0 ratings0% found this document useful (0 votes) 604 views312 pagesDesign Building1 03012018234353
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
Design And Specification of
Power Distribution
And Protection
Systems In Buildings
(1st Edition)
Author: Mr Tan Yan Choon
B.Eng, P.Eng, C.Eng, MIEE, MIES, ACMS
Published by:
lal AMOS TECHNOLOGIES PTE LTDDesign and Specification of
Power Distribution and Protection Systems in Buildings
(1* Edition)
The design, installation and maintenance of electrical distribution and protection system are
essential to the reliability, safety and security of supply to buildings. The contents.of this book
aim at familiarize the readers and designers with the technique in design and specifications of
electrical distribution and protection systems in the buildings, whether it is residential,
commercial or industrial buildings. Case studies and exercises have been used to provide an
insight to the principle and technical information for design and installation of the electrical
distribution and protection system.
‘The contents of this book will certainly benefit those who are involved in design, installation
‘and maintenance of electrical systems, consulting engincers, building services engineers,
electrical maintenance engineer, facilities engineers, contractors, developers, technical officers
from industries, government and statutory bodies, ete.
About the Author
TAN YAN CHOON
BEng. P.Eng, C.Eng, MIEE, MIES, ACMS
‘Mr Tan is a practising consulting engineer and lecturer with extensive experience in the design,
operation and maintenance of M & E systems. Specific experience includes the planning and
design of M & E services for various major industrial, commercial & residential projects.
Mr Tan has more than 27 years of working experience as a Consultant and Professional
Engineer. His early experience includes many years in the planning, installation and
maintenance of extensive electrical distribution system for a power utilities company. He has
also gained wide practical experience with M&E Consulting firms, Ewbank Preece Engineers
Pie Lid, Peter Teo & Associates, Oscar Faber Consultants Pte Ltd and Maunsell Consultants
(Singapore) Pte Ltd in the design and installation of M&E Services. Mr Tan is now a Licensed
Electrical Engineer and an Authorised H.T. Switching & Testing Engineer and currently a
Technical Director of Maunsell Consultants (Singapore) Pte Ltd.
Mr Tan is also an established trainer and adjunct lecturer at a local tertiary institution. He has
delivered many public seminars and in-house courses such as Effective Maintenance
Management of M&E Services; Design & Specification of M&E Services; Lightning
Protection for Electronics, Computer and telecommunication Equipment; High Voltage System
Design, Operation & Maintenance; Electrical Safety; Power System Harmonics; Earthing and
Power Supply Quality problems, Design & Installation of Standby Generators, Design &
Specification of Electrical Power & Distribution for Data Processing & Communication
Centres.
Publisher
Amos Technologies Pte LtdDesign and Specification of Power Distribution
and Protection Systems in Buildings (1* Edition) _
Copyright
All tights to this publication are reserved. No part of this publication may be copied,
reproduced, transmitted or stored in any form or by any means (including electronic,
mechanical, photocopying, recording or otherwise) without prior written permission of the
publisher and the author.
Disclaimer
—]]
Whilst all reasonable care has been taken to ensure that the descriptions, opinions, programs,
listings and diagrams are accurate and workable, Amos Technologies Pte Ltd and the author
do not accept any legal responsibility or liability to any person, organization or other entity for
any direct loss, consequential loss or damage, however caused, that may suffered as a result of
the use of this publication or the associated workshop and software.
In case of any uncertainty, we recommend that you contact the author for clarification or
assistance. .
ISBN 981-04-8063-61
Ld
1.2.
13,
14.
15.
1.6,
17.
18.
19.
CONTENTS
INTRODUCTION TO ELECTRICITY SUPPLY SYSTEM
Electricity Distribution System
DY 11 Distribution Transformer — Winding Connections
Transformer Impedance
Percentage Impedance
Low Voltage 3-Phase 4-Wire System
Rated Full Load Current & Rated Trip Rating of Circuit Breaker
Fault Current and Rated Short Circuit Breaker Capacity of Circuit Breaker
Declared Prospective Short Circuit Current of Power Supply Company
Metering of Electricity Consumption
Questions - Chapter 1
2.
24
22
23
24
25
2.6
27
28
FUNDAMENTAL REQUIREMENTS FOR SAFETY IN DESIGN
Electricity — The Hazards
Protection Against Overcurrent
Protection Against Overcurrent and Earth Leakage Protection
Isolation and Switching
‘Need for Earth Leakage and Earth Fault Protection
Installation of Overcurrent and Earth Leakage Protection Device for
DB Rated at 100A or less
Provision of Earth Leakage Relay (ELR) as Residual Current Device
(RCD) for Small Switchboard with Rated Current less than 300A
Provision of Earth Fault Relay (EFR) as Residual Current Device
(RCD) for Switchboard with Rated Current 300A or more
Questions — Chapter 2
31
32
33
3.4
35
3.6
3.7
38
MINIATURE CIRCUIT BREAKER (MCB) - OVERCURRENT
PROTECTION DEVICE
Protection Against Overload and Short Circuit
Nominal Current Rating (or Rated Trip Rating) In
Rated Short Circuit Breaking Capacity of Circuit Breaker
Miniature Circuit Breaker; (SS359 and BS EN 60898)
Selection of MCB
Examples in Selection of MCB
Selection of MCB for Motor Circuits
Identification of Circuit Breaker in Terms of Number of Poles
Questions — Chapter 3
Bernunsouna
15
15
15
7
18
19
20
20
22
23
25
25
25
25
25
27
31
32
34
37Design and Specification of Power Distribution
and Protection Systems in Building (1" Edtition) Contents
4, RESIDUAL CURRENT DEVICE 40
4.1 Residual Current Device (RCD) 40
4.2 Residual Current Circuit Breaker (RCCB) or Earth Leakage Circuit Breaker
(ELCB) 40
4.3 Specifications of RCCB (SS97:Part 1:1994) 42
4.4 — Application of RCCB & Overcurrent Protection Device 4a
4,5 Earth Leakage Relay (ELR) 44
4.6 — Earth Fault Relay (EFR) 44
4.7 Danger of High Earth-Fault-Loop Impedance 45
Questions ~ Chapter 4 41
5. MOULDED CASE CIRCUIT BREAKER - OVERCURRE]
PROTECTION DEVICE 49
5.1 Moulded Case Circuit Breakers 49
5.2 Thermal Magnetic Trip Units 50
5.3. Adjustable Instantaneous Trip 52
5.4 — Shunt Trip for Remote Tripping 53
5.5 Frame Size Designations 53
5.6 _ Relationship between Rated Breaking Current and Rated Making Current 54
5.7 Specifications of Low Voltage Circuit Breaker 55
5.8 Current Limiting Circuit Breaker 57
