Introduction of “Digital Application in Electrical
System””
System
th
30 April2016 at Vadodara
Dave Kamin
Senior Manager
Business Development & Engineering
[email protected] www.ashidaelectronics.com
What is Digital Technology?
• Electronic technology that generates, stores
and process data in terms of high and low
state or True & False state
Two states: High (1) and Low (0)
Each of these state digits is referred to as a bit
String of Bits addressed as a Byte (1 byte = 8
bits or 16 bits or 32 bits data)
1
4/26/2016
What is Digital Technology?
Why Digital Substation in Electrical
System?
Objectives.....
• Reduced Complex wiring
• Reduced Maintenance cost
• Interoperability between vendors
• Pre and Post information about equipment
health and substation occurrences, provides
the information about reliability and
availability of electrical system
• Faster remedial actions based on data
received
2
4/26/2016
What are the Digital Equipments
used in Electrical System?
• Digital relays (MicroP
(MicroP relays)
• Digital meters
• Ethernet switches / Modem
• Communication cable
• Data concentrators and I/Os
• GPS clock / receiver antenna
• Phasor measurement unit
• HVDC controller
• Generator controller
• Fiber optic CT/VT
• Merging unit
What are the Physical media available for
Digital data transmission in Electrical System?
• RS232 communication cable
Point to point network connection
• RS485 communication cable
Multidrop network connection
• Ethernet RJ45 communication cable
Unicast, Multicast and Broadcast through
ethernet
• Fiber optic communication cable
Unicast, Multicast and Broadcast through
ethernet
3
4/26/2016
What are the Physical media available for
Digital data transmission in Electrical System?
• Data transmission is through Satellite
GPS time synchronization
What are the Communication Protocols for Digital
data transmission used in Electrical System?
• Modbus
Introduced by Modicon
Mainly use for SCADA and metering at local/remote
end
• DNP
• ETHERNET (TCP/IP)
Use for networking (LAN < 5km)
• IEC60870-
IEC60870-5-103/104
Open protocol for protection
• IEC61850
Open protocol for substation automation
Beyond protocol (application for substation
engineering)
4
4/26/2016
What are the Communication Protocols for Digital
data transmission used in Electrical System?
• IEC61850 Protocol
Open protocol for substation automation
Interoperability: Exchange information between
IED’s from different vendors
Use this information for own function (CB status
received by IED1 can send GOOSE message to
IED2)
Flexible configuration
Where to apply Digital technology in
Electrical System?
• Digital Applications in Electrical System
Power Generation
Wind and Solar Generation
Thermal and Hydro Generation
Power Transmission
Power Distribution
5
4/26/2016
Where to apply Digital technology in
Electrical System?
• Operations Optimizations
Power plant/Process Industries Operation
Remote control of generator
Synchronization
Transmission system Operation, monitoring &
control
SCADA, Load dispatch control, Unmanned
control/remote operation of substation
Distribution system Operation
Reactive power control through capacitor bank ON/OFF
Load shedding
• Asset Performance
On line monitoring of equipment
What are the Applications of Digital technology in
Electrical System?
General Purpose:
Monitoring Functions
Online monitoring power system/relaying parameters
(i.e. Voltages/Currents/Power/Status of Digital Inputs &
Outputs, Status of protection function operated/not
operated, Circuit breaker status ON/OFF, Power
transformer operating parameters monitoring etc.)
Control Functions
Circuit breaker / Isolator Operations from remote
location
Load shedding in Auto/Manual mode, Capacitor bank
control, static VAR compensator control
Recording and Analysis
Sequence of Event with time stamping
Disturbance storing and analysis
6
4/26/2016
What are the Applications of Digital technology in
Electrical System?
General Purpose:
Power system and Substation details available at one
point location / remote location
Unmanned Substation / Remote operation
Digital technology used in Electrical
System
• Electrical SCADA system / PMS system
Substation Automation
Power management, Grid Islanding and Load
shedding system
Monitoring of active and reactive power details
at remote end
• Synchrophasor system
Wide area monitoring, protection and control
• Numerical Protection & Control
Line differential application
Disturbance and Event recording
Metering
Transfer trip of distance protection scheme
7
4/26/2016
What Is Conventional S/S?
