CAPACITOR BANK_kVAR RATING CALCULATION PF
###
PROJECT NAME: DATE: ###
CAPACITOR PANEL REF: PREPARED BY: ###
PROJECT NO: PAGE NO: ###
###
Load in Kilowatts Improving Power factor
Ref.No (Kw) Normal Power factor (p.f) (p.f) Required kVAR Selected kVAR ###
1 900 0.85 0.9 121.88 tanØ1
2 500 0.7 0.9 267.94
3 900 0.5 0.8 883.85 ###
###
4 #N/A ###
5 #N/A ###
6 #N/A ###
7 #N/A
8 #N/A ###
###
9 #N/A ###
###
###
Grand Total #N/A
###
###
Formulae ###
kVAR = P x ( tanØ1 - tanØ2) ###
###
Where as,
###
###
BS_EDS V.Prathi
PANEL BOARD _ SIZING CALCULATION
###
25 40 63 16
###
40 250 125 40 25 16
###
40 25 16
###
1900
40 25 16
###
40 100 40 25 16
###
125
###
25 40 25 16
###
###
###
###
Chk Avl Ht 300 Chk Avl Ht 300 250 300 300 250 300 ###
2000 ###
Comments
Approved
Date
BS_EDS V.Prathi
CABLE TRAY _ SIZE CALCULATION
PROJECT NAME: DATE:
CABLE TRAY REF: PREPARED BY:
PROJECT NO: PAGE NO:
BS_EDS V.Prathi
LIGHTING _ CALCULATION
Comments
Approved
Date
Electrical Conversion P.F Power Length
Kilo watts 187.11 Three Phase 0.8 hp 1 mile 5
Ampere 329.3536856 hp (metric) 1.0139 yard 8800.00359
Under Construction
Max.Current Carrying
185
Capacity of the Selected 370
cable in Amps (A)
Max.Current Carrying
10 Capacity of the Selected 47
cable in Amps (A)
mps
tric flow
650
40
0.39
INDEX KVAR PANEL TRAY BUSBAR LIGHT CABLES
Instructions
You may move from worksheet to worksheet by clicking on the blue buttons
located at the top of each worksheet or the blue tabs at the bottom of this workbook.
Panel
Use this "Panel sizing calculation sheet" to get the size of the LV panel's. Use drop down box at the Top left of the fo
Use the drop down boxes in the format to get the standard ratings of the incomers & Outgoings. Select the breaker
boxes in the compartments, Note that the down side dimensions should not be "Check availabilty Height".In such a
Protective Device instead of high rated Protective device or remove (select empty ----------- indicates no compartme
/ Compartment in that particular column.
Tray
In this sheet there are two formats for the cable tray selection whereas first format will gives the exact width with ou
our local regulations) and the second format will be considered as the international standard with having the expand
more for the security reasons notified by the NFPA standards & it should be mainly considered in industrial projects
Busbar
Uses this "Busbar_ Voltage drop calculation" sheet to select the Copper busbar ratings . The constant values are c
distance & connected loads at every tapoff can be fill by rows. The Diversity factor applied by us in the white cell is c
Select the available standard ratings of bus bars by using the drop down boxes. "Increase (A) rating" indicates that
Line current, By selecting the higher size will gives the good result if the voltege drop must not exceeds the limit.
Light
Uses this “Lighting_ Calculation” to find the total lumens O/P & number of fittings required for an area by our recomm
in watts and also fill the inputs such as length, Width & height of the area in the white cells with grey borders.
Cable
In this sheet there are two format for Cable schedule. You can customize your format for the cable schedule as per
Conv.
Enter the value in white cells with grey borders & select the units by using drop down boxes for Unit conversions.
Q.Cals.
Area wise Electrical Load requirements: As per CIBSE rule of thumb we can determine the Approximate electrical lo
Ampere Transformer's required by filling total area of the project in Square meter, Also select the Type of project,Inf
Voltage drop.Current ratings of Multicore XLPE & PVC Cables : Create a quick and easy selection of cable by filling
"Quick Cals" sheet. Enter the "Amps rating,length of cable" in the white cell.Select the "Standard Cable Size"by us
in the cell. The Total Voltage drop & Percentage of Votage Drop (Vd) are calculated for you. "Increase cable size fo
can't carry the connected load, for solution Select the next size cable.
CABLES CONV. Q.CALS MECH. HELP
box at the Top left of the format to select the height of the Panel.
oings. Select the breaker ratings by using the drop down
ailabilty Height".In such a case, Either replace the Low Rated
- indicates no compartment) any of the Protective device
The constant values are common for the calculation. Floor levels,
d by us in the white cell is considered in the line current.
e (A) rating" indicates that the selected Busbar rating the
t not exceeds the limit.
By V.Pradeesh (2007-08)