5.9 Cascading Interruption 58
5.10 Selection of Protective Device 59
5.11 Motor Starters & Motor Control Circuits 61
5.12 _ Examples in Selection of MCCBs 65
Questions ~ Chapter 5 67
6. AIR CIRCUIT BREAKER 69
6.1 Introduction 69
6.2 Construction of Air Circuit Breaker 69
6.3 Range of Air Circuit Breaker 70
6.4 — Operating Principles of Air Circuit Breakers 70
6.5 Function of the Are Chute 2
6.6 Fixed and Moving Contacts n
6.7 Shunt Trip Coil 2
6.8 Instrumentation and Meters B
6.9 Protective Devices for Main Circuit Breaker B
Questions - Chapter 6 16
7. SIZING OF CABLE AND LIVE CONDUCTORS 7
7.1 Introduction 7
7.2 PVC or XLPE Insulation 1
7.3 Armoured Cable 8
7.4 — Cable Selection B
7.5 Current Carrying Capacity Consideration 19
IDesign and Specification of Power Distribution
and Protection Systems in Building (1* Edtitic Contents
7.6 Voltage Drop Consideration 80
7.1 Overload Consideration 84
78 — Short Circuit Consideration 86
Questions ~ Chapter 7 88
8 MAXIMUM DEMAND AND LOAD ESTIMATION 90
8.1 Load Estimation 90
8.2 Design of Electrical System for Large Installation 93
Questions ~ Chapter 8 98
9. CURRENT TRANSFORMERS 100
9.4 Current Transformers 100
9.2 Metering Current Transformers 100
9.3. Protection Current Transformers 100
9.4 Comparison of Metering C.T. and Protection C.T. 100
9.5 Construction 101
9.6 Polarity of Current Transformer and Connection 102
9.7 Burden 103
9.8 Specification of Protection Current Transformers 104
9.9 Metering Current Transformer 107
9.10 Voltage Transformers 107
Questions ~ Chapter 9 108
10. ELECTRICAL SWITCHBOARD 109
10.1 Introduction 109
10.2 Low Voltage Main Switchboard 109
103 Emergency Switchboard (ESB) M1
104 Current Transformer Selection 113
10.5 Busbars 14
10.6 Enclosures 121
10.7 Segregation and Compartmentation i22
10.8 Certification of Switchgear and Equipment 126
10.9 Main Earth Bar 126
Questions — Chapter 10 128
1. EARTHING 129
11. Earthing for Electrical System 129
11.2 TT Earthing System and TN-S Earthing System 130
113 Touch Voltage Concept 134
11.4 _ Installation Earthing 135
11.5. Examples in Sizing of Main Earth Cables - TT Earthing System 141
11.6 Examples in Sizing of Main Earth Cables - TN-S Earthing System 144
11.7 Common Types of Earth Electrodes 148
11.8 _ Measurement of Soil Resistivity 152
Questions - Chapter 11 155
WDesign and Specification of Power Distribution
and Protection Systems in Building (1* Edition) Contents
12. PROTECTION RELAYS 157 i
12.1 Introduction 157
12.2 Overcurrent and Earth Fault Protection for Low Voltage (400V) System 158
12.3 Definite Time Lag Relays (DTL Relays) 161
12.4 Typical Specifications of DTL Relays 162 ;
12.5. Protection Requirements for L.V. Main Switchboard (MSB) 163, i
12.6 Why is Direct Acting Trip Necessary? 164 }
12.7 IDMTL Relays (Inverse Definite Minimum Time Lag Relays) 167
12.8 Grading Margin 173,
12.9 High Set Element 1B
Questions ~ Chapter 12 177 ;
13. FAULT CALCULATION BY OHMIC VALUE METHOD 182
13.1 Introduction 182
13.2 Prospective Short Circuit Current 183,
13.3 Main Objectives of Fault Calculations 185
13.4 Symmetrical Short-Circuit Current 185
13.5 Asymmetrical Fault Current 185,
13.6 Sources of Fault Current 189
13.7 Calculation of Three-phase Balanced Fault Currents 191
Questions — Chapter 13 204
14. FAULT LEVEL CALCULATION USING PER UNIT SYSTEM 207
14.1 Introduction 207
14.2 Definition of Per Unit Value 207
14.3 Per Unit Quantities in Single-phase and Three-phase Systems 208
14.4 Conversion of Per Unit Impedance to other Bases 209
14.5 Selection of Base for Per Unit Quantities 211
14.6 Calculation of Fault Current and Fault Power using Per Unit System 215
14.7 Advantages of Per Unit Computations 219
14.8 Reactors Control of Fault Currents 220
14.9 Examples 224
Questions ~ Chapter 14 233
15. _ CASE STUDIES IN DESIGN OF ELECTRICAL INSTALLATION 235 |
15.1 Introduction 235 i
15.2. Case Study I 235 |
15.3 Case Study 2 248
16. TESTING ON MAIN SWITCHBOARD 252
16.1 Testing Before Turn-On Electricity Supply 252
16.2 Testing After Electricity Supply to Main Switchboard has been Turned On 262
Questions — Chapter 16 269
17, | MAINTENANCE OF ELECTRICAL INSTALLATION 270
17.1 Introduction 270
Vv
iDesign and Specification of Power Distribution
and Protection Systems in Building (1" Edtition) Contents
17.2 _ Inspection and Maintenance of Cables and Conductors 270
17.3 Maintenance of Switchboards 2
Questions — Chapter 17 2B
18. STANDBY GENERATORS 274
18.1 Introduction 274
18.2 Range of Sizes 274
183 Continuous and Standby Ratings 274
18.4 Functions of Standby Generators 215
185 Components of Mains Failure Generating Sets 215
18.6 Control Systems 279
18.7 Protective Systems 219
188 Automatic Voltage Regulation 281
18.9 Sizing of Generators 282
18.10 Parallel Operation 284
18.11. Emergency Switchboard 285
Questions ~ Chapter 18 287
19, _ UNINTERRUPTIBLE POWER SUPPLY (UPS) 288
19.1 Introduction 288
19.2. Main Components of Static UPS 288
19.3. Selection of UPS 292
19.4 Technical Specifications of UPS Systems 297
19.5 Maintenance of Static UPS 298
19.6 _ Standby Generator for UPS 298
Questions — Chapter 19 302
Reference 304
VCHAPTER 1
INTRODUCTION TO
ELECTRICITY SUPPLY SYSTEM
1.1 ELECTRICITY DISTRIBUTION SYSTEM
Electricity Distribution System in the buildings receive bulk electrical power from the high
voltage networks of the electricity supply company and step down the voltage to utilisation
voltage through the distribution transformers.
A typical electricity distribution system in a building is
Figure 1.1 22 kV Supply System
Electrical power is normally distributed at voltage level in the range of 6.6kV, 11kV, or
22kV, and step down to the utilisation voltage at 400V (3-phase) / 230V (single phase)
through the 22kV/400V or 6.6kV/400V distribution transformers. The power rating of the
distribution transformers may be 1000kVA (IMVA), 1500kVA (1SMVA), 1600kVA
(1.6MVA), 2000kVA (2MVA) or 2500KVA (2.SMVA).
1_ Introduction to Electricity Supply System
1.2 DY 11 DISTRIBUTION TRANSFORMER ~ WINDING CONNECTIONS
Medium voltage distribution systems (400V phase to phase, and 230V phase to neutral) are
supplied by the secondary windings of the distribution transformers. As single phase voltage
(230 V phase to neutral) has to be made available to consumers and the neutral (N) has to be
maintained close to earth potential (0 V), secondary windings of the distribution transformers
have to be star connected to allow for neutral point or star point to be connected to earth,
For the satisfactory elimination of the 3" harmonic frequency in the distribution system, the
primary windings of the distribution transformers have to be delta connected.