Digital
•Digital
Substation
8
4/26/2016
IEC61850 Digital S/S: Standards
• Part 1 to 10
• Part 6 for SCL
• Part 8-
8-1 for IEC GOOSE/GSE (Generic object
oriented substation event) message
Also known as Virtual inputs and outputs
Data type Boolean (0 / 1 states)
Station bus application (Interlocks, alarms, trip logic)
• Part 9-
9-2 for Process bus Implementation
Sampled value
Analogue values to be converted in to Digital values
Digital values applied to Protection relays
IEC61850 Digital S/S: Standards
Part 9-2: Sampled values for Process bus
Implementation
80 Samples/Cycle for Protection
Function (4kHz sampling rate)
4000packets
4000packets / seconds
256 Samples/Cycle for Metering
Function (12.
12.8kHz sampling rate)
12800packets
12800packets / seconds
Reduce Field wiring cost
9
4/26/2016
What is IEC61850 Digital Substation?
SCADA Station
HMI
Station Bus Fiber
Communications Optic
IEC61850-7-2/3/4
Gateway cable
IEC61850-8-1
IED1 IED2 IED3
Fiber
Optic
cable
Process Bus
CT IEC61850-9-2 VT
IEC61850 Digital Substation: Typical
Basic Structure
Substation Substation
HMI Computer
Router WAN
Ethernet Substation Bus
Switch
SCADA Master
IED IED IED IED
Ethernet Switch Process Bus
CT CT
MU IOU IOU MU
PT PT
XCBR
10
4/26/2016
IEC61850 Digital Substation: Typical
Basic Structure
“Station Bus” LAN
IEC 61850-8-1
“Process Bus” LAN
IEC 61850-9-2
IEDs
Digital
CT/VT IEDs
C
Intelligent A
Breaker
Power System B
The “Digital Substation”: both power system data and control over the LAN.
IEC61850 Digital Substation: Typical
Basic Structure
11
4/26/2016
IEC61850 Digital Substation: Typical
Basic Structure
IEC61850 Digital Substation: Typical
Basic Structure
12
4/26/2016
IEC61850 Digital Substation: Typical
Basic Structure
IEC61850 Digital Substation: Merging
unit
13
4/26/2016
IEC61850 Digital Substation: Merging
unit
80 samples/cycle
IEC61850 Digital Substation: Merging
unit
Part 9-2:
Where do We need Time Synchronization???
<1 ms (General Applications)
Sequence of Events
DFR, Oscillography
<10 microseconds (High Precision)
Sampled Value (IEC61850
(IEC61850-
61850-9-2)
SynchrophasorW (C37
(C37.
37.118)
118)
14
4/26/2016
IEC61850 Digital Substation: Basic
Structure by using Optical CT/VT
IEC61850 Digital Substation: CFE
project (USA)
15
4/26/2016
IEC61850 Digital Substation: Optical CT
Manufacturer 1 Manufacturer 2
IEC61850 Digital S/S: Optical CT
• Smaller size and Lighter weight
(approximately 20%) compare to
conventional CT
• Easy to install at site
• No CT saturation
• No maintenance
• Require less burden because the high level
output (1A/5A) not require to drive
• Composite insulator (no gas/oil inside)
16
4/26/2016
IEC61850 Digital S/S: Optical CT
Digital Substation: Instrument
Transformer
17
4/26/2016
Digital Substation: Ethernet connector
10Base-T 100Base-T 1000Base-T
IEEE Standard IEEE 802-3i IEEE 802-3u IEEE 802-3ab
Suitable Cable Category 3, 5 Category 5 Category 5e
Transmission 10M bps 100M bps 1000M bps
Speed
Digital Substation: Ethernet connector
1Gbps Ethernet link speed is highly recommended for Process bus
in switch network
18
4/26/2016
Digital Substation: IEC60870
IEC60870--5-103
Control Engineering
HMI
Center
Router
Station
10 MBit/s Switch Controller
RS485-
Ethernet
Bay Relay A Relay B Bay Relay A Relay B
Controller Controller
Conventional Conventional Conventional Conventional
Switchgear CT / VT's Switchgear CT / VT's
Digital Substation: IEC60870
IEC60870--5-103
SCADA HMI
RS232
Station Controller
RS485/RS422/RS232, IEC60870
SWB1 SWB2 SWB3 SWB4
19
4/26/2016
Digital Substation: IEC60870
IEC60870--5-103
Q1A IO module
RS485/RS422/RS232, IEC60870
CB 52
Q2
RS232
Relays Meters
IEC61850 Station Bus Implementation
Ethernet Switch Ethernet Switch
Hardwired
20
4/26/2016
IEC61850 Station Bus Implementation
SCADA HMI
RJ45, IEC60870-
IEC60870-5-104
Station Controller
RJ45-
RJ45-Copper or FO, IEC61850
Bay Switch 1 Bay Switch 2
SWB1 SWB2 SWB3 SWB4
IEC61850 S/S
• Communication
Network Architectures
21
4/26/2016
IEC61850 S/S: Network Topology
(Digital Substation)
Cascading Bus
Architecture
1 2 3 4 N
IED IED IED IED IED IED IED IED IED IED
IED IED IED IED IED
IED IED IED IED IED
• Cost-effective bus architecture – messages cascade from
switch to switch.
