Overcurrent1:
Shot Test Results:
Type Relative To Factor Magnitude Angle tnom tact Deviation Overload Result
R-Y-B I #2 Phase 2.000 2.000 A -60.00 ° 10.03 s 10.01 s -199.4 m % No Passed
R-Y-B I #2 Phase 5.000 5.000 A -60.00 ° 4.280 s 4.300 s 467.3 m % No Passed
R-Y-B I #2 Phase 2.000 2.000 A 25.00 ° 10.03 s 10.01 s -199.4 m % No Passed
R-Y-B I #2 Phase 5.000 5.000 A 25.00 ° 4.280 s 4.300 s 467.3 m % No Passed
R-Y-B I #2 Phase 2.000 2.000 A 35.00 ° No trip No trip n/a No Passed
R-Y-B I #2 Phase 5.000 5.000 A 35.00 ° No trip No trip n/a No Passed
R-Y-B I #2 Phase 2.000 2.000 A 215.00 ° 10.03 s 10.01 s -199.4 m % No Passed
R-Y-B I #2 Phase 5.000 5.000 A 215.00 ° 4.280 s 4.300 s 467.3 m % No Passed
R-Y-B I #2 Phase 2.000 2.000 A 205.00 ° No trip No trip n/a No Passed
R-Y-B I #2 Phase 5.000 5.000 A 205.00 ° No trip No trip n/a No Passed
Charts for Fault Types:
Angle
Type
R-Y-B -60.00 °
10000
1000
100
t/s
10
1.0 2.0 3.0 5.0 7.0 10.0
I/A
+90°
180° 0°
6.0 A -90°
Charts for Fault Types:
Angle
Type
R-Y-B 25.00 °
10000
1000
100
t/s
10
1.0 2.0 3.0 5.0 7.0 10.0
I/A
+90°
180° 0°
6.0 A -90°
Charts for Fault Types:
Angle
Type
R-Y-B 35.00 °
10000.000
1000.000
100.000
10.000
t/s
1.000
0.100
0.010
0.010 0.100 1.000 10.000
I/A
+90°
180° 0°
6.0 A -90°
Charts for Fault Types:
Angle
Type
R-Y-B 215.00 °
10000
1000
100
t/s
10
1.0 2.0 3.0 5.0 7.0 10.0
I/A
+90°
180° 0°
6.0 A -90°
Charts for Fault Types:
Angle
Type
R-Y-B 205.00 °
10000.000
1000.000
100.000
10.000
t/s
1.000
0.100
0.010
0.010 0.100 1.000 10.000
I/A
+90°
180° 0°
6.0 A -90°
State:
10 out of 10 points tested.
10 points passed.
0 points failed.
Test performed offline: Test results are simulated!
General Assessment: Test passed!