‘The most common winding connections are therefore DY 1, DYS, DY7 or DYI1 with DYII
being used widely throughout the world,
In Singapore and Malaysia, the distribution transformers used by the power supply
companies and private sector are in the DY11 connection.
‘The connection of DY 11 as defined in BS 171 is as shown below:
HLV. Windings y
Delta Comection) LY. Windings
(Star Connection)
Figure 1.2 (a)
a
Ve
‘Primary Voltage Secondary Voltage Primary & Secondary
Voltage DY11)
Figure 1.2 (b)Introduction to Electricity Supply System
‘The phasor diagrams of the primary and secondary voltage are as shown:
DYII indicates that the voltage of the secondary star windings lead the primary phase
voltage by 30° and it corresponds to 11 o'clock.
1.3. TRANSFORMER IMPEDANCE
The reactance of power transformers are usually 6 to 30 times greater than the resistance. In
design and comparison of transformers it is useful to express the Z, R and X in percent or
p.u. of MVA rating rather than the ohmic value.
Zr=RrtjXr
where Xr is about 5 to 6 times larger than Rr in transformer of IMVA to 2.5MVA.
1.4 PERCENTAGE IMPEDANCE
‘The transformer percent impedance voltage is the percentage of rated voltage needed to
circulate three-phase rated current when the other winding is shorted.
Figure 1.3
Ip and Is are the primary and secondary rated current.
oy 7 ~ (Applied Primary Voltage
ae ( Rated Primary Voltage ] es)
To convert this percentage impedance value of transformer to ohmic value:
y 2
Zr (ohm) = 42) x()
ey (i 00 MVA)
‘The impedance of distribution transformer Zr (%) has two effects:
(a) It limits the fault current or short circuit current.
(b) It causes voltage drop or voltage dip in the winding of the transformer.Introduction to Electricity Supply System
Therefore a small Z; (%) lead to larger fault current but help to minimise voltage changes at
the output of transformers caused by fluctuation of the loads.
In accordance with British Standard BS171 for distribution transformers, the typical value of
Zr (%) are as follows:
Distribution Transformers: 631 kVA to 1250kVA Zr =5.0%
>1250kVA Zr = 6.25%
Large Power Transformers: >ISMVA. Zr= 10 to 15%
1.5 LOW VOLTAGE 3-PHASE 4-WIRE SYSTEM
Low Voltage (L.V.) system refers to distribution voltage below 1000V. In Singapore, a L.V.
system refers to 3-phase 4-wire (R, Y, B and neutral conductors) system of rated line to line
voltage (or phase to phase voltage) at 400V, and rated phase to neutral voltage at 230V. In
Malaysia and the United Kingdom (UK), the rated phase to phase voltage is 415V (RMS
value), whereas the rated phase to neutral voltage is 240V (RM.S value).
A typical 3-phase 4-wire system obtained from a H.V/L.V. DY 11 Distribution Transformer
is shown in Figure 1.4.
‘Three-phase DY11
Step Down Distribution
‘Transformer in Substation
BS $8 High
rupturing capacity
fuses are normally
used in the
substation of
‘Power supply
company
Figure 1.4 A Typical 400V / 230V Distribution SystemIntroduction to Electricity Supply System
Neutral of 3-phase 4-wire System
The star point or neutral point of the L.V. star winding of the distribution transformers is
solidly connected to earth for the following purposes:
{a) To maintain the potential (or voltage) of the neutral conductor to be close to earth
potential so that the R.M.S value of phase voltages Vn, Vw & Ven can be maintained
at 230V (in Singapore) or 240V (in Malaysia and UK).
(b) To enable the phase to earth fault current on the electrical installation system can return
safely to the star point (or neutral point) of the L.V. winding of the distribution
transformer,
Relationships Between Phase Voltages & Line Voltages of the L.V. 3-phase, 4-wire
System
If the R.M.S values of the phase voltages of the L.V. distribution system are given as:
Van = 230 2 0°
Van = 230 2-120°
and Van = 230 2-240°
It can be proven that the R.M.S value of the line voltages are:
Vay = V3 x 230 2 30° = 400 230°
Vye = V3 x 230 2-90° = 400 2-90°
and Ver = V3 x 230 2-210° = 400 2-210? = 400 2 150°
1.6 RATED FULL LOAD CURRENT & RATED TRIP RATING OF CIRCUIT
BREAKER
uit breaker such as Miniature Circuit Breaker (MCB), Moulded Case Circuit Breaker
(MCCB) and Air Circuit Breaker (ACB) are provided in L.V. electrical installation system to
offer protection against overloading and short circuit.
Rated full load current or rated trip rating of circuit breaker is the maximum load current that
‘may pass continuously through the circuit breaker without causing the circuit breaker to be
overloaded or overheated.
Example 1.1
‘The full load current of the I MVA (or 1000 KVA) 22 KV / 400 V distribution transformer is
calculated to be:
1000 kVA
Trp. = JOOOKVA ~ 14434
FEB xOAKV
Therefore a 1SO0AF/I400AT 4-pole Air Circuit Breaker (ACB) is used as the main circuit
breaker for the 400 V main switchboard,Introduction to Electricity Supply System
400V MSB
15008
22kvi400V ee
1500A/1400AT
ACB (36kA)
COD
4 Nos
4004/5
CLSP10 Protection
Current Transformer
NCIXLPE
Figure 1.5 L.V. Supply Fed Directly From Transformers
The incoming circuit breaker / disconnector and the main busbars of the switchboard (SB) or
distribution boards (DB) will usually be rated at the same current, This value is obtained
normally by adding all the loads of individual outgoing circuits, and multiply by a load
diversity factor (DF). The factor which is smaller than one has to be determined carefully be
the designer.
L.V. Main switchboards (MSBs) are usually designed for standard sizes at 200A, 250A,
300A, 400A, 600A, 800 A, 1000, 1400A, 1500A, 2100A, 2500A, 2800A, 300A.
Copper busbars are often selected based on load capacity at 1.55 Ampere per mm? by
switchboard manufacturer:
The current carrying capacity of busbar = width x thickness x 1.55A/mm’,
Distribution boards (DB) are often designed for standard sizes at 30A, 40A, 60A, 80A, 100A
(single phase or 3-phase).
1.7 FAULT CURRENT AND RATED SHORT CIRCUIT BREAKING CAPACITY
OF CIRCUIT BREAKER.
The fault current or short circuit current that a circuit breaker can break safely is not
determined by the load connected to it, but the impedances of the upstream source
transformers, impedances of the main, submains connected to the circuit breakers.
Electrical short circuit may occur due to breakdown of the insulation materials between
phase conductors or between a phase to neutral or phase to earth. These different types of.
faults are illustrated in Figure 1.6.