IEC61850 S/S: Network Topology
(Digital Substation)
Star Connected Bus Architecture
Station
level
Switches
Bay level
Switches
Communication
of IEDs failed Failed
• Simple Connections & Configurations
• Not Protected against single point failure
22
4/26/2016
IEC61850 S/S: Network Topology
(Digital Substation)
Redundant Star Connected Bus Architecture
Communication
through LAN-
LAN-B Failed
IEDn1 IEDn2 IEDn3 IEDn4 IEDn5 IEDn6
• Entire network is duplicated
• Increase complexity & cost of substation
• Each devices have two IP addresses & two application
instances
IEC61850 S/S: Network Topology
(Digital Substation)
Ring Connected Bus Architecture
PATH 1 PATH 2
Fault
IED IED IED IED IED IED IED IED IED IED
IED IED IED IED IED
IED IED IED IED IED
• N+1 Fault Tolerant Ring Architecture
23
4/26/2016
IEC61850 S/S: Network Topology
(Digital Substation)
Double Ring Connected Bus Architecture
Duplicate ring
IED3 IED4 IED5
IED1 IED2
IEC61850 Standard Contents……:
Part 4/5
Performance Class P1: Total Transmission Time shall be
around 10ms
Performance Class P2/3: Total Transmission Time shall be
around 3ms
24
4/26/2016
IEC61850 Standard Contents……:
Part 4/5
Transmission Time of Point to Point = GOOSE encoding at
sender + Network delay + GOOSE decoding at receiver
• Network delay is 100microS at 100Mbps link speed &
10microS at 1Gbps speed
Digital S/S: Conventional S/S
• Complex wiring of Conventional S/S
• Less Reliability of Conventional S/S
• Required Periodic maintenance for
Conventional S/S
• Required More space and money for
installation of Conventional S/S
• More Commissioning Time for Conventional
S/S
• More Troubleshooting Time for Conventional
S/S
• Require more Manpower for Operations of
Conventional S/S
• Operators & Experienced Technicians can
able to operate Conventional S/S
25
4/26/2016
Digital S/S: Conventional S/S
• Instrument transformer maintenance not
require in case of Fiber optic CT/VT used
• Avoided Current transformer saturation
due to DC offset in case of Fiber optic CT
used
Digital S/S: Key Points
• Digital S/S have following;
Easy to use
Easy to configure
Good cyber security
High availability
Better visualization
Flexible Alarm system
Easy to use report generation
Availability of Historical data
Accurate time synchronization for process bus
Ensure the availability of time sychronization
Merging unit performance shall not be affect by external
ethernet trafic
Merging unit shall have good performance under EMI/EMC
conditions and shall have self diagnostics feature of failure
26
4/26/2016
Digital S/S: Key Standards
IEC61850
IEEE C37.92 Low energy analogue
IEC 61869-
61869-9 Digital Interface for CT/VT
IEC 61869-
61869-13 Standardization of MU
IEC 60044-
60044-7 Electronic VT
IEC 60044-
60044-8 Electronic CT
PC 37.235 Rogowski Coil Guide
PSRC WG I8 Optical CT/PT Guide
IEC TC38WG37L. Kojovic (US), F. Rahmatian (CA)
C37.1 SCADA
C37.111 COMTRADE
C37.118-
C37.118-1/2 Synchrophasor system