical Archives (menu 32)
1- Select the parameters that you want to record,
2- Activate the reccording by adding the following input equation: 4188 = 450C

01/09/2014 Module KERYS ENG 59


Mechanical archives (menu 33)
1- Select the mechanical parameters that you want to record,
2- Activate the reccording by adding the following input equation: 4189 = 450C

01/09/2014 Module KERYS ENG 60


Electrical & mechanical data recording

Measurements to be taken every 60 secs (sampling time)

To give you 1819 measures


=> 30 hours
Variable 4188: Electrical archives and measurements
Variable 4189: Mechanical archives and measurements

To activate the recording, enter the 2 following additionnal equations:

4188= 450C
4189= 450C
Go to CONFIGURATION/APPLICATION/EQUATION/DIGITAL INPUT

450C being the variable for generator running

01/09/2014 Module KERYS ENG 61


Electrical & mechanical data recording

01/09/2014 Module KERYS ENG 62


Event metering (menu 34)
Counter of apparition of anomalies

Example:
7200 is the anormaly variable
number
7300 is the variable where is
stored the number of apparition

Its possible to use this


values to do comparison in the
Equation menu.

To count the changes of status of the binary variables

01/09/2014 Module KERYS ENG 63


Mechanical metering (menu 35)

Possibility to change the


hours and mins if access
code level 3.
Interresting when you
need to replace the IHM.

01/09/2014 Module KERYS ENG 64


Electrical metering (Menu 36)

Display of production of active and reactive powers

Possibility to reset values with an access code

01/09/2014 Module KERYS ENG 65


Thank you for your attention!