Rated short circuit breaking capacity (in kA, R.M.S value) is the maximum short circuit
current (expressed in R.M.S value) that the circuit breaker is capable of breaking safely
without causing damage to itself.Introduction to Electricity Supply System
‘Three-Phase
‘Supply
‘Transformer
Live (B)
Circuit Breaker
Figure 1.6 Three-Phase Supply showing Fault Conditions
‘The relationships of transformer sizes, L.V. circuit breaker rated trip ratings and short circuit
fault levels on the secondary side of the transformers are determined as followed:-
22/0.4kV | Impedance | ACB Trip Prospective CT Ratio for
Transformer | Z(%) RatingI, | 3-phase Short Circuit | __L.V. Side
Current (kA)
1000 475 1400 A 30, 1400 A/5 A
1250 sae 1750 A 35 1750 A/5.A
1500/1600 55. 2100 A 40 2100 A/S A
2000 55 2800 A 50 2800 A/S A
Table 1.1
Base MVA.
Fault Level =
Tmpedance of the Source
(Transformer Zr in per unit,
Prospective 3-phase Short Circuit Current = ( Rr a eve
Circuit breakers must be selected to have rated short circuit breaking capacity bigger than the
prospective 3-phase short circuit current at the point of installation,
18 DECLARED PROSPECTIVE SHORT CIRCUIT CURRENT OF POWER
SUPPLY COMPANY
The Power Supply Company in Singapore has declared that the prospective maximum short
circuit current at their power supply incoming are as follows:Introduction to Electricity Supply System
400V/230V Supply
(a) 9kA for approved load > 15kVA and up to 75kVA from PowerGrid at 230V single phase
supply.
(b) 25kA for approved load > 75kVA and up to I80kVA from PowerGrid at 400V 3-phase
supply.
(c) 36kA for approved load > 180kVA and up to 1000kVA from PowerGrid at 400V 3-phase
supply.
These values must be checked and confirmed with Power Supply Company.
High Voltage Supply
(a) 20kA for 3sec for 6.6kV supply from PowerGrid.
(b) 25kA for 3sec for 22kV supply from PowerGrid.
‘These values must be checked and confirmed with Power Supply Company.
1.9 | METERING OF ELECTRICITY CONSUMPTION
Single Consumer
For premises occupied by a single consumer, the electricity supply is metered at one point
and the appropriate tariff in accordance with the use of electricity is charged.
For electricity supply rated at 100A (single phase or 3-phase), direct meter for recording of
electricity consumption as shown in Figure 1.7 (a) is used. Whereas for electricity supply
more than 100A, C.T. meter as shown in Figure 1.7 (b) is used.
Zero
squint
‘Transfoniner
2008.
Ha
Figure 1. 7 (a) 230V Single Phase Supply Figure 1.7(b) 400V 3-Phase Supply
not Exceeding 100A Exceeding 1004Introduction to Electricity Supply System
Multi-Tenanted Premises
Metered & Unmetered Scheme
In the case of condominium housing or flatted factory development where the consumption
for common service is minor, the electricity supply to development is delivered at low
tension, The supplies to the landlord and tenants are separately metered and billed under their
respective accounts.
To enable the electricity supply company to know that the electricity supply to a tenant is to
be taken from unmetered submain or switchboard, the consumers who plan to take electricity
supply is such a manner has to be indicated in Form CS/3 to inform the power supply
company accordingly.
‘Common Service
—er
meee
Figure 1. 8 (a) Metered & Unmetered System for Figure 1.8 (b) Master & Sub-metering
Multi-Tenanted Premises scheme for Multi-tenanted buildings
Metered & Sub-metering scheme
In commercial buildings where the supply for common services accounts for the bulk of
consumption, the “master / sub-metering scheme” is adopted. Master meters are installed at
the intake switchboard with the tenants’ consumption separately metered and billed under
their respective accounts, The landlord / management corporation pays for the consumption
registered at the master meters after deducting the units billed to the tenants.
To enable the deduction of sub-meters’ readings from the landlord’s master meter by the
electricity supply company, consumers (tenants in the buildings) who plan to take electricity
supplies from the main switchboard or submains which have already been metered by master
meter, has to submit the account number of the master meter via Form CS/3 (as shown in
Figure 1.9),Introduction to Electricity Supply System
crater aay 26 a
Esau SSPUME ats tnt ot ems he
(mere
Ly eteved ander ater hen He
rat
Figure 1.9 Sample of Form CS3
A typical arrangement of master kW-HR meter and sub-meter for tenants in a school is
shown in Figure 1.10, This fundamental requirements for safety in the design of electrical
installation as required by SS CP5:1998 in terms of:
(a) Overcurrent Protection
(b) Earth Fault & Earth Leakage Protection
(©) Isolation for Safety
have also been incorporated in Figure 1.10.
10Introduction to Electricity Supply System
Type Ds tr
oeQuestions — Chapter 1 Introduction to Electricity Supply System
(1) Explain briefly the definition of
(@) Instantaneous Value
(b) Peak or Maximum Value
(c) Root Mean Square Value
(d) Average Value
(©) Crest Factor
(8) Form Factor
of A.C. Voltage and Current
(2) A 3-phase load may be connected in Star or Delta-connection,
If the magnitude of the line voltage is the same in both cases, prove that the magnitude
of line current in Star-connection is '/s that of the Delta-connection.
(3) Describe briefly the meaning of each of the following markings on a transformer
nameplate:
(@) 22kV/400V
(b) IMVA
(©) Dy
(@) Z=5%
(4) A .3-phase star connected load with equal impedance Z; = (10 + }50) Q in each phase is
connected to the star connected secondary winding of a 22 kV / 400 V distribution
transformer.
(a) Draw'the connection diagram to show the connection of the star connected load
and the secondary winding of the transformer. Explain briefly why neutral point
of the star connected winding of the distribution transformers has to be solidly
connected to earth.
(b) Assuming that the phase voltages of the L.V. transformer windings are:
Van = 230 20°
Vy = 230 2-120°
Van = 230 2-240"
Show that the line voltages are given by
Vay = 13 x 230 2 30°
Vya = V3.x.230 2-90°
Var = 3 x 230 2150°
(©) Calculate the magnitude and phase angle of the current in each phase and hence,
determine the magnitude and phase angle of the neutral currents.
@ Express the equation of instantaneous value of the line currents in function of
time,
12Questions — Chapter 1 Introduction to Electricity Supply System
)
(6)
aM
A 3-phase Delta-connected load with equal impedance of (10 + 50j) Q in all three
phases is connected to the Star-connected secondary of a 22 KV / 400 V distribution
transformer.
(@) Draw a diagram to show how the load is connected to the transformer.
(®) Calculate all the three line currents and express them as phasor quantities.
(©) Express the instantaneous value of the line currents.
The star connected secondary winding of a 22 kV / 400 V distribution transformer is
connected to a 3-phase, 4-wire unbalanced star connected load. The load impedances
are:-
Zan = (8 + j50) 2
Zyw= (12 + j40) Q
Zon = (10 + j60) 2
‘The phase voltage of the transformer windings are
Van = 230 20°
30 2-120"
30 2-240°
(a) Draw a diagram to show how the load is connected to the distribution
transformer. Explain briefly why neutral points of distribution transformers have
to be solidly connected to earth.
(b) Using either a mathematical method or a graphical method, prove that the line
voltages are: -
Vay = V3x 230 230°
Vyp = V3.x 230 290°
Var = V3 x 230 2150°
(©) Calculate the magnitude and phase angle of the line current and hence, determine
the magnitude and phase angle of the neutral current.
The L.V. winding of the 22 kV / 400 V DY 1! distribution transformer is connected to
a Star connected load with equal impedance Z,; = (10+j50) Q in each phase and a
Delta connected load with equal impedance Z2 = (10+J60) Q in each phase.
(a) Draw the connection diagram to show the connection of the transformer L.V.
winding and the Star connected load and Delta connected load. Explain briefly why
Neutral point of the transformer L.V. winding has to be solidly connected to earth.
(b) Given the phase voltages of the transformer windings as:
13Questions — Chapter 1 Introduction to Electricity Supply System
Van = 230 20°
Vyn = 230 2-120°
Vpn = 230 2-240°
and the line voltages as
Vay = ¥3.x 230 230°
Vye = V3 x 230 290°
Var = V3 x 230 .2150°
Determine the total line currents (R, Y & B) at the secondary windings of the
distribution transformer and express them in instantaneous value equations.
(8) In the figure shown below, determine the required frame size, rated trip rating & rated
short circuit breaking capacity of the Air Circuit Breaker and the appropriate C.T. ratio
and the busbar current rating at the 400V MSB.
_ABI_ar
= 6.25% Pole ACB
a)
Figure T. 11 (@)
Figure 1.11 (c)CHAPTER 2
FUNDAMENTAL REQUIREMENTS,
FOR SAFETY IN DESIGN
2.1 ELECTRICITY - THE HAZARDS
‘The principal hazards in the use of electricity, as envisaged by statutory regulations such as
Singapore Standard CP5:1998, Code of Practice for Electrical Installations and British
Standard, IEE 16" edition of the Wiring Regulations are as follows:-
electric shock (direct contact and indirect contact),
fire,
bums,
jury from mechanical movement of electrically actuated equipment, in so far as such
ijury is intended to be prevented by electrical emergency switching or by electrical
switching for mechanical maintenance of non-electrical parts of such equipment.
eoee
2.2. PROTECTION AGAINST OVERCURRENT
Overeurrent
‘An overcurrent is a current greater than the rated current of a circuit. It may occur in two
ways:=
(2) Asan overload current, or
(6) Asa short-circuit or fault current,
‘These conditions need to be protected against in order to avoid damage to circuit conductors
and equipment. In practice, fuses and circuit breakers are used to protect against overloading
~ short-circuit,
Overload Current
Overload currents occur in circuits which have no faults but are carrying a higher current
than the design value due to:-
(a) overloaded machines
(b) an error in the assessment of the loads in the circuit, or
(©) _under-design of the circuit conductors.
If overload current is allowed to persist, it will result in an increase in conductor temperature.
If the conductor becomes too hot, the insulation of the cable or conductor may be
deteriorated and eventually fail.
15Fundamental Requirements For Safety in Design
Short Circuit Current
Short circuit current is an overcurrent resulting from a fault of negligible impedance between
‘live’ conductors or between ‘live’ and earthed conductors.
A short circuit may occur due to a direct contact or connection between
(@)_aphase conductor to ‘neutral’ conductor,
(6) a ‘phase’ conductor to ‘earth’ conductor or earthed metal frame,
(©) a ‘neutral’ conductor to ‘earth’ conductor or earthed metal frame,
(@) a ‘phase’ to ‘phase’ short circuit or 3-phase short circuit.
7777 Metal Enelosure
SAO WES Gog? a! Installation or
ib ey a mat a
Figure 2.1 Short Circuit between ‘Live’ and ‘Neutral’ Wire of a ‘Single-Phase’ System
= Metal Enclosure
lof Electrical
{Equipment
1
Earth Fault
or
| Phase to Earth
| Short Circuit
I
1
|
H
Figure 2.2 Short Circuit between ‘Live’ Wire and the Earthed Metal Frame of Equipment
16Fundamental Requirements For Safety in Design
‘Phase Transformer DY11 Vector Group
HY.
Supply Side
La
22K]
la
Dota HonCere Star
n
1
a
f
1
yy
Frame oF Metal Body
Figure 2.3. 3-Phase Short Circuit on a 3 Phase System
2.3 PROTECTION AGAINST OVERCURRENT AND EARTH LEAKAGE
PROTECTION
Overcurrent Protection
Singapore Standard CPS:1998, Code of practice for electrical installations and British
Standard, IEE Wiring Regulations 16" edition requires that:
Clause 130-03-01 Where necessary to prevent danger, every installation and every
circuit thereof shall be protected against overcurrent by devices which:
i. will operate automatically at values of current which are suitably related to the
safe current rating of the circuit, and
ii, are of adequate breaking capacity and, where appropriate, making capacity, and
iii, are suitably located and are constructed so as to prevent danger from overheating,
arcing or the scattering of hot particles when they come into operation and to permit
ready restoration of the supply without danger.
These requirements are stipulated in Clause 130-03-01 of CP5:1998 and IEE™ Wiring
Regulation 16" edition.
Earth Leakage Protection
Clause 130-04-01, 130-04-02, 130-04-03 and 130-04-04 of the Singapore Standard
CP5:1998 and British Standard; IEE Wiring Regulations 16" edition also require that:-
130-04 Precautions Against Earth Leakage and Earth Fault Currents
7Fundamental Requirements For Safety in Design
130-04-01 Where metalwork of electrical equipment, other than current-carrying
conductors, may become charged with electricity in such a manner as to cause danger:
i, the metalwork shall be connected with earth in such a manner as will cause
discharge of electrical energy without danger, or
ii, other equally effective precautions shall be taken to prevent danger.
130-04-02 Every circuit shall be arranged so as to prevent the persistence of
dangerous earth leakage currents.
130-04-03 Where metalwork is connected with earth in accordance with Clause
130-04-01 (i) the circuits concerned shall be protected against the persistence of an earth
fault current by:
i. the overcurrent protective devices required by Clause 130-03-01, or
ii, a residual current device or equally effective device.
‘The method described in item (ii) above shall be used whenever the prospective earth
fault current is insufficient to cause prompt operation of the overcurrent protective
devices,
130-04-04 — Where metalwork of electrical equipment is connected with earth in
accordance with Clause 130-04-01(i) and is accessible simultaneously with substantial
exposed metal parts of other services, the latter shall be effectively connected to the main
earthing terminal of the installation.
24 ISOLATION AND SWITCHING
Clauses 130-06-01, 537-02-01 & 537-02-02L of CP5:1998 and IEE 16" edition requires
that:~
130-06 Isolation and Switching
130-06-01 Effective means, suitably placed for ready operation, shall be provided so
that all voltage may be cut off from every installation, from every circuit thereof and
from all equipment, as may be necessary to prevent or remove danger.
537-02 Devices For Isolation
537-02-01 Except as detailed by Clause 460-01-04, the devices for isolation shall
effectively isolate all live supply conductors from the cireuit concerned. Equipment used
for isolation shall comply with Clauses 537-02-02 to 537-02-10.
537-02-02L The isolating distance between contacts or other means of isolating when
in the open position shall be not less than that determined for an isolator (disconnector) in
aveordance with the requirement of IEC 947-3.
IsFundamental Requirements For Safety in Design
TEC 947-3 Standard requires that the isolator be subjected to a 2kV A.C. pressure test
at open position and the leakage current shall not be more than 2mA.
2.5 NEED FOR EARTH LEAKAGE AND EARTH FAULT PROTECTION
Phase to Earth Fault can best be represented by the fault impedance diagram as shown in
figure 2.4, where a short circuit has occurred from ‘phase’ or ‘live’ conductor to metal
enclosure (or known as Exposed Conductive part) of electrical equipment.
av
ioe
eas a Restate
‘TT Esrthing
System
Zy— Transformer Impedance in Ohmic value
Zp~ Phase Conductor Impedance in Ohmic value
Z_e- Earth Conductor Impedance in Ohmic value
Zyye— Neutral / Earth Conductor Impedance in Ohmic value
Ra— Electrode Resistance of Installation Farthing at the Consumer's
Installation
Rg Electrode Resistance of Neutral Earthing at the Power Supply
Company's Distribution Transformer
Figure 2.4 Phase to Earth Fault & Earth Fault Loop Impedance
where Earth Fault Loop Impedance is defined as the Total Impedance in the path or
Loop of phase to Earth fault current and phase to Earth fault current
Jee = Phase Voltage
er’ Zep
- 230V
Zr + Zp + Ze + (Rat Ru) + Zw
and since Zeru = Zr + Zp + Ze + (RatRe) + Zwe
=RatRe.
where Zr, Zp, Ze & Ze are relatively smallFundamental Requirements For Safety in Design
srefore 230V
Therefore, tue = ae
_ 230
10419 ifR4=Re<10
= IISA to 120A, depending on whether Vryase = 230V or 240V
This current is small and unable to cause the overcurrent protection such as MCB, MCCB
oF overcurrent relay to operate. This will certainly cause electric shock and electrical
hazards. Residual Current Device (RCD) such as RCCB (Residual Current Circuit
Breaker), ELR (Earth Leakage Relay) or EFR (Earth Fault Relay) must be used as
sensitive phase to Earth fault protection device.
{tis also for this reason that a rule by Power Supply Company is imposed to limit the trip
Current setting of EFR (Earth Fault Relay) to maximum value at 120A (i.e. EFR can be
set to 10% to 20% of the rated current of the L.V. switchboard subject to maximum
setting at 120A, please see handbook of Power Supply Ltd.)
2.6 INSTALLATION OF OVERCURRENT AND EARTH LEAKAGE
PROTECTION DEVICE FOR DB RATED AT 100A OR LESS
For Distribution Board (DB) rated at 100A or less, RCCB (Residual Current Circuit
Breaker) or known as ELCB (Earth Leakage Circuit Breaker) are normally used as the
protection device against phase to earth fault as shown in Figure 2.5.
As RCCB is not an overcurrent protection device, a Miniature Circuit Breaker (MCB) at
an appropriate Rated Trip Rating I, must be installed to provide overcurrent protection.
The RCCB with appropriate Rated Normay Current rating |, and sensitivity (or
operating current) I,, must be selected.
As a safety rule to prevent electrical hazards in domestic premises, RCCB of 30mA
sensitivity must be used for protection in domestic residential premises.
The following guidelines are to be compiled with in the design of electrical installation:
@) Use RCCB of 30mA sensitivity for domestic switch socket outlet and lighting
circuits,
(b) Use RCCB of 30mA sensitivity for temporary supply.
(©) Use RCCB of 30mA sensitivity for market and food stall.
(d) Use RCCB of appropriate sensitivity for non-domestic electrical installation.
2.7 PROVISION OF EARTH LEAKAGE RELAY (ELR) AS RESIDUAL
CURRENT DEVICE (RCD) FOR SMALL SWITCHBOARD WITH
RATED CURRENT LESS THAN 300A.
For small switchboard not more than 300A, Earth Leakage Relay (ELR) of adjustable
operating current 0.3 to 3A (primary current) OR 0.3A to 10A (Primary Current) can be
20Fundamental Requirements For Safety in Design
used as Residual Current Device (RCD), ELR come with time delay which can be
adjustable from 0.04 to 0.5 second.
eam)
4018 Te sso
110. Loatame
it 2 6308 1
FLUO. LuMNatee
Gio 808 sy
+ cies 3 2N0S x6
FLV .untatee
Cieut 9 4N0.134550,
CRC. Gea in
Trunking/ Cand
i Treking/ Cond
Cableesere
~Cteut 4 0, 34 TW S80,
FC 7-40.34 THs,
t—cseut 10 seats.
{crest 6 spare
cite 5 seare
amines |
! |
jeeuercw sasmmncain |
|
|
sows cues) USA0 end
58 ConbEacoer
|
[DB - me
Figure 2.5 30mA RCCB provided as Supplementary Protection against Direct Contact
& Protection against Indirect Contact by Automatic Disconnection,
check the phasor sum of cyrrenjs OH the, 4 conductors and it will operate only if this
Phasor sum is not zero (i.e. I+ Iy + I+ TP 0) and exceed the trip setting current (i.e. In
+ly+ Ip +In= lee> setting).
Figure 2.6 ELR (set to operate within 0.4 sec) to provide protection
against Electric Shock by indirect contact
21_ Fundamental Requirements For Safety in Design
2.8 PROVISION OF EARTH FAULT RELAY (EFR) AS RESIDUAL
CURRENT DEVICE (RCD) FOR SWITCHBOARD WITH RATED
CURRENT 300A OR MORE.
For bigger low voltage (400V, 3-phase) installation with rated normal current 300A or
more, Earth Fault Relay (EFR) together with 4 nos. of CLSP10 current transformers are
normally used as shown in Figure 2.7.
The 4 nos. of protection current transformers reduce the primary currents on all 4
conductors (R, Y, B & N) to a smaller current by C.T Ratio (for example: 1000A/5A,
SO0A/SA, 400A/SA, etc.) and check the phasor sum of the secondary currents (ir, iy, iy &
ig), and it will operate only if the phasor sum is not zero (i.e. i; + iy + ip + ig #0) and
exceed the relay setting current.
For Example
If Primary Current Ip + ly + Ip + Iy = In (Phase to Earth Fault Current)
Then
Secondary Current i, + iy +ip + in = Ine x CT Reduction Ratio
A current will flow into the earth fault relay and cause it to operate.
x Lembo
28> eq ho oo
Sat aba)
may
| tassomd UPENC& aetn? FICE
TO TRANSFORMER NO. 1
Figure 2.7 Earth Fault Relay on main switchboard with rated current 300A or more
22Questions — Chapter 2 Fundamental Requirements For Safety in Design
1. Describe briefly the fundamental requirements for safety in the design of electrical
installations for buildings as stipulated by Singapore Standard CP 5:1998 & IEE
Wiring Regulation (16" Edition).
2. The single-line diagram for a distribution board (DB) as shown in Figure 2.8 contains
errors which violate the safety requirements of CP 5:1998, Explain what are these
errors and how you would rectify them.
z
bm Ton 2360 Ft Cora
Ls 99 EB 226 PCa ine
52
ae
>
aE:
is |
poo
i
--j Ree
tC
Pesce ton eARLE TA
Figure 2.8 The Single-Line Diagram of a Distribution Board (DB)
which contains Design Errors
3. ‘The single line diagram of electrical riser tap off unit and meter boards for a high-rise
building is shown in Figure 2.9. Explain briefly the requirements of CP5:1998 and
IEE regulation (16" edition) pertaining to provision of overcurrent protection,
4. Explain briefly the requirements in provision of Residual Current Device(RCD) as
required by CP 5:1998 and the authority.
5. The single line diagram of an electrical riser is shown in Figure 2.10. Explain briefly
23uestions — Chapter 2 Fundamental Requirements For Safety in Design
a y ig
(@) Why overcurrent protection device is omitted at the tap-off unit and how
overcurrent protection is provided in this example.
(b) How Earth leakage and Earth fault protection are provided in this example.
Goa DeMcce aa)
Dele UCM FHC PC Taking
SeayCU ConmerRaod a SIA
‘304 DP MCB 10kA (Type C)
BADPMoB tka (ype vihCFL
[— 2ilaa? FCs PRCT PVC Tig
Cable Lint
Chop ~- ToResidnts Unt
L Et gCetle
a
LE ie = ToResidente Unt
Ext gCabte
‘Typical Single Line Diagram
For Unite' Meter Board (MB)
Figure 2.9 Position of Fault Current Protection Device
—_= >
ain pp ADP
MCB (Type) Isclwor
ao steam, § GS
44570 md PRONE + EIS? PPC
(CABLE INSERVICE DUCT GOM CABLE TRAY /TRUNEING
NOs. 04 soa TPA
ARD DRAW TIONED ees
Coppa BUsaARS cae
‘MAX DEMAND ANMIETER
Figure 2.10 Position of fault current protection deviceCHAPTER 3
MINIATURE CIRCUIT BREAKER
(MCB) - OVERCURRENT
PROTECTION DEVICE
3.1 PROTECTION AGAINST OVERLOAD AND SHORT CIRCUIT
It is often possible to use the same device to protect against overload and short circuit, but
before doing so it is necessary to determine the design current of the circuit and also to
ascertain the prospective short circuit current which is likely to arise.
3.2 NOMINAL CURRENT RATING (OR RATED TRIP RATING) fy,
(a) Nominal current rating or Rated trip rating of the circuit breaker is the current for
which the circuit breaker can carry continuously without causing the breaker to trip,
overheat or deteriorate.
(b) The nominal current rating is easily identified as the nearest available current rating I,
in amperes (A) equal (0 or more than the design current ly of the cire
(c) Miniature Circuit Breakers (MCBs) are manufactured in fixed ratings from SA, 10A,
ISA, 16A, 20, 30A, 32A, 40A, SOA, 60A, 634, 80A & 100A.
3.3. RATED SHORT CIRCUIT BREAKING CAPACITY OF CIRCUIT
BREAKER
(2) Rated short circuit breaking capacity (kA, R.M.S. value) or also known as interrupting
capacity of circuit breaker is the root mean square (R.M.S.) value of the a.c. component
of current at which the circuit breaker can break safely under the specified conditions
of voltage and power factor.
(b) Since short circuit breaking capacity of a protective device is the maximum fault
current that the device can interrupt or break safely, it must therefore not be less than
the maximum prospective short circuit current at the point of installation.
(c) In British standard BS EN 60898 and Singapore standard $8359 for miniature circuit
breaker, MCB may have short circuit breaking capacity from IkA to 25kA, However,
commonly available MCBs are rated at 6kA, 9kA OR 10kA (RMS)
3.4 MINIATURE CIRCUIT BREAKER (SS359 AND BS EN 60898)
Miniature Circuit Breaker (MCB) is the small circuit breaker used for the protection of final
circuits at the Distribution Board (DB) of residential and small commercial and industrial
installations._ Miniature Circuit Breaker
It is used as an alternative to fuse as it can be easily reset and re-closed when the fault in the
circuit is cleared.
1t will trip on a small sustained overcurrent, but not on a harmless transient overcurrent such
as switching surge (For example, on a fluorescent lamp circuit)
‘Magnetic Iron Core
Magnetic Trip Col
(Quick action or
large curren)
Figure 3.1 Miniature Circuit Breaker (MCB)
Functions of the Circuit Breaker
As circuit breaker is a protective device, its basic functions are:~
(a) To permit the electrical installations or appliances it protects to be used up to its full
rated current capacity.
(b) To detect and to protect equipment against dangerous conditions.
(©) To perform the duties as local circuit control switches and fault-making isolation
switches.
Principles of Operation
Miniature Circuit Breakers use one of both of the following principles of operation:~
(a) Thermal Operation
‘Thermal tripping uses a heat-sensitive bi-metal element. The heat produced by the
sustained high current warms the bi-metal strips, which bend to trip the operating
contacts.
(b) Magnetic Operation (Instantaneous Trip)
Magnetic operation is due to the magnetic field set up by a coil carrying the fault
current, which attracts an iron core to trip the breaker when the fault current becomes
large enough,- _ Miniature Circuit Breaker
a |
(2
q
0}
Pa
Z
ao
Contacts of the MCB
Figure 3.2 Operation of Thermal element
Contacts of the MCB
Figure 3.3 Magnetic Oper
Thermal operation is slow, so it is unsuitable for the speedy disconnection required to clear
fault currents. However, it is ideal for operation in the event of small but prolonged overload
current,
Magnetic operation can be very fast and so it is used for breaking fault currents; in many
cases, both thermal and magnetic operation are combined to make the circuit breaker more
suitable for both overload and fault protection
The mechanical operation of opening the contacts takes a definite minimum time, typically
10ms to 20ms, so there can never be any possibility of truly, instantaneous operation.
3.5 SELECTION OF MCB
There are three important parameters to consider when selecting an MCB:
The current rating (5A to 100A)
4 The instantaneous trip current (represented by Type no.)
The short-circuit capacity (1kA to 10kA)Miniature Circuit Breaker
Magnetic trip (or Instantaneous trip) & Type n
As illustrated in Figure 3.4, there are seven types of MCBs currently available. They vary in
the magnitudes of current that can cause the magnetic trip element to operate instantaneously
(defined as within 100ms) although, with smaller current, their thermal element (or overload
characteristic) are the same in all cases.
MCB Types 12.3 & 4
(to BS 3871)
|)
MCB Types B,C & D
(to BS EN 60898 & SS 359)
Time (see)
Time (see)
2747 10 80
‘Multiples at Nominal Rated Current, I, Multiples at Nominal Rated Current, Iy
Figure 3.4 Magnetic trip
Instantaneous Trip Operating Time
Instantaneous trip operating time is therefore defined as being with 100 m-second (0.1
second) and the following table in Table 3.1 show that the range of currents that the MCB
will definitely not operate within 100 m-second and the range of currents that the MCB will
definitely operate within 100 m-second for various types of MCB:-
¢ | WiNNOT trip in [Will trip in
| 100ms at current | 100ms at current |
1<27Xh | 14x, | Low Inrush Curren
Is 1<7x1,
‘Typ Typical Application
General Purpose Use _
High Inrush Currents (Motor Circuits)
Table 3.1. Where In is the Nominal rating or Thermal trip rating of MCB.
For example, the magnetic trip (or instantaneous trip) of a type C MCB definitely will not
trip if fault current is less than 5 x |, and the same MCB will trip magnetically if fault current
is more than 10 x Ih.
ime.
ent Characteristi
Time-current characteristic of protection device (MCB, MCCB and Overcurrent Relay) are
often plotted in graphs with logarithmic scales
28
|
|
|Miniature Cireuit Breaker
Typical characteristic of MCB with fixed and non-adjustable time / current characteristic
calibrated at 30°C for Type 1, 2, 3 and Type B, C, D are available from Singapore Standard
CP5:1998.
SauadWv Sur LNAYUND AALLOSdSOUd
2
z
a
a
a
3
3
Zz
6
a
Figure 3. 5
‘Time-Current Characteristic in Logarithmic Scales ~ Type B MCBMiniature Circuit Breaker
SBusdNY ‘SUN 'LNSYYND FALOASOUd
ooo ook
pe C MCB
rithmic Scales — T
eristic in Log
SONOQ3S ‘BW
Time-Current Charact
“bse SS Fare
igure 3.67 ature Circuit Breaker
3.6 EXAMPLES IN SELECTION OF MCB
Example 3.1
For a final circuit feeding four (4) twin 40-watt fluorescent lightings and six (6) 60-watt
incandescent lightings (filament lamp), determine the appropriate current rating of the MCB.
Assuming power factor of 0.85 and efficiency of the fluorescent lamp be 65%.
Total load for 4 twin 40-watt Fluorescent lights and 6 nos. 60-watt Incandescent lights:
_f_4x2x40W + 6x 60W
“| pf = 0.85 x efficiency = 5%) * [pf = 1x efficiency= 100%
1
1) +
4x (2x 401 0s (estos 6x (60W) x 1
4.x (2x 40) x (1.8) + 360x (1), (Please note: Factor = 1.8 for Fluorescent lights
Factor= | for Incandescent lights)
576 VA +360 VA
= 96VA
ai = 937VA
Designed Circuit Current h= So5y7
=4.07A
Since, Nearest MCB current rating I, = SA or 104.
‘A.10A Type B MCB is preferred in this non-domestic situation.
Example 3.
For a final circuit feeding a 230V, single-phase 3kW instantaneous water heater, determine
the appropriate current rating of the MCB
3000 W
Designed Circuit Current k= 35
= 13A, because Power Factor =1
‘Therefore, use the nearest available MCB current rating, I, = 20A.
A20A MCB Type B is selected.
A typical design of a small lighting and power distribution board (DB) in a residential unit is
shown in Figure 3.7.
3Miniature Circuit Breaker
186 80 i Rett Cet
hg Chest
ght Cit. 2
Leh Crt. 3
(nie id
‘nde ta
B
Dab seb q
o)Mce mca o) MCE) MCR mcE
itged res Yrmet free Propet [rape
ay lise” foto [ato fea” |eto,
ae
a
iz
i
Eb
g
beince
Bm Sees
Figure 3.7 A Typical Distribution Board (DB) using MCBs and RCCBs as Protective
Devices
3.7. SELECTION OF MCB FOR MOTOR CIRCUITS.
Motor Loads present the most complex type of transient inrush current, The starting
phenomenon takes place in two stages, a transient and a steady-state stage. Figure 3.8 shows
the two stages of the motor starting currents:~
(2) An initial peak Inrush current of 2.8 times the r.m.s. value of the motor’s locked rotor
current (Isa) or 15 times x Full Load Current lasting for less than two main cycles
(0.04 sec).
(b) The second stage where the motor starting current decays to about 7.5 times x Full
Load Current which may last for 5 to 15 seconds.
‘The motor finally takes the steady running current at maximum value equal to Full Load
Current,
‘The first stage of in-rush current is due to initial surge of current into a stationary motor
which lasts until the field is established.
The second stage of starting current lasts while the motor speeds builds up. In practice, this
second stage of starting current is not constant as shown but is generally assumed to be so
since it simplifies the problem and assumes the worst case.oak Tawi aah Cane
Figure 3.8
Pea Sted Ste
Srenaleronde
Motor Inrush Current (Shown as Instantaneous Value)
‘The R.M.S values of motor current in the three (3) stages from initial peak to final running
current is shown in Figure 3.9.
‘Motorreted
samperee
Figure 3.9
_= Breskeris unabe to provide
ovesloed protection
Characteristic of dzcuit
breaker theenal element
/@)7-Sxlpy stating curent may
‘caves thermal element to operste
_- Magnet tap
1 (Current)
75alpz__ © @ nal peakmotor ting coment 15x
saci ‘may cee magnetic tpto operate
Characteristic of Motor Starting Current with respect to time (R.M.S. Value)
33_ Miniature Circuit Breaker
(2) As the initial peak last for about 0.04 seconds, it may cause the magnetic trip to trip.
(b) Whereas the second stage starting current which may last for 5 to 15 seconds and may
cause the thermal element to trip.
To overcome these kinds of unnecessary tripping, the following design approach has been
used quite satisfactorily:
(a) _ Rated thermal trip rating or nominal rating (I,) of circuit breakers are selected larger to
avoid unnecessary tripping,
For motor with Full Voltage Starting or Direct-on-line Starting, Iy is select between 2 x
Tp vad and 2.5 X levi Loo.
For motor with Reduced Voltage Sta
Lose
18, In is selected between 1.5 x Ira tow and 2 x
(b) Magnetic trip element or type no. are selected to ensure that magnetic trip element will
not operate at Inrush current.
Example: If Tiyan <3 x In (or maximum current that will definitely not trip magnetic
trip of Type B)
Then Type B will be selected,
Wf Tinsh <5 x ty (or maximum current that will definitely not trip magnetic
trip of Type C)
Then Type C will be selected
However, the above design rule of thumb should be subjected to further closer analysis with
time-current characteristic of the MCB and the characteristic of motor starting currents to
ensure appropriate and proper selection,
Itis also to be noted that, when the circuit breaker is selected with higher thermal trip rating
(ls) for the motor circuit, the circuit breaker selected is unable to provide appropriate
overload protection for the motor cable and the motor itself. Overload relay (which is
normally set to 110% to 120% of Full load running current) must be provided at the motor
starter for overload protection. The circuit breaker will now provide only short circuit
protection,
For motor circuit or motor submain without overload relay (E.g. Fire pumps, essential motor
circuit where overload relays have been removed for safety reason), the cable size and motor
must be selected carefully to have current carrying capacity equal to (or more than) the Rated
trip rating |, of the circuit breaker.
3.8 IDENTIFICATION OF CIRCUIT BREAKER IN TERMS OF NUMBER OF
POLES
Overcurrent devices such as MCB and MCCB are commonly referred to by the number of
poles in terms of switching as shown in Figure 3.10. It is to be noted that overcurrent
detection is normally provided only in each phase conductor, but not in the neutral
conductors, except where it is necessary required as shown in Figure 3.10.
34